Johnson Controls WT-4002-MCR, WT-4002-MCM, WT-4002-MFR, WT-4002-MFM Installation Instructions Manual

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC)
24- 10732- 5, Rev. D
Room Thermostats
Installation Instructions
WT-4002-MCR, WT-4002-MCM, WT-4002-MFR, WT-4002-MFM
Refer to the QuickLIT website for the most up-to-date version of this document.
Application
The WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats provide reliable zone comfort and enhanced energy economy via remote monitoring and temperature setpoint management. This arrangement provides greater energy policy compliance, and facilitates trending of floor space usage in commercial, industrial, and municipal HVAC environments.
The WT-4000 Series Room Thermostats are ideally suited for energy-saving, pneumatic-to-DDC building upgrades. Designed for non-invasive replacement of existing manual pneumatic thermostats, the WT-4000 Series Room Thermostats provide a number of DDC features, including remote wireless setpoint control and occupancy scheduling, and continuous room temperature, branch line pressure, and battery status monitoring. All of these features were previously unavailable in existing pneumatic HVAC control systems.
The innovative design of the WT-4000 Series Room Thermostats completely reshapes the pneumatic HV AC control industry. The room thermostat itself does not utilize any mechanical parts. A solid state temperature sensor replaces the bi-metallic strip elements for precise room temperature mo n ito rin g. In addition, an advanced piezoelectric air valve replaces the mechanical relay for improved branch line pressure control. All of these technologies provide longer, more dependable, and maintenance-free operation.
Models are available for wireless mesh communications, or they can be configured in the field for stand-alone applications. In a wireless mesh network application, the WT- 4000 Series Room Thermostat communicates with the controller by means of a Johnson Controls® WT-ROUTER Router and Johnson Controls WT-BAC-IP Gateway.
Some WT-4000 Series Room Thermostats include a binary dry contact input for an occupancy sensor (field furnished), to detect motion and determine if a space is occupied. This feature maximizes up to 30% energy savings in high-energy usage environments such as schools, dormitories, offices, and hospit als by adjusting the temperature of the space based on the occupancy status.
Part No. 24-10732-5, Rev. D
Issued August 2017
All WT-4000 Series Room Thermostats include an LCD, with either a Fahrenheit or Celsius temperature display. Depending on the model chosen, the room thermostat can transmit sensed temperature, setpoint temperature, occupancy status, and low battery conditions to an associated router and gateway. The WT-4000 Series Room Thermostat is designed for indoor, intra-building applications only.
The WT-4000 Series uses a proprietary direct-sequence, spread-spectrum RF technology, and operates on the 2.4 GHz Industrial, Scientific, and Medical (ISM) band. The room thermostat meets the IEEE 802.15.4 standard for low power, low duty cycle RF transmitting systems.
IMPORTANT: The WT -4000 Series Pneumatic-to-DDC Room Thermostat is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the room thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the room thermostat.
IMPORTANT: Le WT-4000 Series Pneumatic-to-DDC Room Thermostat est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du room thermostat risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du room thermostat.
WT-4 000 Series Pneumatic-to-Direct Digital Control (DDC)
Room Thermostats Installation Instructions
1
IMPORTANT: The WT-4000 Series Pneumatic-to-DDC Room Thermostat is not designed or intended for use in mission-critical or life/safety applications.
North American Emissions Compliance
United States
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Canada
Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Installation
The first step of the installation process is to plan the layout of the devices on the building floor plan. This process includes identifying the desired locations for all WT-4000 Series Pneumatic-to-DDC Room Thermostats, as well as the Johnson Controls WT-BAC-IP Gateway.
Next, measure the radial distances between each WT-4000 Ser ies Room Thermostat and the WT-BAC-IP Gateway, to determine if the distances are within 200 ft (61 m). If the distance exceeds 200 ft (61 m), Johnson Controls WT-ROUTER Routers must be installed to relay signals between each room thermostat and the associated gateway.
The ideal installation provides each room thermostat with at least two routes of transmission to the gateway, to ensure signal transmission success. The nominal transmission range of each router in a standard building is 200 ft (61 m). To ensure proper signal transmission in a wireless mesh network, there should be at least two routers, or one router and one ga teway, located within a 200 ft (61 m) radius of every room thermostat.
