The product discussed in this literature is subject to terms and conditions outlined in Johnson
Controls Inc. selling policies. The sole source governing the rights and remedies of any
purchaser of this equipment is the relevant Johnson Controls Inc. selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM
COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE
INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no
event will Johnson Controls Inc. or Eaton Electrical Inc. be responsible to the purchaser or
user in contract, in tort (including negligence), strict liability or otherwise for any special,
indirect, incidental or consequential damage or loss whatsoever, including but not limited to
damage or loss of use of equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims against the purchaser or
user by its customers resulting from the use of the information, recommendations and
descriptions contained herein.
The information contained in this manual is subject to change without notice.
Cover Photo: Johnson Controls
®
VSD Series II Drives
Warranty and Liability Information
VSD Series II
In accordance with details on next page, Johnson Controls Inc. warrants the product delivered
in the Johnson Controls shipping package to be free from defects in material and
workmanship, under normal use and service. Products that fail during this period will be
repaired or replaced at Johnson Controls discretion, with the same or a functionally equivalent
product, provided the original purchaser (A) returns the failed product, and (B) provides proof
of original date of purchase. The original purchaser of the product must obtain a Johnson
Controls Return Material Authorization (RMA) number prior to returning any defective
product. (When purchased through an Authorized Distributor, the Distributor should supply an
RMA number to their customer.)
The maximum liability of this warranty is limited to the purchase price of the product. In no
event, regardless of cause, shall Johnson Controls Inc. or Eaton Electrical Inc. be liable (a) for
penalties or penalty clauses of any description, or (b) for certification not otherwise
specifically provided herein and/or indemnification of purchaser or others for costs, damages
or expenses, each arising out of or related to the product or services of any order or (c) for any
damages resulting from loss of profits, use of products or for any incidental indirect or
consequential damages, even if advised of the possibility of such damages.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.comi
VSD Series II
Standard Warranty
Subject to the limitations and conditions stated herein, that all new Series II VSD products
shall be free from defects in material and workmanship and shall deliver their rated output as
indicated on the nameplates for a period of thirty (30) months from date of shipment.
This warranty shall provide coverage for replacement parts only and does not cover failure or
damage due to storage, installation, operation or maintenance not in conformance with
Johnson Controls recommendations and industry standard practice or due to accident,
misuse, abuse or negligence. In addition, this warranty does not cover reimbursement for
labor, including any removal/installation expenses which may be incurred in connection with
repair or replacement, unless otherwise agreed upon by Johnson Controls.
Warranty with Certified Start-Up
Provided the equipment is commissioned by an authorized EATON® service
provider (including individuals certified through Johnson Controls VSD Start-up/Commissioning Certification Training), JOHNSON CONTROLS warrants that all new Series II
VSD products shall be free from defects in material and workmanship and shall deliver their
rated output as indicated on the nameplates for a period of thirty-nine (39) months from date
of shipment.
This warranty shall provide coverage for replacement parts and on-site labor, including any
removal/installation expenses associated with the warranty claim.
Return Authorization/General Returns
Product DescriptionCredit
Open, Type 1, Type 12 Drives100%
®
Intellipass
Custom Engineered Drives and Obsolete Products0%
and Intellidisconnect Type 1, Type 12 and Type 3R Enclosed Branded Drives85%
1.JOHNSON CONTROLS agrees to accept VSD Open products for return and without
penalty or restocking charge. JOHNSON CONTROLS will issue a 100% credit—provided
the product is in its original unopened package and is returned within 120 days of receipt
of product by JOHNSON CONTROLS.
2.JOHNSON CONTROLS agrees to accept VSD Intellipass and Intellidisconnect Drives
with a 15% restocking fee provided the product is in its original unopened package and is
returned within 120 days of receipt of product by JOHNSON CONTROLS.
3.JOHNSON CONTROLS shall promptly refund or credit said customer for any and all
payments made by the buyer for such product(s). The buyer will be responsible for all
freight charges associated with products authorized for return to JOHNSON CONTROLS.
iiVSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Support Services
The goal of Johnson Controls is to ensure your greatest possible satisfaction with the
operation of our products. We are dedicated to providing fast, friendly, and accurate
assistance. Whether it’s by phone, fax, or e-mail, you can access support information
listed below.
You should contact your local Johnson Controls Sales Representative for product pricing,
availability, ordering, expediting, and repairs.
Web Site
Use the Johnson Controls Web site to find product information.
Call the Johnson Controls PSO Team if you need assistance with placing an order, stock
availability or proof of shipment, expediting an existing order, emergency shipments, product
price information and returns (including warranty returns).
Support Hours of Operation: Monday–Friday, 6:30 a.m.–5:30 p.m. CST
(No evening or weekend Customer Service hours).
If you are in the U.S. or Canada, you can take advantage of our toll-free line for technical
assistance. Technical support engineers are available for calls during regular business hours.
Johnson Controls Field Support Center
1-888-281-3792 Monday–Friday, 7:30 a.m.–5:30 p.m. CST
email: CGFieldSupportCenter@jci.com
VSD Series II
For emergency assistance, contact: Eaton Technical Resource Center
xVSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Safety
WARNING
WARNING
WARNING
CAUTION
WARNING
WARNING
VSD Series II
Definitions and Symbols
WARNING
This symbol indicates high voltage. It calls your attention
to items or operations that could be dangerous to you
and other persons operating this equipment. Read the
message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with
either of two signal words: CAUTION or WARNING, as
described below.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the
CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION (as
well as WARNING).
Hazardous High Voltage
Warnings and Cautions
This manual contains clearly marked cautions and warnings
which are intended for your personal safety and to avoid any
unintentional damage to the product or connected
appliances.
Please read the information included in cautions and
warnings carefully.
The relay outputs and other I/O-terminals may have a
dangerous control voltage present even when VSD
Series II is disconnected from mains.
Be sure not to plug the Ethernet/BACnet IP cable to the
terminal under the keypad! This might harm your
personal computer.
Be sure not to plug the Modbus TCP cable to the terminal
under the keypad! This might harm your personal
computer.
Remove external Control signal before resetting the fault to
prevent unintentional restart of the drive.
WARNING
Motor control equipment and electronic controllers are
connected to hazardous line voltages. When servicing
drives and electronic controllers, there may be exposed
components with housings or protrusions at or above
line potential. Extreme care should be taken to protect
against shock.
Stand on an insulating pad and make it a habit to use only
one hand when checking components. Always work with
another person in case an emergency occurs. Disconnect
power before checking controllers or performing
maintenance. Be sure equipment is properly grounded. Wear
safety glasses whenever working on electronic controllers or
rotating machinery.
Important Safety Information
Hazardous High Voltage
The components of the power unit of VSD Series II are
live when the AC drive is connected to mains potential.
Coming into contact with this voltage is extremely
dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor
terminals are live when VSD Series II is connected to
mains, even if the motor is not running.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.comxi
VSD Series II
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
After disconnecting the AC drive from the mains, wait
until the indicators on the keypad go out (if no keypad is
attached see the indicators on the cover). Wait 5 more
minutes before doing any work on the connections of
VSD Series II. Do not open the cover before this time has
expired. After expiration of this time, use a measuring
equipment to absolutely ensure that no voltage is
present. Always ensure absence of voltage before
starting any electrical work!
WARNING
The control I/O-terminals are isolated from the mains
potential. However, the relay outputs and other I/Oterminals may have a dangerous control voltage present
even when VSD Series II is disconnected from mains.
WARNING
Before connecting the AC drive to mains make sure that
the front and cable covers of VSD Series II are closed.
WARNING
During a ramp stop (see the Application Manual), the
motor is still generating voltage to the drive. Therefore,
do not touch the components of the AC drive before the
motor has completely stopped. Wait until the indicators
on the keypad go out (if no keypad is attached see the
indicators on the cover). Wait additional 5 minutes
before starting any work on the drive.
Important Warnings
VSD Series II AC drive is meant for fixed installations
only.
Do not perform any measurements when the AC drive is
connected to the mains.
The ground leakage current of VSD Series II AC drives
exceeds 3.5 mA AC. According to standard EN61800-5-1,
a reinforced protective ground connection must be
ensured. See chapter 1.3.
If the AC drive is used as a part of a machine, the
machine manufacturer is responsible for providing the
machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by JCI can be used.
At power-up, power brake or fault reset the motor will
start immediately if the start signal is active, unless the
pulse control for Start/Stop logic has been selected.
Furthermore, the I/O functionalistic (including start
inputs) may change if parameters, applications or
software are changed.Disconnect, therefore, the motor if
an unexpected start can cause danger.
The motor starts automatically after automatic fault
reset if the auto restart function is activated. See the
Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable,
disconnect the motor cable from the AC drive.
Do not touch the components on the circuit boards.
Static voltage discharge may damage the components.
Check that the EMC level of the AC drive corresponds to
the requirements of your supply network.
xiiVSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Additional Cautions
CAUTION
The VSD Series II AC drive must always be grounded with an
grounding conductor connected to the grounding terminal
marked with.
The ground leakage current of VSD Series II exceeds 3.5 mA
AC. According to EN61800-5-1, one or more of the following
conditions for the associated protective circuit shall be
satisfied:
a) The protective conductor shall have a cross-sectional
area of at least 10 mm
total run.
b) Where the protective conductor has a cross-sectional
area of less than 10 mm2 Cu or 16 mm2 Al, a second
protective conductor of at least the same cross-sectional
area shall be provided up to a point where the protective
conductor has a cross-sectional area not less than
10 mm2 Cu or 16 mm2 Al.
c) Automatic disconnection of the supply in case of loss of
continuity of the protective conductor.
The cross-sectional area of every protective grounding
conductor which does not form part of the supply cable or
cable enclosure shall, in any case, be not less than:
— 2.5 mm
—4 mm2 if mechanical protection is not provided. The
ground fault protection inside the AC drive protects only
the drive itself against ground faults in the motor or the
motor cable. It is not intended for personal safety.
The ground fault protection inside the Ac drive protects only
the drive itself against ground faults in the motor or the
motor cable. It is not intended for personal safety.
Due to the high capacitive currents present in the AC drive,
fault current protective switches may not function properly.
Do not perform any voltage withstand tests on any part of
VSD Series II. There is a certain procedure according to
which the tests shall be performed. Ignoring this procedure
may result in damaged product.
2
if mechanical protection is provided or
2
Cu or 16 mm2 Al, through its
VSD Series II
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.comxiii
VSD Series II
xivVSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
VSD Series II Overview
VSD Series II Overview
This chapter describes the purpose and contents of this
manual, the receiving inspection recommendations and the
VSD Series II Open Drive catalog numbering system.
How to Use this Manual
The purpose of this manual is to provide you with information
necessary to install, set and customize parameters, start up,
troubleshoot and maintain the VSD Series II variable speed
drive (VSD). To provide for safe installation and operation of
the equipment, read the safety guidelines at the beginning of
this manual and follow the procedures outlined in the
following chapters before connecting power to the VSD
Series II VSD. Keep this operating manual handy and
distribute to all users, technicians and maintenance
personnel for reference.
Receiving and Inspection
The VSD Series II VSD has met a stringent series of factory
quality requirements before shipment. It is possible that
packaging or equipment damage may have occurred during
shipment. After receiving your VSD Series II VSD, please
check for the following:
Check to make sure that the package includes the Installation
Manual (LIT-12011772), Quick Start Guide (LIT-12011771)
and accessory packet. The accessory packet includes:
●
Rubber grommets
●
EMC grounding clamps for power cables
●
Control cable grounding clamps
●
EMC jumper locking clips
●
M4 screw for EMC level change (FS7 only)
●
Additional grounding screw
●
Real time clock battery
●
UL conduit plate
Inspect the unit to ensure it was not damaged during
shipment.
Make sure that the part number indicated on the nameplate
corresponds with the catalog number on your order.
If shipping damage has occurred, please contact and file a
claim with the carrier involved immediately.
