DESCRIPTION
TVI-TD-6007 series thermostat is mainly used in central air-conditioning and
heating system. It detects room temperature and compares it with setting point,
then provides control signal to central air-conditioning fan coil cool / heat motorized
valves or other actuating mechanism. It can also control the fan blower of fan coil
units and adjust the fan speed. When the TVI-TD-6007 thermostat is turned off or
get power supply after system power shut off, it can output a return signal to make
the motorized valves or other actuating mechanism return.
CHARACTERISTICS
Power surge and instant pulse protection.
Output signal overtime protection function, auto-return function when the
thermostat is turned off or get first power supply (TVI-TD-6007F)
Fixed setting temperature function
Large LCD with background light shows the control state, ambient
temperature, setting temperature and fan speed.
With system on-off switch and fan speed switch.
Inside or outside long-distance temperature sensitive element
(NTC thermistor)
With ABS fireproof plastic, compliance with UL-94 standard.
TECHNICAL DATA
NAME
POWER SUPPLY 24Vac; 220/230Vac AC24V AC220V/230V
OUTPUT
POWER CONSUMPTION 0.6VA ; 6VA (without load)
FAN OUTPUT 24Vac, 2(1) A; 220/230Vac, 2(1)A 24Vac, 2(1) A
RETURN TIME ---
OVERTIME CUT OFF ---
WORKING STATE On/off type Floating (PID) Modulating
TVI-TD-6007A/B (2-pipe sys.)
TVI-TD-6007C (4-pipe sys.)
24Vac, 1(0.8)A;
220/230Vac, 1(0.5)A
TVI-TD-6007F TVI-TD-6007P
DC0-10V 10mA DC0-10V 5mA
0.6VA (without
load)
≥150s or ≥300s (for
option)
Valve operate to the
same direction
≥150s (≥300s),
turns into overtime
protection state.
---
---
6VA
(without load)
220/230Vac,
2(1)A
CONTROL PRECISION ±0.5°C(±1°C)
CONTROL RANGE 10°C - 30°C or 50°F - 86°F
BACKGROUND LIGHT Blue—B
SENSITIVE ELEMENT NTC thermistor 10KΩ (when at 25°C)
WORKING TEMPERATURE 0 ~ 55oC/32 oF ~131 oF
STORAGE TEMPERATURE -10 ~ 60°C/14 oF ~140 oF
AMBIENT HUMIDITY 90% RH maximum
Subject to changes without prior notice
1/3 TVI-TD-6007 Thermostat_1109

INSTRUCTION
1. Cool/heat shift: (TVI-TD-6007A/B/C) in 2-pipe system, the thermostat is on Cooling state when the Power
Supply switch is at position “ ”; on Heating state when the Power Supply switch is at position “ ”; and,
the thermostat is shut off when the Power Supply switch is at position “”. In 4-pipe system, the thermostat
can only output heating or cooling signal according to the position of Power Supply switch. When the
power switch is turned to position “”, the thermostat will self-check, and then make the valve run for 150
seconds (or 300 seconds) continuously towards the closing position. When it finishes operation, the
thermostat will enter into turn off state. When the power supply switch turns to “ ”, the LCD will show the
cooling state symbol “ ”, the action signal will output forward; when it moves to “”, the LCD will show the
heating state symbol“”, the action signal will output backward. When it moves to “”, the LCD will shut off,
the valve will run for 150 seconds (or 300 seconds) continuously towards the closing end, then the system
will be shut off.
2. Fan: When the thermostat is in cooling or heating state, turn the fan switch
corresponding air volume symbol. The terminals will output power and provide operating power for the fan.
If the thermostat isn’t connected to the fan, only or can be shown on the LCD. The symbol can
only be shown when the thermostat is connected to the fan correctly.
3. Temperature setting: When user presses “”(increase)/ “” decrease)button, LCD display temperature
setting will show increase or decrease accordingly. The increase/decrease rate is 0.2oC/0.5
adjusting range is 10~30oC/50~86
thermostat will change the setting temperature data in its memory, and then the LCD shows the ambient
temperature. (The ex-factory setting point is 25oC/77 oF.)
4. Built-in/external sensor: When built-in NTC thermistor is used, the jumper J3 should be put to position
“Int”. If the external NTC sensor is used, the jumper J3 should be put to “Ext” position.
5. Fixed setting temp. function: Put the jumper JP4 to position 1, the setting point can’t be changed by
pressing increase or decrease buttons. (The default setting is on position 0. The setting point can be
changed by pressing increase or decrease buttons)
WIRING DIAGRAM
o
F. When user stops pressing the button for over 5 seconds, the
- - , the LCD will display
o
F. The
TVI-TD-6007A-Heat/Cool
TVI-TD-6007B-Cool Only
TVI-TD-6007C – 4 Pipes Sys.
TVI-TD-6007P – Modulating TVI-TD-6007F – Floating
Subject to changes without prior notice
2/3 TVI-TD-6007 Thermostat_1109