In order for the devices to connect to the same mesh network, they all must have the same group ID. Both the group ID and the device ID can be changed in the field; see Net Config Screen details.
on page 10 for more
Le terme « IC » précédant le numéro d'accréd itation / inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
2
Dimensions
(21)
(95)
(120)
Figure 1: WT-4000 Series Pneumatic-to-DDC Room Thermostat,
Dimensions, in. (mm)
4-23/32
13/16
3-3/4
Mounting
The WT-4000 Series Room Thermostats require the WT-BAC-IP Gateway and WT-ROUTER Router to operate as a complete wireless solution. Refer to the
WT-BAC-IP Gateway Installation Instructions (Part No. 24-10732-21) for details on installing the gateway, and the WT-ROUTER Router Installation Instructions (Part No. 24-10732-13) for details on
installing the router.
Tools and Hardware Required
Couplings or reducers to connect room thermostats to existing air lines
Needle nose pliers
Small level
Fasteners and anchors to se cure room thermost ats (site specific)
Plastic tie wraps to secure routers (site specific)
Electric drill (optional)
Building floor plans identifying where the system is to be installed, serving multiple purposes:
- To plan the wireless network before
installation, by identifying room thermostat locations
- To document the location of where each wireless device is installed
Mounting Procedure
Mount the WT- 4000 Series Room Thermostat according to the steps that follow. Only those individuals that are experienced with HVAC maintenance and commercial room thermostats sh ould perform this installation.
1. Remove the old room thermostat from the mounting surface and disconnect the air lines connected to it. Be sure to label the branch line and the main line.
2. Bend the four locking tabs on the wallplate outward to separate the wallplate from the new WT-4000 Series Room Thermostat.
3. Mount the wallplate to the mounting surface: a. Thread the existing air lines from the wall
through the large opening in the wallplate.
b. Position the wallplate against the mounting
surface to be sure it seats flush with the surface.
c. Use a small level or visually check that the
wallplate is level.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
3
d. Mounting holes on the wallplate are designed
Figure 2: LCD during Initialization
to fit a standard electrical box. If additional mounting holes are required, mark the locations on the mounting surface.
e. Remove the wallplate from the mounting
surface and drill any additional mounting holes as needed at each of the marked locations.
f. Use the appropriate mounting hardware (field
furnished) for the specific mounting surface and secure the wallplate to the surface.
Figure 2 illustrates the LCD during room thermostat initialization.
4. Connect the air lines to the room thermostat. See
Clean Air Requirements
on page 5 to ensure that
the air supply is clean, dry, and oil-free.
IMPORTANT: Avoid applying excessive pressure while making the air line connections to the barbed fittings on the room thermostat. Failure to do so may damage the room thermostat and void the warranty.
5. Install the four 3.6 V lithium batteries included with the room thermostat into the battery compartment. Be sure to match the positive (+) battery ends with the positive (+) battery terminals in the battery compartment.
Note: The room thermostat can operate with just two batteries installed; however, it operates for a significantly shorter period of time. To maximize battery life, we recommend that all four batteries be installed.
6. Once powered up, the room thermostat initializes in:
a. 30 seconds if the room thermostat can connect
to a network.
b. 3 minutes if a network is not present.
IMPORTANT: Do not press any buttons during the initialization process. Configuration changes made during initialization are not saved.
FIG:lcd_initliztn
7. Check the wireless connectivity at the intended room thermostat installation location. It may take approximately 30 seconds for the room thermostat to initialize.
a. Look at the wireless connection status
indicator on the room thermostat LCD (Figure 4). If shows on the upper-right
corner of the LCD, the wireless connection is established and the room thermostat is operating properly. If the LCD is blank in the upper-right corner, there is no wireless connection.
b. Look at the number of routes to the
WT-BAC-IP Gateway on the room thermostat LCD (Figure 4). If the number of routes is blank, the room thermostat is not connected to the gateway. If the number 1 shows, there is one connection. If the number 2 shows, there are two or more connections and the room thermostat is operating properly.
