Johnson Controls V-3766, V-3966, V-4332 Catalog Page

Brass Pneumatic Flare Valves
Code No. LIT-1924115 Issued January 2, 2014
V-3766, V-3966, and V-4332 Brass Pneumatic Flare Valves, 1/2 in. Two-Way and Three-Way
Description
The 1/2 in. flared valve line accurately regulates the flow of hot or cold water in small HVAC terminal units. These 1/2 in. valves are available with a factory-installed V-3000-1 exposed type pneumatic actuator; enclosed actuators (V-3000-2) are also available (order separately). This valve style is available for field mounting the VA-805x Series electric actuators or with a factory-coupled VA-805x Series electric actuator.
Refer to the Flare Valves 1/2 in. T wo-Way and Three-Way Product Bulletin (LIT-977175) for important product application information.
Features
• 1/2 in. OD SAE 45 flare connections do not require solder installation with copper tubing; provides easy removal for maintenance
• standard Johnson Controls® non-adjustable ring pack packings provide proven reliability and long life
• body rated 400 psig static pressure does not restrict building location
• every valve tested for tight initial and long-term shutoff; ensures occupant comfort and energy conservation
• factory-assembled valves available with pneumatic or electric actuators; install quickly and easily, minimizing job site time
Selection Charts
Pneumatically Actuated V-3766, V-3966, and V-4332 Flare Valves
Valve Body
V-3766 N.O. 1.0 7:1 -1001 (345)
V-3966 N.C. 1.7 12:1 -1001 (240)
V-4332 MIX 1.2 7:1 -1007 (240/240) -1004 (240/240)
1. Normally Open (N.O.); Normally Closed (N.C.); Mixing Valve (MIX); maximum closeoff pressure (N.C. port/N.O. port)
2. Rangeability is defined as the ratio of maximum flow to minimum controllable flow.
3. Maximum closeoff pressures listed are for 20 psi supply pressure to diaphragm for normally open and 0 psi supply pressure to diaphragm for normally closed.
Electrically Actuated VB-3766, VB-3966, and VB-4332 Flare Valves
Valve Body
VB-3766-1 PDTC 1.0 7:1 AV-8050-1007(150) AV-8051-1 007 (150) VB-3766-2 PDTC 1.7 12:1 AV-8050-1008 (150) AV-8051-1008 (150) VB-3766-3 PDTC 3.2 23:1 AV-8050-1009 (150) AV-8051-1009 (150) VB-4332-4 MIX 1.2 7:1 AV-8050-1016 (100 ) AV-8051-1016 (100) VB-4332-5 MIX 2.0 12:1 AV-8050-1017 (100 ) AV-8051-1017 (100)
1
Style
Max. CvRange-
ability
Valve Suffix with V-3000 Actuator
2
(Maximum Closeoff Pressure, psi Spring Ranges, psi 3 to 6 4 to 8 9 to 13
N.O. 1.7 12:1 -1002 (345) N.O. 3.2 23:1 -1003 (345)
N.C. 3.2 23:1 -1002 (240)
MIX 2.0 12:1 -1009 (240/240) -1006 (240/240)
Style Max.CvRange-
ability
Assembly Order Code Number (Maximum Shutoff Pressure, psi)
VA-8050 VA-8051
Valid Code Numbers of V-3766, V-3966, and V-4332 Flare Valve and Pneumatic Actuator Combinations
Valid Pneumatic Valve/Actuator
3
Assembly Code Number
)
V-3766-1001 V-3766-1002 V-3766-1003
V-3966-1001 V-3966-1002
V-4332-1004 V-4332-1006 V-4332-1007 V-4332-1009
VB-3766-1 VB-3766-2 VB-3766-3
VB-3966-1 VB-3966-2
VB-4332-4 VB-4332-5
1. Push-Down-to-Close (PDTC); Push-Down-to-Open (PDTO)
Spring Range, psi
3 to 6 3 to 6 3 to 6
9 to 13 9 to 13
9 to 13 9 to 13 4 to 8 4 to 8
None None None
None None
None None
Valid Code Numbers of VB-3766, VB-3966, and VB-4332 Flare Valve and Electric Actuator Combinations
Valid Actuator/V alve Factory Assembly
Actuator Valve
Body
Max. CvFlared
Code Number
AV-8050-1007 VA-8050-1 AV-8050-1008 VB-3766-2 1.7 AV-8050-1009 VB-3766-3 3.2 AV-8050-1016 VB-4332-4 1.2 Three-Way AV-8050-1017 VB-4332-5 2.0 AV-8051-1007 VA-8051-1 AV-8051-1008 VB-3766-2 1.7 AV-8051-1009 VB-3766-3 3.2 AV-8051-1016 VB-4332-4 1.2 Three-Way AV-8051-1017 VA-8050-1 VB-4333-5 2.0
Floating/ Incremental
Floating/ Incremental Feedback
VB-3766-1 1.0 Two-Way
VB-3766-1 1.0 Two-Way
Max. CvStyle
1.0
N.O.
1.7
3.2
1.7
N.C.
