VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators
Installation Instructions
VA9208-BAA-3, VA9208-BAC-3, VA9208-BDA-3 VA9208-BDC-3, VA9208-BGA-3, VA9208-BGC-3
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications
The VA9208-Bxx-x Series On/Off Electric Spring Return Actuator s are direct-mount valve actuators that operate on AC 24 V power at 50/60 Hz, DC 24 V power, AC 120 V power at 60 Hz, or AC 230 V power at 50/60 Hz. These bidirectional actuators are used to provide two position control on Johnson Controls® VG1000 Series 1-1/4, 1-1/2, and 2 in. (DN32, DN40, and DN50) ball valves in Heating, V entilating, and Air Conditioning (HVAC) applications.
The VA9208 Series Electric Spring Return Actuators provide a running torque of 70 lb·in. (8 N·m). Integral line voltage auxiliary switches, available only on the VA9208-xxC-3 models, indicate end-stop position, or perform switching functions within the selected rotation range.
IMPORTANT: Use this VA9208-Bxx-x Series On/ Off Electric Spring Return Actuator only to control equipment under normal operating conditions. Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other pr op er ty, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the electric actuator.
Part No. 14-1379-13, Rev. E
Issued October 2017
Installation
Install the ball valve with the actuator at or above the center line of the horizontal piping (see Figure 1).
IMPORTANT: In steam applications, install the valve with the stem horizontal to the piping. Failure to follow this precaution may shorten the life of the actuator.
IMPORTANT: Before specifying VA9208 Series Electric Spring Return Valve Actuators for plenum applications, verify acceptance of exposed plastic materials in plenum areas with the local building authority. Building codes for plenum requirements vary by location. Some local building authorities accept compliance to UL 1995, Heating and Cooling Equipment, while others use different acceptance criteria.
IMPORTANT: Do not install or use this VA9208 Series Electric Spring Return Valve Actuator in or near environments where corrosive subst an ce s or vapors could be present. Exposure of the actuator to corrosive environments may damage the device’s internal components, and will void the warranty.
IMPORTANT : Utiliser ce V A9208-Bxx-x Series On/ Off Electric Spring Return Actuator uniquement po ur commander des équipements dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du electric actuator risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du electric actuator.
VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation
1
Instructions
Special Tools Needed
Figure 2: Spring Return VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
Dimensions, in. (mm)
3-29/32
(99)
2-7/8
(73)
Port Marking
Locations
F
I
G
:
V
A
9
2
0
8
X
_
d
i
m
s
3-1/2 (89)
Clearance Required
Digital voltmeter
T-2 0 T ORX® driver
Dimensions
Valve Actuat or
See Figure 2 and Table 1 for valve actuator dimensions.
Table 1: VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve Dimensions, in. (mm)
Valve Size in. (DN)
1-1/4 (DN32)
1-1/2 (DN40)
2 (DN50) 2-way 5-17/32
1. Port A must always be connected to the coil (see Figure 2).
Valve
1
Style
All 5-5/32
All 5-5/16
3-way 7-7/8 (200)
ABC D E F G
(131)
(135)
(140)
1-1/32 (26)
1-9/64 (29)
1-15/32 (37)
1-23/32
7-5/32 (182) 3-15/16 (100) 11/32 (9) 1-31/32 (50)
(44) 1-57/64
7-3/8 (187) 4-21/64 (110) 11/32 (9) 2-11/64 (55)
(48) 2-1/8 (54) 7-19/32 (193) 4-27/32 (123) 11/32 (9) 2-27/64 (62)
VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions2
Valve Actuator with Thermal Barr ier
Figure 3: Spring Return VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
with Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
3-29/32
(99)
A
B
3-1/2 (89)
Clearance Req ui red
GCFBC
E
Port Marking
Locations
D
See Figure 3 and Table 2 for valve actuator dimensions with optional M9000-561 Thermal Barrier insta lled.
Table 2: VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional
M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
Valve Size in.
Valve
Style
ABC D E FG
1
(DN)
1-1/4 (DN32)
1-1/2 (DN40)
2 (DN50) 2-way 9-31/32
1. Port A must always be connected to the coil (See Figure 2).
All 9-17/64
(235)
All 9-15/16
(240)
(244)
1-1/32 (26) 1-23/32
7-1/4 (184) 3-15/16 (100) 11/32 (9) 1-31/32
(44)
1-9/64 (29) 1-57/64
7-7/16 (189) 4-21/64 (110) 11/32 (9) 2-11/64
(48)
1-15/32 (37) 2-1/8 (54) 7-11/16
(195)
(50)
(55)
4-27/32 (123) 11/32 (9) N/A
3-way 7-7/8 (200) 2-27/64
(62)
Accessories
Table 3: Accessories (Order Separately)
Code Number Description
M9000-560 Ball Valve Linkage Kit for applying M9203 and M9208 Series Actuators to VG1000 Series Valves
M9000-561 Thermal Barrier Extends M(VA)9104, M(VA)9203, and M(V A)9208 Series Electric Spring Return Actuator
M9000-341 Weathershield Kit for VG1000 Series Ball Valve application of M(VA)9104, M(VA)9203, and M(VA)9208
M9220-604 Replacement Manual Override Cranks with Long Crank Radius: 2.83 in. (72 mm) (Quantity 5) M9208-605 Replacement Manual Override Cranks with Short Crank Radius: 1.83 in. (46.5 mm) (Quantity 5)
(Quantity 1)
Applications to Include Low Pressure Steam (Quantity 1)
Series Electric Spring Return Actuators (Quantity 1)
VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions 3
Mounting
Figure 4: Positioning the Valve Stem
F
I
G
:
V
G
1
0
0
0
3 Way2 Way
Figure 5: Removing the Linkage
F
I
G
:
R
M
V
_
L
N
K
Figure 6: Inserting the Drive
F
I
G
:
D
R
V
_
S
H
F
T
_
B
Figure 7: Installing the Linkage
Mounting the Actuator to Spring Return Port A (Coil) Open
To mount the actuator to Spring Return Port A (Coil) open:
1. Turn the valve stem to the position outlined in Figure 4.
2. Mount optional M9000-561 Thermal Barrier to the valve if fluid temperature exceeds 212°F (100°C). See the Mounting the Thermal Barrier more information.
Note: Proceed to Step 7 if the ball valve linkage is on actuator Side B.
section for
4. Insert the drive shaft into Side B (Figure 6).
5. Install linkage base on Side B using the two #10-14 x 2.75 in. long screws (Figure 7). The recommended torque is 20 to 24 lb·in. (2.3 to 2.7 N·m).
3. Remove the linkage from Side A (Figure 5).
VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions4