Johnson Controls TY5811, Tyco ELO-231 SERIES, TY5111, TY5211 User Manual

Page 1
Worldwide
Contacts
Series ELO-231 – 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage
www.tyco-fire.com
General Description
TYCO Series ELO-231 11.2K Stan­dard Response, Standard Coverage Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprinklers of the fusible solder type. They are stan­dard response, spray sprinklers that produce a hemispherical water distri­bution pattern below the deflector.
The 11.2 K-factor, ELO-231 Sprinklers were subjected to full scale, high-piled storage, fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high-piled storage.
Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231 Sprinklers, making their use highly advantageous in high density applications, such as the pro­tection of high-piled storage.
Wax or lead coatings can be used to extend the life of the copper alloy components used in Series ELO-231 sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although wax and lead coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all pos­sible corrosive atmospheres. Conse­quently, it is recommended that the end user be consulted with respect to the suitability of these corrosion resistant coatings for any given corrosive envi-
IMPORTANT
Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal­lation of sprinkler systems and com­ponents. Improper handling and installation can permanently damage a sprinkler system or its compo­nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
ronment. The effects of ambient tem­perature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.
An upright intermediate level version of the Series ELO-231 Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231 Upright Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231 Sprinklers can be obtained by utilizing the Series ELO-231 Pendent Sprinkler with the WS-2 Shield. If there is a pos­sibility of the pendent intermediate level version being exposed to mechanical damage, a G-2 Guard can be added.
NOTICE
The 11.2 K-factor, Series ELO-231 Upright and Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica­ble standards of the National Fire Pro­tection Association (NFPA), in addition to the standards of any other authori­ties having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for main­taining their fire protection system and devices in proper operating con­dition. Contact the installing contrac­tor or product manufacturer with any questions.
Installation of Series ELO-231 Pendent Sprinklers in recessed escutcheons will void all sprinkler warranties, as well as possibly void the sprinkler’s Approvals and/or Listings.
Sprinkler Identification Numbers (SINs)
Refer to Table A for sprinkler identifica­tion numbers.
Technical Data
Approvals
UL and C-UL Listed FM Approved NYC Approved
Refer to Table C for specific details on laboratory listings and approvals, including corrosion-resistant status. The approvals apply to the service con­ditions indicated in the Design Criteria section.
Finishes
Refer to Table C
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Seal Disc . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
Strut Assembly ..Solder, Bronze Stainless Steel
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Helper Spring . . . . . . . . . . . . . . . Stainless Steel
Ejector Spring . . . . . . . . . . . . . . . . . . . . . . Nickel
Strut Clip . . . . . . . . . . . . . . . . . . . Stainless Steel
Additional Technical Data
Refer to Table A for additional techni­cal data.
Page 1 of 6 AUGUST 2018 TFP340
Page 2
TFP340
TY5211
TY5811
TY5111
SECTION
(71,4 mm)
1/2" (12,7 mm)
Compression
Components:
deector
Page 2 of 6
2-13/16"
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
WRENCH
FLATS
1/2" NPT
SERIES ELO-231 11.2K UPRIGHT - 3/4 IN. NPT (TY5111), UPRIGHT - 1/2 IN. NPT (TY5811), AND
PENDENT - 3/4 IN. NPT ( TY5211) SPRINKLERS
Operation
A fusible alloy is sealed into a bronze actuating rod (center strut) by a stain­less steel ball. When the alloy melts at its rated temperature, the ball is forced upward into the center strut, releas­ing the two ejectors and operating the sprinkler.
Design Criteria
UL and C-UL Listing Requirements
TYCO Series ELO-231 11.2K Stan­dard Response, Standard Coverage Upright and Pendent Sprinklers are to be installed in accordance with NFPA 13 standard sprinkler posi­tion and area/density flow calcula­tion requirements for light, ordinary, or extra hazard occupancies, as well as high piled storage occupancies, such as solid piled, palletized, rack storage, bin box, and shelf storage including but not limited to Class I-IV and Group A plastics, with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems.
FM Approval Requirements
The 11.2 K-factor, Model ELO-231 Sprinklers are to be installed in accor­dance with the applicable control mode density/area guidelines provided by FM Global.
Note: FM Approval guidelines may differ from UL and C-UL Listing criteria.
