IMPORTANT: This guide is intended to provide a quick reference to
the VSD Series drive’s Application Software features for start-up,
programming and service. It does not replace the need to thoroughly
read and understand the User Manual.
Table of Contents
Description Page
NEMA Type 1/12 Open Drives (1 – 250 HP) . . . . . . . . . . . . . .2
NEMA Type 1 IntelliPass/IntelliDisconnect Drive . . . . . . . . .5
Upon receipt of the unit, verify that the catalog number and unit
options stated on the shipping container match those stated on
the order/purchase form.
Inspect the equipment upon delivery. Report any carton damage
to the carrier prior to accepting the delivery. Have this
information noted on the freight bill. Johnson Controls is not
responsible for damage incurred in shipping.
Unpacking
Remove all packing material from the unit. Be sure to remove all
packing material from lug location. Also, make sure no packing
material is left behind that would block the airflow to the fan.
Check the unit for any signs of shipping damage. If damage to
the product is found after unpacking, report it to the freight
company. Retain the packing materials for the carrier to review.
Storage
It is recommended that the unit be stored in its original shipping
box/crate until it is to be installed.
The unit should be stored in a location where:
•
The ambient temperature is between -40°F and 158°F
(-40°C and 70°C)
•
The relative humidity is between 0% and 95%,
non-condensing
•
The environment is dry, clean, and non-corrosive
•
The unit will not be subjected to high shock or vibration
conditions
NEMA Type 3R
Technical Support Phone Numbers
Branch: 800-281-3792 (Option 1)
Third Party (ABCS/DIST): 800-445-4757 (Option 1)
LIT-1201858
For more information visit: www.johnsoncontrols.com
Mandatory Ground Wiring (See Appendix D on Page 18)
Be sure to pull low impendance ground wiring from customer
power to drive and ground wire from drive to motor.
UtilityDriveMotor Ground
(Inside Motor Conduit Box)
1
VSD Series Quick Start Guide
NEMA Type 1/12 Open Drives (1 – 250 HP)
Table 1: Control Wiring Instructions
Mounting Drive
1. Mount Drive
(See Table below for dimensions.)
VSD Series Open Drive Dimensions
Frame
Size
FR4230V3/4 – 312.9
FR5230V5 – 7-1/216.5
FR6230V10 – 1522.0
FR7230V20 – 3024.8
FR8480V75 – 12529.7
FR9
FR10480V250 – 35044
Voltagehp (VT)Approximate Dimensions in Inches (mm)Weight
H1H2H3D1D2D3W1W2R1 dia.R2 dia.
480V1 – 5
480V7-1/2 – 15
480V20 – 30
575V2 – 25
480V40 – 60
575V30 – 40
575V
480V150 – 20045.3
575V100 – 150
575V200 – 300
50 – 75
(327)
(419)
(558)
(630)
(755)
(1150)
(1120)
12.3
(313)
16.0
(406)
21.3
(541)
24.2
(614)
28.8
(732)
44.1
(1120)
33.5
(850)
Power Wiring
Notice
Do not discard the plastic bag containing the wiring plate.
2. Remove the bottom cover by rotating the cover toward
you on the base hinges, then lifting the cover away from
the base.
D1
11.5
(292)
15.4
(391)
20.4
(519)
23.3
(591)
28.4
(721)
—14.3
—23.6
7.5
(190)
8.4
(214)
9.3
(237)
10.1
(257)
11.3
(288)
(362)
(600)
H1
H3
H2
Figure 1:
2.5
(64)
2.7
(68)
2.7
(68)
2.7
(68)
1.3
(34)
5.4
(137)
NANA23.6
5.0
(126)
5.8
(148)
6.7
(171)
7.5
(189)
11.0
(279)
8.8
(224)
5.0
(128)
5.7
(144)
7.7
(195)
9.3
(237)
11.2
(285)
18.9
(480)
(600)
W1
W2
Powered by
R2
R1
R2
3.9
(100)
3.9
(100)
5.8
(148)
7.5
(190)
10.0
(255)
15.7
(400)
16.7
(425).9(23)
.5
(13)
.5
(13)
.7
(18)
.7
(18)
.7
(18)
.7
(18)
Eaton’s Technology
November 2009
D2
D3
Knockouts
Lbs. (kg)
.3
(7)
.3
(7)
.4
(9)
.4
(9)
.4
(9)
.4
(9)
.47
(12)
11
(5)
17.9
(8.1)
40.8
(18.5)
77.2
(35)
127.8
(58)
321.9
(146)
550.7
(250)
Power Wiring
3. Locate the plastic bag shipped with the drive containing
the wiring plate, and remove the wiring plate.
2
For more information visit: www.johnsoncontrols.com
LIT-1201858
Powered by
November 2009
Eaton’s Technology
NEMA Type 1/12 Open Drives (1 – 250 HP)
Table 1: Control Wiring Instructions (continued)
Power Wiring
4. If conduit is being used, attach the wiring plate to it.
5. Pass the motor and input power wires/cables through the
holes of the wiring plate.
6. If shielded cable is used, connect the shields of the input
line power cable and the motor cable to the motor and
power ground terminals of the VSD Series drive.
Power Wiring/Grounding
7. Wire power terminals, motor terminals, and grounding
terminals per diagram. Power and Motor leads must be in
separate conduit.
Note: Do not wire motor loads to B- B+ R-. This will cause
damage.
VSD Series Quick Start Guide
GROUND WIRING
•
Run motor cables in separate conduit.
DO NOT RUN CONTROL WIRES in same conduit
•
Cables sized per NEC.
•
Provide low impedance ground between drive and
•
motor.
UtilityDriveMotor Ground
IMPORTANT: Improper grounding could result in damage to the
motor and/or drive and could void warranty
Control Wiring
8. Wire the control terminals following the details for the
specific option boards shown on the following pages.
Note: For ease of access, the option board terminal blocks can
be unplugged for wiring.
Note: If using conduit or Seal Tite for control wiring for Frame
4, you must order NEMA Type 12 kit.
(Inside Motor Conduit Box)
LIT-1201858
For more information visit: www.johnsoncontrols.com
3
VSD Series Quick Start Guide
NEMA Type 1/12 Open Drives (1 – 250 HP)
Table 1: Control Wiring Instructions (continued)
Control Wiring
9. Wire control to the OPTA9 Control Board and OPTA2.
Note: Drive default is programmed for Damper Interlock.
Note: Option Boards OPTC2 (N2/XT/SA Bus) and OPTC4
(LonWorks) are optional.
Mandatory Ground Wiring
Be sure to pull low impendance ground wiring from
customer power to drive and ground wire from drive
to motor.
UtilityDriveMotor Ground
I/O Connection
Run 110 Vac and 24 Vdc Control wiring in separate
•
conduit.
Communication wire to be shielded.
•
RS-232 Keypad cable less than 20 feet.
•
(Inside Motor Conduit Box)
Incoming Power
Optional
CB
Note: Must pull
dedicated
ground wire
to drive
and motor.