Note: Do not destroy the packing. The template printed on
the protective cardboard can be used for marking the
mounting points of the VSD Series II VSD on the wall
or in a cabinet.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com1
VSD Series II Overview
Rating Plates
Manuals
Carton Label
2VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
VS-XMX-B2 = 1 RO (NC/NO), 1 RO (NO), 1 Thermistor
VS-XMX-B4 = 1 AI (mA isolated), 2 AO (mA isolated)
VS-XMX-B5 = Card-3 Relay Dry Contact
VS-XMX-B9 = 1 RO (NO), 5 DI 42–240 Vac Input
VS-XMX-BF = Expander IO—1*AO, 1*DO, 1*RO
VS-XMX-CS = SA Bus (JC-VSD only)
VS-XMX-C4 = Lon Works Comm Card
I/O Options in Slot B
(Ordered Separately)
VS-XMX-F1 = 3 relay (spare/replacement part only—
not option w/standard VSD)
VS-XMX-F2 = 2 relay and 1 Thermistor—not available
with L3/L4 Pilot light option replaces standard
Relay1 pcb in Slot B and Fault Relay function
Enclosure Rating
1 = Nema-UL Type 1 (IP21)
2 = Nema-UL Type 12 (IP54)
4 = Flange Mtd for FS8 and
FS9 (IP00)
Drive Style
0 = Open
RS-485 Optional Comms Slot D and E
0 = STD BACnet/Modbus
S = SA Bus, CS card (added to JC-VSD)
L = Lon Works, C4 Card (Open Only)
1
Revision
B = Rev 2 (Americas)
D = Rev 2 (Canada)
1
VSD Series II Open Drives
VSD Series II Overview
Note
1
Solutions pending. Check with your Johnson Controls representative for availability.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com3
VSD Series II Overview
Power Ratings and Product Selection
VSD Series II Drives—208–230 Volt
NEMA Type 1/IP21 or NEMA Type 12/IP54
Drive Rated Current and hp
De-Rated
Drive Rating
FS
Frame
Size
Low Overload
Full Load
Amps at 40°C
230V
60 Hz
Horsepower
Drive
Input
Amps
NEC Motor
60 Hz
230V Amps
1
Low Overload
Full Load
Amps at 50°C
FS43.70.753.23.22.60.55VS3D72x0B-00000
4.8 14.34.23.7 0.75VS4D82x0B-00000
6.61.5664.61.1VS6D62x0B-00000
8 27.26.86.61.5VS8D02x0B-00000
11 39.79.682.2 VS0112x0B-00000
12.5410.9N/A93VS0122x0B-00000
FS518 516.115.212.54VS0182x0B-00000
247.521.722185.5VS0242x0B-00000
31 1027.728257.5 VS0312x0B-00000
FS648 1543.8423111VS0482x0B-00000
622057544815VS0622x0B-00000
FS7752569686218.5VS0752x0B-00000
88 3082.1807522VS0882x0B-00000
10540991048830VS1052x0B-00000
FS81405013313011437VS1402x0B-00000
170 6016315414045VS1702x0B-00000
2057519819217055VS2052x0B-00000
FS926110025624821175VS2612x0B-00000
310125303N/A25190VS3102x0B-00000
Notes
1
For sizing reference, full-load motor running currents—UL508C.
2
If SA-Bus is required, replace -00000 with -S0000.
Assigned
Motor Ratingsx = Can Be:
Open Drive
kW
1 = N1 = IP21
2 = N12 = IP54
230V
50 Hz
Catalog Number
2
4VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
VSD Series II Overview
VSD Series II Drives—380–480 Volt
NEMA Type 1/IP21 or NEMA Type 12/IP54
Assigned
Motor Ratingsx = Can Be:
Open Drive
kW
1 = N1 = IP21
2 = N12 = IP54
400V
50 Hz
Catalog Number
1
De-Rated
Low Overload
Full Load
Amps at 50°C
FS
Frame
Size
Drive Input Rated Current and hp
Low Overload
Full Load
Amps at 40°C
460V
60 Hz
Horsepower
Drive
Input
Amps
NEC Motor
60 Hz
460V Amps
FS43.41.53.432.61.1VS3D44x0B-00000
4.8 2 4.63.43.41.5VS4D84x0B-00000
5.6 3 5.44.84.32.2VS5D64x0B-00000
8.05 8.17.65.63.0VS8D04x0B-00000
9.6 5 9.3N/A84VS9064x0B-00000
127.511.3119.65.5VS0124x0B-00000
FS516 10 15.414127.5 VS0164x0B-00000
23 15 21.3211611VS0234x0B-00000
31 20 28.4272315VS0314x0B-00000
FS638 25 36.73431 18.5VS0384x0B-00000
46 30 43.6403822VS0464x0B-00000
6140 58.2524630VS0614x0B-00000
FS772 50 67.56561 37VS0724x0B-00000
87 60 85.3777245VS0874x0B-00000
105 75 100.6968755VS1054x0B-00000
FS8140 100 139.412410575VS1404x0B-00000
170125 166.515614090VS1704x0B-00000
205150 200180170110VS2054x0B-00000
FS9261 200 258240205 132VS2614x0B-00000
310 250 303302251 160VS3104x0B-00000
2
VSD Series II Variable Speed Drive Option Boards
Assigned to
Option Board
Part Number
Control
Module Slot:Description
VS-XMX-B1D or EExpanded 6 digital output—two outputs are programmable as digital inputs or outputs
VS-XMX-B2D or EExpanded relay outputs—two programmable relays (each with a NO and NC contact) and thermistor input
VS-XMX-B4D or EExpanded analog inputs and outputs—one analog input and two analog outputs (isolated)
VS-XMX-B5D or EExpanded relay outputs—contains three programmable relays (one NO contact each)
VS-XMX-B9D or EAccepts up to five AC inputs (42–240 Vac) and one relay output (NO)
VS-XMX-BFD or EExpanded analog and digital output—one analog, one digital, and one relay output (NO)
®
VS-XMX-C4D or ELonWorks
communication
VS-XMX-CSD or ESA-Bus communication
Notes
1
For sizing reference, full-load motor running currents—UL508C.
2
If SA-Bus is required, replace -00000 with -S0000.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com5
HVAC Application
HVAC Application
The Johnson Controls VSD Series II drive contains a
preloaded application for instant use.
The parameters of this application are listed in the complete
Application Manual. The Application Manual can be found at
http://www.johnsoncontrols.com —> HVAC Controls —>
Variable Speed Drives.
Specific Functions of Johnson Controls
VSD Series II Application
The Johnson Controls VSD Series II application is an
easy-to-use application for not only basic pump and fan
applications where only one motor and one drive is needed,
but also offers extensive possibilities for PID control.
Features
●
Startup Wizard for extremely fast setup for basic pump or
fan applications
●
Mini-Wizards to ease the setup of applications
●
Hand/Off/Auto button for easy change between Hand
(keypad), OFF, and Auto (Remote control) place. The auto
control place is selectable by parameter (I/O or Fieldbus)
●
Control page for easy operation and monitoring of the
most essential values
●
Run interlock input (damper interlock). Drive will not start
before this input is activated
●
Maximum output frequency 320 Hz
●
Real-time clock and timer functions available. Possible to
program three time channels to achieve different functions
on the drive (for example, Start/Stop and Preset
frequencies)
●
External PID-controller available. Can be used to control a
valve using the drive’s I/O, for example
●
Sleep mode function which automatically enables and
disables drive running with user defined levels to save
energy
●
Two-zone PID-controller (two different feedback signals;
minimum and maximum control)
●
Two setpoint sources for the PID-control. Selectable with
digital input
●
PID setpoint boost function
●
Feed forward function to improve the response to the
process changes
●
Process value supervision
●
Multi-pump control
●
Pressure loss compensation for compensating pressure
losses in the pipework, for example, when sensor is
incorrectly placed near the pump or fan
6VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Example of Control Connections
Slot A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
A
+10V
AI–1+
V
in
AI–2+
AI–2–
24V
out
GND
DIN1
DIN2
DIN3
24V
out
GND
DIN4
DIN5
DIN6
AO–1+
AO–1–
DATA–
Reference Output
Analog Input Voltage (Range 0–10 Vdc)
(can be programmed to current 4–20 mA)
Analog Output Common (Ground)
Analog Input Common
PI Setpoint or Feedback
Control Voltage Output (0.1A max.)
I/O Ground
START/STOP (Contact closed = start)
External Fault (Closed = fault)
Run Interlock Permissive IP Interlock
(Closed = OK)
DIN1–DIN6 Common
Control Voltage Output (0.1A max.)
I/O Ground
Fire Mode (Contact closed = fire mode)
Force Bypass (Contact closed = bypass)
DIN1–DIN6 Common
Output Frequency (0–20 mA)
Analog Output Common (Ground)
RS-485 DATA–
Speed Select 0–100% (Preset speed)
U (T1)
V (T2)
W (T3)
R+
R–
L1
L2
L3
Three-Phase Input
Input
(Single-Phase not available)
Three-Phase
Output
DB
Chopper
Terminal
Factory Default Signal
Resistor
Analog Input Current (Range 4–20 mA)
(can be programmed to voltage 0–10 Vdc)
PI Setpoint or Feedback
B
DATA+
RO1 Bypass Run
RO2 Drive Run
RO3 Fault
24 Vdc/8A
250 Vac/8A
125 Vdc/0.4A
Relay Board 1
Default Signal
21
22
23
24
25
26
32
33
Slot B
Analog
RS-485 DATA+
Factory
Jumper
COM
CMB
30
24 VdcinAuxiliary Input Voltage
Circuit
Breaker
Optional
Motor
RJ-45
BACnet/IP Ethernet Industrial Protocol
Modbus/TCP Transmission Control Protocol (Ethernet Based)
5% DC Link
Reactor
Programmable BACnet,
Modbus, FLN, N2
ON
CURRENT
CURRENT
CURRENT
RS485
AO1
AI2
AI1
OFF
VOLTAGE
VOLTAGE
VOLTAGE
Test
Control Connections
HVAC Application
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com7
Keypad of the Drive
Switching Between
Drive and Bypass
Move Cursor Left
Back when Pressed
for two Seconds
Stop Button/Fault ResetStart Button
Change Control Place
Between Hand-Off-Auto
Move Cursor Right
Increase Value
Scroll Menu Up
Decrease Value
Scroll Menu Down
Enter Menu
Confirm Selection
Back Fault Reset
Move Cursor Left
Stop ButtonStart Button
Change Control Place
Between Hand-Off-Auto
Move Cursor Right
Increase Value
Scroll Menu Up
Decrease Value
Scroll Menu Down
Enter Menu
Confirm Selection
Keypad of the Drive
The control keypad is the interface between the Johnson
Controls VSD Series II frequency converter and the user.
With the control keypad it is possible to control the speed of
a motor, to supervise the state of the equipment and to set
the frequency converter’s parameters.
US Keypad Buttons
There are two different keypads used with the VSD Series II
drive. The North American Keypad is slightly different than
the EMEA Keypad. Functionality is quite similar. The EMEA
keypad does not support the bypass functionality commonly
used in the United States.
EMEA Keypad Buttons
8VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Keypad Display
Status Field
STOP/RUN
STOP
E-EnergyHandI/O
Direction
Run Mode
Hand/Off/Auto
Control Place
PC/IO/KEYPAD/FIELDBUS
Location Field
(Parameter ID number and
current menu location)
Activated Group/Item
Press OK to Enter
The keypad display indicates the status of the motor and the drive and any irregularities in
motor or drive functions. On the display, the user sees information about his present location
in the menu structure and the item displayed.
Main Menu
The data on the control keypad are arranged in menus and submenus. Use the up and down
arrows to move between the menus. Enter the group/item by pressing the OK button and
return to the former level by pressing the Back/Reset button.
The Location field indicates your current location. The Status field gives information about the
present status of the drive. See “Control Connections” on Page 7.
Main Menu
Keypad of the Drive
Using the Graphical Keypad
Editing Values
Change value of a parameter following the procedure below:
1.Locate the parameter.
2.Enter the Edit mode.
3.Set new value with the up/down arrow buttons. You can also move from digit to digit with
the arrow buttons left/right if the value is numerical and then change the value with the
up/down arrow buttons.
4.Confirm change with OK button or ignore change by returning to previous level with Back/
Reset button.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com9
Keypad of the Drive
STOPREADYI/O
STOPREADYI/O
OKOK
OK
STOPREADYI/O
OR:
BACK
RESET
Editing Values on Graphical Keypad
STOPREADYI/O
HOA Control Button
The HOA (Hand-Off-Auto) button is used for two functions:
to quickly access the Control page and to easily change
between the Hand (Keypad), Off, and Auto (Remote) control
places.
Control Place
The control place is the source of control where the drive can
be started and stopped. Every control place has its own
parameter for selecting the frequency reference source. In
the HVAC drive, the Hand control place is always the keypad.
The Auto control place is determined by parameter P2.1.1
(Keypad, I/O Terminal, I/O three-wire, or Fieldbus CTRL). The
selected control place can be seen on the status bar of the
keypad.
Local Control
The keypad is always used as control place while in hand
control. Hand control has higher priority than auto control.
Therefore, if, for example, bypassed by parameter P2.1.17
through digital input while in Remote, the control place will
still switch to Keypad if Hand is selected. Switching between
Hand, Off, and Auto Control can be done by pressing the
HOA button on the keypad.
STOPREADYI/O
Changing Control Place
Change of control place from Hand to Auto (keypad).
1.Anywhere in the menu structure, push the HOA button.
2.Push the arrow up or the arrow down button to select Hand/Off/Auto and confirm with the OK button.
3.On the next display, select Hand, Off, or Auto and again
confirm with the OK button.
4.The display will return to the same location as it was
when the HOA button was pushed. However, if the
Remote control place was changed to Hand (Keypad)
you will be prompted for keypad reference.
10VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Accessing the Control Page
HOA
STOPREADYKeypad
OK
OK
STOPREADYKeypad
OK
STOPREADYI/O
The Control page is meant for easy operation and monitoring of the most essential values.
1.Anywhere in the menu structure, push the HOA button.
2.Push the arrow up or the arrow down button to select Control page and confirm with the OK button.
3.The control page appears. If keypad control place and keypad reference are selected to
be used, you can set the Keypad reference after having pressed the OK button. If other
control places or reference values are used, the display will show Frequency reference
which is not editable. The other values on the page are Multimonitoring values. You can
choose which values appear here for monitoring (for this procedure, see Application
Manual).
Accessing Control Page
Keypad of the Drive
STOPREADYKeypad
0.00 Hz
Edit
0.00 Hz
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com11
Keypad of the Drive
Copying Parameters
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to
another drive. Finally, the parameters are downloaded to the new drive, restoring them from
the keypad.
Before any parameters can successfully be copied from one drive to another, the drive has to
be stopped when the parameters are downloaded.
