VA9203-xxx-xx Series Electric Spring-Return Actuators
Code No. LIT-1900692
Issued January 2, 2014
Description
The VA9203-xxx-xx Series Electric
Spring-Return Ball Valve Actuators are
direct-mount valve actuators that operate on
AC/DC 24 V power. These bidirectional
actuators are used to provide accurate
positioning on Johnson Controls®
VG1000 Series 1/2, 3/4, and 1 in. (DN15,
DN20, and DN25) ball valves in HVAC
applications. A mechanical spring-return
system provides rated torque with or without
power applied to the actuator. The series
includes the following control options:
• On/Off, 24 V, or 85 to 264 VAC power
• On/Off and Floating Point, 24 V power
• Proportional, 24 V power, for 0(2) to
10 VDC or 0(4) to 20 mA Control Signal
An accessory crankarm and remote mounting
kit are available for applications where the
actuator cannot be direct-coupled to the
damper shaft. An optional line voltage
auxiliary switch indicates an end-stop position
or performs switching functions within the
selected rotation range.
Refer to the VA9203-xxx-xx Series Electric
Features
• direct mounting with a single screw
• electronic stall detection
• double-insulated construction
• microprocessor-controlled
brushless DC motor
(-AGx and -GGx types)
• external mode selection switch
(-AGx and -GGx types)
• integral cables with colored and numbered
conductors
• integral connectors for 1/2 in. (13 mm)
threaded conduit connector(s)
• optional integrated auxiliary switch
• plenum rated models
• optional thermal barrier
• available weather shield for field mounting
• override control (Proportional Models only)
• Underwriters Laboratories (UL),
CE Mark, and C-Tick Compliance
• manufactured under International
Standards Organization (ISO) 9001 Quality
Control Standards
• 5-year warranty
Spring-Return Actuators Product Bulletin
(LIT-12011702) for important product
application information.
Accessories and Replacement Parts
Code Number Description
M9000-200Commissioning Tool that Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional, and/or Resistive Electric Actuators
M9000-560Ball Valve Linkage Kit for Applying M9203 and M9208 Series Actuators to VG1000 Series Valves (Quantity 1)
M9000-561Thermal Barrier Extends M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring-Return Actuator Applications to Include
M9000-341Weather Shield Kit for VG1000 Series Ball Valve Application of M(VA)9104, M(VA)9203, and M(VA)9208 Series Electric Spring-Return
M9000-607Position Indicator for VG1000 Series Ball Valve Applications (Quantity 5)
VA9203-xxx-xx Series Electric Spring-Return Actuators (Continued)
Technical Specifications
VA9203-GGx-2Z Series Proportional Electric Spring-Return Actuator
Power RequirementsAC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
Input Signal/AdjustmentsFactory Set at DC 0 to 10 V, CW Rotation with Signal Increase
Control Input ImpedanceVoltage Input: 100,000 Ohms
Feedback SignalDC 0 (2) to 10 V for Desired Rotation Range up to 95°
Auxiliary Switch
Rating
Spring ReturnDirection is Selectable with Mounting Position of Actuator:
Rated TorquePower On (Running)27 lb·in (3 N·m) All Operating Temperatures
Rotation RangeMaximum Full Stroke: 95°
Rotation Time for 90
Degrees of Travel
Life Cycles60,000 Full Stroke Cycles with 27 lb·in (3 N·m) Load
Audible Noise Rating Power On (Running)< 37 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical Connections -GGA-2Z Models120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm
Conduit ConnectionsIntegral 1/2 in. (13 mm) Threaded Conduit Connector(s)
Fluid Temperature
Limits
Ambient ConditionsStandard Operating-22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing
Enclosure RatingNEMA 2 (IP54) for All Mounting Directions
ComplianceUnited StatesUL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for
Shipping Weight-GGA Models2.0 lb (0.9 kg)
-xxB ModelsOne Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver Contacts:
Power Off
(Spring Returning)
Power On (Running)90 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at All Operating Conditions
Power Off
(Spring Returning)
Power On (Holding)< 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
-GGB-2Z Models48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series
with M9000-561 Thermal
Barrier Installed
Storage-40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
CanadaUL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
EuropeCE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
-GGB Models2.4 lb (1.1 kg)
(Europe), 4.7 VA Running, 2.7 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2
(North America) or SELV (Europe) 1.8 W Running, 1 W Holding Position
Minimum Transformer Size: 6 VA per Actuator
Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with Field Furnished 500 Ohm, 0.25 W Minimum Resistor
Switch Selectable Direct or Reverse Action with Signal Increase
Current Input: 500 Ohms with Field Furnished 500 Ohm Resistor
Corresponds to Rotation Limits, 0.5 mA at 10 V Maximum
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Actuator Face Labeled A is away from Valve: CCW Spring Return
Actuator Face Labeled B is away from Valve: CW Spring Return
27 lb·in (3 N·m) All Operating Temperatures
Adjustable Stop: 35° to 95° Maximum Position
12 to 17 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
16 Seconds Nominal at Full Rated Load
22 Seconds Maximum with 27 lb·in (3 N·m) Load, at -22°F (-30°C)
1,500,000 Repositions with 27 lb·in (3 N·m) Load
< 56 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
2
1/4 in. (6 mm) Ferrule Ends
(6 mm) Ferrule Ends
-22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam
Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for
Electric Actuators
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating
and Regulating Equipment
requirements and other relevant provisions of the EMC Directive 2004/108/EC and Low Voltage Directive
2006/95/EC
VA9203-xxx-xx Series Electric Spring-Return Actuators (Continued)
VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring-Return Actuators