1
+1DV
2
Vin+
3
GND
4
Lin+
5
Lin–
6
24Vout
7
GND
8
DIN1
9
DIN2
10
DIN3
11
CMA
12
24Vout
13
GND
14
DIN4
15
DIN5
16
DIN6
17
CMB
18
Lout+
19
Lout–
20
DO1
Powered by
Reference Output
Analog Input Voltage
(Range 0-10V DC)
I/O Ground
Analog Input Current
(Range 4-20mA)
Control Voltage Output
I/O GroundStart/Stop
External Fault
Run Permisive Damper Interlock
DIN1-DIN3 Common
Control Voltage Output
I/O GroundSpeed Select 1
Fire Mode
Bypass Overload Fault
DIN4-DIN6 Common
Output Frequency
Analog Output
Digital Output Ready
X1
A
B
C
D
X2
A
B
C
D
X3
X6
A
B
C
D
Eaton’s Technology
November 2009
Note:
See Figure 3
for Dip X1, X2,
X3, X6 Switch
settings.
Start-Up Wizard
X1 Jumper Setting
Analog Input 1 (AI1)
0 to 10V*
Voltage Input
0 to 20 mA
Current Input
0 to 10V
(Differential)
Voltage Input
-10 to 10V
Voltage Input
A
A
A
A
Note:
Optional Communication Cards can be
supplied with the Drive or as a Field Option.
Figure 2:
X2 Jumper Setting
Analog Input 2 (AI2)
B
A
0 to 20 mA*
B
CD
CD
B
B
CD
B
C D
Current Input
0 to 10V
Voltage Input
0 to 10V
(Differential)
Voltage Input
-10 to 10V
Voltage Input
B
A
C D
X1X3X2
A
CD
B
A
CD
A
CD
B
B
A
C D
B
C D
X6
B
A
C D
X6 Jumper Setting
Analog Output 1 (A01)
B
A
0 to 20 mA*
Current Output
0 to 10V
Voltage Output
CMA and CMB Grounding
* Designates Default Jumper Settings
CD
B
A
CD
X3 Jumper Setting
CMB Connected to Ground*
CMA Connected to Ground
CMB Isolated from Ground
CMA Isolated from Ground
CMB and CMA Internally
Connected and Isolated
from Ground
Figure 3: Option Board A9 Location and Settings
See Appendix G.
4
For more information visit: www.johnsoncontrols.com
LIT-1201858
November 2009
Powered by
Eaton’s Technology
VSD Series Quick Start Guide
NEMA Type 1 IntelliPass/IntelliDisconnect Drive
Circuit Breaker Endplate
Circuit Breaker
Extension Bar
Circuit Breaker
Ribbon
Cable Hinge
Output & Bypass
Contactor*
24V DC Power Supply *
Optional 3rd Input Contactor *
Contactor Overload *
Manual/Auto Reset *
24V DC Motor Overload
Terminal Block *
* IntelliPass only.
Optional 3rd Contactor S1 Switch *
(provided for drive isolation)
Figure 4: Identification of NEMA Type 1 Components
Figure 5: VSD Series IntelliPass/IntelliDisconnect Drive Dimensions
Ground Studs
Drive Enclosure Endplate
(located at bottom)
Table 2: VSD Series NEMA Type 1 IntelliPass/IntelliDisconnect Drive
Dimensions
Drive
Horsepower (VT)
208V, 1 – 3 hp
230V, 1 – 3 hp
480V, 1 – 7-1/2 hp
208V, 5 – 7-1/2 hp
230V, 5 – 10 hp
480V, 10 – 20 hp
208V, 10 – 20 hp
230V, 15 and 20 hp
480V, 25 – 40 hp
208V, 25 and 30 hp
230V, 25 and 30 hp
480V, 50 – 75 hp
If mounting two or more IntelliPass Drives next to each other, make sure to use the
proper spacing between the drives for hinged door operation.
Frame
Approximate
Size
Dimensions in
Inches (mm)
ABCD
FR45.04
FR55.50
FR67.50
FR79.10
(128)
(140)
(191)
(231)
18.25
(464)
23.25
(591)
29.38
(746)
37.53
(953)
13.24
(336)
13.24
(336)
15.25
(387)
15.25
(387)
Approx.
Weight
in lbs. (kg)
21 (9.5)5.3 (134.6)
35 (15.9)5.7 (144.8)
67 (30.4)7.5 (190.5)
108 (49.0)9.0 (228.6)
Distance
Between
Drives in
Inches (mm)
LIT-1201858
For more information visit: www.johnsoncontrols.com
5
VSD Series Quick Start Guide
NEMA Type 1 IntelliPass/IntelliDisconnect Drive
Table 3: Bypass Power Wiring Instructions — NEMA Type 1
Mounting Drive
1. Mount drive per dimensions. (See Page 5.)
2. Verify that the main power source is removed upstream.
3. Using a flat-blade screwdriver, remove the four screws
securing the outer cover of the drive and remove the
cover.
4. Using the same screwdriver, remove the two center
screws securing the side cover.
5. Make sure there is adequate room, and open the hinged
side cover.
Power Wiring
6. Using a flat-blade screwdriver, remove the screws
securing the endplate at the bottom of the drive enclosure,
and remove the endplate.
7. Using a Greenlee conduit cutter (recommended), cut one
or more holes in the endplate, located at the bottom of the
drive’s enclosure, for the motor and power leads.
Note: If bringing the power leads in through the top of the
drive’s enclosure, go to step 8. If not, proceed to step 10.
Outer Cover
Bottom
Endplate
Powered by
Eaton’s Technology
November 2009
Two Screws on
Side Cover
Power Wiring
8. Using a flat-blade screwdriver, remove the screws
securing the endplate for the circuit breaker enclosure,
and remove the endplate.
9. Using a Greenlee conduit cutter (recommended), cut one
hole in the circuit breaker endplate for the power leads.
Power Wiring
10. Calibrate the circuit breaker amperage, so it is 1.25 times
the amperage on the motor nameplate, by turning the
red set screw located below the circuit breaker extension
bar. See the circuit breaker user’s manual supplied with
the drive.
11. Connect the incoming power leads to circuit breaker
terminals labeled L1, L2 and L3. Cables sized per NEC.
12. Using the torque wrench, tighten each terminal to the
torque value found in the appropriate user’s manual
supplied with the drive.
POWER WIRING
Run cabling in separate metal conduit or wiring tray.
•
DO NOT RUN CONTROL WIRING with incoming
•
power wiring.
Provide low impedance ground connection to drive
•
chassis.
DO NOT CONNECT to B+, B-, R terminals.
•
Incoming
Power Leads
Circuit Breaker
Set Screw
Circuit Breaker
Extension Bar
Circuit Breaker
Endplate
Circuit Breaker
Terminals
6
For more information visit: www.johnsoncontrols.com
LIT-1201858
Powered by
November 2009
Eaton’s Technology
NEMA Type 1 IntelliPass/IntelliDisconnect Drive
Table 3: Bypass Power Wiring Instructions — NEMA Type 1 (continued)
Motor Wiring
13. Use your first and second fingers and simultaneously
push down to release the two orange retaining clips (one
on each side of the 24V DC motor overload terminal
block).