●
First, go into User settings menu and locate the Parameter backup submenu. In the
Parameter backup submenu, there are three possible functions to be selected:
1.Restore factory defaults will re-establish the parameter settings originally made at the
factory.
2.By selecting Save to keypad you can copy all parameters to the keypad.
3.Restore from keypad will copy all parameters from keypad to a drive.
Parameter Copy
STOPREADYKeypad
STOPREADYKeypadSTOPREADYKeypad
Note: If the keypad is changed between drives of different sizes, the copied values of these
parameters will not be used:
Motor nominal current (P2.1.12)
Motor nominal voltage (P2.1.13)
Motor nominal speed (P2.1.15)
Motor power factor (P2.1.16)
Motor nominal frequency (P2.1.14)
Service factor (P2.1.18)
Switching frequency (P2.7.7)
Motor current limit (P2.1.17)
Maximum frequency (P2.1.9)
12VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Help Texts
STOPREADYI/OSTOPREADYI/O
OKOK
STOPREADYI/O
Basic Sett ings
Motor Nom Voltg
230.00 V
Motor Nom Speed
1430 rpm
The graphical keypad features instant help and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms, and the Startup Wizard.
Help Text Example
Adding Item To Favorites
You might need to refer to certain parameter values or other items often. Instead of locating
them one by one in the menu structure, you may want to add them to a folder called Favorites
where they can easily be reached.
Keypad of the Drive
Adding Item To Favorites
STOPREADYI/OSTOPREADYI/OSTOPREADYI/O
Motor Nom Freq
50.00 Hz
Motor N om Freq
Edit
Help
Add to favorites
Motor N om Fr eq
was added to
favorites. Press OK
to continue.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com13
Keypad of the Drive
Monitor
Multi-Monitor
On the multi-monitor page, you can collect nine values that you wish to monitor.
Multi-Monitoring Page
STOPREADYI/OSTOPREADYI/O
STOPREADYI/OSTOPREADYI/O
Change the monitored value by activating the value cell (with arrow buttons left/right) and
clicking OK. Then choose a new item on the Monitoring values list and click OK again.
14VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
VSD Series II—Startup
BACK
RESET
Startup Wizard
In the Startup Wizard, you will be prompted for essential
information needed by the drive so that it can start
controlling your process. In the Wizard, you will need the
following keypad buttons:
Left/Right arrows. Use these to easily move
between digits and decimals.
Up/Down arrows. Use these to move between
options in menu and to change value.
OK
Once you have connected power to your Johnson Controls
VSD Series II frequency converter, follow these instructions
to easily set up your drive.
1
2
3
4
5
6
Note
1
OK button. Confirm selection with this button.
Back/Reset button. Pressing this button, you can
return to the previous question in the Wizard. If
pressed at the first question, the Startup Wizard will
be cancelled.
Run Startup WizardYes
Language SelectDepends on language package
Daylight Saving
1
Time
1
Day
1
Year
These questions appear if battery is installed.
1
No
Russia
US
EU
OFF
hh:mm:ss
dd.mm.
yyyy
VSD Series II—Startup
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by pressing and
holding the back/reset button for two seconds. The Startup
Wizard will appear upon next power up.
ApplicationVSD Series II Standard
PID
Multi-Pump
BypassEnabled
Disabled
Motor Nominal CurrentMin: 0.26A
Max: Drive Dependent
Motor Nominal VoltageMin: 180.0V
Max: 690.0V
Motor Nominal FrequencyMin: 8 Hz
Max: 320 Hz
Motor Nominal SpeedMin: 24 RPM
Max: 19200 RPM
Min FrequencyMin: 0 Hz
Max: 60 Hz
Max FrequencyMin: 12 Hz
Max: 320 Hz
Accel Time 1Min: 0.1s
Max: 3000s
Decel Time 1Min: 0.1s
Max: 3000s
StartSourceHandKeypad
FieldbusCTRL
I/O Three-Wire
I/O Terminal
StartSourceAutoI/O Terminal
Keypad
FieldbusCTRL
I/O Three-Wire
SpeedSetptHandKeypad Ref
P1D1 Activated
AI1 + AI2
AI2
AI1
Fieldbus
SpeedSetptAutoPID1 Activated
AI1 + AI2
AI2
AI1
Fieldbus
Keypad Ref
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com15
VSD Series II—Startup
PID Mini-Wizard
The PID Mini-Wizard is activated in the Quick Setup menu.
This Wizard presupposes that you are going to use the PID
controller in the “one feedback/one setpoint” mode. The
control place will be I/O A and the default process unit “%”.
The PID Mini-Wizard asks for the following values to be set:
1
2
3
FeedBack1 SrceAI2
AI1
Not Used
ProceDataIn8
ProceDataIn7
ProceDataIn6
ProceDataIn5
ProceDataIn4
ProceDataIn3
ProceDataIn2
ProceDataIn1
AI6
AI5
AI4
AI3
Process Unit Selection(Several Selections)
Process Unit Min—
Multi-Pump
If Multi-Pump is the selected application, parameter group
2.16 will be visible in the menu structure. Default values may
need to be adjusted to meet your application needs.
Parameter
Group Name
Parameter Group 2.16:
Multi-Pump
Parameter
Number
P2.16.1Number of motors
P2.16.2Interlock function
P2.16.3Include FC
P2.16.4Autochange
P2.16.5Autochange interval
P2.16.6Autochange frequency limit
P2.16.7Autochange motor limit
P2.16.8Bandwidth
P2.16.9Bandwidth delay
Parameter
Name
4
5
6
7
Process Unit Max—
P-GainMin: 0%
Max: 200%
Integration TimeMin: 0.00s
Max: 600.00s
SetPT1 SourceKeypad SP1
Not Used
ProceDataIn8
ProceDataIn7
ProceDataIn6
ProceDataIn5
ProceDataIn4
ProceDataIn3
ProceDataIn2
ProceDataIn1
AI6
AI5
AI4
AI3
AI2
AI1
16VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Menu Structure
Keypad Menus
MonitorBasicDiagnosticsActive Faults
Timer FunctionsReset Faults
MultimonitorFault History
ParametersBasic ParametersTotal Counters
Analog InputsTrip Counters
Digital InputsSoftware Info
Analog OutputsI/O & HardwareBasic I/O
Digital OutputsSlot D
Drive ControlSlot E
Motor ControlReal Time Clock
ProtectionsPower Unit Settings
Fixed FrequenciesKeypad
Fire ModeRS485
Multi-Pump—
BrakingEthernet
FieldbusUser Settings—
Second Parameter SetFavorites—
Timer Functions
Menu St ructure
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com17
Parameter Functions
Parameter Functions
Basic Monitoring Functions
Parameter
NumberParameter NameUnitIDDescription
V1.1.1Output frequencyHz1Output Frequency of the Drive
V1.1.2Frequency ReferenceHz25Frequency Reference to Motor Control
V1.1.3Motor Speed RPMrpm2Motor speed in rpm
V1.1.4Motor CurrentA3Motor Current
V1.1.5Motor Torque%4Calculated Shaft Torque
V1.1.6Motor Power %%5Total Power Consumption of AC Drive
V1.1.7Motor VoltageV6Motor Voltage
V1.1.8DC-Link VoltageV7DC-Link Voltage
V1.1.9Unit Temperature°C8Heatsink temperature
V1.1.10Motor Temperature%9Calculated Motor Temperature
V1.1.11Analog Input 1%13Analog input signal scaled according to the range or custom min and max chosen
V1.1.12Analog Input 2%14Analog input signal scaled according to the range or custom min and max chosen
V1.1.13Analog Output 1%26Value of analog output in % of the signal range
V1.1.14DI1, DI2, DI3Binary15This monitor value shows the status of the I/Os
V1.1.15DI4, DI5, DI6Binary16This monitor value shows the status of the I/Os
V1.1.16PID1 Setpoint%20Setpoint value fed to the PID controller in process units
V1.1.17PID1 Feedback%21Feedback Value fed to the PID controller in process units
V1.1.18PID1 Error%22Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.1.19PID2 Setpoint%83Setpoint value fed to the PID controller in process units
V1.1.20PID2 Feedback%84Feedback Value fed to the PID controller in process units
V1.1.21PID2 Error%85Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.1.22Drive Status WordBitCoded43Bitcoded status of the drive. B1=Ready, B2=Run, B3=Fault, B6=RunEnable, B7=Alarm Active,
V1.1.23Motor Speed %%1360Percent of full motor speed
V1.1.24Last Active FaultNum37The fault code of the latest activated fault that has not been reset
in the I/O config menu
in the I/O config menu
B12=Run Request, B13=Motor Regulator Active
18VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Parameter Functions
Timer Monitoring Functions
Parameter
NumberParameter NameUnitIDDescription
V1.2.1TC1, TC2, TC3 ON/OFF1703This monitor value shows the status of the time channels
V1.2.2Interval 1ON/OFF1704This monitor value shows the status of the timer interval
V1.2.3Interval 2ON/OFF1705This monitor value shows the status of the timer interval
V1.2.4Interval 3ON/OFF1706This monitor value shows the status of the timer interval
V1.2.5Interval 4ON/OFF1707This monitor value shows the status of the timer interval
V1.2.6Interval 5ON/OFF1708This monitor value shows the status of the timer interval
V1.2.7Timer 1sec1709If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.2.8Timer 2sec1710If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.2.9Timer 3sec1711If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.2.10Real Time Clockh/m/s1712Time of Day (Military Time)
Multi-Monitor Functions
Parameter
NumberParameter NameUnitIDDescription
V1.3.x.1Drive Status WordBinary43Bitcoded status of the drive. B1=Ready, B2=Run, B3=Fault, B6=RunEnable, B7=Alarm Active,
V1.3.x.2Analog Input 1%13Analog input signal scaled according to the range or custom min and max chosen
V1.3.x.3Analog Input 2%14Analog input signal scaled according to the range or custom min and max chosen
V1.3.x.4Analog Output 1%26Value of analog output in % of the signal range
V1.3.x.5AutoChangeN/A1720No Function
V1.3.x.6DC-Link VoltageV7DC-Link Voltage of the Drive
V1.3.x.7DI1, DI2, DI3Binary15This monitor value shows the status of the I/Os
V1.3.x.8DI4, DI5, DI6Binary16This monitor value shows the status of the I/Os
V1.3.x.9RO1, RO2, RO3Binary17This monitor value shows the status of the I/Os
V1.3.x.10Frequency ReferenceHz25Frequency Reference to Motor Control
V1.3.x.11Interval 1ON/OFF1704This monitor value shows the status of the timer interval
V1.3.x.12Interval 2ON/OFF1705This monitor value shows the status of the timer interval
V1.3.x.13Interval 3ON/OFF1706This monitor value shows the status of the timer interval
V1.3.x.14Interval 4ON/OFF1707This monitor value shows the status of the timer interval
V1.3.x.15Interval 5ON/OFF1708This monitor value shows the status of the timer interval
V1.3.x.16Motor CurrentA3Motor Current
V1.3.x.17Motor Power KWKW73Calculated Power Consumption of the Motor
V1.3.x.18Motor Power %%5Total Power Consumption of AC Drive
V1.3.x.19Motor Speed RPMrpm2Motor speed in rpm
V1.3.x.20Motor Torque%4Calculated Shaft Torque
V1.3.x.21Motor VoltageV6Motor Voltage
B12=Run Request, B13=Motor Regulator Active
in the I/O config menu
in the I/O config menu
Note: The “x” in the parameter number represents the assembled monitoring window. Values range from 1 to 9.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com19
Parameter Functions
Multi-Monitor Functions, continued
Parameter
NumberParameter NameUnitIDDescription
V1.3.x.22Motor RunningBinary30This monitor value shows if the motor is running
V1.3.x.23Motor Temperature%9Calculated Motor Temperature
V1.3.x.25PID1 StatusWords24This monitor value shows if the PID is Active
V1.3.x.26PID2 StatusWords87This monitor value shows if the PID is Active
V1.3.x.27PID1 Error%22Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.3.x.28PID1 Feedback%21Feedback Value fed to the PID controller in process units
V1.3.x.29PID1 Output%23Output value delivered from the PID controller in process units
V1.3.x.30PID1 Setpoint%20Setpoint value fed to the PID controller in process units
V1.3.x.31PID2 Error%85Error value of the PID controller. Deviation of the feedback from setpoint in process units.
V1.3.x.32PID2 Feedback%84Feedback Value fed to the PID controller in process units
V1.3.x.33PID2 Output%86Output value delivered from the PID controller in process units
V1.3.x.34PID2 Setpoint%83Setpoint value fed to the PID controller in process units
V1.3.x.35Real Time Clockh/m/s1712Time of Day (Military Time)
V1.3.x.36Run Request ChainWords1361This monitor value shows the status of a run request
V1.3.x.37TC1, TC2, TC3ON/OFF1703This monitor value shows the status of the time channels
V1.3.x.38Timer 1sec1709If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.3.x.39Timer 2sec1710If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.3.x.40Timer 3sec1711If the timer has been activated, this monitor value shows the remaining time of the timer.
