Johnson Controls TY5811, Tyco ELO-231 SERIES, TY5111, TY5211 User Manual

Worldwide
Contacts
Series ELO-231 – 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage
www.tyco-fire.com
General Description
TYCO Series ELO-231 11.2K Stan­dard Response, Standard Coverage Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprinklers of the fusible solder type. They are stan­dard response, spray sprinklers that produce a hemispherical water distri­bution pattern below the deflector.
The 11.2 K-factor, ELO-231 Sprinklers were subjected to full scale, high-piled storage, fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high-piled storage.
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231 Sprinklers, making their use highly advantageous in high density applications, such as the pro­tection of high-piled storage.
Wax or lead coatings can be used to extend the life of the copper alloy components used in Series ELO-231 sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although wax and lead coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all pos­sible corrosive atmospheres. Conse­quently, it is recommended that the end user be consulted with respect to the suitability of these corrosion resistant coatings for any given corrosive envi-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and installation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
ronment. The effects of ambient tem­perature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
An upright intermediate level version of the Series ELO-231 Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231 Upright Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231 Sprinklers can be obtained by utilizing the Series ELO-231 Pendent Sprinkler with the WS-2 Shield. If there is a pos­sibility of the pendent intermediate level version being exposed to mechanical damage, a G-2 Guard can be added.
NOTICE
The 11.2 K-factor, Series ELO-231 Upright and Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Installation of Series ELO-231 Pendent Sprinklers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Sprinkler Identification Numbers (SINs)
Refer to Table A for sprinkler identifica­tion numbers.
Technical Data
Approvals
UL and C-UL Listed FM Approved NYC Approved
Refer to Table C for specific details on laboratory listings and approvals, including corrosion-resistant status. The approvals apply to the service con­ditions indicated in the Design Criteria section.
Finishes
Refer to Table C
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal Disc . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Strut Assembly ..Solder, Bronze Stainless Steel
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Helper Spring . . . . . . . . . . . . . . . Stainless Steel
Ejector Spring . . . . . . . . . . . . . . . . . . . . . . Nickel
Strut Clip . . . . . . . . . . . . . . . . . . . Stainless Steel
Additional Technical Data
Refer to Table A for additional techni­cal data.
Page 1 of 6 AUGUST 2018 TFP340
TFP340
TY5211
TY5811
TY5111
SECTION
(71,4 mm)
1/2" (12,7 mm)
Compression
Components:
deector
Page 2 of 6
2-13/16"
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
WRENCH
FLATS
1/2" NPT
SERIES ELO-231 11.2K UPRIGHT - 3/4 IN. NPT (TY5111), UPRIGHT - 1/2 IN. NPT (TY5811), AND
PENDENT - 3/4 IN. NPT ( TY5211) SPRINKLERS
Operation
A fusible alloy is sealed into a bronze actuating rod (center strut) by a stain­less steel ball. When the alloy melts at its rated temperature, the ball is forced upward into the center strut, releas­ing the two ejectors and operating the sprinkler.
Design Criteria
UL and C-UL Listing Requirements
TYCO Series ELO-231 11.2K Stan­dard Response, Standard Coverage Upright and Pendent Sprinklers are to be installed in accordance with NFPA 13 standard sprinkler posi­tion and area/density flow calcula­tion requirements for light, ordinary, or extra hazard occupancies, as well as high piled storage occupancies, such as solid piled, palletized, rack storage, bin box, and shelf storage including but not limited to Class I-IV and Group A plastics, with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231 Sprinklers are to be installed in accor­dance with the applicable control mode density/area guidelines provided by FM Global.
Note: FM Approval guidelines may differ from UL and C-UL Listing criteria.
NOMINAL MAKE-IN
THREAD
RELIEF
3/4" NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
PENDENT
FIGURE 1
Item Description
Sprinkler Identication Number (SIN)
K-factor, (gpm/psi) (lpm/bar) 11.2 gpm/psi½ (161,4 lpm/bar½)
Temperature Rating ºF (ºC)
Thread Size
Sprinkler Orientation Upright/Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
NOTES
1. Refer to Table C f or laboratory listing s and app rovals.
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLER
3/4"
1
NPT
2
7
3
8
4
9
5
6
TY5111 – Upright - 3/4 in. NPT
TY5211 – Pendent - 3/4 in. NPT
TY5811 – Upright - 1/2 in. NPT
TY5111 is a redesigna tion for C entral S IN C5111. TY5211 is a redes ignati on for Central SIN C5211. TY5811 is a rede signation for Ce ntral SI N C5811.
1
TABL E A
TECHNICAL DATA
-
1
Frame
-
Seal Disc
2
-
Cap
3
-
4
Strut Assembly
-
5
Screw
-
6
Deector
-
7
Helper Spring
-
8
Ejector Spring
-
9
Strut Clip
Temperature
*
rating is
CROSS
16 5°F ( 74 ° C)1 212°F (100°C) 28 6°F (141° C)
3/4 in. NPT or ISO 7-R 3/4
1/2 in. NPT
indicated on
*