14. If necessary, use a flat-blade screwdriver to carefully
remove the terminal block in a straight plane to avoid
damaging it.
Motor Wiring
15. Connect the motor leads to the motor overload terminals
labeled 1TA, 1TB and 1TC.
16. Using the appropriate metric Allen wrench (2.5 mm, 3 mm
or 4 mm), tighten each overload terminal per the
specifications in the contactor user’s manual.
MOTOR WIRING
An SAE allen wrench will damage the terminals,
and the motor overload will need to be replaced
(not covered by warranty).
17. Using the torque wrench, tighten each terminal to the
torque value found in the appropriate user’s manual
supplied with the drive.
18. Reinsert the motor overload terminal block.
Motor
Leads
VSD Series Quick Start Guide
Motor
Overload
Terminals
Grounding
19. Use a flat-blade screwdriver to connect the motor ground
wire to the ground stud (located at either the top or
bottom of the drive’s enclosure). (Mandatory) Ground
connection main power ground must be connected to
other ground screws.
GROUND WIRING
Run motor cables in separate conduit.
•
DO NOT RUN CONTROL WIRES in same conduit
•
•
Cables sized per NEC.
Provide low impedance ground between drive and
•
motor.
UtilityDriveMotor Ground
IMPORTANT: Improper grounding could result in damage to the
motor and/or drive and could void warranty
LIT-1201858
(Inside Motor Conduit Box)
For more information visit: www.johnsoncontrols.com
Motor
Ground
Stud
7
VSD Series Quick Start Guide
NEMA Type 1 IntelliPass/IntelliDisconnect Drive
Table 3: Bypass Power Wiring Instructions — NEMA Type 1 (continued)
Setting Overload
20. Lift to open the cover on the motor overload, and use a
1/8" flat-blade screwdriver to set the overload amperage to
match the value on the motor nameplate.
21. Turn the auto/manual reset (factory default is manual) on
the motor overload 90° to the auto position.
Control Wiring
22. Use a flat-blade screwdriver to carefully remove the lowvoltage I/O terminal block.
23. Insert the incoming control leads into the terminal block.
Refer to the electrical schematic supplied with the drive.
24. Reinsert the I/O terminal block into the control board.
25. Verify that all other wires to the terminal block are
connected.
26. Terminate control wiring to the OPTA9 and OPTA2 board
(Terminals 1 – 26).
Powered by
Eaton’s Technology
November 2009
Auto/Manual
Reset
CONTROL WIRING
Run 110 Vac and 24 Vdc control wiring in separate
•
conduit.
•
Communication wire must be shielded.
RS-232 keypad cable must be less then 25 feet.
•
OptionalOptional
Customer
Ground
Drive
Ground
Start/Stop
Speed Select 1
Fire Mode
Bypass Overload Fault
Drive
Ground
Motor
Ground
Note: See Figure 3
for Dip X1, X2,
X3, X6 Switch
settings.
Note: Optional COMM cards can be supplied
Note: with the drive or as a field option.
Figure 6: VSD Series IntelliPass with Three Contactors
8
For more information visit: www.johnsoncontrols.com
LIT-1201858
Powered by
November 2009
Eaton’s Technology
NEMA Type 1 IntelliPass/IntelliDisconnect Drive
able 3: Bypass Power Wiring Instructions — NEMA Type 1 (continued)
Static Check
27. Make sure power is off, and perform static checks as
described in Table 7
(for the inverter) and Table 9 (for the DC bus). Refer to
Page 25, Appendix H.
Note: Static check shown is for L3 and B+ terminals.
28. Once the pre-power static checks are completed,
reinstall the drive’s outer and side covers, tightening
all the screws.
High Voltage is present on L1, L2, L3, B-, B+, BT, T1, T2, T3.
Starting Drive
29. Make sure that the drive’s 3rd contactor S1 switch, if
present, is in the ON position (shown in OFF position).
Note: The bypass mode operates with the switch in the OFF
position, however the drive will not run. Yet the keypad
will operate.
(for the converter), Table 8
WARNING
VSD Series Quick Start Guide
L1, L2, L3B-, B+, BTT1, T2, T3
Starting Drive
30. Turn the circuit breaker handle in a clockwise direction.
WARNING
High Voltage
• Always work with another person.
• Be sure equipment is properly grounded.
• Wear safety glasses.
Start-Up Wizard
Circuit Breaker
Handle
See Appendix G.
LIT-1201858
For more information visit: www.johnsoncontrols.com
9
VSD Series Quick Start GuidePowered by
Enclosed NEMA Type 12/3R
Optional NEMA Type 3R Hood
(Hood not present on
NEMA Type 12 drive)
Power Ground Stud
Circuit Breaker
Eaton’s Technology
November 2009
Circuit Breaker
Handle
24V DC Power Supply
Optional 3rd Input Contactor
Keypad Cable
Space Heater (not on
electrical schematic)
Output & Bypass Contactor
50 hp NEMA Type 3R
480V AC Variable
Frequency Drive
(behind drive cover)
Optional 3rd Contactor S1 Switch
(provided for drive isolation)
Contactor Overload
24V DC Motor Overload
Terminal Block
Motor Ground Stud
Figure 7: Identification of NEMA Type 12 and NEMA Type 3R Components
Note: You will need to consult the electrical schematic supplied with the drive and the appropriate wiring diagram in Appendix D.
Table 4: VSD Series NEMA Type 12 Enclosed IntelliPass Drive
Dimensions
Drive
Horsepower (VT)
208V, 1 – 15 hp
230V, 1 – 15 hp
480V, 1 – 30 hp
575V, 3 – 30 hp
208V, 20 – 30 hp
230V, 20 – 30 hp
480V, 40 – 75 hp
575V, 40 – 50 hp
208V, 40 – 60 hp
230V, 40 – 60 hp
480V, 100 – 150 hp
Floor Stands available on Box C only and can be purchased and shipped separately
as kit.
Frame
Size
FR4 – FR6
FR4 – FR6
FR4 – FR6
FR6
FR6 – FR7B20.92
FR8C30.92
Enclosure
Box
A16.92
Approximate Dimensions in
Inches (mm)
ABC
(429.8)
(531.3)
(785.3)
29.00
(736.6)
40.00
(1016.0)
52.00
(1320.8)
18.60
(472.4)
19.10
(485.1)
19.10
(485.1)
Table 5: VSD Series NEMA Type 3R Enclosed IntelliPass Drive
Dimensions
Drive
Horsepower (VT)
208V, 1 – 15 hp
230V, 1 – 15 hp
480V, 1 – 30 hp
575V, 3 – 30 hp
208V, 20 – 30 hp
230V, 20 – 30 hp
480V, 40 – 75 hp
575V, 40 – 50 hp
208V, 40 – 60 hp
230V, 40 – 60 hp
480V, 100 – 150 hp
Floor Stands available on Box C only and can be purchased and shipped separately
as kit.