NOMINAL MAKE-IN
THREAD
RELIEF
3/4" NPT
1/2" (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
PENDENT
FIGURE 1
Item Description
Sprinkler Identication Number (SIN)
K-factor, (gpm/psi) (lpm/bar) 11.2 gpm/psi½ (161,4 lpm/bar½)
Temperature Rating ºF (ºC)
Thread Size
Sprinkler Orientation Upright/Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
NOTES
1. Refer to Table C f or laboratory listing s and app rovals.
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLER
3/4"
1
NPT
2
7
3
8
4
9
5
6
TY5111 – Upright - 3/4 in. NPT
TY5211 – Pendent - 3/4 in. NPT
TY5811 – Upright - 1/2 in. NPT
TY5111 is a redesigna tion for C entral S IN C5111. TY5211 is a redes ignati on for Central SIN C5211. TY5811 is a rede signation for Ce ntral SI N C5811.
1
TABL E A
TECHNICAL DATA
-
1
Frame
-
Seal Disc
2
-
Cap
3
-
4
Strut Assembly
-
5
Screw
-
6
Deector
-
7
Helper Spring
-
8
Ejector Spring
-
9
Strut Clip
Temperature
*
rating is
CROSS
16 5°F ( 74 ° C)1 212°F (100°C) 28 6°F (141° C)
3/4 in. NPT or ISO 7-R 3/4
1/2 in. NPT
indicated on
*
Page 3
Storage Type NFPA FM Global
Sprinkler Type Standard Coverage Storage
Response Type SR SR
System Type Wet Wet
TFP340
Page 3 of 6
Temperature Rating ºF (ºC)
1
Open Frame (i.e., no solid shelves) Single, Double, Multiple­Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard)
Flammable/Ignitable Liquid Storage
(Refer to the Standard)
Aerosol Storage
(Refer to the Standard)
Automotive Components in Portable Racks
(Control mode only; refer to the Standard)
NOTES
1. Refer to Table C f or laboratory listing s and app rovals. N/A – Not App licable
SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TABL E B
16 5°F ( 74 ° C) 212°F (100°C) 28 6°F (141° C)
1
16 5°F ( 74 ° C) 212°F (100°C) 28 6°F (141° C)
1
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Refer to NFPA 13 Refer to FM 8-21
Refer to NFPA 30 Refer to FM 7-29
Refer to NFPA 30B Refer to FM 7-31
N/A N/A
SPRINKLER
TYPE
UPRIGHT
(TY5111 & T Y 5 811)
PENDENT
(TY52 11)
NOTES
1. UL Listed
2. C-Ul Liste d
11.2K SERIES ELO-231 UPRIGHT & PENDENT SPRINKLERS, STANDARD RESPONSE
TEMPERATURE
RATI NG
FRAME COLOR
16 5°F ( 74 ° C) Unpainted
212°F (100°C) White
NATURAL
BRASS
1, 2, 3, 4
CHROME
PL ATED
SPRINKLER FINISH
LEAD
COATE D
WAX
COATE D
WAX-OVER-LEAD
1, 2, 3, 4
28 6°F (141° C) Blue 1, 2, 3, 4 1*, 2*, 3*, 4*
16 5°F ( 74 ° C) Unpainted
212°F (100°C) White
1, 2, 3, 4
1, 2, 4
28 6°F (141° C) Blue 1, 2, 4 1*, 2*, 4*
3. F M Approve d
4. A pprove d by the Cit y of New York (NYC) un der ME A 291-04-E * Listed /Approve d for a ma ximum ce iling tem perature of 150 °F (66 °C)
TABL E C
LABORATORY LISTINGS AND APPROVALS
COATE D
Page 4
TFP340
"FITTING SIDE"
WRENCH
(END "A")
Page 4 of 6
TOWARDS SPRINKLER
FITTING
RECESS
FIGURE 2 W-T Y P E 3
SPRINKLER WRENCH
Installation
TYCO Series ELO-231 11.2K Stan­dard Response, Standard Coverage Upright and Pendent Sprinklers must be installed in accordance with this section.
A leak-tight 3/4 in. NPT sprinkler joint should be obtained by applying a min­imum-to-maximum torque of 10 to 20 lb-ft (13,4 to 26,8 Nm). A leak­tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum­to-maximum torque of 7 to 14 lb-ft (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.
Do not attempt to make up for insuf­ficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit.
The Series ELO-231 Upright and Pendent Sprinklers must be installed in accordance with the following instructions:
Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklers are to be installed in the upright position.
Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 3 Sprinkler Wrench (Ref. Figure 2), except that an 8 in. or 10 in. adjust­able Crescent wrench is to be used for wax coated sprinklers. With refer­ence to Figure 1, the W-Type 3 Sprin­kler Wrench or the adjustable wrench, as applicable, is to be applied to the wrench flats.
