V146 Series Two-Way Pressure-Actuated Water-Regulating Valves
Description
The V146 Series Two-Way PressureActuated Water-Regulating Valves regulate
water flow to control refrigerant head pressure
in systems with water-cooled condensers. The
V146 valves are ideal for applications with
system water pressures of up to 350 psig
(24.1 bar), such as high-rise buildings.
V146EK and V146AL valves have an
adjustable opening point in a refrigerant
pressure range of 70 to 260 psi (4.8 to
17.9 bar). V146EK and V146AL valves are
available in a 3/4 in. and 1 in. size. Use these
valves with standard, non-corrosive
refrigerants.
V146GK1 and V146GL1 valves have an
adjustable opening point in a refrigerant
pressure range of 200 to 400 psi (13.8 to
27.6 bar). The V146GK1 and V146GL1 valves
are available in 3/4 in. and 1 in. size for use
with standard, non-corrosive, high-pressure
refrigerants.
Refer to the V146 Series 2-Way
Pressure-Actuated Water-Regulating Valves
Product Bulletin (LIT-121709) for important
product application information.
Valves and Valve Accessories
Features
• no close-fitting or sliding parts in water
passages
• high-pressure design
• pressure-balanced design
• corrosion-resistant material for internal
parts
• accessible range spring
• take-apart construction
Applications
Each application is unique and requires
specific engineering data to properly size and
design a system to fulfill the appropriate
requirements. Typically, a valve is replaced
with another valve of the same size in a
properly sized and engineered system.
To make a rough field estimate of the size of valve for an application,
find the valve size by locating a point on a flow chartthat satisfies these
requirements:
• water flow required by the condenser (Flow)
• refrigerant head pressure rise (P
• available water pressure (P
Follow these steps, and use the information obtained to locate a point
on one of the flowcharts that satisfies all three steps.
1. Take the water flow required by the condenser (Flow) from
information provided by the manufacturer of the condensing unit. If
the manufacturer’s information is unavailable, use the following
information to make a rough approximation of maximum water flow
in gallons per minute (gpm) (cubic meters per hour [m
Note: If the outlet temperature is unknown, assume it to be 10F
(5.6C) above the inlet temperature.
2. Determine refrigerant head pressure rise above the valve opening
point (P
a. The Valve Closing Pressure (P
3
/hr]):
)
pressure at the highest ambient temperature the refrigeration
equipment experiences in the Off cycle. Use a
Pressure-Temperature Chart for the refrigerant selected to find
this pressure.
b. To approximate the Valve Opening Pressure (P
about 7 psi (0.5 bar) for EK and AL models or 10 psi (0.7 bar) for
GL1 or GK1 models to the Valve Closing Pressure.
R-162
) using the following steps:
RISE
) is equal to the refrigerant
CLOSE
OPEN
), add
Valve Opening Pressure, EK and AL Models (Top) or GK1 and
GL1 Models (Bottom)
FIG:V14
OPENCLOSE
OPENCLOSE
Figure 1: Refrigerant Head Pressure Rise
FIG
P = P - P
Available Water Pressure
Cooling Tower
P
1
P
2
P
Loss 2
2-Way
Valve
P
COND
P
P
1P2
=
-
P
P
P
=
+
+ ...
FIG:2 wy_prss _d
3/4 in. V146EK Valve
55
60
40
45 5035302510 15
20
0
5
10
15
20
25
30
35
40
45
(gpm)
20
30
FIG:V146EK_chrt
1 in. V146AL Valve
10 15 20 25
30
35
40 45 50 55
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
(gpm)
10
40
20
30
50
60
FIG:V146AL_chrt
Pressure Drop Through Valve (psi)
Valves and Valve Accessories
V146 Series Two-Way Pressure-Actuated Water-Regulating Valves
(Continued)
P = P +7 psi (0.5 bar)
P = P +10 psi (0.7 bar)
c. From the Pressure-Temperature Chart for the refrigerant
selected, read the Refrigerant Condensing Pressure (P
(operating head pressure) corresponding to the selected
condensing temperature.
d. Subtract the Valve Opening Pressure from the Refrigerant
Condensing Pressure. This gives the head pressure rise.
RISECONDOPEN
3. Determine the available water pressure to the valve (P
the following steps. This is the actual water pressure available to
force water through the valve.
a. Determine the minimum inlet pressure (P
pressure from city water mains, pumps, or other sources.
b. Pressure drop through condenser (P
water pressure between the condenser inlet and the condenser
COND
outlet. Obtain this information from the condenser manufacturer.
c. Estimate or calculate the pressure drop through all associated
piping (P
d. Subtract the P
LOSS
).
COND
and P
from PIN. The result is P
LOSS
:eqn_hd_prssr_rs
AVAIL
). This is the water
IN
) is the difference in
x_eqn_opn _prssr
COND
) using
AVAIL
The maximum recommendeddifferential water pressure across a
valve is 60 psi (4.1 bar).
Flow
60
50
40
)
10
Pressure Drop Thr ough Valve ( psi )
Refrigerant Head Pressure Rise (psi)
Flow
.
Pump
Condenser
Loss 1
4. Select the proper valve size from the flowcharts by locating a point
on a chart that satisfies the flow, the head pressure rise above
opening point, and the pressure drop across the valve.
Use these equations to convert between U.S. and S.I. units.
If the V146 Series Two-Way Pressure-Actuated Water-Regulating Valve fails to operate within its specifications, refer to the V146 Series
Two-Way Pressure-Actuated Water-Regulating Valves Product Bulletin (LIT-1201709) for a list of repair parts available.
Technical Specifications
V146 Series 2-Way Pressure-Actuated Water-Regulating Valves
Maximum Refrigerant PressureV146EK: 370 psi (25.5 bar)
Maximum Working PressureV146GK1, V146GL1: 630 psi (43.4 bar)
Opening Point Adjustment RangeV146EK, V146AL: 70 to 260 psi (4.8 to 17.9 bar)