8. Attach the room thermostat to the previously installed wallplate by aligning the slot in the room thermostat housing with the top of the wallplate and sliding the bottom of the room thermostat housing over the bottom of the wallplate.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
9. Document the device ID and the location of each room thermostat on the floor plan.
4
Safety Measures for Electrostatic Sensitive Devices (ESDs)
The WT-4000 Series Room Thermostat includes an ESD-sensitive circuit board. Use caution when handling the room thermostat when the backplate (wallplate) is removed. Do not physically touch any part of the circuit board while connecting air lines, without wearing ESD protective gear . Even minimal electrostatic discharge can severely damage the room thermostat.
Clean Air Requirements
Before installing WT-4000 Series Room Thermostats, check that the air in the pneumatic lines is properly cleaned. Clean, dry, and oil-free air in the main supply line is required for normal room thermostat operation.
The pneumatic system must include a properly operating air dryer and coalescing air filter that removes water, oil, and other impurities from the main supply air before it reaches the room thermostat. If the existing pneumatic system is contaminated with water or oil, Johnson Controls recommends installation of a pre-filter before each room thermostat to protect the device from contaminants and failure.
Note: Room thermostat failures due to main supply air contamination with impurities including water, oil, dust, or other solid particles are not replaceable under the product warranty.
Johnson Controls recommends using the following in-line air filter with WT-4000 Series Room Thermostats:
Johnson Controls A-4000-1037 In-Line Air Filter Before installing room thermostats, check for the
following:
An air dryer that is operating properly
A coalescing air filter that is replaced and maintained properly
In-line air filters before each room thermostat where necessary
Order of Installation for Wireless Room Thermostat Models
The WT-4000 Series Room Thermostats look for a wireless network as soon as they are powered up. We recommend that the WT-BAC-IP Gateway and WT-ROUTER Router are installed first to establish a network connection before the room thermostats are installed and powered.
If the room thermostats are installed before establishing a wireless network, be aware of the following:
Once powered up, the room thermostat initializes and looks for a network for 3 minutes. During initialization, the LCD shows code 512 (Figure 2).
IMPORTANT: Do not press any buttons during the initialization process. Configuration changes made during initialization are not saved.
The room thermostat operates in the Occupied Mode with the following default settings:
Setpoint temperature: 70°F (21°C)
Comfort Zone: ±3F° (±1.8C°)
The default settings can only be changed from the controller tool, once the WT-BAC-IP Gateway is installed.
Once the WT-BAC-IP Gateway and the WT-ROUTER Routers are inst alled, check the LCD on each room thermostat to confirm that they are connected to the network (Figure 4).
The default sampling interval is 5 minutes, so it may take some time for all of the room the rmost at s to establish a network connection.
In summary, install the components of the mesh network in the following order:
1. Install the WT-BAC-IP Gateway.
2. Install the WT-ROUTER Routers.
3. Configure the WT -4000 Series Room Th ermostat s; see Setup and Adjustments
4. Install the WT -4000 Series Room Thermost ats; see
Mounting Procedure
on page 3.
on page 6.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
5
Setup and Adjustments
Shoulder Mode Button –
Triggers Manual Shoulder (Unoccupied) Mode
Override Mode Button – Triggers Manual Override (Occupied) Mode
Light Button – Lights the Display for 10 Seconds
Up Button –
Increases the Room
Temperature Setpoint
Down Button –
Decreases the Room
Temperature Setpoint
LCD – See Figure 4
for LCD Details
Figure 3: WT-4000 Series Pneumatic-to-DDC Room Thermostat
Button Descriptions
Figure 4: Expanded View of LCD Showing Details
Error Code Display
Fan Outp ut
WT-BAC-IP Ga teway
Requested Branch
Line Pressure (psig)
Received Signal
Strength Indicator
Actual Branch
Line Pressure (psig)
Room Temperature or
Requested Setpoint
(When Up or Down
Buttons ar e Pressed)
Since the room thermostats are battery-po wered devices with internal memory, they can be configured prior to, or right after, installation. Johnson Controls recommends that all of the room thermostats be configured before installation, to prevent any possible issues with operation.
