LIT-1201828For more information visit: www.johnsoncontrols.com
November 2009
Powered by
Eaton Technology
VSD Series Drives User Manual
IMPORTANT NOTICE – PLEASE READ
The product discussed in this literature is subject to terms and conditions outlined in
Johnson Controls Inc. selling policies. The sole source governing the rights and remedies of
any purchaser of this equipment is the relevant Johnson Controls Inc. selling policy.
NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A
PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION,
RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Johnson
Controls Inc. or Eaton Electrical Inc. be responsible to the purchaser or user in contract, in tort
(including negligence), strict liability or otherwise for any special, indirect, incidental or
consequential damage or loss whatsoever, including but not limited to damage or loss of use of
equipment, plant or power system, cost of capital, loss of power, additional expenses in the use
of existing power facilities, or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations and descriptions contained herein.
The information contained in this manual is subject to change without notice.
Cover Photo: Johnson Controls VSD Series Drive.
LIT-1201828
For more information visit: www.johnsoncontrols.com
i
VSD Series Drives User Manual
Powered by
Eaton Technology
November 2009
ii
For more information visit: www.johnsoncontrols.com
For more information visit: www.johnsoncontrols.com
ix
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
Safety Issues
Definitions and Symbols
WARNING
This symbol indicates high voltage. It calls your attention to items
or operations that could be dangerous to you and other persons
operating this equipment. Read the message and follow the
instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with either of
two signal words: WARNING or CAUTION as described below.
WARNING
Indicates a potentially hazardous situation which, if not avoided,
can result in serious injury or death.
Indicates a potentially hazardous situation which, if not avoided,
can result in minor to moderate injury, or serious damage to the
equipment. The situation described in the CAUTION may, if not
avoided, lead to serious results. Important safety measures are
described in CAUTION (as well as WARNING).
Hazardous High Voltage
Motor control equipment and electronic controllers are connected
to hazardous line voltages. When servicing drives and electronic
controllers, there may be exposed components with housings or
protrusions at or above line potential. Extreme care should be taken
to protect against shock.
• Stand on an insulating pad and make it a habit to use only one
• Always work with another person in case an emergency occurs.
• Disconnect power before checking controllers or performing
• Be sure equipment is properly grounded.
• Wear safety glasses whenever working on electronic controllers
CAUTION
WARNING
hand when checking components.
maintenance.
or rotating machinery.
xFor more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
Warnings, Cautions and Notices
Read this manual thoroughly and make sure you understand the procedures before you
attempt to install, set up or operate this Johnson Controls VSD Series Variable Speed Drive
powered by Cutler-Hammer® technology from Eaton’s electrical business.
Warnings
Be sure to ground the unit following the instructions in this manual.
Ungrounded units may cause electric shock and/or fire.
This equipment should be installed, adjusted, and serviced by
qualified electrical maintenance personnel familiar with the
construction and operation of this type of equipment and the
hazards involved. Failure to observe this precaution could result in
death or severe injury.
WARNING
WARNING
WARNING
Components within the VSD Series power unit are live when the
drive is connected to power. Contact with this voltage is extremely
dangerous and may cause death or severe injury.
WARNING
Line terminals (L1, L2, L3), motor terminals (U, V, W) and the DClink/brake resistor terminals (-/+) are live when the drive is
connected to power, even if the motor is not running. Contact with
this voltage is extremely dangerous and may cause death or severe
injury.
WARNING
Even though the control I/O-terminals are isolated from line
voltage, the relay outputs and other I/O-terminals may have
dangerous voltage present even when the drive is disconnected
from power. Contact with this voltage is extremely dangerous and
may cause death or severe injury.
WARNING
The VSD Series drive has a large capacitive leakage current during
operation, which can cause enclosure parts to be above ground
potential. Proper grounding, as described in this manual, is
required. Failure to observe this precaution could result in death or
severe injury.
LIT-1201828
WARNING
Before applying power to the VSD Series drive, make sure that the
front and cable covers are closed and fastened to prevent exposure
to potential electrical fault conditions. Failure to observe this
precaution could result in death or severe injury.
For more information visit: www.johnsoncontrols.comxi
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
WARNING
An upstream disconnect/protective device must be provided as
required by the National Electric Code (NEC). Failure to follow this
precaution may result in death or severe injury.
WARNING
Before opening the VSD Series drive covers:
• Disconnect all power to the VSD Series drive.