Frame
Size
FR4 – FR6A21.05
FR6 – FR7B26.31
FR8C37.73
Enclosure
Box
Approximate Dimensions in
Inches (mm)
ABC
(534.7)
(668.3)
(958.3)
33.00
(838.2)
46.09
(1170.7)
58.09
(1475.5)
19.57
(497.0)
20.07
(509.9)
20.08
(510.0)
NEMA Type 12
Figure 8: VSD Series Enclosed Drive Dimensions
10For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
Space Heater
Temperature
Setting
November 2009
Eaton’s TechnologyVSD Series Quick Start Guide
Enclosed NEMA Type 12/3R
Table 6: Bypass Power Wiring Instructions — NEMA Type 12/3R
Mounting Drive
1. Mount drive per dimensions. (See Page 10.)
2. Verify that the main power source is removed upstream.
3. Remove the keypad cable from the drive.
4. Remove the screws from the drive cover, and remove the
cover.
CAUTION
The circuit breaker extension bar is sharp and can cause injury.
5. Calibrate the circuit breaker amperage, so it is 1.25 times
the value on the motor nameplate, by turning the red set
screw located below the circuit breaker extension bar. See
the circuit breaker user’s manual supplied with the drive.
Keypad Cable
Circuit
Breaker
Extension Bar
Circuit
Breaker
Set Screw
Power and Ground Wiring
6. Using a Greenlee conduit cutter (recommended), cut three
holes in the drive’s enclosure for the incoming power,
motor and low-voltage control leads.
POWER WIRING
Note: Power, motor and control leads must each be
located in separate conduit.
• DO NOT RUN CONTROL WIRING in same conduit
with power wiring.
• Provide low impedance ground connection to drive
chassis.
• DO NOT CONNECT B+, B-, R terminal.
(Reserved for Braking Resistor only.)
7. Connect the incoming power leads to circuit breaker
terminals labeled L1, L2 and L3.
8. Using the torque wrench, tighten each terminal to
the torque value found in the appropriate user’s
manual supplied with the drive.
9. Connect the power ground wire to the ground stud.
Connect motor ground to ground stud.
Setting Space Heater
10. If applicable, set the space heater. See the space heater
user’s manual supplied with the drive.
Note: The space heater is used to prevent condensation from
damaging the equipment when the drive is not operating
(OFF).
Incoming
Power Leads
Power
Ground Wire
LIT-1201858
For more information visit: www.johnsoncontrols.com11
VSD Series Quick Start GuidePowered by
Enclosed NEMA Type 12/3R
Table 6: Bypass Power Wiring Instructions — NEMA Type 12/3R (continued)
Motor Wiring
11. Use your first and second fingers and simultaneously
push down to release the two orange retaining clips (one
on each side of the 24V DC motor overload terminal
block).
12. If necessary, use a flat-blade screwdriver to carefully
remove the terminal block in a straight plane to avoid
damaging it.
Setting Motor Overload
13. Lift to open the cover on the motor overload, and use a
1/8" flat-blade screwdriver to set the overload amperage
to match the value on the motor nameplate.
14. Turn the auto/manual reset (factory default is manual) on
the motor overload 90° to the auto position.
Bypass
Contactor
Assembly
Eaton’s Technology
November 2009
Orange
Retaining Clips
Auto/Manual
Reset
Motor Wiring
15. Connect the motor leads to the motor overload terminals
labeled 1TA, 1TB and 1TC.
16. Using the appropriate metric Allen wrench (2.5 mm, 3 mm
or 4 mm), tighten each overload terminal per the
specifications in the contactor user’s manual.
MOTOR WIRING
An SAE allen wrench will damage the terminals,
and the motor overload will need to be replaced
(not covered by warranty).
17. Using the torque wrench, tighten each terminal to
the torque value found in the appropriate user’s
manual supplied with the drive.
18. Reinsert the motor overload terminal block.
19. Connect the motor ground wire to the ground stud.
Note:
• Run motor cables in separate conduit.
• Do not run control wires in same conduit.
• Size motor leads per NEC.
• Provide low impedance ground.
Motor Leads
Bypass
Contactor
Assembly
Motor
Overload
Terminals
Motor
Ground
Stud
12For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
Eaton’s TechnologyVSD Series Quick Start Guide
November 2009
Enclosed NEMA Type 12/3R
Table 6: Bypass Power Wiring Instructions — NEMA Type 12/3R (continued)
Control Wiring
20. Use a flat-blade screwdriver to carefully remove the lowvoltage I/O terminal block.
21. Reinsert the I/O terminal block into the control board.
22. Terminate control wiring to the OPTA9 and OPTA2 board
(Terminals 1 – 26).
Note: Use 1/8" flat-blade.
CAUTION
• Run 110 Vac and 24 Vdc control wiring in separate conduit.
• Communication wire to be shielded.
• RS-232 keypad cable must be less then 25 feet (to prevent
nuisance trips).
Optional Spacer Heater
R
(DC 2)
FAN
Space Heater
Drive
Ground
Motor
Ground
Customer
Ground
Drive
Ground
(Optional)
Start/Stop
Speed Select 1
Fire Mode
Bypass Overload Fault
Note:See Figure 3
for Dip X1, X2,
X3, X6 Switch
settings.
LIT-1201858
Note: Optional COMM cards can be supplied
Note: supplied with the drive or as a field option.
Figure 9:
For more information visit: www.johnsoncontrols.com13
VSD Series Quick Start GuidePowered by
Enclosed NEMA Type 12/3R
Table 6: Bypass Power Wiring Instructions — NEMA Type 12/3R (continued)
Static Check
23. Use a Phillips screwdriver to remove all the faceplate
screws on the high-voltage faceplate, and remove the
faceplate.
Note: Location of the screws may vary from the drive
illustrated. There may be screws securing a bottom faceplate,
which also need to be removed.
Eaton’s Technology
November 2009
High-Voltage
Faceplate
Optional Bottom
Faceplate
Static Check
24. Make sure power is off, and perform static checks as
described in Table 7 (for the converter), Table 8
(for the inverter) and Table 9 (for the DC bus). Refer to
Page 21, Appendix H.
Note: Static check shown is for L3 and B+ terminals.
25. Once the pre-power static checks are completed,
reinstall the drive’s outer and side covers, tightening
all the screws.
WARNING
High Voltage is present on L1, L2, L3, B-, B+, BT, T1, T2, T3.
Starting Drive
26. Make sure that the drive’s 3rd contactor S1 switch, if
present, is in the ON position (shown in OFF position).
Note: The bypass mode operates with the switch in the OFF
position, however the drive will not run. Yet the keypad
will operate.
27. Reinsert the keypad cable and control board on
small drives.
Starting Drive
28. Close the drive door, and turn the circuit breaker handle in
a clockwise direction.
29. Go to Appendix E for keypad operation.
Note: If the circuit breaker latch is locked, use a flat-blade
screwdriver to turn the screw to release the handle.
L1, L2, L3B-, B+, BTT1, T2, T3
WARNING
High Voltage
• Always work with another person.
• Be sure equipment is properly grounded.
• Wear safety glasses.