Operating Mode
Wireless Connection Status
Number of Routes to the
Battery Voltage Level
Heat or Coo l O utput
FIG:lcd_dtls
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
6
LCD Details
Battery Voltage Level
Operating Mode
a. Occupied – Scheduled Occupied Mode: The
temperature can be adjusted within the Comfort Zone.
b. Unoccupied – Scheduled Unoccupied
Mode: The HVAC controls are off and the temperature cannot be adjusted. To turn the HVAC controls on, press the Override button
to put the room thermostat in the
Override mode, and then adjust the temperature setting using the Up/Down buttons.
c. Override – Manual Override Mode: The
temperature can be adjusted within the Comfort Zone.
d. Shoulder – Manual Unoccupied Mode: The
temperature cannot be adjusted. To put the room thermostat back to its scheduled mode,
press the Shoulder button again;
Occupied reappears on the main screen.
Wireless Connection Status
Indicates if the room thermostat is connected to the WT-BAC-IP Gateway.
a. : A connection is established. b. Blank: There is no connection.
Number of Routes to the WT-BAC-IP Gateway
Indicates how many communication paths exist between the room thermostat and the WT-BAC-IP Gateway.
a. Blank: The room thermostat is not connected
to the WT-BAC-IP Gateway. b. 1: One connection exists. c. 2: Two or more connections exist and the room
thermostat is operating properly.
a. : The battery is fully charged.
b. : The battery charge is low and the
batteries should be replaced.
Heat or Cool Output
a. : Cooling is on.
b. : Heating is on.
Requested Branch Line Pressure – psig (kPa)
Indicates the required branch line pressure based on the control calculation.
Actual Branch Line Pressure – psig (kPa)
Indicates the measured values of the branch line pressure. The actual branch line pressure should be within 0.6 psig (4 kPa) of the requested branch line pressure.
Display Codes Table 1: Display Codes
Display
Description
Code
2 0 psig (0 kPa) available in main line 4 Insufficient branch line pressure 8 Pressure down leak in the system (pressure
12 Insufficient branch line pressure and pressure
16 Pressure up leak in the system (pressure
22 Insufficient branch line pressure and pressure
24 Both pressure down leak and pressure up leak
512 Configuring wireless network 1024 Time and Date need to be configured
Any Other Number
decreases when it should remain constant)
down leak in the system
increases when it should remain constant)
up leak in the system
in the system
(Stand-Alone Mode) Product error; contact the local
Johnson Controls representative
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
7
Received Signal Strength Indicator
Indicates the relative strength of the wireless signal between the room thermostat and the device it is communicating with.
a. -39 and higher: A strong and solid wireless
connection exists; no further analysis is
required. b. -44 to -40: The wireless signal is getting
through; however, the room thermostat should
be monitored. If the signal strength
deteriorates further, there is a risk of data loss.
Consider adding a WT-ROUTER Router
between the devices to strengthen the signal. c. -45 and lower, or --- : The room thermostat
has a very weak wireless connection or it is
failing to connect to other devices on the
network, resulting in the loss of a significant
number of data packets. The room thermostat
may be located too far from the other devices
or there may be wireless interference in the
area. To strengthen the wireless signal, add a
WT-ROUTER Router between the problematic
devices on the network to create an additional
connection point.
Room Temperature or Requested Setpoint
Indicates the current room temperature. Pressing the Up/Down buttons once shows the locally-defined setpoint temperature.
Adjusting the Room Setpoint Temperature
The WT-4000 Series Room Thermostat operates in conjunction with the preset building configuration parameters; therefore, the room setpoint temperature can only be changed within predefined Comfort Zone limits.
1. Confirm that the room thermostat is in the scheduled Occupied Mode; the top of the LCD must read Occupied.
2. The temperature reading on the LCD displays the current room temperature. To increase or decrease the room setpoint temperature, press the Up/Down buttons to select the desired setpoint.
a. When the Up/Down buttons are pressed once,
the LCD shows the user-defined room setpoint value and the LCD reads Setpoint.
c. When the setpoint is displayed, keep pressing
the Up/Down buttons to reach the desired room setpoint temperature.
d. If the Up/Down buttons are pressed and the
setpoint stops increasing or decreasing, predefined Comfort Zone limits have been reached. If the setpoint does not change, the local controls are disabled.