• Wait a minimum of 5 (five) minutes after all the lights on the
keypad are off. This allows time for the DC bus capacitors to
discharge.
• A hazardous voltage may still remain in the DC bus capacitors
even if the power has been turned off. Confirm that the
capacitors have fully discharged by measuring their voltage
using a multimeter set to measure DC voltage.
Failure to follow the above precautions may cause death or severe
injury.
Cautions
WARNING
The VSD Series output terminals U, V and W correspond to a phase
rotation of ABC. If the input terminals L1, L2 and L3 have not been
wired for ABC, the motor rotation will be different when powered
from the bypass instead of the VSD Series drive which can result in
personal injury and equipment damage. In this situation the input
line wiring must be changed to correspond to ABC rotation.
CAUTION
Do not perform any Megger or voltage withstand tests on any part
of the VSD Series drive or its components. Improper testing may
result in damage.
CAUTION
Prior to any tests or measurements of the motor or the motor cable,
disconnect the motor cable at the VSD Series output terminals (U,
V, W) to avoid damaging the VSD Series drive during the motor or
cable testing.
CAUTION
Do not touch any components on the circuit boards. Static voltage
discharge may damage the components.
CAUTION
Any electrical or mechanical modification to this equipment
without prior written consent of Johnson Controls will void all
warranties and may result in a safety hazard in addition and
voiding of the UL listing.
xiiFor more information visit: www.johnsoncontrols.comLIT-1201828
November 2009
Powered by Eaton TechnologyVSD Series Drives User Manual
CAUTION
Install the VSD Series drive on flame-resistant material such as a
steel plate to reduce the risk of fire.
CAUTION
Install the VSD Series drive on a perpendicular surface that is able
to support the weight of the drive and is not subject to vibration, to
lessen the risk of the drive falling and being damaged and/or
causing personal injury.
CAUTION
Prevent foreign material such as wire clippings or metal shavings
from entering the drive enclosure, as this may cause arcing
damage and fire.
CAUTION
Install the VSD Series drive in a well-ventilated room that is not
subject to temperature extremes, high humidity, or condensation,
and avoid locations that are directly exposed to sunlight, or have
high concentrations of dust, corrosive gas, explosive gas,
inflammable gas, grinding fluid mist, etc. Improper installation may
result in a fire hazard.
Motor and Equipment Safety
Before starting the motor, check that the motor is mounted properly
and aligned with the driven equipment. Ensure that starting the
motor will not cause personal injury or damage equipment
connected to the motor.
Set the maximum motor speed (frequency) in the VSD Series drive
according to the requirements of the motor and the equipment
connected to it. Incorrect maximum frequency settings can cause
motor or equipment damage and the potential for personal injury.
Before reversing the motor rotation, ensure that this will not cause
personal injury or equipment damage.
Make sure that no power factor correction capacitors are connected
to the VSD Series output or the motor terminals to prevent VSD
Series drive malfunction and potential damage.
Make sure that the VSD Series output terminals (U, V, W) are not
connected to the utility line power as severe damage to the VSD
Series drive and personal injury may occur.
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
LIT-1201828
For more information visit: www.johnsoncontrols.comxiii
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
xivFor more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
Chapter 1 — Overview
This chapter describes the purpose and contents of this manual, the receiving inspection
recommendations and the Johnson Controls VSD Series Open Drive catalog numbering
system.
How to Use This Manual
The purpose of this manual is to provide you with information necessary to install, set and
customize parameters, start up, troubleshoot and maintain the Johnson Controls VSD Series
drive powered by Cutler-Hammer® technology from Eaton’s electrical business. To provide
for safe installation and operation of the equipment, read the safety guidelines at the
beginning of this manual and follow the procedures outlined in the following chapters before
connecting power to the VSD Series drive. Keep this operating manual handy and distribute
to all users, technicians and maintenance personnel for reference.
Chapter 1 – Overview
Chapter 2 – Mounting
Chapter 3 – Power Wiring
Chapter 4 – Control Wiring
Chapter 5 – IntelliPass Bypass Option
Chapter 6 – Menu Information
Chapter 7 – Start-Up
Chapter 8 – Johnson Controls Metasys N2 Protocol
Chapter 9 to 14 – Applications
Chapter 15 – Description of Parameters
Appendix A – Technical Data
Appendix B – Fault and Warning Codes
Appendix C – Accessories
Receiving and Inspection
The VSD Series AC drive has met a stringent series of factory quality requirements before
shipment. It is possible that packaging or equipment damage may have occurred during
shipment. After receiving your VSD Series drive, please check for the following:
●Check to make sure that the package(s) includes the VSD Series drive, the User Manual,
rubber conduit covers, screws, conduit plate and ground straps.
●Inspect the unit to ensure it was not damaged during shipment.
●Make sure that the part number indicated on the nameplate corresponds with the
Catalog Number on your order.
If shipping damage has occurred, please contact and file a claim with the carrier involved
immediately.
If the delivery does not correspond to your order, please contact your Johnson Controls
representative.
Note: Do not destroy the packing. The template printed on the protective cardboard can be
used for marking the mounting points of the VSD Series on the wall or cabinet.
LIT-1201828
For more information visit: www.johnsoncontrols.com1-1
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
Catalog Numbering System
Table 1-1: VSD Series Open Drives Selection Chart
Code NumberVS0A-N0000
Base ProductVS = Variable Speed Drive Prefix
Horsepower (VT) 001 = 1.0 hp to
Voltage
250 = 250 hp
2 = 230V (or 208V)
4 = 480V
5 = 575V
Enclosure Rating1 = TYPE 1
2 = TYPE 12
Enclosure Style0 = None (Open Drive)
Revision #A = Rev 1 (Americas)
C = Rev 1 (Canada)
Separator (–)
Communications 0 = None
N = N2/XT/SA
L = L
Option 100 = None
Option 200 = None
All horsepower ratings are Variable Torque (VT).
3 to 200 @ 575V; 1-1/2 to 250 hp @ 480V; 1 to 100 hp @ 230V.
TYPE 1 & TYPE 12, 208 – 240V, 380 – 500V, 525 – 690V
Johnson Controls Open Drive
1-2For more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
Chapter 2 — Mounting Open TYPE 1, TYPE 12 Drives
VSD Series open drives may be mounted side-by-side or stacked vertically, as outlined in the
following section.
Note: See Chapter 5 for mounting TYPE 1, TYPE 12 and TYPE 3R IntelliPass drives.
Space Requirements
To ensure proper air circulation and cooling, follow the guidelines below.
Table 2-1: Space Requirements for Mounting a VSD Series Drive
Drive Type
Variable Torque Rating
Approximate Dimensions in Inches (mm)
AA2BCD
230V, 1 – 3 hp
0.8 (20)0.8 (20)3.9 (100)2.0 (50)
480V, 1-1/2 – 7-1/2 hp
230V, 5 – 10 hp
0.8 (20)0.8 (20)4.7 (120)2.4 (60)
480V, 10 – 20 hp
230V, 15 – 20 hp
1.2 (30)1.2 (30)6.3 (160)3.1 (80)
480V, 25 – 40 hp
575V, 3 – 30 hp
230V, 25 – 40 hp
3.1 (80)3.1 (80)11.8 (300)3.9 (100)
480V, 50 – 75 hp
575V, 40 – 50 hp
230, 50 – 75 hp
3.1 (80)5.9 (150)3.1 (80)11.8 (300)7.9 (200)
480V, 100 – 150 hp
575V, 60 – 100 hp
230V, 100 hp
2.0 (50)3.1 (80)15.7 (400)9.8 (250)
480V, 200 – 250 hp
575V, 125 – 200 hp
Dimensions represent the minimum clearance needed when mounting a drive. See Figure 2-1 below.
A = clearance around the VSD Series drive.
= clearance needed to change the fan without disconnecting the motor cables.
A
2
B = distance between adjacent VSD Series drives or between the VSD Series drive and an enclosure wall.
C = clearance above the VSD Series drive.
D = clearance below the VSD Series drive.
Minimum clearance below the VSD Series drive needed to change the fan.
C
13.8
(350)
LIT-1201828
A
A
2
B
A
A
2
2
D
B
Figure 2-1: Mounting Space Requirements
If several units are mounted above each other, the clearance between the drives should equal
C + D (see Table 2-1 and Figure 2-1 above). In addition, the outlet air used for cooling the
lower unit must be directed away from the inlet air used by the upper unit.
For more information visit: www.johnsoncontrols.com2-1
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
Environmental Requirements
Ensure that the environment meets the requirements listed in Table A-1 of Appendix A for
any storage or operating situation.
The following table specifies the minimum airflow required in the area where the drive will
be mounted.