Start-Up Wizard
14For more information visit: www.johnsoncontrols.comLIT-1201858
See Appendix G.
Powered by
Eaton’s TechnologyVSD Series Quick Start Guide
November 2009
Appendix A — Main Control Board Wiring
Main Control Board Wiring Default in Slot A and B
+
Digital Input
24V DC
OPTA9 Slot A
24V DC
DI-1
DI-3
6
Close Terminal (6-8)
8
to Start VFD
10
Damper/External Interlock
Control Relay
Outputs
OPTA2 Slot B
CR Ratings
8A / 24V DC
.4A / 125V DC
.8A / 250V AC
Continuous Capacity
Analog Outputs
Analog Input
+
Com
+
–
AI-1
AI-2
12
21
22
23
24
25
26
18
19
2
3
4
5
(22-21) Opens on Run (Default)
(22-23) Closes on Run (Default)
(24-25) Opens on Fault (Default)
(25-26) Closes on Fault (Default)
AO-1
0-10V DC Factory Default Source Auto
4-20 mA Default
Setpoint Software Selectable
inStart-Up Wizard
+
Output Frequency (0-f max)
0-20 mA Default
–
500 Ω Resistor to be Added
for 0-10V DC
Applications
Remote Input
Duct Static
Building Static
Pressure Control
Temperature
Generic PI
+
24V DC
≤
2 RMS
PI Applications Using Internal Power Supply from VFD
AI+1
PI Feedback Pressure
0-10V DC Transducer
Connection
PI Feedback Pressure
4-20 mA Pressure
Transducer
2
3
12
3
4
6
0-10V DC
Com GND
24V DC
Com GND
AI+2
4-20 mA
24V DC
Figure 10: Wiring Diagrams (Default)
Out
Com
Power
Com
Out
Power
Pressure
Tra nsducer
Pressure
Tra nsducer
PI Feedback Sensor –
Used for the following
Applications
Duct Static
Building Static
Pressure Control
Temperature
Generic PI
Card is programmable for a 0 – 10V DC with change in jumper. Add X6 jumper on Board A6 from A-B to C-D.
LIT-1201858
For more information visit: www.johnsoncontrols.com15
VSD Series Quick Start GuidePowered by
Appendix B — Interlock Damper Start Example
Interlock Damper Start Example Using 4 – 20 mA Control Signal
Eaton’s Technology
November 2009
1012
To Drive Damper
Interlock Terminals
Fan
Figure 11: Interlock Damper Start Example with
Remote 4 – 20 mA Application
Step 1. Wire Load, Line, Digital In/Out per example and verify
voltage and amperage
Step 2. Static check drive SCR, IGBT, DC Bus per Static Check,
Step. 4. Set Interlock Start P1.2.1 (Programmable Options)
0. Normal start with Interlock
1. Interlock start from one D1-2….D1-6 (D1-3 Default)
2. Interlock start and timeout supervision. If feedback is
not given in timeout request, the unit will not start.
3. Delay start from Run command
Note: Interlock damper controller works in drive or bypass.
Step 5. Select Handto test motor rotation
Step 6. To verify proper motor rotation, press start andto
increase speed in Hand mode
HOA
+
Step 7. To run in Remote Auto mode, run Remote Auto –
Hit stop
HOA
Hittwice, enter
Send START Signal from Field Controller to start drive.
Field
Controller
Terminals
Damper Actuator
Input Terminals
Figure 12: Programming Example
OPTA9 Slot A
+
4 – 20 mA
-
Run
Factory
Jumper
OPTA2 Slot B
(D1-3 Default)
4
A1-2+ Speed
A1-2- Ref
5
6
24 Vdc Control
Close Terminal
(6 – 8) to start VFD
8
D1-1
D1-3 Run Permisive
10
Damper Interlock
(Default)
24 Vdc Control
12
Voltage
22
23
Closes on Run
(Default)
8 A/24 Vdc
.8 A/125 Vac
.4 A/250 Vac
16For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
Eaton’s TechnologyVSD Series Quick Start Guide
November 2009
Appendix C — Interlock Damper Start Example
Interlock Damper Start Example Using PID Duct Static Control Signal
Max WC = 2.5”
Main WC = 0.0”
Setpt WC = 2.0“
1012
To Drive Damper
Interlock Terminals
Fan
Set PT Keypad Default
Error
Actual PI Feedback
A1-1, 0-10 Vdc Default
Figure 13: Interlock Damper Start with PID Duct Static Example
2.50”
Water
O
H
2
Step 1. Wire load line, digital I/O per example and verify
voltage and amperage
Step 2. Static check drive SCR, IGBT, DC Bus per Static Check,
Page 20 and 21
Step 3. Start-up wizard (Duct static application)
Step 4. Select handto check motor rotation
Step 5. Press Start andto increase speed in Hand mode
Step 6. Select Remoteto run in Auto
HOA
+
HOA
Step 7. Tune PID per diagram below
Out
Com
Power
Pressure
X Drive
Damper Actuator
Input Terminals
2
3
6
OPTA9 Slot A
Actual
+
0 ñ 10 Vdc
-
24 Vdc
Factory
Jumper
OPTA2 Slot B
A1-1+ 0 ñ 10 Vdc
2
A1-1- Default
3
24 Vdc Control
6
Close Terminal
(6 ñ 8) to Start VFD
8
D1-1
10
D1-3 Run Permisive
Damper Interlock
(Default)
12
24 Vdc Control Voltage
22
23
Closed on
Run
Default
8 A/24 Vdc
.8 A/125 Vac
.4 A/250 Vac
Hand Mode (M1)
P1.1.13
A1 - 1
A1 - 2
Keypad
Motor Pot
Actual PI (M1)
Feedback
P1.1.17
A1 - 1
A1 - 2
Fieldbus
Min A1-1, A1-2
Max A1-1, A1-2
Ave A1-1, A1-2
Sensor Parameter
Adjustments
Auto Mode (M1)
P1.1.15
A1 - 1
A1 - 2
OR
Keypad
Motor Pot
Fieldbus
Sensor
Output
Signal
PI Setpoint
Figure 15: PID Flow Chart
PI
Error
Amp
PID Gain (M1)
P1.1.20
PID I-Time
P1.1.21
PID Control D
P1.1.22
PI Ref Rise T
P1.1.23
PI Ref Fall Time
P1.1.24
PI Ref Max
P1.1.19
PI Ref Min
P1.1.18
Figure 14:
Output
Frequency
P10 Parameter
Adjustments
LIT-1201858
For more information visit: www.johnsoncontrols.com17
VSD Series Quick Start GuidePowered by
Appendix D — Bypass Wiring Diagram
Motor
Ground
Drive
Ground
B
C
A
D
X1
B
C
A
D
X2
for Dip X1, X2,
X3, X6 Switch
settings.
Note:See Figure 3
X3
B
C
A
D
X6
Eaton’s Technology
November 2009
Close Terminals 6 to 8 or 8 to 12
to Start VFD in Auto Mode.
Relays Shown in De-Energized State.