When installing wax-coated sprinklers with the adjustable wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damaging the wax coating. Before wrench-tightening the sprinkler, the jaws of the wrench are to be adjusted to just contact the sprin­kler wrench flats. After wrench-tight­ening the sprinkler, loosen the wrench jaws before removing the wrench.
After installation, the sprinkler wrench flats and frame arms must be inspected and the wax coating re-touched (repaired) whenever the coating has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gently applying a heated 1/8 in. diam­eter steel rod to the areas of wax that have been damaged, to smooth it back over areas where bare metal is exposed.
Note:
Only reto uching of the wax c oating applied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation.
The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precau­tions need to be taken, when handling the heated rod, in order to prevent the installer from being burned.
If attempts to retouch the wax coating with complete coverage are unsuc­cessful, additional wax can be ordered in the form of a wax stick (the end of which is color coded). Only the correct color-coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel rod heated as previously described, touch the rod to the area requiring additional wax with the rod angled downward, and then touch the wax stick to the rod approximately 1/2 in. away from the area requiring retouching. The wax will melt and run down onto the sprinkler.
Care and Maintenance
TYCO Series ELO-231 11.2K Standard Response, Standard Coverage Upright and Pendent Sprinklers must be main­tained and serviced in accordance with this section.
Before closing a fire protection system control valve for maintenance work on the fire protection system that it con­trols, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated or otherwise altered after leaving the factory. Modi­fied or over-heated sprinklers must be replaced.
Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin­klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced.
Frequent visual inspections are rec­ommended to be initially performed for corrosion resistant sprinklers, after the installation has been completed, to verify the long term potential integrity of the sprinkler coatings. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present.
The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associ­ation, such as NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the install­ing contractor or product manufacturer with any questions.
It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec­tion Service in accordance with local requirements and/or national codes.
Page 5
P/N 50 – XXX – X – XXX
TFP340
Page 5 of 6
110 11.2K UPRIGHT (3/4 in. NPT) T Y5111
112 11.2K PENDENT (3/4 in. NPT ) T Y5211
210 11.2K UPRIGHT (1/2 in. NPT ) TY 5 811
SERIES ELO231 11.2K UPRIGHT AND PENDENT SPRINKLERS, STANDARD RESPONSE
Limited Warranty
For warranty terms and conditions, visit www.tyco-fire.com.
SIN
1
6
7
8
9
TABL E D
PART NUMBER SELECTION
SPRINKLER
FINISH
NAT U R AL
BRASS
WAX
CO ATED
LEAD
CO ATED
WAX- OVER- LE AD
CO ATED
CHROME
PL AT ED
Ordering Procedure
Contact your local distributor for avail­ability. When placing an order, indicate the full product name and part number (P/N).
Sprinkler
Specify: ELO-231 11.2K Standard Response (specify Pendent or Upright) Sprinkler, SIN (specify), temperature rating (specify), with (specify) finish, P/N (specify from Table D)
Sprinkler Wrench
Specify: W-Type 3 Sprinkler Wrench, P/ N 5 6 - 89 5 -1-0 01
TEMPERATURE
RATI NG
165 16 5°F ( 74 ° C)
212 212°F (100°C)
286 286° F (141°C)
Wax Sticks
(for retouching wrench-damaged wax coating)
Specify: (specify Color) color-coded Wax Stick for retouching (specify temperature rating) temperature­rated Series ELO-231 Sprinklers, P/N (specify):
Red for 165°F (74°C) . . . . . . . . . . . 5 6 - 065 -1-155
Blue for 212°F (100°C) and
28 6° F ( 141°C) .................5 6 - 065 -1- 28 6
Note:
Each wax stick is suitable for retouching up to twenty-five sprinklers. The wax used for 286°F (141°C) sprinklers is the same as for 212°F (100°C) sprinklers, and, therefore, the 286°F (141°C)sprinkler is limited to the same maximum ceiling temperature as the 212°F (100°C) sprinkler, such as 150°F (66°C).
Page 6
TFP340
Page 6 of 6
1400 Pennbrook Par kway, Lansdale, PA 194 46 | Telep hone +1-215- 362-0700
© 2018 John son Control s. All right s reserved. A ll specifica tions and ot her informa tion shown wer e current as o f document rev ision date an d are subject t o change wit hout notice.
NATIONAL FIRE P ROTECTION ASSOCIATIO N and NFPA are register ed trademarks of N ational Fire Protec tion Associati on
Loading...