V148 Series Three-Way Pressure-Actuated Water-Regulating Valves
Description
The V148 Series Three-Way
Pressure-Actuated Water-Regulating Valves
regulate water flow to control refrigerant head
pressure in systems with single or multiple
water-cooled condensers. The V148 valves
are designed for applications with system
water pressures of up to 350 psi (24.1 bar),
such as high-rise buildings.
V148EK and V148AL valves have an
adjustable opening point in a refrigerant
pressure range of 145 to 190 psi (10.0 to
13.1 bar). V148EK and V148AL valves are
available in 3/4 in. and 1 in. sizes. Use these
valves with standard, non-corrosive
refrigerants.
V148GK1 and V148GL1 valves have an
adjustable opening point in a refrigerant
pressure range of 200 to 400 psi (13.8 to
27.6 bar). The V148GK1 and V148GL1
Valves are available in 3/4 in. and 1 in. sizes
for use with standard, non-corrosive,
high-pressure refrigerants.
Refer to the V148 Series 3-Way
Pressure-Actuated Water-Regulating Valves
Product Bulletin (LIT-121712) for important
product application information.
Valves and Valve Accessories
Features
• no close-fitting or sliding parts in water
passages
• high water pressure design
• pressure-balanced design
• corrosion-resistant material for internal
parts
• accessible range spring
• take-apart construction
Applications
Each application is unique and requires
specific engineering data to properly size and
design a system to fulfill the appropriate
requirements. Typically, a valve is replaced
with another valve of the same size in a
properly sized and engineered system.
To make a rough field estimate of the size of valve for an application,
find the valve size by locating a point on a flow chart that satisfies these
requirements:
• water flow required by the condenser (Flow)
• refrigerant head pressure rise (P
• available water pressure (P
Follow these steps, and use the information obtained to locate a point
on one of the flowcharts that satisfies all three steps.
1. Take the water flow required by the condenser (Flow) from
information provided by the manufacturer of the condensing unit. If
the manufacturer’s information is unavailable, use the following
information to make a rough approximation of maximum water flow
in gallons per minute (gpm) (cubic meters per hour [m
Note: If the outlet temperature is unknown, assume it to be 10F
(5.6C) above the inlet temperature.
2. Determine refrigerant head pressure rise above the valve opening
point (P
3
/hr]):
a. The Valve Closing Pressure (P
refrigerant pressure at the highest ambient temperature the
refrigeration equipment experiences in the Off cycle. Use a
)
Pressure-Temperature Chart for the refrigerant selected to find
this pressure.
b. To approximate the Valve Opening Pressure (P
about 7 psi (0.5 bar) for EK and AL models or 10 psi (0.7 bar) for
GK1 and GL1 models to the Valve Closing Pressure.
R-167
) using the following steps:
RISE
) is equal to the
CLOSE
OPEN
), add
Valve Opening Pressure, EK and AL Models (Top) or
GK1 and GL1 Models (Bottom)
OPENCLOSE
OPENCLOSE
Refrigerant Head Pressure Rise
FIG
P = P - P
Available Water Pressure
Cooling Tower
P
1
P
2
P
Loss 2
3-Way
Valve
P
IN
COND
P
P
1P2
=
-
P
P
P
=
+
+ ...
Balan c ing Valve
FIG:3w y_prss_d
3/4 in. V148EK Valve
30
25
20
15
10
5
0
10 1520 25 30 35
7
(gpm)
Pressure Drop Through Valve (psi)
FIG:V148EK_chrt
1 in. V148AL Valve
55
50
45
40
35
30
25
20
15
10
5
10 15
20
7
(gpm)
0
Pressure Drop Thr ough Valve ( psi )
FIG:V148 AL_chrt
Valves and Valve Accessories
V148 Series Three-Way Pressure-Actuated Water-Regulating Valves
(Continued)
P = P +7 psi (0.5 bar)
P = P +10 psi (0.7 bar)
c. From the Pressure-Temperature Chart for the refrigerant
selected, read the Refrigerant Condensing Pressure (P
(operating head pressure) corresponding to the selected
condensing temperature.
d. Subtract the Valve Opening Pressure from the Refrigerant
Condensing Pressure. This gives the head pressure rise.
RISECONDOPEN
3. Determine the available water pressure to the valve (P
the following steps. This is the actual water pressure available to
force water through the valve.
a. Determine the minimum inlet pressure (P
pressure from city water mains, pumps, or other sources.
b. Pressure drop through condenser (P
water pressure between the condenser inlet and the condenser
COND
outlet. Obtain this information from the condenser manufacturer.
c. Estimate or calculate the pressure drop through all associated
piping (P
d. Subtract the P
LOSS
).
COND
and P
from PIN. The result is P
LOSS
:eqn_h d_prssr_r s
AVAIL
). This is the water
IN
) is the difference in
rp
FIG:V14 x_eqn_opn_pr ssr
COND
) using
AVAIL
Use these equations to convert between U.S. and S.I. units.
4. Select the proper valve size from the flowcharts by locating a point
on a chart that satisfies the flow, the head pressure rise above
opening point, and the pressure drop across the valve.
If the V148 Series Three-Way Pressure-Actuated Water-Regulating Valve fails to operate within its specifications, refer to the V148 Series
Three-Way Pressure-Actuated Water-Regulating Valves Product Bulletin (LIT-121712) for a list of repair parts available.
Inlet and Outlet PortsPressure Connection Style Shipping Weight, lb (kg)
Technical Specifications
V148 Series 3-Way Pressure-Actuated Water-Regulating Valves
Maximum Refrigerant PressureV148EK: 370 psig (25.5 bar)
Maximum Working PressureV148GK1, V148GL1: 630 psig (43.4 bar)