V1.3.x.41Unit Temperature°C8Heatsink temperature
V1.3.x.42Motor Speed %%1360Motor Speed in %
V1.3.x.43Last Active FaultNum37The fault code of the latest activated fault that has not been reset
V1.3.x.44Run Time HoursHrs1364Drive Run Time in Hours
V1.3.x.45Power On HoursHrs1363Power On Time in Hours
V1.3.x.46Frequency ReferenceHz1365Frequency Reference to Motor Control
V1.3.x.53Energy Countervaries2291Amount of Energy taken from the Supply Network, No Reset
V1.3.x.55Run Time a d hh:minN/ARun Time of Drive
V1.3.x.56Power On Timea d hh:minN/APower On Time of Drive
V1.3.x.57Start Command CounterNum2295The number of times the power unit has been started
V1.3.x.58Energy Countervaries2296Resettable Energy Counter
V1.3.x.60Run TimeN/AN/AN/A
V1.3.x.61Run TimeN/AN/AN/A
V1.3.x.62Run TimeN/AN/AN/A
V1.3.x.63Power On TimeN/AN/AN/A
V1.3.x.64Power On TimeN/AN/AN/A
V1.3.x.65Power On TimeN/AN/AN/A
Note: The “x” in the parameter number represents the assembled monitoring window. Values range from 1 to 9.
20VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Parameters
Basic Parameters
Basic Settings
Parameter
NumberParameter Name
P2.1.1 ApplicationN0202130 = Standard
P2.1.2 ByPassN0112140 = Disabled
P2.1.3 HOA Control StcN01013590 = Keypad Ctrl
P2.1.4 Start Srce HandN03013000 = Keypad
P2.1.5 Speed Setpt HandN27213012 = Keypad Ref
P2.1.6 Start Srce AutoN03113020 = Keypad
P2.1.7 Speed Setpt Auto
(see P2.1.5)
P2.1.8 Min FrequencyN0,00 HzMax frequency 12,00 Hz101See Range
P2.1.9 Max FrequencyNMin frequency 320,00 Hz50,00/60,00102See Range
P2.1.10 Accel Time 1Y0.1 s3000,0 s60,0 s103See Range
P2.1.11 Decel Time 1Y0.1 s3000,0 s60,0 s104See Range
P2.1.12 Motor Nom CurrntNvariesvariesvaries113See Range
P2.1.13 Motor Nom VoltgN180,0 V690,0 Vvaries110See Range
P2.1.14 Motor Nom FreqN12,00 Hz320,00 Hz50,00/60,00111See Range
P2.1.15 Motor Nom SpeedN24 rpm19200 rpm1440/1750112See Range
P2.1.16 MotorPowerFactorN0,301,000,82120See Range
P2.1.17 Current LimitNvariesvariesvaries107See Range
2 = Run enable Missing!
3 = Vibration Cutout
4 = High motor temperature
5 = Freeze Stat Trip
6 = Low Pressure detect
7 = High Pressure detect
8 = Low water detect
9 = Smoke detect
10 =3-wire Off
11 = Damper Interlock
12 = Open Safety
13 = Seal Leakage
14 = Valve sequence
15 = Megger Shutdown
16 = High Pump Temp
2 = Run enable Missing!
3 = Vibration Cutout
4 = High motor temperature
5 = Freeze Stat Trip
6 = Low Pressure detect
7 = High Pressure detect
8 = Low water detect
9 = Smoke detect
10 =3-wire Off
11 = Damper Interlock
12 = Open Safety
13 = Seal Leakage
14 = Valve sequence
15 = Megger Shutdown
16 = High Pump Temp
Parameters
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com31
2 = Run enable Missing!
3 = Vibration Cutout
4 = High motor temperature
5 = Freeze Stat Trip
6 = Low Pressure detect
7 = High Pressure detect
8 = Low water detect
9 = Smoke detect
10 =3-wire Off
11 = Damper Interlock
12 = Open Safety
13 = Seal Leakage
14 = Valve sequence
15 = Megger Shutdown
16 = High Pump Temp
Analog Outputs
Analog Output 1
Parameter
NumberParameter Name
P2.4.1.1 AO1 FunctionY0152100500 = Forced 0%
P2.4.1.2 AO1 Filter TimeY0,00 s300,00 s1,00 s10051See Range
P2.4.1.3 AO1 Min SignalY010100520 = 0mA / 0V
P2.4.1.4 AO1 MinScaleYvariesvaries0,010053See Range
P2.4.1.5 AO1 MaxScaleYvariesvaries0,010054See Range
1 = Time channel 1
2 = Time channel 2
3 = Time channel 3
Timer 1
Parameter
NumberParameter Name
P2.16.6.1 DurationY0 s72000 s0 s1695See Range
P2.16.6.2 Assign to channelY03016960 = Not used
Change
in RunMin.Max.DefaultIDValues
Timer 2
Parameter
NumberParameter Name
P2.16.7.1 DurationY0 s72000 s0 s1697See Range
P2.16.7.2 Assign to channel
(see above)
Change
in RunMin.Max.DefaultIDValues
Y03016980 = Not used
Timer 3
Parameter
NumberParameter Name
P2.16.8.1 DurationY0 s72000 s0 s1699See Range
P2.16.8.2 Assign to channel
(see above)
Change
in RunMin.Max.DefaultIDValues
Y03017000 = Not used
1 = Time channel 1
2 = Time channel 2
3 = Time channel 3
1 = Time channel 1
2 = Time channel 2
3 = Time channel 3
1 = Time channel 1
2 = Time channel 2
3
=
Time chan
nel 3
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com55
I/O and Hardware
I/O and Hardware
Basic I/O
Basic Parameters
Parameter
NumberParameter NameUnitIDDescription
M4.1.1 Digital Input 1BinaryN/AState of digital input signal
0 =Off
1 =On
M4.1.2 Digital Input 2BinaryN/AState of digital input signal
0 =Off
1 =On
M4.1.3 Digital Input 3BinaryN/AState of digital input signal
0 =Off
1 =On
M4.1.4 Digital Input 4BinaryN/AState of digital input signal
0 =Off
1 =On
M4.1.5 Digital Input 5BinaryN/AState of digital input signal
0 =Off
1 =On
M4.1.6 Digital Input 6BinaryN/AState of digital input signal
0 =Off
1 =On
M4.1.7 Analog Input 1 ModeUnitsN/AMode of analog input signal
M4.1.8 Analog Input 1%N/AState of analog input signal
M4.1.9 Analog Input 2 ModeUnitsN/AMode of analog input signal
M4.1.10 Analog Input 2%N/AState of analog input signal
M4.1.11 Analog Output 1 Mode UnitsN/AMode of analog output signal
M4.1.12 Analog Output 1%N/AState of analog output signal
M4.1.13 Relay Output 1BinaryN/AState of digital output signal
0 =Off
1 =On
M4.1.14 Relay Output 2BinaryN/AState of digital output signal
0 =Off
1 =On
M4.1.15 Relay Output 3BinaryN/AState of digital output signal
0 =Off
1 =On
56VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Real-Time Clock
Parameter
NumberParameter NameUnitIDDescription
M4.4.1 Battery stateNumeric2205Status of battery
1 = Not installed
2 = Installed
3 = Need to change
I/O and Hardware
Parameter
NumberParameter Name
P4.4.2 TimeYxx:xx:xxxx:xx:xx—2201See Range
P4.4.3 DateYxx.xxxx.xx20112202See Range
P4.4.4 YearY2011999920112203See Range
P4.4.5 Daylight savingY14322041 =Off
Change In
RunMin.Max.DefaultIDDescription
Power Unit Settings
Fan Control
Parameter
NumberParameter NameUnitIDDescription
M4.5.1.2 Fan speed%848Fan Speed Percentage
Parameter
NumberParameter Name
P4.5.1.3 Fan StopY01Binary8261 = Disabled
Sine Filter
Parameter
NumberParameter Name
P4.5.4.1 Sine filterY01TextN/A1 = Disabled
Change In
RunMin.Max.DefaultIDDescription
Change In
RunMin.Max.DefaultIDDescription
2 =EU
3 =US
4 = Russia
2 = Enabled
2 = Enabled
Keypad
Parameter
NumberParameter Name
P4.6.1 Time Out TimeY0 min.60 min1 minN/ASee Range
P4.6.2 Default PageY043 N/A0 =None
P4.6.3 Menu IndexY0 sec.255 sec.0N/ASee Range
P4.6.4 ContrastY30%70%40%N/ASee Range
P4.6.5 Backlight TimeY0 min.60 min5 minN/ASee Range
Change In
RunMin.Max.DefaultIDDescription
1 = Enter Menu Index
2 = Main Menu
3 = Control Page
4 = MultiMonitor
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com57
I/O and Hardware
Common Settings
RS-485
Parameter
NumberParameter Name
P4.7.1.1 ProtocolN03Binary22080 = No Protocol
Ethernet
Parameter
NumberParameter Name
P4.8.1.1 IP Address ModeN121 N/A1 = DHCP with Auto IP
P4.8.1.2 IP AddressN02550N/ASee Range
P4.8.1.3 Subnet MaskN02550N/ASee Range
P4.8.1.4 Default GatewayN02550N/ASee Range
Parameter
NumberParameter NameUnitIDDescription
M 4.8.1.5 MAC AddressN/AN/AMAC Address
Change In
RunMin.Max.DefaultIDDescription
1 = ModBus RTU
2 =N2
3 = BACnet MSTP
Change In
RunMin.Max.DefaultIDDescription
2 = Fixed IP
Modbus TCP
Parameter
NumberParameter Name
P4.8.2.1.1 Connection limitN020N/ASee Range
P4.8.2.1.2 Slave addressN02550N/ASee Range
P4.8.2.1.3 Comm. TimeoutN0 sec65535 sec10 secN/ASee Range
Change In
RunMin.Max.DefaultIDDescription
BACnet IP
Parameter
NumberParameter Name
P4.8.3.1.1 Instance NumberN0655350N/ASee Range
P4.8.3.1.2 Comm. TimeoutN0655350N/ASee Range
P4.8.3.1.3 Protocol in useN010N/ASee Range
P4.8.3.1.4 BBMD IPN02550N/ASee Range
P4.8.3.1.5 BBMD PortN1655350N/ASee Range
P4.8.3.1.6 Time to liveN02550N/ASee Range
Change In
RunMin.Max.DefaultIDDescription
Monitoring
Monitoring
Parameter
NumberParameter NameUnitIDDescription
M 4.8.3.2.1 FB Protocol StatusN/AN/AFB Protocol Status
M 4.8.3.2.2 Comm. StatusN/AN/AComm. Status
M 4.8.3.2.3 Actual InstanceN/AN/AActual Instance
M 4.8.3.2.4 Control WordN/AN/AControl Word
M 4.8.3.2.5 Status WordN/AN/AStatus Word
58VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
User Settings
User Settings
Parameter
NumberParameter Name
P 5.1 Language selectY10010000802129 = English
P 5.2 Application selectN000 8010 = Application0
P 5.5.1 Restore DefaultsNNoYesNo831See Range
P 5.5.2 Save to KeypadNN/AN/AN/AN/AN/A
P 5.5.3 From KeypadNN/AN/AN/AN/AN/A
P 5.7 Drive NameNN/AN/ADriveN/AAny
User Settings
Change In
RunMin.Max.DefaultIDDescription
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com59
Parameter Descriptions
Parameter Descriptions
P2.1…
Parameter
NumberParameter NameDescription
P2.1.1 ApplicationDetermines Necessary Viewable and Hidden Parameters in accordance with Application Requirements
P2.1.2 ByPassUsed for 2 or 3 Contactor Bypass Applications. EMEA Products will have this default set to 0
P2.1.3 HOA Control StcDefines the HOA Control Location
P2.1.4 Start Srce HandDetermines where the Hand Start Signal Source is controlled from. If I/O 3-wire is chosen the user must also
P2.1.5 Speed Setpt HandDefines the frequency reference input source when operating in the Hand mode
P2.1.6 Start Srce AutoDetermines where the Auto Start Signal Source is controlled from. If I/O 3-wire is chosen the user must also
P2.1.7 Speed Setpt AutoDefines the frequency reference input source when operating in the Auto mode
P2.1.8 Min FrequencyMinimum Output Frequency (Hz)
P2.1.9 Max FrequencyMaximum Output Frequency (Hz). US product defaulted to 60 Hz. EMEA product defaulted to 50 Hz
P2.1.10 Accel Time 1Time from Minimum Frequency to Maximum Frequency
P2.1.11 Decel Time 1Time from Maximum Frequency to Minimum Frequency
P2.1.12 Motor Nom CurrntMotor Nameplate Current (Amps)
P2.1.13 Motor Nom VoltgMotor Nameplate Voltage (Volts)
P2.1.14 Motor Nom FreqMotor Nameplate Frequency in Hertz
P2.1.15 Motor Nom SpeedMotor Nameplate Speed in RPMs
P2.1.16 MotorPowerFactorMotor Nameplate Power Factor (Cos Phi)
P2.1.17 Current LimitOutput current limit of the unit in Amperes. When current limit is active, the output frequency will be decreased
P2.1.18 Service FactorMotor service factor (SF). This will calculate the motor current limit. (MotorNomCurrent x Service Factor)
program a “3-wire off” to input DI2–DI6
program a “3-wire off” to input DI2–DI6
P2.2…
Parameter
NumberParameter NameDescription
P2.2.1.1 AI1 Signal selectionAnalog Input 1 signal (connect to terminals 2 and 3 on the basic I/O board)
P2.2.1.2 AI1 Signal InvInvert Input Signal
P2.2.1.3 AI1 Signal RangeAnalog Signal Ranges (Dip Switches on side of drive changes signal from voltage to current)
P2.2.1.4 AI1 Custom MinCustom Range Min Setting 20% = 4–20mA/2–10 Vdc (Example: if you will use a signal from 8 to 16 mA, you set
P2.2.1.5 AI1 Custom MaxCustom Range Max Setting
P2.2.1.6 AI1 Filter TimeFilter Time for Analog Input (When this parameter is given a value greater than 0 the function that filters
P2.2.2.1 AI2 Signal selectionAnalog Input 2 signal (connect to terminals 4 and 5 on the basic I/O board)
P2.2.2.2 AI2 Signal InvInvert Input Signal
P2.2.2.3 AI2 Signal RangeAnalog Signal Ranges (Dip Switches on side of drive changes signal from voltage to current)
P2.2.2.4 AI2 Custom MinCustom Range Min Setting 20% = 4–20mA/2–10 Vdc (Example: if you will use a signal from 8 to 16 mA, you set
P2.2.2.5 AI2 Custom MaxCustom Range Max Setting
P2.2.2.6 AI2 Filter TimeFilter Time for Analog Input (When this parameter is given a value greater than 0 the function that filters out
ID380 to 40% and ID381 to 80%)
out disturbances from the incoming analog signal is activated. A long filtering time makes the regulation
response slower)
ID380 to 40% and ID381 to 80%)
disturbances from the incoming analog signal is
slower)
activated. A long filtering time makes the regulation response
60VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Parameter Descriptions
P2.2…, continued
Parameter
NumberParameter NameDescription
P2.2.3.1 AI3 Signal selectionAnalog Input 3 signal programmed by TTF (Terminal to Function)
P2.2.3.2 AI3 Signal InvInvert Input Signal
P2.2.3.3 AI3 Signal RangeAnalog Signal Ranges
P2.2.3.4 AI3 Custom MinCustom Range Min Setting 20% = 4–20mA/2–10 Vdc (Example: if you will use a signal from 8 to 16 mA, you set
P2.2.3.5 AI3 Custom MaxCustom Range Max Setting
P2.2.3.6 AI3 Filter TimeFilter Time for Analog Input (When this parameter is given a value greater than 0 the function that filters out
P2.2.4.1 AI4 Signal selectionAnalog Input 4 signal programmed by TTF (Terminal to Function)
P2.2.4.2 AI4 Signal InvInvert Input Signal
P2.2.4.3 AI4 Signal RangeAnalog Signal Ranges
P2.2.4.4 AI4 Custom MinCustom Range Min Setting 20% = 4–20mA/2–10 Vdc (Example: if you will use a signal from 8 to 16 mA, you set