Table 2-2: Cooling Airflow Requirements
Drive Type
Variable Torque RatingsCooling Air Required
230V, 1 – 3 hp
480V, 1-1/2 – 7-1/2 hp
230V, 5 – 10 hp
480V, 10 – 20 hp
230V, 15 – 20 hp
480V, 25 – 40 hp
575V, 3 – 30 hp
230V, 25 – 40 hp
480V, 50 – 75 hp
575V, 40 – 50 hp
230V, 50 – 75 hp
480V, 100 – 150 hp
575V, 60 – 100 hp
230V, 100 hp
480V, 200 – 250 hp
575V, 125 – 200 hp
41 cfm (70 m
112 cfm (190 m
250 cfm (425 m
250 cfm (425 m
383 cfm (650 m
765 cfm (1300 m
3
/h)
3
/h)
3
/h)
3
/h)
3
/h)
3
/h)
Standard Mounting Instructions
1. Measure the mounting space to ensure that it allows for the minimum space
surrounding the VSD Series drive. Drive dimensions are in Appendix A.
2. Make sure the mounting surface is flat and strong enough to support the drive, is not
flammable, and is not subject to excessive motion or vibration.
3. Ensure that the minimum airflow requirements for your drive are met at the mounting
location.
4. Mark the location of the mounting holes on the mounting surface, using the template
provided on the cover of the cardboard shipping package.
5. Using fasteners appropriate to your drive and mounting surface, securely attach the
drive to the mounting surface using all 4 screws or bolts.
2-2For more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
Chapter 3 — Power Wiring
Guidelines
To ensure proper wiring, use the following guidelines:
●Use heat-resistant copper cables only, +75°C or higher.
●The input line cable and line fuses must be sized in accordance with the rated input
current of the unit. See Tables 3-2 and 3-5.
●Consistent with UL listing requirements, for maximum protection of the VSD Series
drive, UL recognized fuses type RK should be used.
●If motor temperature sensing is used for overload protection, the output wire size may
be selected based on the motor specifications.
●If three or more shielded cables are used in parallel for the output on the larger units,
every cable must have its own overload protection.
●Avoid placing the motor cables in long parallel lines with other cables.
●If the motor cables run in parallel with other cables, note the minimum distances
between the motor cables and other cables given in Table 3-1 below:
Table 3-1: Cable Spacings
Minimum Distance Between Cables in Feet (m)Shielded Cable Length in Feet (m)
1 (0.3)≤164 (50)
3.3 (1.0)≤656 (200)
●The spacings of Table 3-1 also apply between the motor cables and signal cables of
other systems.
●Maximum length of the motor cables is as follows:
– 1 – 2 hp 230V units, 328 ft. (100m); filters required on lead length ≥175 ft.
– All other hp units, 984 ft. (300m); filters required on lead length ≥200 ft.
Note: Lead lengths ≥500 ft. require sine wave filter for all voltages.
●The motor cables should cross other cables at an angle of 90 degrees.
●If conduit is being used for wiring, use separate conduits for the input power wiring,
the output power wiring, the signal wiring, and the control wiring.
●For Frame 4 installations, refer to conduit mounting requirements in Chapter 4.
LIT-1201828
For more information visit: www.johnsoncontrols.com3-1
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
UL Compatible Cable Selection and Installation
Use only copper wire with temperature rating of at least 167°F (75°C).
If power cubes are used, a UL recognized RK fuse is recommended.
Based on maximum environment of 104°F (40°C).
If bypass is used, a UL recognized RK5 fuse is recommended.
Frame
NEC I
(A)
3
3.4
4.8
7.6
11
14
21
27
34
40
52
65
77
96
124
156
180
240
302
Il
l
(A)Fuse (A)
3.3
4.3
5.6
7.6
12
16
23
31
38
46
61
72
87
105
140
170
205
261
300
10
10
10
10
15
20
30
35
50
60
80
100
110
125
175
200
250
350
400
Wire SizeTerminal Size
PowerGroundPowerGround
14
14
14
14
12
10
10
8
6
4
2
2
1
1/0
3/0
4/0
300
350
2 X 250
3-2For more information visit: www.johnsoncontrols.comLIT-1201828
November 2009
Powered by Eaton TechnologyVSD Series Drives User Manual
If power cubes are used, a UL recognized RK fuse is recommended.
Based on maximum environment of 104°F (40°C).