3.2
1.2
MIX
2.0
1.2
2.0
1.0
PDTC
1.7
3.2
1.7
PDTO
3.2
1.2
MIX
2.0
Valve Body Style
PDTC
MIX
PDTC
MIX
1
1
Accessories
Code Number Description
V-3000-8003 Enclosed V-3000 Actuator for Field Mounting V-3000-10 Valve Position Indicator for V-3000-1 Exposed Style Pneumatically Actuated Valves V-9502-15 Valve Positioner for Field Mounting to a V-3000-1 Exposed Style Pneumatically Actuated Valve V-9502-20 Valve Positioner Spring for V-3000-1 Exposed Style Pneumatically Actuated Valves Using a V-9502-15 Positioner; 3.0 psi (21 kPa) Span V-9502-101 Valve Positioner Spring for V-3000-1 Exposed Style Pneumatically Actuated Valves Using a V-9502-15 Positioner; 4.3 psi (30 kPa) Span V-9502-19 Valve Positioner Spring for V-3000-1 Exposed Style Pneumatically Actuated Valves Using a V-9502-15 Positioner 8.0 psi (56 kPa) Span
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
1
V-3766, V-3966, and V-4332 Brass Pneumatic Flare Valves, 1/2 in. Two-Way and Three-Way (Continued)
Repair Parts
Valve Code Number
V-3766 VB-3766
V-3966 VB-3966
V-4332 VB-4322
All Assemblies
1. Spring kit contains: sp ring, upper and lower spring plate, stem extension, lock screw, and instructions.
2. Packing kit contains: O-rings, crocus cloth, assembly tool, gland nut liner, guid e, extractor/installer, ring pack assembly, follower, grease, and instructions.
3. Silicone grease is not included in this kit; order V-9999-606 separately.
Repair Kit Code Number
V-3754-6010
V-3754-6009
V-4332-6001
V-3752-6022
V-9999-608 V-9999-610 V-9999-630
1
1
1
1
2
2
3
Description
Spring Kit, 3-6 psig, 1/2 in. Stroke for V-3011, V-3020, V-3752, V-3755, V-4510, V-5250 (1-1/2 and 2), V-3754 (1/2 and 3/4), and V-3766 (1/2) Valve with V-3000-1 or V-3000-2 Actu ator
Spring Kit, 9-13 psig, 1/2 in. Stroke for V-3011, V-3020, V-3212, V-3752, V-3755, V-3970, V-4322 (1-1/2 and 2), V-397 4, V-3966, V-6139 (1/2), V-3754, V-3974, V-4324 (1/2 and 3/4) Valve with V-3000-1 or V-3000-2 Actuator
Spring Kit, 4-8 psig, 5/16 in. Stroke for V-3212, V-3970, V-4322 (1/2 and 3/4), V-4332, V-4333 (1/2), V-4334 (5/8), and VT Valve with V-3000-1 or V-3000-2 Actuator
Spring Kit, 9-13 psig, 5/16 in. Stroke for V-3011, V-3020, V-3212, V-3752, V-3755, V-3970, V-4322 (1/2 and 3/4), V-4334 (5/8), V-4332, V-4333, V-5416, V-7416 (1/2), V-6143 (3/8 and 3/4) and VT Valve with V-3000-1 or V-3000-2 Actuator
Ring Pack Packing Kits: Single Pack 10 Pack (Contains Enough Materials to Repack 10 Valves) 50 Pack (Contains U-Cups and O-Rings Only to Repack 50 Valves)
Technical Specifications
V-3766, V-3966, and V-4332 Brass Pneumatic Flare Valves, 1/2 in. Two-Way and Three-Way
Models Pneumatic V-3766 - PDTC (Normally Open), V-3966 - PDTO (Normally Closed), V-4332 - Three-Way Mixing
Electric VB-3766 - PDTC, VB-3996 - PDTO, VB-4332 - Three-Way Mixing Service Hot and Cold Water Control Air Connection (Pneumatic Operation) 1/8 in. NPT Barbed Fitting for 5/32 or 1/4 in. OD Polytubing for Pneumatic Actuators Flow Characteristics Equal Percentage Actuator Sizing/Maximum Closeoff Pressure See Selection Charts. Valve Stem Diameter 1/4 in. Flow Coefficients (Cv) Two-Way: 1.0, 1.7, 3.2; Three-Way (Mixing): 1.2, 2.0.
Maximum Seat Leakage PDTC (N.O.) and PDTO (N.C.): 0.05% of Maximum Rated Valve Capacity
Maximum Recommended Differential Pressure for Valve Sizing
Rangeability Refer to the Flare Valves 1/2 in. Two-Way and Three-Way Product Bulletin (LIT-977175). Valve Stroke 5/16 in. Maximum Allowable Pressure/Temperature (Two-Way) V-3766, VB-3766, V-3966, VB-3966 400 psi (2,800 kPa) up to 150°F (66°C)
Ambient Temperature Limit -10 to 150°F (-23 to 66°C) for Pneumatic Actuators; -10 to 140°F (-23 to 60°C) with VA-805x Actuator Fluid Operating Temperature Limits 281°F (140°C) Maximum for Pneumatic Actuators; 195°F (90°C) Maximum with VA-805x Actuator Materials Stem Stainless Steel
Plug PDTC (N.O.) and PDTO (N.C.): Brass with Molded and Bonded Composition Disc
Body Cast Brass with Natural Finish
Actuator Die Cast Aluminum for Pneumatic Actuators. For Electric Actuators, Refer to the Relevant Electr ic Actuator
Diaphragm Molded Reinforced Synthetic Rubber for Pneumatic Actuators Spring Ranges (Nominal) 3 to 6 psi (21 to 42 kPa) N.O. only; 4 to 8 psi (28 to 56 kPa) MIX Only;
Body Style and Sizes Offset Globe for 1/2 in. SAE Flared Connections Maximum Control Pressure 30 psi (210 kPa) for Pneumatic Actuators
See Selection Charts.
Three-Way Mixing: 0.5% of Maximum Rated Valve Capacity 35 psi (245 kPa)
Decreasing to 345 psi (2,415 kPa) at 281°F (140°C) (Three-Way Mixing) V-4332 and VB-4332 250 psi (1,750 kPa) Maximum at 281°F (140°C)
Three-Way Mixing: Brass (Metal-to-Metal Seating)
Product Bulletin.
9 to 13 psi (63 to 91 kPa) N.C. and MIX for Pneumatic Actuators
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
2
Loading...