Series ELO-231 – 11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
www.tyco-fire.com
General
Description
TYCO Series ELO-231 11.2K Standard Response, Standard Coverage
Upright and Pendent Sprinklers (Ref.
Figure 1) are automatic sprinklers of
the fusible solder type. They are standard response, spray sprinklers that
produce a hemispherical water distribution pattern below the deflector.
The 11.2 K-factor, ELO-231 Sprinklers
were subjected to full scale, high-piled
storage, fire tests to qualify their use
in lieu of 5.6 or 8.0 K-factor standard
spray sprinklers for the protection of
high-piled storage.
Higher flow rates can be achieved at
much lower pressures with the 11.2
K-factor, ELO-231 Sprinklers, making
their use highly advantageous in high
density applications, such as the protection of high-piled storage.
Wax or lead coatings can be used
to extend the life of the copper alloy
components used in Series ELO-231
sprinklers beyond that which would
otherwise be obtained when exposed
to corrosive atmospheres. Although
wax and lead coated sprinklers have
passed the standard corrosion tests of
the applicable approval agencies, the
testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end
user be consulted with respect to the
suitability of these corrosion resistant
coatings for any given corrosive envi-
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
ronment. The effects of ambient temperature, concentration of chemicals,
and gas/chemical velocity, should be
considered, as a minimum, along with
the corrosive nature of the chemical to
which the sprinklers will be exposed.
An upright intermediate level version
of the Series ELO-231 Sprinklers for
in-rack applications can be obtained
by utilizing the Series ELO-231 Upright
Sprinkler with the WSG-2 Guard &
Shield, and a pendent intermediate
level version of the Series ELO-231
Sprinklers can be obtained by utilizing
the Series ELO-231 Pendent Sprinkler
with the WS-2 Shield. If there is a possibility of the pendent intermediate level
version being exposed to mechanical
damage, a G-2 Guard can be added.
NOTICE
The 11.2 K-factor, Series ELO-231
Upright and Pendent Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
Installation of Series ELO-231 Pendent
Sprinklers in recessed escutcheons will
void all sprinkler warranties, as well as
possibly void the sprinkler’s Approvals
and/or Listings.
Sprinkler
Identification
Numbers (SINs)
Refer to Table A for sprinkler identification numbers.
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
NYC Approved
Refer to Table C for specific details
on laboratory listings and approvals,
including corrosion-resistant status.
The approvals apply to the service conditions indicated in the Design Criteria
section.
Finishes
Refer to Table C
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal Disc . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Strut Assembly ..Solder, Bronze Stainless Steel
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Helper Spring . . . . . . . . . . . . . . . Stainless Steel
Ejector Spring . . . . . . . . . . . . . . . . . . . . . . Nickel
Strut Clip . . . . . . . . . . . . . . . . . . . Stainless Steel
Additional Technical Data
Refer to Table A for additional technical data.
Page 1 of 6 AUGUST 2018 TFP340

TFP340
Page 2 of 6
2-13/16"
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
WRENCH
FLATS
1/2"
NPT
SERIES ELO-231 11.2K UPRIGHT - 3/4 IN. NPT (TY5111), UPRIGHT - 1/2 IN. NPT (TY5811), AND
PENDENT - 3/4 IN. NPT ( TY5211) SPRINKLERS
Operation
A fusible alloy is sealed into a bronze
actuating rod (center strut) by a stainless steel ball. When the alloy melts at
its rated temperature, the ball is forced
upward into the center strut, releasing the two ejectors and operating the
sprinkler.
Design
Criteria
UL and C-UL
Listing Requirements
TYCO Series ELO-231 11.2K Standard Response, Standard Coverage
Upright and Pendent Sprinklers are
to be installed in accordance with
NFPA 13 standard sprinkler position and area/density flow calculation requirements for light, ordinary,
or extra hazard occupancies, as well
as high piled storage occupancies,
such as solid piled, palletized, rack
storage, bin box, and shelf storage
including but not limited to Class I-IV
and Group A plastics, with a minimum
residual (flowing) pressure of 7 psi
(0,5 bar) for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231
Sprinklers are to be installed in accordance with the applicable control mode
density/area guidelines provided by FM
Global.
Note: FM Approval guidelines may
differ from UL and C-UL Listing criteria.
NOMINAL MAKE-IN
THREAD
RELIEF
3/4"
NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
PENDENT
FIGURE 1
Item Description
Sprinkler Identication Number (SIN)
K-factor, (gpm/psi) (lpm/bar) 11.2 gpm/psi½ (161,4 lpm/bar½)
Temperature Rating ºF (ºC)
Thread Size
Sprinkler Orientation Upright/Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
NOTES
1. Refer to Table C f or laboratory listing s and app rovals.
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLER
3/4"
1
NPT
2
7
3
8
4
9
5
6
TY5111 – Upright - 3/4 in. NPT
TY5211 – Pendent - 3/4 in. NPT
TY5811 – Upright - 1/2 in. NPT
TY5111 is a redesigna tion for C entral S IN C5111.
TY5211 is a redes ignati on for Central SIN C5211.
TY5811 is a rede signation for Ce ntral SI N C5811.
1
TABL E A
TECHNICAL DATA
-
1
Frame
-
Seal Disc
2
-
Cap
3
-
4
Strut
Assembly
-
5
Screw
-
6
Deector
-
7
Helper
Spring
-
8
Ejector
Spring
-
9
Strut Clip
Temperature
*
rating is
CROSS
16 5°F ( 74 ° C)1
212°F (100°C)
28 6°F (141° C)
3/4 in. NPT or ISO 7-R 3/4
1/2 in. NPT
indicated on
*