VA-9070 Series Electric Rotary Actuator Mounted on a
VF Series Butterfly Valve
Butterfly Valves and Actuators
Code No. LIT-1924415
VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating
Service
Description
The VA-9070 Series Electric Rotary Actuators for Two-Position and
Modulating Service are designed for direct mounting on VF Series
Butterfly Valves. The VA-9070 is available in eight different sizes, for
two-position and modulating service on VF Series Standard-Pressure,
Standard-Temperature Butterfly Valves and VF Series High-Pressure,
High-Temperature Buttery Valves.
Refer to the VA-9070 Series Electric Rotary Actuators for Two-Position
and Modulating Service Product Bulletin (LIT-977319) for important
product application information.
Features
• low-profile and lightweight design
• built-in motor overload protection
• pre-wired actuator switches to terminal block; field-configurable
power and input signals
• patented travel limit switch cam design
• external manual handwheel override
• rugged, die-cast aluminum National Electrical Manufacturers'
Association (NEMA) 4, 4X, IP65 Type enclosure and captive
housing screws
• valve status display
• heater/thermostat
Selection Charts
Code Numbers and Cross-Reference Data
Johnson Controls
Actuator Only
Code Number
Electric Two-Position Models
VA-9072-02 -722 S70-005 On/Off
VA-9073-02 -723 S70-008 On/Off
VA-9074-02 -724 S70-012 On/Off
VA-9075-02 -725 S70-020 On/Off
VA-9076-02 -726 S70-030 On/Off
VA-9077-02 -727 S70-050 On/Off
VA-9078-02 -728 S70-065 On/Off
VA-9072-12 -722D4 S70-005 On/Off,
VA-9075-12 -725D4 S70-020 On/Off,
VA-9077-12 -727D4 S70-050 On/Off,
Electric Modulating Models
VA-9072-01 -702 S70-005 Modulating
VA-9073-01 -703 S70-008 Modulating
VA-9074-01 -704 S70-012 Modulating
VA-9075-01 -705 S70-020 Modulating
VA-9076-01 -706 S70-030 Modulating
VA-9077-01 -707 S70-050 Modulating
VA-9078-01 -708 S70-065 Modulating
VA-9072-11 -702N4 S70-005 Modulating,
VA-9075-11 -705N4 S70-020 Modulating,
VA-9077-11 -707N4 S70-050 Modulating,
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
Johnson Controls
VF Series Butterfly
Valve Assembly
Actuator Sub-Code
Bray Series Number
AC 24V
AC 24V
AC 24V
AC 24V
AC 24V
AC 24V
Repair Information
If the VA-9070 Series Electric Actuator fails to operate within its
specifications, replace the unit. For a replacement actuator, contact the
nearest Johnson Controls® representative.
Actuator Selection for Two-Way Standard-Performance
VF Series Butterfly Valves
Valve
Size, in.
150 or 175 psig (High) Closeoff Pressure
2 158 (17.9)
2-1/2 188 (21.2)
3 225 (25.4)
4 465 (52.5)
5 585 (66.1)
6 705 (79.7)
8 1,530 (172.9)
10 3,296 (372.4)
12 5,165 (583.6)
14 6,450 (728.8)
50 psig (Low) Closeoff Pressure
4 225 (25.4)
5 390 (44.1)
6 570 (64.4)
8 705 (79.7)
10 1,410 (159.3)
12 2,595 (293.2)
14 3,300 (372.9)
16 4,268 (482.2)
18 5,267 (595.1)
1. 150 psig (1,034 kPa) for 14 in. valves; 175 psig (1,20 7kPa) for 2 through
2. T orque values h ave already been adjusted for 25% safety fact or on 2through
3. 50 psig (345 kPa) for 4 through 20 in. valves
Torque
Required, lb·in
(N·m)
2
2
2
2
2
2
2
2
2
2
12 in. valves
12 in. valves, and 10% safety factor on 14 in. valves.