3
4
Run Motor Cables inSeparate Metal Conduit or
Wire Tray.
Do Not Run with Control Wiring or Power Cables.
Cables to be Sized per NEC.
Provide Low Impedance Ground Connection Between
and Drive.
Reference Output
I/O Ground
Control Voltage Output
I/O Ground
External Fault
DIN1-DIN3 Common
Control Voltage Output
I/O Ground
Bypass Overload Fault
DIN4-DIN6 Common
Output Frequency
Analog Output
Fire Mode
DIN5
DIN6
CMB
Lout+
Digital Output Ready
Lout–
DO1
Enclosure and Motor(s) Must be Grounded.
See Instruction Manual. A continuous wire
must be run from drive to motor.
1
Jumper is Factory Installed to Enable
Start Permissive. Can be Replaced with
N/C Contact.
2
Analog Input Voltage
(Range 0-10V DC)
+1DV
Vin+
OptionalOptional
Start/Stop
Analog Input Current
(Range 4-20mA)
GND
Lin+
Lin–
24Vout
GND
DIN1
Speed Select 1
DIN2
DIN3
CMA
GND
DIN4
24Vout
Notes:
Ground
Drive
Customer
Ground
Run 110 Vac and 24 Vdc Control Wiring
inSeparate Conduit.
Communication Wire to be Shielded.
Run Cabling inSeparate Metal Conduit or Wire Tray.
Do Not Run With Control Wiring or Motor Cables.
Cables to be Sized per NEC.
Provide Low Impedance Ground Connection to
Drive Chassis.
Do Not Connect to B+, B-, R Terminals. These
Terminals are Used for External Braking or Single-
Incoming Power Connection Notes:Motor Connection Notes:
Phase Capacitors.
I/O Connection Notes:
RS-232 Keypad Cable Less Than 20 Feet.
Figure 16:
18For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
November 2009
Keypad Navigation
Eaton’s TechnologyVSD Series Quick Start Guide
Appendix E — Keypad Navigation
Figure 17: Keypad and Display
One Touch Operate Menu Navigation
Monitor Display
Navigation Left
Exit Operate Menu by navigating
to Programming display and
pressing ENTER button or simply
press ENTER button 1 second.
Acknowledgement password
Freq Ref Up
Freq Ref Down
value if defined.
Monitor Display
Navigation Right
Password ?
Note!
HOA OFF-MODE OR HAND-MODE
• Up and down arrows are used to
adjust speed setpoint
HOA AUTO-MODE
• Up and down arrows are used to
adjust PI-Setpoint
Programming Menu *
M1 Parameters
M2 Keypad Control
M3 Active Faults
M4 Fault History
M5 System Menu
M6 Expander Boards
M7 Monitor
Return to Operate
Note!
While in Programming
Menu the display will
automatically return to
default Operate Menu
display after 1 minute
of inactivity. (Time can
be adjusted with
Parameter P5.6.3).
or time delay
LIT-1201858
* See User Manual (LIT-1201828) for complete parameter list.
Figure 18: Operate Menu Navigation
For more information visit: www.johnsoncontrols.com19
VSD Series Quick Start GuidePowered by
Appendix F — Main Menu Navigation
Eaton’s Technology
November 2009
Main Menu Navigation
+
+
Menu Navigation:
Up Arrow
The up arrow advances
to the next menu item.
For example, pressing the
up arrow once will
advance from M1 to M2.
Down Arrow
The down arrow backs up to
the previous menu item.
For example, pressing the
down arrow once will back
up from M2 to M1.
Right Arrow
The right arrow will advance
to the next level in the menu.
For example, pressing the
right arrow once will
advance from M2 to R2.1.
Left Arrow
The left arrow will back up
one level in the menu structure.
For example, pressing the
left arrow once will back
up from R2.1 to M2.
+
+
+
+
+
+
M1 Programming
G1.1
. . .
G1.x
M2 Keypad Control
R2.1 Keypad Reference
. . .
P2.x Stop Button Active
M3 Active Faults
A3.1 Active Fault 1
T3.1.1 Operation Days
. . .
T3.1.13 Zero Speed
. . .
A3.x Active Fault x
M4 Fault History
H4.1 Most Recent Fault
T4.1.1 Operation Days
. . .
T4.1.13 Zero Speed
. . .
H4.1.x Oldest Saved Fault
M5 System Menu
S5.1 Language
S5.2 Application
S5.3 Copy Parameters
S5.4 Compare Parameters
S5.5 Security
S5.6 Keypad Settings
S5.7 Hardware Settings
S5.8 System Information
M6 Expander Boards
G6.1 Slot A Board
. . .
G6.5 Slot E Board
M7 Monitor
V7.1 Actual Speed
V7.2 Output Frequency
V7.3 Speed Setpoint
V7.4 Motor Speed
V7.5 Motor Current
V7.6 Motor Torque
V7.7 Motor Power
V7.8 Motor Voltage
V7.9 DC-Bus Voltage
V7.10 Unit Temperature
V7.11 Motor Temperature
V7.12 (A) AI-1
V7.13 (A) AI-2
V7.14 DI-1 DI-2 DI-3
V7.15 DI-4 DI-5 DI-6
V7.16 DO-1 RO-1 RO-2
V7.17 (A) AO-1
V7.18 ActFaultCode
V7.19 ActWarnCode
V7.20 Status Word
V7.21 PI-Setpoint
V7.22 PI-Input
V7.23 PI-Error
V7.24 PI-Output
V7.25 RO-1 RO-2 RO-3
G7.26 Multimonitor
M8 Operate Mode
O1 Output Frequency
O2 Actual Speed
. . .
Ox Motor Temperature
See Figure 3.
Parameter Menu Structure Example
M1 Programming Menu
+
G1.1 Quick Setup
+
G1.2 Input Signals
+
G1.3 Output Signals
+
G1.4 Drive Control
+
G1.5 Prohibit Frequency
+
G1.6 Motor Control
+
G1.7 Protections
G1.8 Fieldbus
+
G1.9 PI-Control
+
G1.10 Preset Speed
+
Figure 20: Parameter Menu Structure Example
P1.1.1 Minimum Frequency
P1.1.2 Maximum Frequency
. . .
P1.1.26 PI-Contr. I-Time
20For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
Eaton’s TechnologyVSD Series Quick Start Guide
November 2009
Appendix G — Start-Up Wizard
Start-Up Wizard
Duct Static, Building Static, Pressure Control, Temperature Control, Generic PI
Upon initial power up, the Start-Up Wizard guides the commissioner through the basic VSD Series setup.
The Start-Up Wizard may be set to function upon power up by setting parameter P5.5.3, or by pressing the
STOP/RESET button for 5 seconds while in the “Operate Menu”. The display will read “Start-Up Wizard
Activate!” after 5 seconds.
Start of the Start-Up Wizard
Language selection
Duct, Building, Pressure, Temperature, Generic PI
By pressing
By pressing
US/Metric units are used only in Duct,
Building, Pressure and Temperature applications.
Motor Name Plate current in Amps
XX.X A – Default will vary depending
on drive size
Motor Name Plate voltage in Volts
XXX V – Default is same as drive nominal
voltage
setup will start
the setup will be stopped
*
start up wizard
press enter
language
english
application
remote input
setup starts
press enter
US/ metric units
us
motor Np current
XX.X A
motor Np voltage
XXX V
Continued
1Steps:
2
3
4
5
6
7
Figure 21: Start-Up Wizard Navigation (1 of 3)
Note: Use for changing parameter. Then press ENTER to save and move forward.
LIT-1201858
For more information visit: www.johnsoncontrols.com21
VSD Series Quick Start GuidePowered by
Eaton’s Technology
November 2009
8Steps:
9
10
11
12
13
14
15
motor NP freq
60.00 Hz
motor NP rpm
1720 rpm
min. frequency
12.00 Hz
max. frequency
60.00
AUTO ACCEL Time
60.0s
AUTO DECEL time
60.0s
PI-input source
(a) ai-1
sensor min. scale
XXX.X
Motor Name Plate Frequency
default 60.00 Hz
Motor Name Plate Speed
1720 rpm
Drive Minimum Output Frequency
default 12.00 Hz
Drive Maximum Output Frequency
default 60.00 Hz
Acceleration time from zero to Max. Frequency,
when running in auto mode and PI-regulator is not active.
default 60.0 seconds
Deceleration time from Max. Frequency to zero,
when in auto mode and drive is stopped.
default 60.0 seconds
PI Input/Feedback Auto source, when PI is active:
AI-1 (0-10V DC); AI-2 (0-20 mA); Fieldbus
default AI-1
PID Input/Feedback device min. value
This value corresponds to the min. value of the sensor
output and to P1.2.10 or P1.2.14
(not available in Remote Input and Generic PI applications)
16
17
18
AI-1 Min.
0.0%
sensor max. scale
XXX.X
AI-1 Max.
100.00%
Continued
Figure 22: Start-Up Wizard Navigation (2 of 3)
Analog Input 1 min. value
0.00% = 0V
(not available in Remote Input and Generic PI applications)
PID Input/Feedback device max. value
This value corresponds to the max. value of the sensor
output and to P1.2.11 or P1.2.15
(not available in Remote Input and Generic PI applications)
Analog Input 1 max. value
100.00% = 10V
(not available in Remote Input and Generic PI applications)
22For more information visit: www.johnsoncontrols.comLIT-1201858
November 2009
Powered by
Eaton’s TechnologyVSD Series Quick Start Guide
19Steps:
20
21
22
23
PI-contr. p-gain
0.10
PI-contr I-time
30.00
PI-stpt
repeat setup?
NO yes
setup done
press enter
When keypad is used for copying
parameters to or from another drive
new keypad
press enter
copy parameters
NO yes
PI control gain value
default will vary depending on application
PI control integration time
default 30.00 second
PI Setpoint if source is fieldbus
(not available in Remote Input application)
Jump to
*
copy from keypad
NO yes
downloading . . .
wait. . .
copy to keypad
NO yes
uploading . . .
wait. . .
operate menu
default page
Figure 23: Start-Up Wizard Navigation (3 of 3)
Note: Start-Up Wizard can be cancelled with the STOP/RESET button. If pressed, the text “EXIT?” is shown
on the display along with “No” and “Yes”.
Note: In Pressure Control application, inverse selection is an option.
LIT-1201858
For more information visit: www.johnsoncontrols.com23
VSD Series Quick Start GuidePowered by
Remote Input Application
The Remote Input application uses a slightly different Start-Up Wizard:
14610Steps: to , and to are exactly the same.
Eaton’s Technology
November 2009
New
Steps:
Skip to
Step:
12
13
14
15
22
Figure 24: Remote Input Start-Up Wizard
acceleration time
60 s
deceleration time
60 s
start srce auto
DI-1 start
stpt source auto
(a) ai-1
Acceleration time from min. Frequency
to max. Frequency
Deceleration time from max. Frequency
to min. Frequency
Keypad
DI-Start
I/O 3 wire
Fieldbus
(A) AI-1
(A) AI-2
Keypad StPt
Fieldbus
Start source location
Set point of Auto Source
24For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
November 2009
Eaton’s TechnologyVSD Series Quick Start Guide
Appendix H — Static Checking
Static Checking
Static checking tests the integrity of the power-carrying components (diodes, capacitors
and IGBTs) within the drive assembly. Performing these static checks ensures that no
damage occurred during shipping or installation that could cause a failure when the drive
is powered.
Make sure there is no power to the drive before proceeding with any of the static checks.
After checking each set of terminals, zero out the multimeter by touching the metal tips of
the red (positive) and black (negative) leads to each other.
Note: Set the multimeter to the diode function, and check each power terminal
consecutively with each DC bus terminal as indicated in Table 7.
Table 7: Static Checks of Converter
DC Bus TerminalPower TerminalMultimeter
L1L2L3
Reading
B+ (1st Overload Check)
Insert red (+) multimeter lead.
B- (2nd Overload Check)
Insert black (-) multimeter lead.
B- (1st Voltage Check)
Insert red (+) multimeter lead.
B+ (2nd Voltage Check)
Insert black (-) multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
.OL
.OL
.25 – .55V DC
(±10%)
.25 – .55V DC
(±10%)
Note: Set the multimeter to the diode function, and check each motor terminal
consecutively with each DC bus terminal as indicated in Table 8.
Table 8: Static Checks of Inverter
DC Bus TerminalMotor Terminal on Contactor if Bypass or Output ContactorMultimeter
T1T2T3
B+ (1st Overload Check)
Insert red (+) multimeter lead.
B- (2nd Overload Check)
Insert black (-) multimeter lead.
B- (1st Voltage Check)
Insert red (+) multimeter lead.
B+ (2nd Voltage Check)
Insert black (-) multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Insert black (-)
multimeter lead.
Insert red (+)
multimeter lead.
Reading
.OL
.OL
.25 – .40V DC (±10%)
.25 – .40V DC (±10%)
LIT-1201858
For more information visit: www.johnsoncontrols.com25
VSD Series Quick Start GuidePowered by
Eaton’s Technology
November 2009
Appendix H — Static Checking, continued
Note: Set the multimeter to the ohm function, and check the power gµround terminal and DC bus terminals as indicated in Table 9.
Note: Frame 6 and larger use a “Hybrid” rectifier section. “Shown in Service Manual.”
Readings will be different when taking measurements from (B+) DC.
Table 9: Static Checks of DC Bus
DC Bus TerminalDC Bus Terminal (B-)Ground Terminal (Power)Multimeter Reading
B+ (Overload Check)
Insert red (+) multimeter lead.
B+ (1st Ohm Check)
Insert black (-) multimeter lead.
B- (2nd Ohm Check)
Insert black (-) multimeter lead.
Insert black (-) multimeter lead.Not used..OL
Not used.Insert red (+) multimeter lead.O.L
Not used.Insert red (+) multimeter lead.O.L
Figure 25 is a detailed schematic to aid in performing the static checks.
Continuity Test to Ground
TestL1, L2, L3 to ground.