If bypass is used, a UL recognized RK5 fuse is recommended.
Frame
Il
(A)Fuse (A)
4.5
7.5
10
13.5
18
22
27
34
41
52
62
80
100
125
144
208
10
10
10
15
20
30
35
40
50
60
80
100
125
175
200
250
Wire SizeTerminal Size
PowerGroundPowerGround
14
14
14
12
10
10
8
8
6
4
2
1
1/0
3/0
4/0
350
Table 3-5: Maximum Symmetrical Supply Current
ProductVoltageMaximum RMS Symmetrical Amperes on Supply Circuit
1 – 75 hp230100,000A
1-1/2 – 250 hp480100,000A
3 – 200 hp575100,000A
Table 3-6: Power Connection Tightening Torque
RatingFrame Size
230V, 1 – 3 hp
FR450.6
(in-lbs)
480V, 1-1/2 – 7-1/2 hp
Tightening Torque
230V, 5 – 10 hp
FR5131.5
480V, 10 – 20 hp
230V, 15 – 20 hp
FR6354
480V, 25 – 40 hp
575V, 3 – 30 hp
230V, 25 – 40 hp
FR78810
480V, 50 – 75 hp
575V, 40 – 50 hp
230, 50 – 75 hp
FR8170/80
480V, 100 hp
480V, 125 – 150 hp
FR8354/195
575V, 60 – 100 hp
230V, 100 hp
FR9354/195
480V, 200 – 250 hp
575V, 125 – 200 hp
The isolation standoff of the bus bar will not withstand the listed tightening torque. Use a wrench to apply a counter torque when
tightening.
Tightening Torque
(Nm)
20/9
40/22
40/22
LIT-1201828
For more information visit: www.johnsoncontrols.com3-3
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
Installation Instructions
Strip the motor and power cables as shown in Figure 3-1 and Table 3-7.
GroundGround
A1
B1
C1
D1
PowerMotor
A2
B2
C2
D2
Figure 3-1: Input Power and Motor Cable Stripping and Wire Lengths
Table 3-7: Power and Motor Cable Stripping Lengths
Product
Horsepower VoltageA1B1C1D1A2B2C2D2
1 – 3
1-1/2 – 7-1/2
5 – 10
10 – 20
15 and 20
25 – 40
3 – 30
25 – 40
50 – 75
40 – 50
50 – 75
100 – 150
60 – 100
100
200 – 250
125 – 200
230
480
230
480
230
480
575
230
480
575
230
480
575
230
480
575
Frame
Size
FR40.59
FR50.79
FR60.79
FR70.98
FR81.1
FR91.1
Power Wiring in Inches (mm)Motor Wiring in Inches (mm)
(15)
(20)
(20)
(25)
(28)
(28)
1.38
(35)
1.57
(40)
3.54
(90)
4.72
(120)
9.45
(240)
11.61
(295)
0.39
(10)
0.39
(10)
0.59
(15)
0.98
(25)
1.1
(28)
1.1
(28)
0.79
(20)
1.18
(30)
2.36
(60)
4.72
(120)
9.45
(240)
11.61
(295)
0.28
(7)
0.79
(20)
0.79
(20)
0.98
(25)
1.1
(28)
1.1
(28)
1.97
(50)
2.36
(60)
3.54
(90)
4.72
(120)
9.45
(240)
11.61
(295)
0.28
(7)
0.39
(10)
0.59
(15)
0.98
(25)
1.1
(28)
1.1
(28)
1.38
(35)
1.57
(40)
2.36
(60)
4.72
(120)
9.45
(240)
11.61
(295)
3-4For more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
NEMA Type 1/12 Open Drives (1 – 250 HP)
Table 3-8: Control Wiring Instructions — NEMA Type 1/12 Open Drives
Mounting Drive
1. Mount Drive
(See Table below for dimensions.)
D1
W1
W2
R2
R1
VSD Series Open Drive Dimensions
Frame
Size
FR4230V3/4 – 312.9
FR5230V5 – 7-1/216.5
FR6230V10 – 1522.0
FR7230V20 – 3024.8
FR8480V75 – 12529.7
FR9480V150 – 20045.3
FR10480V250 – 35044
Voltagehp (VT)Approximate Dimensions in Inches (mm)Weight
H1H2H3D1D2D3W1W2R1 dia.R2 dia.
