Johnson Controls VA-9070 Series Data Sheet

VA-9070 Series Electric Rotary Actuator Mounted on a
VF Series Butterfly Valve
Butterfly Valves and Actuators
Code No. LIT-1924415
VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service
Description
Refer to the VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service Product Bulletin (LIT-977319) for important product application information.
Features
• low-profile and lightweight design
• built-in motor overload protection
• pre-wired actuator switches to terminal block; field-configurable power and input signals
• patented travel limit switch cam design
• external manual handwheel override
• rugged, die-cast aluminum National Electrical Manufacturers' Association (NEMA) 4, 4X, IP65 Type enclosure and captive housing screws
• valve status display
• heater/thermostat
Selection Charts
Code Numbers and Cross-Reference Data
Johnson Controls Actuator Only Code Number
Electric Two-Position Models VA-9072-02 -722 S70-005 On/Off VA-9073-02 -723 S70-008 On/Off VA-9074-02 -724 S70-012 On/Off VA-9075-02 -725 S70-020 On/Off VA-9076-02 -726 S70-030 On/Off VA-9077-02 -727 S70-050 On/Off VA-9078-02 -728 S70-065 On/Off VA-9072-12 -722D4 S70-005 On/Off,
VA-9075-12 -725D4 S70-020 On/Off,
VA-9077-12 -727D4 S70-050 On/Off,
Electric Modulating Models VA-9072-01 -702 S70-005 Modulating VA-9073-01 -703 S70-008 Modulating VA-9074-01 -704 S70-012 Modulating VA-9075-01 -705 S70-020 Modulating VA-9076-01 -706 S70-030 Modulating VA-9077-01 -707 S70-050 Modulating VA-9078-01 -708 S70-065 Modulating VA-9072-11 -702N4 S70-005 Modulating,
VA-9075-11 -705N4 S70-020 Modulating,
VA-9077-11 -707N4 S70-050 Modulating,
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
Johnson Controls VF Series Butterfly Valve Assembly Actuator Sub-Code
Bray Series Number
AC 24V
AC 24V
AC 24V
AC 24V
AC 24V
AC 24V
Repair Information
If the VA-9070 Series Electric Actuator fails to operate within its specifications, replace the unit. For a replacement actuator, contact the nearest Johnson Controls® representative.
Actuator Selection for Two-Way Standard-Performance VF Series Butterfly Valves
Valve Size, in.
150 or 175 psig (High) Closeoff Pressure 2 158 (17.9) 2-1/2 188 (21.2) 3 225 (25.4) 4 465 (52.5) 5 585 (66.1) 6 705 (79.7) 8 1,530 (172.9)
10 3,296 (372.4)
12 5,165 (583.6)
14 6,450 (728.8) 50 psig (Low) Closeoff Pressure
4 225 (25.4) 5 390 (44.1) 6 570 (64.4) 8 705 (79.7)
10 1,410 (159.3)
12 2,595 (293.2)
14 3,300 (372.9)
16 4,268 (482.2)
18 5,267 (595.1)
1. 150 psig (1,034 kPa) for 14 in. valves; 175 psig (1,20 7kPa) for 2 through
2. T orque values h ave already been adjusted for 25% safety fact or on 2through
3. 50 psig (345 kPa) for 4 through 20 in. valves
Torque Required, lb·in (N·m)
2 2 2 2 2 2
2 2 2 2
12 in. valves 12 in. valves, and 10% safety factor on 14 in. valves.