Actuator Code Number for
Two-Position
Service
1
VA-9072-02 or
VA-9072-12
VA-9073-02 or
VA-9075-12
2
VA-9075-02 or
VA-9075-12
2
VA-9076-02 or
VA-9077-12
2
VA-9077-02 or
VA-9077-12
2
VA-9078-02 VA-9078-01
3
VA-9072-02 or
VA-9072-12
VA-9073-02 or
VA-9075-12
2
VA-9075-02 or
VA-9075-12
2
VA-9076-02 or
VA-9077-12
2
VA-9077-02 or
VA-9077-12
2
VA-9077-02 or
VA-9077-12
2
VA-9078-02 VA-9078-01
Modulating
Service
VA-9072-01 or
VA-9072-11
VA-9073-01 or
VA-9075-11
VA-9075-01 or
VA-9075-11
VA-9076-01 or
VA-9077-11
VA-9077-01 or
VA-9077-11
VA-9072-01 or
VA-9072-11
VA-9073-01 or
VA-9075-11
VA-9075-01 or
VA-9075-11
VA-9076-01 or
VA-9077-11
VA-9077-01 or
VA-9077-11
VA-9077-01 or
VA-9077-11
Actuators
Actuators
Actuators
Actuators
Pneumatic Damper
Pneumatic Damper
Buttery Valves and
Buttery Valves and
V–293
VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service
(Continued)
Actuator Selection for Two-Way High-Performance VF Series
Butterfly Valves
Valve
Size, in.
550 psig Closeoff Pressure
2-1/2 510 (57.6) VA-9073-02 or
3 530 (59.9)
4 730 (82.5)
5 1,850 (209) VA-9075-02 or
6 2,300 (260) VA-9076-02 or
8 4,300 (486) VA-9077-02 or
240 psig Closeoff Pressure
Actuators
Actuators
2-1/2 300 (33.9) VA-9072-02 or
Pneumatic Damper
Buttery Valves and
3 320 (36.2)
4 460 (52.0)
5 1,040 (118) VA-9074-02 or
6 1,200 (136) VA-9075-02 or
8 2,100 (237) VA-9076-02 or
10 4,100 (463) VA-9077-02 or
12 6,500 (734) VA-9078-02 VA-9078 -01
1. Torque values include a safety factor.
Torque
Required,
lb·in (N·m)
Actuator Code Number for
1
Two-Position
Service
VA-9075-12
VA-9075-12
VA-9077-12
VA-9077-12
VA-9075-12
VA-9075-12
VA-9075-12
VA-9077-12
VA-9077-12
Modulating
Service
VA-9073-01 or
VA-9075-11
VA-9075-01 or
VA-9075-11
VA-9076-01 or
VA-9077-11
VA-9077-01 or
VA-9077-11
VA-9072-01 or
VA-9075-11
VA-9074-01 or
VA-9075-11
VA-9075-01 or
VA-9075-11
VA-9076-01 or
VA-9077-11
VA-9077-01 or
VA-9077-11
Butterfly Valves and Actuators
Actuator Selection for Three-Way Standard-Performance
VF Series Butterfly Valves
Valve
Size, in.
175 psig (High) Closeoff Pressure
2 190 (21.5)
2-1/2 225 (25.4)
3 270 (30.5)
4 558 (63.0)
5 702 (79.3)
6 846 (95.6)
8 1,836 (207.4)
10 3,955 (446.9)
12 6,198 (700.3)
50 psig (Low) Closeoff Pressure
4 270 (30.5)
5 468 (52.9)
6 684 (77.3)
8 846 (95.6)
10 1,692 (191.2)
12 3,114 (351.8)
1. 175 psig (1,207 kPa) for 2 through 12 in. valves
2. Torque values have already been adjusted for 25% safety factor for all sizes.
3. 50 psig (345 kPa) for 4 through 12 in. valves
Torque
Required, lb·in
(N·m)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Actuator Code Number for
Two-Position
Service
1
VA-9072-02 or
VA-9072-12
VA-9073-02 or
VA-9075-12
VA-9074-02 or
VA-9075-12
VA-9075-02 or
VA-9075-12
VA-9077-02 or
VA-9077-12
VA-9078-02 VA-9078-01
3
VA-9072-02 or
VA-9072-12
VA-9073-02 or
VA-9075-12
VA-9074-02 or
VA-9075-12
VA-9075-02 or
VA-9075-12
VA-9077-02 or
VA-9077-12
Modulating
Service
VA-9072-01 or
VA-9072-11
VA-9073-01 or
VA-9075-11
VA-9074-01 or
VA-9075-11
VA-9075-01 or
VA-9075-11
VA-9077-01 or
VA-9077-11
VA-9072-01 or
VA-9072-11
VA-9073-01 or
VA-9075-11
VA-9074-01 or
VA-9075-11
VA-9075-01 or
VA-9075-11
VA-9077-01 or
VA-9077-11
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–294