Note: Contact the building administrator if the room temperature minimum or maximum allowable settings are not comfortable.
e. The room thermostat decides to heat or cool
based on the current room temperature and the specified setpoint.
3. When the desired setpoint is specified, the LCD returns to the main screen within 5 seconds.
4. If the LCD reads Unoccupied, the room thermostat is scheduled to be in the Unoccupied Mode. If the area requires heating or cooling while the room thermostat is in the Unoccupied Mode,
press the Override button to change the room thermostat to the Override Mode. See Using
the Override Mode Button that follows.
Using the Override Mode Button
If the LCD reads Unoccupied, the room thermostat is scheduled to be in the Unoccupied Mode and the local room thermostat controls are disabled. If the area requires heating or cooling:
1. Press the Override button to change the room thermostat to the Override Mode.
2. The room thermostat stays in the Override Mode, as defined by the configuration parameters (default 2 hours). The room setpoint temperature can be adjusted within predefined Comfort Zone limits for the duration of the Override Mode period.
3. See Step 2 in the Adjusting the Room Setpoint Temperature section to change the room setpoint temperature.
4. Once the Override Mode period expires, the room thermostat returns to its originally scheduled mo de. If the heating or cooling period needs to be
Note: When the room temperature and the setpoint value are the same, the HVAC equipment is off.
b. If neither the Up or Down button is pressed
again, the LCD returns to the main screen within 5 seconds.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
extended, press the Override button again and follow Step 2 in the Adjusting the Room
Setpoint Temperature section.
8
Using the Shoulder Mode Button
Figure 5: WT-4000 Series Room Thermostat Firmware Version Screen
CH:
GI:
Device Net w or k G r oup ID
DI:
Unique Thermostat Device ID
DF:
Display Firmware Number
The Shoulder Mode button allows the WT-4000 Series Room Thermostat to be placed into a shallow setback mode. When the room thermostat is activated, it does not use HV AC equipment as lon g as the temperature is within the Shoulder Mode configured setpoint limits (default ±5F° [±3C°]).
For example, with a setpoint of 70°F (21°C) and the Shoulder Mode activated, the room thermostat does not turn the HVAC equipment on as long as the room temperature is between 65 and 75°F (18 and 24°C). Use the Shoulder Mode to save energy wh en a room or zone is vacated earlier than when the Unoccupied Mode is scheduled to begin.
Configuration
The following steps describe pre-installation, device-level configuration.
Room Thermostat Configuration Mode
1. Bend the four locking tabs on the wallplate outward to separate the wallplate from the room thermost at.
2. Install the four 3.6 V lithium batteries included with the room thermostat into the battery compartment. Be sure to match the positive (+) battery ends with the positive (+) battery terminals in the battery compartment.
3. Once powered up, the room thermostat initializes in:
1. Press the Shoulder button to activate the Shoulder Mode.
2. The Shoulder Mode period has a limited duration; the room thermostat goes back to its regularly scheduled mode at the next scheduled Unoccupied Mode change.
3. Press the Shoulder button again to return to the Occupied Mode.
a. 30 seconds if the room thermostat can connect
to a network.
b. 3 minutes if a network is not present.
IMPORTANT: Do not press any buttons during the initialization process. Configuration changes made during initialization are not saved.
Figure 2 illustrates the LCD during room thermostat initialization.
4. Press and hold the Shoulder button and the
Override button simultaneously for 6 seconds to set the room thermostat in the
Configuration Mode. Initially, the LCD changes to the firmware version screen (Figure 5), and then after 10 seconds the configuration menu appears (Figure 6).
5. Use the Up/Down buttons to navigate thr o ug h th e room thermostat menu. All further configuration settings must be made while in the Configuration Mode.
Note: If the configuration screen is left idle for 10 seconds, it returns to the normal operation screen.
RF:
Radio Module Firmware Number
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
Radio Ch annel Num ber
Firmware DF 0. 3. 37
RF 1. 16. 14 CH 11 GI 111.111 DI 71.40
FIG:frmwr_vrsn_ scrn
9
Loading...
+ 19 hidden pages