Actuator Code Number for Two-Position
Service
1
VA-9072-02 or VA-9072-12
VA-9073-02 or VA-9075-12
2
VA-9075-02 or VA-9075-12
2
VA-9076-02 or VA-9077-12
2
VA-9077-02 or VA-9077-12
2
VA-9078-02 VA-9078-01
3
VA-9072-02 or VA-9072-12
VA-9073-02 or VA-9075-12
2
VA-9075-02 or VA-9075-12
2
VA-9076-02 or VA-9077-12
2
VA-9077-02 or VA-9077-12
2
VA-9077-02 or VA-9077-12
2
VA-9078-02 VA-9078-01
Modulating Service
VA-9072-01 or VA-9072-11
VA-9073-01 or VA-9075-11
VA-9075-01 or VA-9075-11
VA-9076-01 or VA-9077-11
VA-9077-01 or VA-9077-11
VA-9072-01 or VA-9072-11
VA-9073-01 or VA-9075-11
VA-9075-01 or VA-9075-11
VA-9076-01 or VA-9077-11
VA-9077-01 or VA-9077-11
VA-9077-01 or VA-9077-11
Actuators
Actuators
Actuators
Actuators
Pneumatic Damper
Pneumatic Damper
Buttery Valves and
Buttery Valves and
V–293
VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service (Continued)
Actuator Selection for Two-Way High-Performance VF Series Butterfly Valves
Valve Size, in.
550 psig Closeoff Pressure 2-1/2 510 (57.6) VA-9073-02 or 3 530 (59.9) 4 730 (82.5) 5 1,850 (209) VA-9075-02 or
6 2,300 (260) VA-9076-02 or
8 4,300 (486) VA-9077-02 or
240 psig Closeoff Pressure
Actuators
Actuators
2-1/2 300 (33.9) VA-9072-02 or
Pneumatic Damper
Buttery Valves and
3 320 (36.2) 4 460 (52.0) 5 1,040 (118) VA-9074-02 or
6 1,200 (136) VA-9075-02 or
8 2,100 (237) VA-9076-02 or
10 4,100 (463) VA-9077-02 or
12 6,500 (734) VA-9078-02 VA-9078 -01
1. Torque values include a safety factor.
Torque Required,
lb·in (N·m)
Actuator Code Number for
1
Two-Position Service
VA-9075-12
VA-9075-12
VA-9077-12
VA-9077-12
VA-9075-12
VA-9075-12
VA-9075-12
VA-9077-12
VA-9077-12
Modulating Service
VA-9073-01 or VA-9075-11
VA-9075-01 or VA-9075-11
VA-9076-01 or VA-9077-11
VA-9077-01 or VA-9077-11
VA-9072-01 or VA-9075-11
VA-9074-01 or VA-9075-11
VA-9075-01 or VA-9075-11
VA-9076-01 or VA-9077-11
VA-9077-01 or VA-9077-11
Butterfly Valves and Actuators
Actuator Selection for Three-Way Standard-Performance VF Series Butterfly Valves
Valve Size, in.
175 psig (High) Closeoff Pressure 2 190 (21.5) 2-1/2 225 (25.4) 3 270 (30.5) 4 558 (63.0) 5 702 (79.3) 6 846 (95.6)
8 1,836 (207.4)
10 3,955 (446.9)
12 6,198 (700.3) 50 psig (Low) Closeoff Pressure
4 270 (30.5) 5 468 (52.9) 6 684 (77.3)
8 846 (95.6)
10 1,692 (191.2)
12 3,114 (351.8)
1. 175 psig (1,207 kPa) for 2 through 12 in. valves
2. Torque values have already been adjusted for 25% safety factor for all sizes.
3. 50 psig (345 kPa) for 4 through 12 in. valves
Torque Required, lb·in (N·m)
2 2 2 2 2 2
2
2
2
2 2 2
2
2
2
Actuator Code Number for Two-Position
Service
1
VA-9072-02 or VA-9072-12
VA-9073-02 or VA-9075-12
VA-9074-02 or VA-9075-12
VA-9075-02 or VA-9075-12
VA-9077-02 or VA-9077-12
VA-9078-02 VA-9078-01
3
VA-9072-02 or VA-9072-12
VA-9073-02 or VA-9075-12
VA-9074-02 or VA-9075-12
VA-9075-02 or VA-9075-12
VA-9077-02 or VA-9077-12
Modulating Service
VA-9072-01 or VA-9072-11
VA-9073-01 or VA-9075-11
VA-9074-01 or VA-9075-11
VA-9075-01 or VA-9075-11
VA-9077-01 or VA-9077-11
VA-9072-01 or VA-9072-11
VA-9073-01 or VA-9075-11
VA-9074-01 or VA-9075-11
VA-9075-01 or VA-9075-11
VA-9077-01 or VA-9077-11
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.