480V1 – 5
480V7-1/2 – 15
480V20 – 30
575V2 – 25
480V40 – 60
575V30 – 40
575V50 – 75
575V100 – 150
575V200 – 300
(327)
(419)
(558)
(630)
(755)
(1150)
(1120)
12.3
(313)
16.0
(406)
21.3
(541)
24.2
(614)
28.8
(732)
44.1
(1120)
33.5
(850)
11.5
(292)
15.4
(391)
20.4
(519)
23.3
(591)
28.4
(721)
—14.3
—23.6
Power Wiring
Notice
Do not discard the plastic bag containing the wiring plate.
2. Remove the bottom cover by rotating the cover toward
you on the base hinges, then lifting the cover away from
the base.
7.5
(190)
8.4
(214)
9.3
(237)
10.1
(257)
11.3
(288)
(362)
(600)
H1
H3
H2
Figure 3-2:
2.5
(64)
2.7
(68)
2.7
(68)
2.7
(68)
1.3
(34)
5.4
(137)
NANA23.6
5.0
(126)
5.8
(148)
6.7
(171)
7.5
(189)
11.0
(279)
8.8
(224)
5.0
(128)
5.7
(144)
7.7
(195)
9.3
(237)
11.2
(285)
18.9
(480)
(600)
R2
3.9
(100)
3.9
(100)
5.8
(148)
7.5
(190)
10.0
(255)
15.7
(400)
16.7
(425).9(23)
.5
(13)
.5
(13)
.7
(18)
.7
(18)
.7
(18)
.7
(18)
D2
D3
Knockouts
.3
(7)
.3
(7)
.4
(9)
.4
(9)
.4
(9)
.4
(9)
.47
(12)
Lbs. (kg)
11
(5)
17.9
(8.1)
40.8
(18.5)
77.2
(35)
127.8
(58)
321.9
(146)
550.7
(250)
Power Wiring
3. Locate the plastic bag shipped with the drive containing
the wiring plate, and remove the wiring plate.
LIT-1201828
For more information visit: www.johnsoncontrols.com3-5
VSD Series Drives User ManualPowered by Eaton Technology
U+See
oteL3
3
e
n
otor
3
(
)
t
(
)
t
Control
d
p
p
p
November 2009
Standard Wiring Diagrams and Terminal Locations
Power and Motor Wiring Terminal Schematics for VSD Series Drives
The following wiring diagrams show the line and motor connections of the drive.
Power
Board
VT
230V 1 - 20 h
480V 1-1/2 - 40 h
575V 3 - 30 h
Boar
L
Note:
Integrated Brake
Chopper Circuit Not
Included on 575V units.
Brak
Optio
M
N
Line
Separate Condui
~
Load
Separate Condui
Figure 3-3: Principle Wiring Diagram of VSD Series Power Unit,
FR4, FR5 and FR6
Note: When using a 1-phase supply, for units rated for such, connect the input power to
terminals L1 and L2. Refer to Tables A-2 and A-3 in Appendix A.
3-6For more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
Table 3-8: Control Wiring Instructions — NEMA Type 1/12 Open Drives (Continued)
Power Wiring
4. If conduit is being used, attach the wiring plate to it.
5. Pass the motor and input power wires/cables through the
holes of the wiring plate.
6. If shielded cable is used, connect the shields of the input
line power cable and the motor cable to the motor and
power ground terminals of the VSD Series drive.
Power Wiring/Grounding
7. Wire power terminals, motor terminals, and grounding
terminals per diagram. Power and Motor leads must be in
separate conduit.
Note: Do not wire motor loads to B- B+ R-. This will cause
damage.
GROUND WIRING
● Run motor cables in separate conduit.
● DO NOT RUN CONTROL WIRES in same conduit
● Cables sized per NEC.
● Provide low impedance ground between drive and
motor.
UtilityDriveMotor Ground
IMPORTANT: Improper grounding could result in damage to the
motor and/or drive and could void warranty
Control Wiring
8. Wire the control terminals following the details for the
specific option boards shown on the following pages.
Note: For ease of access, the option board terminal blocks can
be unplugged for wiring.
Note: If using conduit or Seal Tite for control wiring for Frame
4, you must order NEMA Type 12 kit.
(Inside Motor Conduit Box)
LIT-1201828
For more information visit: www.johnsoncontrols.com3-7
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
Table 3-8: Control Wiring Instructions — NEMA Type 1/12 Open Drives (Continued)
Control Wiring
9. Wire control to the OPTA9 Control Board and OPTA2.
Note: Drive default is programmed for Damper Interlock.
