Code No. LIT-1922175
Issued November 13, 2015
Y63, Y64, Y65, Y66, and Y69 Series Transformers
Description
The Y63, Y64, Y65, Y66, and Y69 Series
Transformers provide 24 VAC power for loads
of 40 VA through 300 VA. These transformers
are designed for use on digital controllers, gas
controls, ignition systems, motor actuators,
staging controls, and most other 24 VAC
HVAC/R control systems.
The Y6x Series meets the requirements of UL
1585, UL 506, and CSA C22.2 No. 66,
providing compliance in both the United States
and Canada. The Y63, Y64, Y65, and Y66
transformers are listed as Class 2
transformers (UL 1585, CSA C22.2 No. 66).
The Y69 is listed as a general purpose
transformer (UL 506, CSA C22.2 No. 66).
Refer to the Series Y63, Y64, Y65, Y66, and
Y69 Transformers Product Bulletin
(LIT-125755) for important product application
information.
Features
• split-bobbin design provides best
primary/secondary isolation
• multi-tap primaries reduce stocking
requirements and offer application
flexibility
• choice of foot, plate, or conduit hub
mounting provides mounting flexibility
• choice of primary voltages meets a wide
range of power requirements from 24 VAC
through 480 VAC
• color-coded lead wires provide simplicity
and standardization
• cULus listed or cURus recognized meets
US and Canadian requirements for Class 2
transformers (Y63, Y64, Y65, and Y66) and
general purpose transformers (Y69)
• built-in, easy-reset circuit breakers
eliminate replacement time and cost
caused by burn-out (Y63, Y64, Y66, and
Y69)
Repair Information
Do not make any field repairs to transformers.
For a replacement transformer, contact the
nearest Johnson Controls® distributor or
sales representative.
• open frame Y65 models serve as ideal
models when end bells are not required
Selection Chart
Y63, Y64, Y65, Y66, and Y69 Series Transformers (Part 1 of 2)
Product Code
Number
Y65G13-0 24 24 External Fitting
Y65A13-0 120 24 External Fitting
Y65A21-0 120 24 End bell holes
Y65T31-0 120/208/240 24 External Fitting
Y65T42-0 120/208/240 24 Common External Fitting
Y65T54-0 120/208/240 24 8 in. primary leads 8 in. secondary leads Foot-skeleton cURus Class 2
Y65S13-0 208/240 24 External Fitting
Y65F13-0 277/480 24 External Fitting
Y65F42-0 277/480 24 Common External Fitting
Y63T22-0 120/208/240 24 End bell Hole
Y63T31-0 120/208/240 24 External Fitting
Y63F22-0 277/480 24 End bell Hole
Primary
Voltage
VAC
Secondary
Voltage
Primary
Connection
Secondary
Connection
Mounting Agency
VAC
40 VA Capacity Transformers with Energy Limiting Type Overload Protection
8 in. primary leads
8 in. primary leads
8 in. primary leads
8 in. primary leads
8 in. primary leads
8 in. primary leads
8 in. primary leads
8 in. primary leads
External Fitting
30 in. secondary leads
External Fitting
30 in. secondary leads
Three screw terminals
(one is blind)
Three screw terminals
(one is blind)
Common External Fitting
8 in. secondary leads
External Fittings
30 in. secondary leads
External Fitting
30 in. secondary leads
Common External Fitting
8 in. secondary leads
Foot cULus Class 2
Foot cULus Class 2
4 in. x 4 in. plate cULus Class 2
Foot
4 in. x 4 in. plate
Hub
4 in. x 4 in. plate
Foot cULus Class 2
Foot cULus Class 2
Hub
4 in. x 4 in. plate
50 VA Capacity Transformers with Circuit Breakers
8 in. primary leads
8 in. primary leads
8 in. primary leads
End bell Hole
8 in. secondary leads
Three screw terminals
(one is blind)
End bell Hole
8 in. secondary leads
4 in. x 4 in. plate cURus Class 2
Foot
4 in. x 4 in. plate
4 in. x 4 in. plate cURus Class 2
1
1
1
1
Requirement
cULus Class 2
cURus Class 2
cURus Class 2
cULus Class 2
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com
1
Relays and Transformers
Y63, Y64, Y65, Y66, and Y69 Series Transformers (Continued)
Y63, Y64, Y65, Y66, and Y69 Series Transformers (Part 2 of 2)
Product Code
Number
Y66T12-0 120/208/240 24 Common External Fitting
Y66T13-0 120/208/240 24 External Fitting
Y66F12-0 277/480 24 Common External Fitting
Y66F13-0 277/480 24 External Fitting
Y64T15-0 120/208/240 24 External Fitting
Y64T21-0 120/208/240 24 End bell holes
Y64T22-0 120/208/240 24 End bell Hole
Y69T15-0 120/208/240 24 External Fitting
1. 4 in. x 4 in. plate and nut packed with transformer.
Primary
Voltage
VAC
Secondary
Voltage
VAC
Primary
Connection
75 VA Capacity Transformers with Circuit Breakers
8 in. primary leads
8 in. primary leads
8 in. primary leads
8 in. primary leads
92 VA Capacity Transformers with Circuit Breakers
8 in. primary leads
8 in. primary leads
8 in. primary leads
300 VA Capacity Transformers with Circuit Breakers
8 in. primary leads
Secondary
Connection
Common External Fitting
8 in. secondary leads
External Fitting
30 in. secondary leads
Common External Fitting
8 in. secondary leads
External Fitting
30 in. secondary leads
Internal Fitting
30 in. secondary leads
Three screw terminals
(one is blind)
End bell Hole
8 in. secondary leads
Internal Fitting
30 in. secondary leads
Mounting Agency
Requirement
Foot cURus Class 2
Foot cULus Class 2
Foot cURus Class 2
Foot cULus Class 2
Foot cULus Class 2
Plate cULus Class 2
Plate cURus Class 2
Foot cULus
Power Transformer
Technical Specifications
Series Y63, Y64, Y65, Y66, Y69 Transformers
Input Power Requirements 24 to 480 VAC at 60 Hz
Full Load Secondary V oltage 23.5 VAC (Nominal)
Open Circuit Secondary Voltage (No Load) 27.0 VAC (Nominal)
Full Load Secondary VA Rating Series
Y63
Y64
Y65
Y66
Y69
Finish End bells, frame, feet, and mounting plates are corrosion resistant
Ambient Operating Temperature -40 to 104°F (-40 to 40°C)
Ambient Storage Tem p erature -40 to 140°F (-40 to 60°C)
Shipping Weight Y63
Y64
Y65
Y66
Y69
Agency Compliance UL Listed Y63, Y64, Y65, Y66; File E95575, CCN’s XOKV (US) and XOKV7 (Canada)
UL Recognized Y63, Y64, Y65, Y66; File E95575, CCN’s XOKV2 (US) and XOKV8 (Canada)
UL Listed Y69; File E95138, CCN’s XPTQ (US) and XPTQ7 (Canada)
All transformers are Class 2 except the Y69 (300 VA), which is listed as a power transformer.
Volt-Amperes
50 VA
92 VA
40 VA
75 VA
300 VA
3.0 lb/1.4 kg
4.0 lb/1.8 kg
2.0 lb/0.9 kg
3.0 lb/1.4 kg
11.0 lb/5.0 kg
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
www.johnsoncontrols.com
2