Power RequirementsAC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage
Input Signal/AdjustmentsAC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10%
Control Input Impedance4,700 Ohm Control Inputs
Auxiliary Switch Rating -xxB ModelsOne Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver Contacts:
Spring ReturnDirection is Selectable with Mounting Position of Actuator:
Rated TorquePower On (Running)27 lb·in (3 N·m) All Operating Temperatures
Power Off
(Spring Returning)
Rotation RangeMaximum Full Stroke: 95°
Rotation Time for 90
Degrees of Travel
Life Cycles60,000 Full Stroke Cycles with 27 lb·in (3 N·m) Load
Audible Noise RatingPower On (Running)< 37 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical Connections -AGA-2Z Models120 in. (3.05 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm
Conduit ConnectionsIntegral 1/2 in. (13 mm) Threaded Conduit Connectors
Fluid Temperature
Limits
Ambient ConditionsStandard Operating-22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing
Enclosure RatingNEMA 2 (IP54) for All Mounting Directions
ComplianceUnited StatesUL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls
Shipping Weight-AGA Models2.0 lb (0.9 kg)
Power On (Running)90 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at All Operating Conditions
Power Off
(Spring Returning)
Power On (Holding)< 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
-AGB-2Z Models48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series
with M9000-561 Thermal
Barrier Installed
Storage-40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
CanadaUL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
EuropeCE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
-AGB Models2.4 lb (1.1 kg)
(SELV) (Europe), 5.1 VA Running, 2.8 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2
(North America) or SELV (Europe)
1.9 W Running, 1.1 W Holding
Holding Position Minimum Transformer Size: 6 VA per Actuator
Class 2 (North America) or SELV (Europe)
Minimum Pulse Width: 500 ms
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Actuator Face Labeled A is away from Valve: CCW Spring Return
Actuator Face Labeled B is away from Valve: CW Spring Return
27 lb·in (3 N·m) All Operating Temperatures
12 to 17 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
16 Seconds Nominal at Full Rated Load
22 Seconds Maximum with 27 lb·in (3 N·m) Load, at -22°F (-30°C)
1,500,000 Repositions with 27 lb·in (3 N·m) Load
< 56 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
2
1/4 in. (6 mm) Ferrule Ends
(6 mm) Ferrule Ends
-22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam
for Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for
Electric Actuators
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating
and Regulating Equipment
requirements and other relevant provisions of the EMC Directive 2004/108/EC and the
Low Voltage Directive 2006/95/EC.
VA9203-xxx-xx Series Electric Spring-Return Actuators (Continued)
VA9203-Bxx-x Series On/Off Electric Spring-Return Actuator
Power Requirements -BGx-2 ModelsAC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV)
-BUx-2 ModelsAC 100 V to 240 V (AC 85 V to 264 V) at 50/60 Hz: 0.06 A Running,
Auxiliary Switch
Rating
Spring ReturnDirection is Selectable with Mounting Position of Actuator:
Rated TorquePower On (Running)27 lb·in (3 N·m) All Operating Temperatures
Rotation RangeMaximum Full Stroke: 95°
Rotation Time for 90
Degrees of Travel
Life Cycles60,000 Full Stroke Cycles with 27 lb·in (3 N·m) Load
Audible Noise Rating Power On (Running)< 36 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
Electrical
Connections
Conduit ConnectionsIntegral 1/2 in. (13 mm) Threaded Conduit Connectors
Fluid Temperature
Limits
Ambient Conditions Standard Operating-22 to 140°F (-30 to 60°C); 90% RH Maximum, Noncondensing
Enclosure RatingNEMA 2 (IP54) for All Mounting Directions
ComplianceUnited StatesUL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for
Shipping Weight-xxA Models2.0 lb (0.9 kg)
-xxB-2 ModelsOne Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver Contacts:
Power Off
(Spring Returning)
Power On (Running)
Bxx-2 Models
Power Off
(Spring Returning)
Power On (Holding)< 20 dBA at a Distance of 39-13/32 in. (1 m)
Power Off
(Spring Returning)
Actuator (All Models)48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
Auxiliary Switches
(-xxB-2 Models)
VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C), Not Rated for Steam Service
VG12x5 and VG18x5 Series
with M9000-561 Thermal
Barrier Installed
Storage-40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing
CanadaUL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic
EuropeCE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
-xxB Models2.4 lb (1.1 kg)
(Europe), 5 VA Running, 1.6 VA Holding Position DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America)
or SELV (Europe) 2.8 W Running, 0.8 W Holding Position
Minimum Transformer Size: 6 VA per Actuator
0.02 A Holding Position
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Actuator Face Labeled A is away from Valve: CCW Spring Return
Actuator Face Labeled B is away from Valve: CW Spring Return
27 lb·in (3 N·m) All Operating Temperatures
53 to 71 Seconds Constant for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
60 Seconds Nominal at Full Rated Load (0.25 rpm)
37 to 46 Seconds for 0 to 27 lb·in (3 N·m) Load, at Room Temperature
44 Seconds Nominal at Full Rated Load
75 Seconds Maximum with 27 lb·in (3 N·m) Load at -22°F (-30°C)
< 35 dBA at 27 lb·in (3 N·m) Load, at a Distance of 39-13/32 in. (1 m)
2
(6 mm) Ferrule Ends
48 in. (1.2 m) UL 758 Type AWM Halogen-Free Cable with 18 AWG (0.85 mm
(6 mm) Ferrule Ends
-22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam
Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for
Electric Actuators
Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and
Regulating Equipment
requirements and other relevant provisions of the EMC Directive 2004/108/EC and the Low Voltage
Directive 2006/95/EC.