Note: Option Boards OPTC2 (N2/XT/SA Bus) and OPTC4
(LonWorks) are optional.
Mandatory Ground Wiring
Be sure to pull low impendance ground wiring from
customer power to drive and ground wire from drive
to motor.
UtilityDriveMotor Ground
(Inside Motor Conduit Box)
I/O Connection
● Run 110 Vac and 24 Vdc Control wiring in separate
conduit.
● Communication wire to be shielded.
● RS-232 Keypad cable less than 20 feet.
Incoming Power
Optional
CB
Note: Must pull
dedicated
ground wire
to drive
and motor.
Reference Output
1
+1DV
Analog Input Voltage
2
Vin+
(Range 0-10V DC)
I/O Ground
3
GND
Analog Input Current
4
Lin+
(Range 4-20mA)
5
Lin–
Control Voltage Output
6
24Vout
I/O Ground
7
GND
Start/Stop
8
DIN1
External Fault
9
DIN2
Run Permisive Damper Interlock
10
DIN3
DIN1-DIN3 Common
11
CMA
Control Voltage Output
12
24Vout
I/O Ground
13
GND
Speed Select 1
14
DIN4
Fire Mode
15
DIN5
Bypass Overload Fault
16
DIN6
DIN4-DIN6 Common
17
CMB
Output Frequency
18
Lout+
Analog Output
19
Lout–
Digital Output Ready
20
DO1
X1
A
B
C
D
X2
A
B
C
D
X3
X6
A
B
C
D
Note:
See Figure 3
for Dip X1, X2,
X3, X6 Switch
settings.
Start-Up Wizard
X1 Jumper Setting
Analog Input 1 (AI1)
0 to 10V*
Voltage Input
0 to 20 mA
Current Input
0 to 10V
(Differential)
Voltage Input
-10 to 10V
Voltage Input
A
A
A
A
Note:
Optional Communication Cards can be
supplied with the Drive or as a Field Option.
Figure 3-4:
X2 Jumper Setting
Analog Input 2 (AI2)
B
A
0 to 20 mA*
B
CD
CD
B
B
CD
B
D
C
Current Input
0 to 10V
Voltage Input
0 to 10V
(Differential)
Voltage Input
-10 to 10V
Voltage Input
B
A
D
C
X1X3X2X6
CD
B
A
CD
A
CD
B
B
A
D
C
B
A
D
C
B
A
D
C
X6 Jumper Setting
Analog Output 1 (A01)
A
0 to 20 mA
Current Output
0 to 10V
Voltage Output
*
A
X3 Jumper Setting
CMA and CMB Grounding
CMB Connected to Ground*
CMA Connected to Ground
CMB Isolated from Ground
CMA Isolated from Ground
CMB and CMA Internally
Connected and Isolated
from Ground
B
CD
B
CD
* Designates Default Jumper Settings
Figure 3-5: Option Board A9 Location and Settings
See Page 7-4, Start-Up Wizard
3-8For more information visit: www.johnsoncontrols.comLIT-1201828
Powered by Eaton TechnologyVSD Series Drives User Manual
November 2009
Checking the Cable and Motor Insulation
1. Check the motor cable insulation as follows:
● Disconnect the motor cable from terminals U, V and W of the VSD Series drive and
from the motor.
● Measure the insulation resistance of the motor cable between each phase conductor
as well as between each phase conductor and the protective ground conductor.
● The insulation resistance must be >1MΩ.
2. Check the input power cable insulation as follows:
● Disconnect the input power cable from terminals L1, L2 and L3 of the VSD Series
drive and from the utility line feeder.
● Measure the insulation resistance of the input power cable between each phase
conductor as well as between each phase conductor and the protective ground
conductor.
● The insulation resistance must be >1MΩ.
3. Check the motor insulation as follows:
● Disconnect the motor cable from the motor and open any bridging connections in
the motor connection box.
● Measure the insulation resistance of each motor winding. The measurement voltage
must equal at least the motor nominal voltage but not exceed 1000V.
● The insulation resistance must be >1MΩ.
LIT-1201828
For more information visit: www.johnsoncontrols.com3-9
VSD Series Drives User ManualPowered by Eaton Technology
November 2009
3-10For more information visit: www.johnsoncontrols.comLIT-1201828
Loading...
+ 222 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.