P2.2.4.5 AI4 Custom MaxCustom Range Max Setting
P2.2.4.6 AI4 Filter TimeFilter Time for Analog Input (When this parameter is given a value greater than 0 the function that filters out
P2.2.5.1 AI5 Signal selectionAnalog Input 5 signal programmed by TTF (Terminal to Function)
P2.2.5.2 AI5 Signal InvInvert Input Signal
P2.2.5.3 AI5 Signal RangeAnalog Signal Ranges
P2.2.5.4 AI5 Custom MinCustom Range Min Setting 20% = 4–20mA/2–10 Vdc (Example: if you will use a signal from 8 to 16 mA, you set
P2.2.5.5 AI5 Custom MaxCustom Range Max Setting
P2.2.5.6 AI5 Filter TimeFilter Time for Analog Input (When this parameter is given a value greater than 0 the function that filters out
P2.2.6.1 AI6 Signal selectionAnalog Input 6 signal programmed by TTF (Terminal to Function)
P2.2.6.2 AI6 Signal InvInvert Input Signal
P2.2.6.3 AI6 Signal RangeAnalog Signal Ranges
P2.2.6.4 AI6 Custom MinCustom Range Min Setting 20% = 4–20mA/2–10 Vdc (Example: if you will use a signal from 8 to 16 mA, you set
P2.2.6.5 AI6 Custom MaxCustom Range Max Setting
P2.2.6.6 AI6 Filter TimeFilter Time for Analog Input (When this parameter is given a value greater than 0 the function that filters
P2.2.7.1 Ref Scale Min.This parameter allows the scaling of the minimum frequency reference from its preset value to a value less than
P2.2.7.2 Ref Scale Max.This parameter allows the scaling of the maximum frequency reference from its preset value to a value greater
ID380 to 40% and ID381 to 80%)
disturbances from the incoming analog signal is activated. A long filtering time makes the regulation response
slower)
ID380 to 40% and ID381 to 80%)
disturbances from the incoming analog signal is activated. A long filtering time makes the regulation response
slower)
ID380 to 40% and ID381 to 80%)
disturbances from the incoming analog signal is activated. A long filtering time makes the regulation response
slower)
ID380 to 40% and ID381 to 80%)
out disturbances from the incoming analog signal is activated. A long filtering time makes the
regulation response slower)
that set by the Reference Scale Maximum (ID 1
than that set by the Reference Scale Minimum (ID1307) parameter
parameter. If no scaling is desired, set this parameter to 0
308)
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com61
Parameter Descriptions
P2.3…
Parameter
NumberParameter NameDescription
P2.3.1.1 DI1 Open InvertDigital Input 1 is locked in at Normally Open and is not editable
P2.3.1.2 DI1 FunctionStart input signal (non-configurable)
P2.3.2.1 DIN 2 Invert This input allows the Digital Input to be either a Normally Open or a Normally Closed contact to cause the
P2.3.2.2 DIN2 FunctionFunction of DIN2 within Drive
P2.3.3.1 DIN 3 Invert This input allows the Digital Input to be either a Normally Open or a Normally Closed contact to cause the
P2.3.3.2 DIN3 FunctionFunction of DIN3 within Drive
P2.3.4.1 DIN 4 Invert This input allows the Digital Input to be either a Normally Open or a Normally Closed contact to cause the
P2.3.4.2 DIN4 FunctionFunction of DIN4 within Drive
P2.3.5.1 DIN 5 Invert This input allows the Digital Input to be either a Normally Open or a Normally Closed contact to cause the
P2.3.5.2 DIN5 FunctionFunction of DIN5 within Drive
P2.3.6.1 DIN 6 Invert This input allows the Digital Input to be either a Normally Open or a Normally Closed contact to cause the
P2.3.6.2 DIN6 FunctionFunction of DIN6 within Drive. Default value is 33 if bypass is enabled
P2.3.7.1 Ext-D1 TerminalThis parameter allows programming an external Digital Input using the “Terminal-to-Function” method
P2.3.7.2 Ext-D1 FunctionFunction of Ext-D1 within Drive
P2.3.8.1 Ext-D2 TerminalThis parameter allows programming an external Digital Input using the “Terminal-to-Function” method
P2.3.8.2 Ext-D2 FunctionFunction of Ext-D2 within Drive
P2.3.9.1 Start logicStart Functionality
P2.3.9.2 INTLK TimeoutInterlock timeout time for Start Function #2
P2.3.9.3 Delay TimeStart Delay time for Start Function #3
P2.3.9.4 Intrlk Stop ModeStop Mode if the Interlock Start is Triggered
P2.3.9.5 Interlock 1 TextText Associated with Interlock 1
P2.3.9.6 Interlock 2 TextText Associated with Interlock 2
P2.3.9.7 Interlock 3 TextText Associated with Interlock 3
programmed function of this DIN
programmed function of this DIN
programmed function of this DIN
programmed function of this DIN
programmed function of this DIN
Normal—Interlocks are not used.
Interlock start—When a start command is given, output signal “Damper Control Relay” is activated. The signal
can be programmed to relay output and it can be connected to control an element of the driven system, such as
damper. The drive is started when a feedback is provided to the Interlock input of the drive.
Interlock time start—Functionality is similar to Interlock start. If the feedback signal is not active within the
defined time, a message “Interlock Time Expired. Restart the drive” is given.
Delay Start—Feedback signals are not used. The drive is started after a pre-defined delay.
P2.4…
Parameter
NumberParameter NameDescription
og Output Functionality
P2.4.1.1 AO1 FunctionAna
P2.4.1.2 AO1 Filter TimeAnalog Output AO1 Filter
P2.4.1.3 AO1 Min SignalAnalog Output AO1 Minimum Signal Value
P2.4.1.4 AO1 MinScaleMin Scale in Process Unit
P2.4.1.5 AO1 MaxScaleMax Scale in Process Unit
P2.4.1.6 AO1 InvertAnalog Output Signal Invert
62VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
l
P2.5…
Parameter
NumberParameter NameDescription
P2.5.1.1 RO1 functionDefault value is 35 if bypass is enabled!
P2.5.1.2 RO1 InvertRO1 Invert Function
P2.5.1.3 RO1 ON delayDelay On time before relay turns on
P2.5.1.4 RO1 OFF delayDelay Off time before relay turns on
P2.5.2.1 RO2 functionRO2 Function Setting
P2.5.2.2 RO2 InvertRO2 Invert Function
P2.5.2.3 RO2 ON delayDelay On time before relay turns on
P2.5.2.4 RO2 OFF delayDelay Off time before relay turns off
P2.5.3.1 RO3 functionRO3 Function Setting
P2.5.9.1 Superv1 ItemAllows Drive to Trigger based on High or Low Limit
P2.5.9.2 Supervision #1 modeSelect a Low or High Limit if used
P2.5.9.3 Supervision #1 limitSupervisory Limit Value
P2.5.9.4 Supervision #1 limit
hysteresis
P2.5.9.4 Supervision #2 limit
hysteresis
P2.5.9.5 Superv2 ItemAllows Drive to Trigger based on High or Low Limit
P2.5.9.6 Supervision #2 modeSelect a Low or High Limit if used
P2.5.9.7 Supervision #2 limitSupervisory Limit Value
Supervisory Limit Reset Buffer
Supervisory Limit Reset Buffer
Parameter Descriptions
P2.6…
Parameter
NumberParameter NameDescription
P2.6.1.1 Start FunctionStart function from zero speed or when load is spinning
P2.6.1.2 Stop FunctionHow the drive stops the load after stop is given
P2.6.1.3 InhibitDirectionFunction Prevents spinning in defined direction
P2.6.1.4 Reference UnitReference Unit that is displayed on the keypad
P2.6.1.5 Keypad ReferenceKeypad Reference
P2.6.1.6 Keypad DirectionDirection of motor when in keypad control operation
P2.6.1.7 Keypad Reference copySelects function for Run State and Reference copy when changing to Keypad Control
P2.6.1.8 Keypad Stop ButtonKeypad STOP button active or not, regardless of control place
P2.6.1.9 Accel Time 2A second parameter for Acceleration can be set and can be chosen by inputs
P2.6.1.10 Decel Time 2A second parameter for Deceleration can be set and can be chosen by inputs
P2.6.1.11 RampselectModeUse this parameter to select acceleration ramp and deceleration ramp 2 by frequency limit or digital input
P2.6.1.12 Accel2ThresholdAcceleration ramp 2 is activated when output frequency goes over this limit. 0.0 = Not Used. It can also be turned
P2.6.1.13 Decel2ThresholdDeceleration ramp 2 is activated when output frequency goes below this limit. 0.0 = Not Used. It can also be
P2.6.1.14 S-Ramp 1 ShapeS-curve time ramp 1 used for smooth acceleration
P2.6.1.15 S-Ramp 2 ShapeS-curve time ramp 2 used for smooth acceleration
on with a digital input
turned on with a digital input
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com63
Parameter Descriptions
P2.6…, continued
Parameter
NumberParameter NameDescription
P2.6.2.1 Range 1 Low LimSkip frequency low limit area 1
P2.6.2.2 Range 1 High LimSkip frequency high limit area 1
P2.6.2.3 Range 2 Low LimSkip frequency low limit area 2
P2.6.2.4 Range 2 High LimSkip frequency high limit area 2
P2.6.2.5 Range 3 Low LimSkip frequency low limit area 3
P2.6.2.6 Range 3 High LimSkip frequency high limit area 3
P2.6.2.7 Range 4 Low LimSkip frequency low limit area 4
P2.6.2.8 Range 4 High LimSkip frequency high limit area 4
P2.6.2.9 Range 5 Low LimSkip frequency low limit area 5
P2.6.2.10 Range 5 High LimSkip frequency high limit area 5
P2.6.2.11 Range 6 Low LimSkip frequency low limit area 6
P2.6.2.12 Range 6 High LimSkip frequency high limit area 6
P2.6.2.13 RampTimeFactorDefines the acceleration/deceleration time when the output frequency is between the selected skip frequency
range limits. The accel/decel times (1 or 2) is multiplied by this factor
P2.7…
Parameter
NumberParameter NameDescription
P2.7.1 V/Hz RatioSelectV/Hz Ratio Selection
P2.7.2 Field WeakngPntProgrammable Field Weakening (The field weakening point is the output frequency at which the output voltage
P2.7.3 Voltage at FWPAbove the frequency at the field weakening point, the output voltage remains at the set maximum value. Below
P2.7.4 V/Hz Mid FreqIf the programmable U/f curve has been selected with parameter U/f Ratio, this parameter defines the middle
P2.7.5 V/Hz Mid VoltageIf the programmable U/f curve has been selected with parameter U/f Ratio, this parameter defines the middle
P2.7.6 Zero Freq VoltgThis parameter defines the zero frequency voltage of the U/f curve. The default value varies according to unit size
P2.7.7 Switching FreqMotor noise can be minimized using a high switching frequency. Increasing switching frequency reduces the
reaches the nameplate rated voltage of the motor)
the frequency at the field weakening point, the output voltage depends on the setting of the V/Hz curve
parameters
point frequency of the curve
point voltage of the curve
capacity of the frequency converter
P2.8…
Parameter
NumberParameter NameDescription
P2.8.1.1 AI Low FaultResponse when an analog signal in use goes below 50% of the minimum signal range. If alarm + preset
P2.8.1.2 Undervoltage FltEnable or Disable Undervoltage Fault
P2.8.1.3 OutputPhase FltOutput phase supervision of the motor ensures that the motor phases have an approximately equal current
P2.8.1.4 Motor Duty CycleDefines how much of the nominal motor load is applied
P2.8.1.5 Underload FltThe purpose of motor underload protection is to ensure that there is load on the motor while the drive is running
P2.8.1.6 Motor Therm ProtMotor thermal protection is based on a calculated model and uses the output current and output frequency to
P2.8.1.7 MotAmbient TempThis parameter relates to the ambient temperature the motor is in
frequency is used, the frequency can be set in the references menu
determine the load on the motor
64VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Parameter Descriptions
P2.8…, continued
Parameter
NumberParameter NameDescription
P2.8.1.8 ZeroSpeedCoolingDefines the cooling factor at zero speed in relation to the point where the motor is running at nominal speed
P2.8.1.9 ThermTimeConstThe time constant is the time within which the calculated thermal stage has reached 63% of its final value. The
P2.8.1.10 Thermistor FaultResponse when the thermistor circuit opens in an available thermistor input. Thermistor inputs might be an
P2.8.1.11 External FaultResponse when an external fault is activated
P2.8.1.12 FieldbusComm FltResponse when fieldbus communication timeout occurs
P2.8.1.13 InputPhaseFaultThe input phase supervision ensures that the input phases of the frequency converter have an approximately
P2.8.1.14 MotorStall FltStall protection is a type of overcurrent protection. It protects the motor from short time overload situations like a
P2.8.1.15 PID1 SupervisionUpper and lower limits around the reference are set. When the actual value goes above or below these a counter
P2.8.1.16 PID2 SupervisionSame as PID1 Supervision
P2.8.1.17 SlotCommFltResponse for a Slot Fault
P2.8.1.18 Preset Alarm FreqThis frequency is used as reference when AI Low Fault response is Alarm and Preset Frequency
P2.8.2.1 Automatic ResetParameter to select mode for the automatic restart function
P2.8.2.2 Restart functionWe can choose what kind of start function we want to use when doing an autoreset of the drive if run command
P2.8.2.3 Wait TimeDefines the time before the frequency converter tries to automatically reset a fault
P2.8.2.4 Trial TimeThe automatic reset function keeps trying to reset the faults appearing during the time set with this parameter. If
P2.8.2.5 Number of trialsHow many times we should try to reset the drive
P2.8.2.6 Undervoltage FltDefines if we should include fault in the automatic reset functions
P2.8.2.7 Overvoltage FltDefines if we should include fault in the automatic reset functions
P2.8.2.8 Overcurrent FltDefines if we should include fault in the automatic reset functions
P2.8.2.9 AI Low FaultDefines if we should include fault in the automatic reset functions
P2.8.2.10 UnitOverTemp FltDefines if we should include fault in the automatic reset functions
P2.8.2.11 MotorOverTempFlt
(Yes or No)
P2.8.2.12 External Fault (Yes or No) Defines if we should inc
P2.8.2.13 IGBT tempDefines if we should include fault in the automatic reset functions
without external cooling
larger the motor, the longer the time constant
option depending on frequency converter
equal current
stalled shaft
starts counting up towards the Delay. When the actual value is within the allowed area the same counter counts
down instead. When ever the counter reaches its limit, the response selected will enable
is kept active during the autoreset sequence
the number of reset tries is exceeded within this time, or the fault remains, a non-automatically resettable fault is
generated
Defines if we should include fault in the automatic reset functions
ude fault in the automatic reset functions
l
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com65
Parameter Descriptions
P2.9…
Parameter
NumberParameter NameDescription
P2.9.1.1.1 Gain, PID Controller 1Defines the gain of the PID Controller
P2.9.1.1.2 Integration Time,
PID Controller 1
P2.9.1.1.3 Derivation Time,
PID Controller 1
P2.9.1.1.4 ProcessUnitSel,
PID Controller 1
P2.9.1.1.5 ProcessUnitMin,
PID Controller 1
P2.9.1.1.6 ProcessUnitMax,
PID Controller 1
P2.9.1.1.7 ProcessUnitDecimals,
PID Controller 1
P2.9.1.1.8 Error Inversion,
PID Controller 1
P2.9.1.1.9 Dead Band,
PID Controller 1
P2.9.1.1.10 Dead band delay,
PID Controller 1
P2.9.1.2.1 Keypad SP 1,
PID Controller 1
P2.9.1.2.2 Keypad SP 2,
PID Controller 1
P2.9.1.2.3 Ramp Time,
PID Controller 1
P2.9.1.2.4 SetPt 1 Source,
PID Controller 1
P2.9.1.2.5 SetPt 1 min,
PID Controller 1
P2.9.1.2.6 SP 1 maximum,
PID Controller 1
P2.9.1.2.7 SP 1 Sleep Freq,
PID Controller 1
P2.9.1.2.8 SP 1 Sleep delay,
PID Controller 1
P2.9.1.2.9 SP 1 WakeUpLevel,
PID Controller 1
P2.9.1.2.10 SP 1 boost,
PID Controller 1
P2.9.1.2.11 SP 2 Source,
PID Controller 1
P2.9.1.2.12 SP 2 minimum,
PID Controller 1
P2.9.1.2.13 SP 2 maximum,
PID Controller 1
P2.9.1.2.14 SP 2 Sleep Freq,
PID Controller 1
Defines the integration time of the PID Controller
Defines the derivation time of the PID Controller
Defines the unit type for PID Feedback
Minimum Unit Value
Maximum Unit Value
Decimal places in Unit Value
Normal = If feedback is less than setpoint, PID controller output increases. Inverted = If feedback is less than
setpoint, PID controller output decreases
PID Deadband around setpoint
Delay in Locking the Deadband Output
Keypad setpoint 1
Keypad setpiont 2
Defines the rising and falling ramp times for setpoint changes
Defines source of the setpoint
Defines Minimum Value at AI Minimum level
Defines Maximum Value at AI Maximum level
Drive goes to sleep mode when the output frequency stays below this limit for a time greater than that defined by
parameter Sleep delay
The minimum amount of time the frequency has to remain below the sleep level before the drive is stopped
Defines the level for the PID feedback value wake-up supervision. Uses selected process units
The setpoint can be boosted with a digital input
Defines source of the setpoint
Defines Minimum Value at AI Minimum level
Defines Maximum Value at AI Maximum level
Drive goes to sleep mode when the output frequency stays below this limit for a time greater than that defined by
parameter Sleep delay
66VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
P2.9…, continued
Parameter
NumberParameter NameDescription
P2.9.1.2.15 SP 2 Sleep delay,
PID Controller 1
P2.9.1.2.16 SP 2 WakeUpLevel,
PID Controller 1
P2.9.1.2.17 SP 2 boost,
PID Controller 1
P2.9.1.3.1 Function, PID Controller 1 Choose a single signal used as feedback
P2.9.1.3.2 Gain, PID Controller 1Define Gain associated with feedback
P2.9.1.3.3 FeedBack 1 Srce,
PID Controller 1
P2.9.1.3.4 FB 1 Minimum,
PID Controller 1
P2.9.1.3.5 FB 1 Maximum,
PID Controller 1
P2.9.1.3.6 FB 2 Source,
PID Controller 1
P2.9.1.3.7 FB 2 Minimum,
PID Controller 1
P2.9.1.3.8 FB 2 Maximum,
PID Controller 1
P2.9.1.4.1 Function, PID Controller 1 Choose a single signal used as feedforward
P2.9.1.4.2 Gain, PID Controller 1Define feedforward gain
P2.9.1.4.3 FF 1 Source,
PID Controller 1
P2.9.1.4.4 FF1 Minimum,
PID Controller 1
P2.9.1.4.5 FF1 Maximum,
PID Controller 1
P2.9.1.4.6 FF 2 Source,
PID Controller 1
P2.9.1.4.7 FF2 Minimum,
PID Controller 1
P2.9.1.4.8 FF2 Maximum,
PID Controller 1
P2.9.1.5.1 Enable Superv,
PID Controller 1
P2.9.1.5.2 Upper limit,
PID Controller 1
P2.9.1.5.3 Lower limit,
PID Controller 1
P2.9.1.5.4 Delay, PID Controller 1If the desired value is not reached within this time a fault or alarm is created
P2.9.1.6.1 Enable SP 1,
PID Controller 1
P2.9.1.6.2 SP 1 Max Comp.,
PID Controller 1
P2.9.1.6.3 Enable SP 2,
PID Controller 1
The minimum amount of time the frequency has to remain below the sleep level before the drive is stopped
Defines the level for the PID feedback value wake-up supervision. Uses selected process units
The setpoint can be boosted with a digital input
Define where feedback signal is from
Minimum Unit Value
Maximum Unit Value
Define where feedback signal is from
Minimum Unit Value
Maximum Unit Value
Define where feedforward signal is from
Minimum Unit Value
Maximum Unit Value
Define where feedforward signal is from
Minimum Unit Value
Maximum Unit Value
Controls the actual value within predefined limits. Can detect a major pipe burst or unnecessary flooding
Upper actual/process value supervision
Lower actual/process value supervision
Enables pressure loss compensation for setpoint 1
Value added proportionally to the frequency
Enables pressure loss compensation for setpoint 2
Parameter Descriptions
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com67
Parameter Descriptions
P2.9…, continued
Parameter
NumberParameter NameDescription
P2.9.1.6.4 SP 2 Max Comp.,
PID Controller 1
P2.9.2.1.1 Gain, PID Controller 2Defines the gain of the PID Controller
P2.9.2.1.2 Integration Time,
PID Controller 2
P2.9.2.1.3 Derivation Time,
PID Controller 2
P2.9.2.1.4 ProcessUnitSel,
PID Controller 2
P2.9.2.1.5 ProcessUnitMin,
PID Controller 2
P2.9.2.1.6 ProcessUnitMax,
PID Controller 2
P2.9.2.1.7 ProcessUnitDecimals,
PID Controller 2
P2.9.2.1.8 Error Inversion,
PID Controller 2
P2.9.2.1.9 Dead Band,
PID Controller 2
P2.9.2.1.10 Dead band delay,
PID Controller 2
P2.9.2.2.1 Keypad SP 1,
PID Controller 2
P2.9.2.2.2 Keypad SP 2,
PID Controller 2
P2.9.2.2.3 Ramp Time,
PID Controller 2
P2.9.2.2.4 SetPt 1 Source,
PID Controller 2
P2.9.2.2.5 SetPt 1 min,
PID Controller 2
P2.9.2.2.6 SP 1 maximum,
PID Controller 2
P2.9.2.2.7 SP 2 Source,
PID Controller 2
P2.9.2.2.8 SP 2 minimum,
PID Controller 2
P2.9.2.2.9 SP 2 maximum,
PID Controller 2
P2.9.2.3.1 Function, PID Controller 2 Choose a single signal used as feedback
P2.9.2.3.2 Gain, PID Controller 2Define Gain associated with feedback
P2.9.2.3.3 FeedBack 1 Srce,
PID Controller 2
P2.9.2.3.4 FB 1 Minimum,
PID Controller 2
P2.9.2.3.5 FB 1 Maximum,
PID Controller 2
Value added proportionally to the frequency
Defines the integration time of the PID Controller
Defines the derivation time of the PID Controller
Defines the unit type for PID Feedback
Minimum Unit Value
Maximum Unit Value
Decimal places in Unit Value
Normal = If feedback is less than setpoint, PID controller output increases. Inverted = If feedback is less than
setpoint, PID controller output decreases
PID Deadband around setpoint
Delay in Locking the Deadband Output
Keypad setpoint 1
Keypad setpiont 2
Defines the rising and falling ramp times for setpoint changes
Defines source of the setpoint
Defines Minimum Value at AI Minimum level
Defines Maximum Value at AI Maximum level
Defines source of the setpoint
Defines Minimum Value at AI Minimum level
Defines Maximum Value at AI Maximum level
Define where feedback signal is from
Minimum Unit Value
Maximum Unit Value
68VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
P2.9… , continued
Parameter
NumberParameter NameDescription
P2.9.2.3.6 FB 2 Source,
PID Controller 2
P2.9.2.3.7 FB 2 Minimum,
PID Controller 2
P2.9.2.3.8 FB 2 Maximum,
PID Controller 2
P2.9.2.4.1 Enable Superv,
PID Controller 2
P2.9.2.4.2 Upper limit,
PID Controller 2
P2.9.2.4.3 Lower limit,
PID Controller 2
P2.9.2.4.4 Delay, PID Controller 2If the desired value is not reached within this time a fault or alarm is created
Define where feedback signal is from
Minimum Unit Value
Maximum Unit Value
Controls the actual value within predefined limits. Can detect a major pipe burst or unnecessary flooding
Upper actual/process value supervision
Lower actual/process value supervision
P2.10…
Parameter
NumberParameter NameDescription
P2.10.1 Preset Freq 1Used according to state of digital inputs Preset Frequency Sel0, Sel1, Sel2
P2.10.2 Preset Freq 2Same as Preset Freq 1
P2.10.3 Preset Freq 3Same as Preset Freq 1
P2.10.4 Preset Freq 4Same as Preset Freq 1
P2.10.5 Preset Freq 5Same as Preset Freq 1
P2.10.6 Preset Freq 6Same as Preset Freq 1
P2.10.7 Preset Freq 7Same as Preset Freq 1
Parameter Descriptions
P2.11…
Parameter
NumberParameter NameDescription
P2.11.1 Firemode FreqFrequency to be used in when fire mode is activated. This will be hidden if in Multi-Pump Mode
P2.12…
Parameter
NumberParameter NameDescription
P2.12.1 Number of motorsTotal number of motors/pumps used with the Multi-Pump System
P2.12.2 Interlock functionInput tells the drive if a motor/pump is connected or not
P2.12.3 Include FCInput tells the drive if the motor/pump is included in the autochange and interlock system
P2.12.4 AutochangeAutochange will rotate the starting order/priority of the motors in the system to get equal wear on all motors
P2.12.5 Autochange intervalDefines how often to rotate starting order of motors/pumps
P2.12.6 Autochange:
frequency limit
P2.12.7 Autochange:
motor limit
P2.12.8 BandwidthPercentage of the setpoint defining when motor disconnection of removal will not take place
P2.12.9 Bandwidth delayWith feedback outside the bandwidth, this time must pass before pumps are added or removed
An autochange is done when the autochange interval has elapsed and the drive is running below autochange
frequency limit
An autochange is done when the autochange interval has elapsed and the number of running motors is less than
autochange motor limit
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com69
Parameter Descriptions
P2.13…
Parameter
NumberParameter NameDescription
P2.13.1 DC Brake CurrentDC Brake Current in Stop
P2.13.2 DC Time StopDC Braking Time at Stop
P2.13.3 DC BrakeFreqStopThe output frequency at which the DC-braking is applied
P2.13.4 StartMagnTimeDC brake time in start
P2.13.5 StartMagnCurrentDC brake current in Start
P2.13.6 Preheat CurrentDC current for Pre-heating of motor and drive in stop state. Activated by digital input or by temperature limit
P2.14…
Parameter
NumberParameter NameDescription
P2.14.1 FB Data Out1 SelData sent to fieldbus can be chosen with parameter and monitor value ID numbers. The data is scaled to unsigned
P2.14.2 FB Data Out2 SelSame as FB Data Out1 Sel
P2.14.3 FB Data Out3 SelSame as FB Data Out1 Sel
P2.14.4 FB Data Out4 SelSame as FB Data Out1 Sel
P2.14.5 FB Data Out5 SelSame as FB Data Out1 Sel
P2.14.6 FB Data Out6 SelSame as FB Data Out1 Sel
P2.14.7 FB Data Out7 SelSame as FB Data Out1 Sel
P2.14.8 FB Data Out8 SelSame as FB Data Out1 Sel
16bit format according to format on panel
P2.15…
Parameter
NumberParameter NameDescription
P2.15.1.1 Motor Nom Currnt, Set2Motor 2 Nameplate Data
P2.15.1.2 Motor Nom Voltg, Set2Motor 2 Nameplate Data
P2.15.1.3 Motor Nom Freq, Set2Motor 2 Nameplate Data
P2.15.1.4 Motor Nom Speed, Set2Motor 2 Nameplate Data
P2.15.1.5 MotorPowerFactor, Set2Motor 2 Nameplate Data
P2.15.1.6 Current Limit, Set2Output current limit of the frequency converter
P2.15.1.7 Motor Therm Prot, Set2Motor 2 thermal protection is based on a calculated model and uses the output current and output frequency to
P2.15.2.1 Min Frequency, Set2Motor 2 Minimum Frequency
P2.15.2.2 Max Frequency, Set2Motor 2 Maximum Frequency
P2.15.2.3 Accel Time 1, Set2Time from Minimum Frequency to Maximum Frequency
