Johnson Controls W351P Series Catalog Page

Code No. LIT-1922405 Issued February 1, 2009
W351P Series

Electronic Proportional Plus Integral Humidity Control

The W351P Electronic Humidity Control series has proportional outputs of 0 to 10 VDC and 0 to 20 mA. Proportional plus integral (PI) control is an option to hold setpoint regardless of load shifts on a system. The control covers a range of 10 to 90% RH and has adjustments for setpoint, integration constant, throttling .
Interior of W351P

Selection Chart

Code Number
W351PP-1C Proportional W351PN-1C HE-67S3-0N0BT
W351PN-2C HE-67S3-0N00P
Note: Order the corresponding humidity transmitter separately. Staging, power, and display modules can be ordered optionally, if required.
Output Humidity
Range
Voltage: 0 to 10 VDC and Proportional Current: 0 to 20 mA
10 to 90% RH2 to 20% RH none
range, minimum output, and mode (humidification or dehumidification). This control is used in conjunction with the HE-67S3-0N0BT or HE-67S3-0N00P series of humidity transmitters. The S351 Stage Module, Y350R Power Module, and D351 Display Module can be used with the W351P.
Throttling Range
Humidity Transmitter
(included)
(included)

Features

• field selectable proportional only or proportional plus integral control
• surface or DIN rail mounting
• ten segment LED displays percent of output signal
• field selectable humidification or dehumidification mode
• minimum output adjustment
9300062fig2.eps
• 5-pin connectors eliminate wiring between modules
Applications
Use for modulating steam valves for humidification.

W351P

Technical Specifications
W351P Electronic Proportional Plus
Integral Static Pressure Control
Supply Voltage
Sensor Input Range 0 to 10 VDC, corresponding to 0 to 100% RH Proportional Output 0 to 10 VDC (550 ohm load minimum) and
Minimum Output Adjustable to 0 to 60% of full output span Output Indication A ten segment LED bar graph indicates
Control Action Direct or reverse action is jumper selectable Power Consumption 3.2 VA maximum Integration Constant Three selectable rates Fast, Medium, Slow,
Ambient Temperature
Ambient Humidity 0 to 95% RH non-condensing Case and Cover Material NEMA 1 high-impact thermoplastic
1. Only one input voltage source may be used.
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2008 Johnson Controls, Inc.
1
Transformer
Operating -30 to 150°F (-34 to 66°C)
Shipping -40 to 185°F (-40 to 85°C)
20 to 30 VAC, 50/60 Hz, Class 2
Y350R 120/240 VAC, 50/60 Hz
0 to 20 mA (600 ohm load maximum).
percentage of output
and Off position
W351P Dimensions, in. (mm)
www.johnsoncontrols.com
1 of 1
9300062fig7.eps
Loading...