T1, T2, T3 to ground.
This should read .OL ohms.
Figure 25: Schematic for Static Checks (Sample for Frames 4 and 5)
26For more information visit: www.johnsoncontrols.comLIT-1201858
Powered by
Eaton’s TechnologyVSD Series Quick Start Guide
November 2009
Appendix I — Fault and Warning Codes
Table 10: Fault and Warning Codes/Solutions
Fault
CodeFaultPossible CauseSolution
1OvercurrentVSD Series drive has detected a high current (>4xI
2OvervoltageThe DC-link voltage has exceeded its high limit due to:
3Ground (Earth) FaultCurrent sensing indicates that the sum of motor phase
5Charging SwitchThe charging switch was open, when the START
6Emergency stopAn Emergency stop signal was received from one of the
7Saturation trip• defective component
8System fault• component failure
9UndervoltageDC-link voltage is less than the minimum safe operating
10Input line supervisionInput line phase is low or missing.Check the utility supply voltage, cables and connections.
11Output phase supervisionCurrent sensing indicates that there is no current in one
12Brake chopper supervision• no brake resistor installed
13VSD Series under-
14VSD Series overtemperatureHeatsink temperature is over 90°C. An overtemperature warning is issued when the heatsink
15Motor stalled• motor or load mechanical failure
16Motor overtemperature• motor is overloaded
17Motor underload• mechanical or load problem
22
23
25Microprocessor watchdog
temperature
EEPROM checksum fault• Parameter save fault
fault
output due to:
• sudden heavy load increase
• short in the motor
• short in the cables to the motor
• unsuitable motor
• too short a deceleration time
• high voltage levels or surges in the utility supply
currents is not zero.
• insulation failure in motor or motor cables
command was given due to:
• faulty operation
• component failure
digital inputs
• motor or motor cable short
• faulty operation
Note: exceptional fault data record, see Active Fault Menu
for more information
voltage limit
• most probable cause: too low a utility supply voltage
• VSD Series internal fault
motor phase
• brake resistor is broken
• brake chopper failure
Heatsink temperature is under -10°CProvide supplemental heating or relocate the VSD Series
• load too high
• stall parameter settings incorrect
• motor overheating has been detected by VSD Series •
motor temperature model
• underload parameter settings incorrect
• faulty operation
• component failure
• faulty operation
• component failure
) in its
Check loading.
n
Check motor.
Check cables.
Make the deceleration time longer.
Use brake chopper and brake resistor (standard on some
models, available as options on others).
Correct utility supply voltage (level is too high).
Add input impedance to limit surges.
Check motor and motor cables.
Reset the fault and restart. Should the fault re-occur,
contact your Johnson Controls distributor.
Determine reason for the Emergency stop and remedy it.
Cannot be reset from the keypad.
Switch off power.
IF THE PROBLEM IS NOT IN THE MOTOR OR ITS CABLES,
DO NOT RE-CONNECT POWER!
Contact your Johnson Controls distributor.
If this fault appears simultaneously with Fault 1, check the
motor and motor cables.
Reset the fault and restart. Should the fault re-occur,
contact your Johnson Controls distributor.
If there was a supply voltage loss or dip, reset the fault
and restart the VSD Series drive. Check the supply
voltage. If it was within specification at the time of the
fault, an internal failure has occurred. Contact your
Johnson Controls distributor.
Check the motor cables, connections and motor.
Check the brake resistor. If the resistor is ok, the chopper
is faulty. Contact your Johnson Controls distributor.
drive to a warmer location.
temperature exceeds 85°C, a fault occurs at 90°C. Check
for the correct amount and unrestricted flow of cooling
air.
Check the heatsink for dust or dirt buildup.
Check the highest ambient temperature level.
Make sure that the switching frequency is not set too high
in relation to the ambient temperature and motor load.
Check the motor, mechanical system and load level.
Confirm the stall parameter settings.
Decrease the motor load.
If no motor overload exists, check the temperature model
parameters.
Check the motor, check for a loose belt, broken coupling
or load problems.
Confirm underload parameter settings.
Upon reset of this fault, the VSD Series drive will
automatically reload the parameter default settings.
Check all parameter settings after reset. If the fault
reoccurs, contact your Johnson Controls distributor.
Reset the fault and restart. If the fault reoccurs, contact
your Johnson Controls distributor.
LIT-1201858
For more information visit: www.johnsoncontrols.com27
Appendix I — Fault and Warning Codes, continued
Table 10: Fault and Warning Codes/Solutions (continued)
Fault
CodeFaultPossible CauseSolution
26Start-up preventedStart-up of the drive has been prevented.Check Start Enable/Interlock settings.
29Thermistor faultThe thermistor input of an option board has detected a
31IGBT temperature hardwareIGBT Inverter Bridge overtemperature protection has
32Fan coolingThe VSD Series cooling fan did not start when
high motor temperature
detected high short term overload current
commanded
34CAN bus communicationSent message not acknowledgedEnsure that there is another device on the bus with the
36Control unitControl unit cannot control the power unit and vise-versa Change control unit.
37Device change• option board changed
• different power rating of drive
38Device added• option board added
• drive of different power rating added
39Device removed• option board removed
• drive removed
40Device unknownUnknown option board or driveContact your Johnson Controls distributor.
41IGBT temperature softwareIGBT Inverter Bridge overtemperature protection has
42Brake resistor
overtemperature
43Encoder faultNote: the exceptional Fault data record. See Active Fault
detected high short term overload current
Brake resistor overtemperature protection has detected
excessive braking
Menu for more information. Additional codes:
1 Encoder 1 channel A is missing
2 Encoder 1 channel B is missing
3 Both encoder 1 channels are missing
4 Encoder reversed
50Analog input I
(for signal range 4 to 20 mA)
< 4 mA
in
Current at the analog input is
< 4 mA
• control cable is broken or loose
• signal source has failed
51External faultDigital input set as an external fault input has been
52Keypad communication fault The connection between the control keypad and the VSD
53Communication bus faultThe data connection between the communication bus
triggered.
Series drive has been lost.
master and the communication bus board has failed
54Slot faultDefective option board or slotCheck that the board is properly installed and seated in
82BypassOverLoadThe motor has been overloaded while connected to the
bypass
Check the motor cooling and the motor loading.
Check the thermistor connection.
(If the thermistor input of an option board is not being
used, it must be short-circuited.)
Check loading.
Check motor size.
Contact your Johnson Controls distributor.
appropriate configuration.
Reset.
Note: No fault time data record!
Reset.
Note: No fault time data record!
Reset.
Note: No fault time data record!
Check loading.
Check motor size.
Set the deceleration time longer.
Use an external brake resistor.
Check encoder channel connections.
Check the encoder board.
Check the current loop, signal source and wiring.
Check source of trigger.
Check keypad connection and keypad cable.
Check installation.
If installation is correct, contact your Johnson Controls
distributor.
slot. If installation is correct, contact your Johnson
Controls distributor.
Decrease the motor load.
Disable the Current Imbalance feature – see the IT.
manual.
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201