P2.15.2.4 Decel Time 1, Set2Time from Maximum Frequency to Minimum Frequency
P2.15.2.5 V/Hz RatioSelect, Set2Type of U/f curve between zero frequency and field weakening point
determine the load on the motor
70VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
P2.16…
Parameter
NumberParameter NameDescription
P2.16.1.1 ON Time, Interval 1Drive timer On time
P2.16.1.2 Off Time, Interval 1Drive timer Off time
P2.16.1.3 From Day, Interval 1On day of week
P2.16.1.4 To Day, Interval 1Off day of week
P2.16.1.5 Assign to channel,
Interval 1
P2.16.2.1 ON Time, Interval 2Drive timer On time
P2.16.2.2 Off Time, Interval 2Drive timer Off time
P2.16.2.3 From Day, Interval 2On day of week
P2.16.2.4 To Day, Interval 2Off day of week
P2.16.2.5 Assign to channel,
Interval 2
P2.16.3.1 ON Time, Interval 3Drive timer On time
P2.16.3.2 Off Time, Interval 3Drive timer Off time
P2.16.3.3 From Day, Interval 3On day of week
P2.16.3.4 To Day, Interval 3Off day of week
P2.16.3.5 Assign to channel,
Interval 3
P2.16.4.1 ON Time, Interval 4Drive timer On time
P2.16.4.2 Off Time, Interval 4Drive timer Off time
P2.16.4.3 From Day, Interval 4On day of week
P2.16.4.4 To Day, Interval 4Off day of week
P2.16.4.5 Assign to channel,
Interval 4
P2.16.5.1 ON Time, Interval 5Drive timer On time
P2.16.5.2 Off Time, Interval 5Drive timer Off time
P2.16.5.3 From Day, Interval 5On day of week
P2.16.5.4 To Day, Interval 5Off day of week
P2.16.5.5 Assign to channel,
Interval 5
P2.16.6.1 DurationThe time the timer will run when activated
P2.16.6.2 Assign to channelAssociate duration with a time channel
P2.16.7.1 DurationThe time the timer will run when activated
P2.16.7.2 Assign to channelAssociate duration with a time channel
P2.16.8.1 DurationThe time the timer will run when activated
P2.16.8.2 Assign to channelAssociate duration with a time channel
Select affected time channel
Select affected time channel
Select affected time channel
Select affected time channel
Select affected time channel
Parameter Descriptions
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com71
Diagnostics
Diagnostics
Under this menu, you can find Active faults, Reset faults, Fault history, Counters and Software info.
Active Faults
MenuFunctionNote
Active faultsWhen a fault/faults appear(s), the display with the name of
the fault starts to blink. Press OK to return to the
Diagnostics menu. The Active faults submenu shows the
number of faults. Select the fault and push OK to see the
fault-time data.
Reset Faults
MenuFunctionNote
Reset faultsIn this menu you can reset faults. For closer instructions.CAUTION! Remove external Control signal before
Fault History
MenuFunctionNote
Fault history40 latest faults are stored in the Fault history.Entering the Fault history and clicking OK on the selected
The fault remains active until it is cleared with the Reset
button (push for 2s) or with a reset signal from the I/O
terminal or Fieldbus or by choosing Reset faults (see
below). The memory of active faults can store the
maximum of 10 faults in the order of appearance.
resetting the fault to prevent unintentional restart
of the drive.
fault shows the fault time data (details).
Fault Codes
Fault Codes and Descriptions
Fault
Code
11Overcurrent
210Overvoltage
320Earth fault
540Charging switchThe charging switch is open, when the
Fault
IDFault NamePossible CauseRemedy
AC drive has detected too high a current
(hardware fault)
2Overcurrent
(software fault)
(hardware fault)
11Overvoltage
(software fault)
(hardware fault)
21Earth fault
(software fault)
) in the motor cable:
(>4*I
H
• Sudden heavy load increase
• Short circuit in motor cables
• Unsuitable motor
The DC-link voltage has exceeded the
limits defined:
• Too short a deceleration time
• Brake chopper is disabled
• High overvoltage spikes in supply
• Start/Stop sequence too fast
Current measurement has detected that
the sum of motor phase current is not zero:
• Insulation failure in cables or motor
START command has been given:
• Faulty operation
• Component failure
• Check loading
• Check motor
• Check cables and connections
• Make identification run
• Check ramp times
• Make deceleration time longer
• Use brake chopper or brake resistor
(available as options)
• Activate overvoltage controller
• Check input voltage
Check motor cables and motor
• Reset the fault and restart
• Should the fault re-occur, contact the
distributor near to you
72VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Diagnostics
Fault Codes and Descriptions, continued
Fault
Code
760SaturationVarious causes:
8600System faultCommunication between control board
980Undervoltage
1091Input phaseInput line phase is missingCheck supply voltage, fuses and cable
11100Output phase
Fault
IDFault NamePossible CauseRemedy
• Cannot be reset from keypad
• Defective component
• Brake resistor short-circuit or overload
and power unit has failed
602Watchdog has reset the CPU
603Voltage of auxiliary power in power unit
604Phase fault: Voltage of an output phase
605CPLD has faulted but there is no detailed
606Control and power unit software are
607Software version cannot be read. There is
608CPU overload. Some part of the software
609Memory access has failed. For example,
610Necessary device properties cannot be read
647Software errorUpdate software. Should the fault re-occur,
648Invalid function block used in application.
649Resource overload:
(fault)
81Undervoltage
(alarm)
supervision
is too low
does not follow the reference
information about the fault
incompatible
no software in power unit
(for example application) has caused an
overload situation. The source of fault
has been suspended
retain variables could not be restored
System software and application are not
compatible
• Error when loading parameter initial
values
• Error when restoring parameters
• Error when saving parameters
DC link voltage is under the voltage limits
defined:
• Most probable cause: Too low a supply
voltage
• AC drive internal fault
• Defect input fuse
• External charge switch not closed
Note: This fault is activated only if the drive
is in Run state.
Current measurement has detected that there
is no current in one motor phase
• Switch off power
• DO NOT RECONNECT POWER! Contact
factory
• If this fault appears simultaneously with
F1, check motor cables and motor
Reset the fault and restart. Should the fault
re-occur, contact the distributor near you
Update software. Should the fault re-occur,
contact the distributor near you
Update power unit software. Should the fault
re-occur, contact the distributor near you
Reset the fault and restart. Should the fault
re-occur, contact the distributor near you
contact the distributor near you
In case of temporary supply voltage break reset
the fault and restart the AC drive. Check the
supply voltage. If it is adequate, an internal
failure has occurred. Contact the distributor
near you
Check motor cable and motor
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com73
Diagnostics
Fault Codes and Descriptions, continued
Fault
Code
12110Brake chopper supervision
13120AC drive undertemperature
14130AC drive overtemperature
15140Motor stalledMotor is stalledCheck motor and load
16150Motor overtemperatureMotor is overloadedDecrease motor load. If no motor overload
17160Motor underloadMotor is underloadedCheck load
19180Power overload
25—Motor control faultStart angle identification has failed.
32312Fan coolingFan lifetime is upChange fan and reset fan lifetime counter
33—Fire mode enabledFire mode of the drive is enabled. The
37360Device changed
38370Device changed
39380Device removedOptional board removed from slotDevice no longer available
41400IGBT temperatureIGBT temperature (unit temperature + I
43420Encoder faultEncoder 1 channel A is missing• Check encoder connections
Fault
IDFault NamePossible CauseRemedy
(hardware fault)
111Brake chopper
saturation alarm
(fault)
121AC drive overtemperature
(alarm)
(fault, heatsink)
131AC drive overtemperature
(alarm, heatsink)
132AC drive overtemperature
(fault, board)
133AC drive overtemperature
(alarm, board)
(short-time supervision)
181Power overload
(long-time supervision)
(same type)
(same type)
421Encoder 1 channel B is missing
422Both encoder 1 channels are missing
423Encoder reversed
424Encoder board missing
• No brake resistor installed
• Brake resistor is broken
• Brake chopper failure
Too low temperature measured in power
unit’s heatsink or board. Heat- sink
temperature is under –10°C
Too high temperature measured in power
unit’s heatsink or board. Heat- sink
temperature is over 100°C
Drive power is too highDecrease load
Generic motor control fault
drive’s protections are not in use
Option board changed for one previously
inserted in the same slot. The board’s
parameter settings are saved
Option board added. The option board was
previously inserted in the same slot. The
board’s parameter settings are saved
unit/option board)
is too high
2
Check brake resistor and cabling. If these are
OK, the chopper is faulty. Contact the
distributor near you
—
• Check the correct amount and flow of
cooling air
• Check the heatsink for dust
• Check the ambient temperature
• Make sure that the switching
frequency is not too high in relation to
ambient temperature and motor load
exists, check the temperature model
parameters
—
—
Device is ready for use. Old parameter settings
will be used
Device is ready for use. Old parameter settings
will be used
Device no longer available
T)
• Check loading
• Check motor size
• Make identification run
• Check encoder and encoder cable
• Check encoder board
• Check encoder frequency in open loop
74VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Fault Codes and Descriptions, continued
Fault
Code
44430Device changed
45440Device changed
511051External faultDigital input—
521052Keypad communication
531053Fieldbus communication
541354Slot A faultDefective option board or slotCheck board and slot
651065PC communication faultThe data connection between the PC and
661066Thermistor faultThe thermistor input has detected an
691310Fieldbus mapping errorNon-existing ID number is used for
1011101Process supervision fault
1051105Process supervision fault
Fault
IDFault NamePossible CauseRemedy
(different type)
(different type)
1352
1454Slot B fault
1654Slot D fault
1754Slot E fault
1311Not possible to convert one or more
1312Overflow when mapping and converting
fault
fault
(PID1)
(PID2)
Option board changed for one not present
in the same slot before. No parameter
settings are saved
Option board added. The option board was
not previously present in the same slot. No
parameter settings are saved
The connection between the control
keypad and frequency converter is broken
The data connection between the Fieldbus
master and Fieldbus board is broken
frequency converter is broken
increase of motor temperature
mapping values to Fieldbus Process
Data Out
values for Fieldbus Process Data Out
values for Fieldbus Process Data Out
(16-bit)
PID controller: Feedback value outside
of supervision limits (and the delay if set)
PID controller: Feedback value outside
of supervision limits (and the delay if set)
Set the option board parameters again
Set the option board parameters again
Check keypad connection and possible keypad
cable
Check installation and Fieldbus master
—
• Check motor cooling and load
• Check thermistor connection (if
thermistor input is not in use it has to
be short circuited)
Check parameters in Fieldbus Data Mapping
menu
The value being mapped may be of undefined
type. Check parameters in Fieldbus Data
Mapping menu
—
—
—
Diagnostics
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com75
Diagnostics
Counters
Total Counters (Counters cannot be cleared)
Parameter
NumberParameter NameUnitIDDescription
M 3.4.1 Energy counterkWh2291Amount of energy taken from net
M 3.4.3 Operating time0a xxd xx:xx0Control unit's operating time
M 3.4.7 Run Time0a xxd xx:xx0Motor running time
M 3.4.11 Power On Time0a xxd xx:xx0Power unit's power on time
M 3.4.15 Start Cmd CounterNumber2295How many times power unit has been
Trip Counters (Counters can be reset)
Parameter
NumberParameter Name
P 3.5.1 Energy counterY0.00099999.999Running2296Amount of energy taken from the
P 3.5.3 Operating timeY0a 5d 00:000a 5d 00:00RunningNADuration of the energy consumption
Change
in RunMin.Max.DefaultIDDescription
started
network during operating time
associated with P3.5.1
This is resettable
Software
Software Information
Parameter
NumberParameter NameUnitIDDescription
M 3.6.1 Software packageN/AN/ASoftware package
M 3.6.4 System loadN/A2300Control units CPU usage
M 3.6.5 Application NameN/AN/AApplication Name
M 3.6.6 Application IDN/AN/AApplication ID
M 3.6.7 Application Ver.N/AN/AApplication Ver.
76VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
Communications
WARNING
WARNING
Switch
Ethernet to
MS/TP Router
BACnet MS/TP
BACnet IP
BACnet Protocol
Communications
BACnet General Information
BACnet stands for Building Automation and Control
Networks. It is the common name for the communication
standard ISO 16484-5 which defines the methods and the
protocol for cooperating building automation devices to
communicate. Devices can be designed to operate using
BACnet communication protocol as well as utilizing BACnet
protocol to communicate between systems. BACnet is an
internationally accepted protocol for building automation
(such as lightning control, air conditioning and heating
automation) and control over a communications network.
BACnet provides a method by which computer-based control
equipment, from different manufacturers can work together,
or “interoperate”. For this to be achieved, components must
be able to exchange and understand BACnet data messages.
Your VSD Series II HVAC drive is equipped with BACnet
support as standard.
Principal Example Diagram of BACnet
BACnet IP—Ethernet
BACnet Technical Data
BACnet MS/TP Protocol
ConnectionCommunication
InterfaceRS-485
Data transfer methodRS-485 MS/TP, half-duplex
Transfer cableSTP (Shielded Twisted Pair), type Belden or similar
Connector2.5 mm
Electrical isolationFunctional
BACnet MS/TPAs described in ANSI/ASHRAE Standards 135-2004
Baud rate9600, 19200, 38400 and 76800 baud
BACnet IP Protocol
ConnectionCommunication
Interface100BaseTX, IEEE 802.3 compatible
Data transfer methodEthernet half-/full-duplex
Data transfer speed10/100 MBit/s, autosensing
ProtocolBACnet over UDP/IP
ConnectorShielded RJ45 connector
Cable typeCAT5e STP
BACnet IPAs described in ANSI/ASHRAE Standards 135-2004
Default IPSelectable: Fixed or DHCP
2
(supports autobaud detection)
BACnet Installation
1.Open the cover of the AC drive.
The relay outputs and other I/O-terminals may have a
dangerous control voltage present even when VSD
Series II is disconnected from mains.
2.Locate the components that you will need on the AC
drive to connect and run the BACnet cables.
Be sure not to plug the Ethernet/BACnet IP cable to the
terminal under the keypad! This might harm your
personal computer.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com77
Communications
IMPORTANT
21
Grounding Bar
22 2324 25 2632 33
12 13 14 15 16 17 18 19 30 B A
RS-485 Terminals
1 2 3 4 5 6 7 8 9 10 11
I/O Terminal
(see larger view)
DIP Switches
Ethernet
(BACnet IP)
Connector
Ethernet Cable
Run Conduit
Ethernet
Cable
0.59 (15.0)
AC Drive Components (BACnet)
You can use the BACnet communication protocol through Ethernet and RS-485.
Prepare For Use Through Ethernet
1.Connect the Ethernet cable (see specification on Page
77) to its terminal and run the cable through the conduit
as shown below.
BACnet Ethernet Cable
2.Remount the AC drive cover.
Note: When planning the cable runs, remember to keep the
distance between the Ethernet cable and the motor
cable at a minimum of 11.81 in (30 cm).
Prepare For Use Through MS/TP
1.Strip about 0.59 in (15 mm) of the RS-485 cable (see
specification on Page 77) and cut off the grey cable
shield. Remember to do this for both bus cables (except
for the last device).
Leave no more than 0.39 in (10 mm) of the cable outside
the terminal block and strip the cables at about 0.20 in
(5 mm) to fit in the terminals. See illustration below.
RS-485 Cable Strip
0.39 (10.0)
0.20 (5.0)
Also strip the cable now at such a distance from the
terminal that you can fix it to the frame with the
grounding clamp. Strip the cable at a maximum length of
0.59 in (15 mm).
!
Do not strip the aluminum cable shield!
RS-485 Cable Strip (Aluminum Shield)
78VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
2.Then connect the cable to its appropriate terminals
Cable Clamp
on VSD Series II AC drive standard terminal block,
terminals A and B (A = negative, B = positive). See
illustration below.
VSD Series II AC Drive Terminals (BACnet)
8910
Communications
RS485 Terminals
(A and B)
3.Using the cable clamp included in the delivery of the
drive, ground the shield of the RS-485 cable to the frame
of the AC drive.
RS-485 Ground
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com79
Communications
Termination
Activated
BACnet MS/TP
Termination
Deactivated
4.If VSD Series II is the last device on the bus, the bus
termination must be set. Locate the DIP switches to the
right of the control keypad of the drive and turn the
switch for the RS-485 bus termination resistor to
position ON. Biasing is built in the termination resistor.
See also step 6 below.
RS-485 Bus Termination Setup
RS485*
CurrentVoltage
CurrentVoltage
CurrentVoltage
* Bus termination resistor
AO1
AI1
AI2
5.Remount the AC drive cover.
Note: When planning the cable runs, remember to keep the
distance between the fieldbus cable and the motor
cable at a minimum of 11.81 in (30 cm).
6.The bus termination must be set for the first and last
device of the fieldbus line. See illustration below. See
also step 4 above. We recommend that the first device
on the bus terminated is the Master device.
BACnet MS/TP Bus Termination
OFFON
VSD Series II
= Bus Termination
80VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
VSD Series II VSD Series II VSD Series IIVSD Series II
Termination
Activated with
DIP switch
BACnet Programming
The navigation path to the fieldbus parameters may differ
from application to application. The exemplary paths below
apply to the VSD Series II HVAC drive.
1.First ensure that the right fieldbus protocol is selected.
P4.8.3.2.2 Communication status0.099.999—0.0—0–99 = Number of messages with errors
P4.8.3.2.3 Actual instance number065535—Serial number —Shows actual Device Object’s instance
P4.8.3.2.4 Control word——hex——See Page 89
P4.8.3.2.5 Status word——hex——See Page 89
0–999 = Number of messages without
communication errors
number
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com83
Communications
BACnet MS/TP Parameter Descriptions
BACnet MS/TP Parameters
P4.7.3.1.1Baud Rate
Select the communication speed for the network. The
default value is 9600 baud. If value Auto is chosen this
parameter is not editable.
P4.7.3.1.2Autobauding
This function is set off by default. If the parameter is given
value 1 the automatic baud rate detection is used. The
automatically detected baud rate is then shown as value of
parameter P4.7.3.1.1 Baud Rate.
P4.7.3.1.3MAC Address
The parameters of every device must be set before
connecting to the bus. Especially the parameters MAC address and baud rate must be the same as in the master’s
configuration.
The first parameter, MAC (Medium Access Control) address,
must be unique on the network to which it is connected. The
same MAC address may be used on a device on another
network within the internetwork.
Addresses 128–254 are reserved for slaves. Addresses
1–127 are valid for both masters and slaves. The portion of
the address space that is actually used for masters in a
particular installation is determined by the value of the
Max_Master property of the device object.
It is recommended that MAC address 0 be reserved for use
by the MS/TP router. 255 is reserved for broadcasts.
P4.7.3.1.4Instance Number
The Device Object’s Instance number must be unique across
the entire BACnet internetwork because it is used to
uniquely identify the BACnet devices. It may be used to
conveniently identify the BACnet device from other devices
during installation.
If 0 (default) is selected, the Device Instance number is read
from Drive. This unique number is then shown in the Monitor
menu. If any other value than zero is selected, the value is
used as Device Object's Instance number. The actual value is
shown in the Monitor menu. The default value for this
parameter is generated from the Ethernet MAC address.
Last 2 octets will be used. XX.XX.XX.XX.FF.FF.
P4.7.3.1.5Communication Time-out
BACnet board initiates a communication error if the board is
a “sole master” in the network for a time defined with this
parameter. “0” means that no fault is generated.
BACnet MS/TP Monitoring Values
P4.7.3.2.1Fieldbus Protocol Status
Fieldbus Protocol Status tells the status of the protocol.
P4.7.3.2.2Communication Status
The Communication status shows how many error and how
many good messages the frequency converter has received.
The Communication status includes a common error counter
that counts CRC and parity errors and a counter for good
messages.
Only messages to the current slave in use are counted in the
good messages, not MS/TP token packages.
BACnet MS/TP—Good Messages
CodeDescription
0–999Number of messages received without errors
BACnet MS/TP—Bad Frames
CodeDescription
0–99Number of messages received with errors
P4.7.3.2.3Actual Instance Number
Shows the actual instance number.
P4.7.3.2.4Fault Code
Shows BACnet MS/TP fault codes.
P4.7.3.2.5Control Word
Shows the Control Word received from the bus.
P4.7.3.2.6Status Word
Shows the current Status Word that is sent to the bus.
84VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com
BACnet IP Parameter Descriptions
Communications
Ethernet Common Settings
P4.8.1.1 IP Address Mode
Selectable alternatives are DHCP (Dynamic Host
Configuration Protocol) and Fixed.
DHCP protocol gives IP addresses to new devices
connecting to local network. This address is valid for a certain
period of time.
A fixed IP address is specified manually and it does not
change.
When the mode is changed from DHCP to Fixed the
addresses will read
An IP address is a series of numbers (like above) specific to
the device connected to the Internet.
P4.8.1.3Subnet Mask
The network mask marks all the bits of an IP address for the
identification of the network and the subnetwork.
P4.8.1.4Default Gateway
Gateway address is the IP address of a network point that
acts as an entrance to another network.
P4.8.1.5 MAC Address
The MAC address of the control board.
MAC address (Media Access Control) is a unique address
given to each network host.
IP Monitoring Values
P4.8.3.2.1Fieldbus Protocol Status
Fieldbus Protocol Status tells the status of the protocol.
P4.8.3.2.2Communication Status
The Communication status shows how many error and how
many good messages the frequency converter has received.
The Communication status includes a common error counter
that counts CRC and parity errors and a counter for good
messages.
BACnet IP—Good Messages
CodeDescription
0–999Number of messages received without errors
BACnet IP—Bad Frames
CodeDescription
0–99Number of messages received with errors
P4.8.3.2.3Actual Instance Number
The Device Object’s actual instance number. This monitoring
value is needed when value 0 is written to parameter
P4.8.3.1.1.
P4.8.3.2.3Control Word
Shows the Control Word received from the bus.
P4.8.3.2.4Status Word
Shows the current Status Word that is sent to the bus.
BACnet IP Settings
P4.8.3.1.1Instance Number
Similar to BACnet MS/TP device object instance number (see
Page 84).
P4.8.3.1.2Communication Time-out
BACnet board initiates a communication error if the Ethernet
connection is lost. Communication time-out parameters
define the minimum delay between UDP packages received
from the master. The timer is reset and started after each
received UDP package. This parameter can be used if the
master is periodically polling the slaves.
P4.8.3.1.3Protocol In Use
BACnet/IP protocol can be enabled and disabled with this
parameter. When the parameter value is set to “1” the
BACnet/IP protocol is enabled and disabled when set to “0”.
VSD Series II LIT12011771—April 2013 www.johnsoncontrols.com85
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.