Johnson Controls TSS, TSL Installation Operation & Maintenance

Page 1
SINGLE DUCT VAV TERMINALS
INSTALLATION, OPERATION & MAINTENANCE
New Release
MODELS TSS & TSL
TSS
Form 130.13-NOM1 (114)
TSL
Page 2
FORM 130.13-NOM1 (114)
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ........................................................................................................................3
INSPECTION .................................................................................................................................................4
STORAGE .....................................................................................................................................................4
PRE-INSTALLATION INSPECTION ..............................................................................................................5
SEQUENCE OF OPERATION .......................................................................................................................5
Single Duct .............................................................................................................................................5
INSTALLATION .............................................................................................................................................5
Clearances .............................................................................................................................................5
Hanging and Mounting Equipment ......................................................................................................5
Unit Weights ...........................................................................................................................................6
Duct Connections Critically Sound Applications
Coil Connections ...................................................................................................................................7
Electrical .................................................................................................................................................7
OPERATION ..................................................................................................................................................7
Start-Up ..................................................................................................................................................7
3 Phase Balancing .................................................................................................................................7
MAINTENANCE ............................................................................................................................................8
Optional Damper Actuator ....................................................................................................................8
Manual Override ....................................................................................................................................8
Mechanical Angle of Rotation Stops ...................................................................................................8
External Terminal Strip .........................................................................................................................8
Overload Protection ..............................................................................................................................8
Checkout Instructions ...........................................................................................................................8
Damper Shaft .........................................................................................................................................8
Coil ..........................................................................................................................................................8
Cleaning ............................................................................................................................................9
Electric Heat ..........................................................................................................................................9
Minimum Operating Conditions ......................................................................................................9
Electric Heater Rack Replacement .................................................................................................9
Electric Heater Element Replacement ............................................................................................9
Heater Troubleshooting Guide ......................................................................................................10
(SSR) Troubleshooting Guide .......................................................................................................11
..................................................................................................................................6
...............................................................................................................7
Calibration Charts ...............................................................................................................................15
2
Page 3
FORM 130.13-NOM1 (114)
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not
avoided, could result in death or se-
rious injury.
SAFETY CONSIDERATIONS
The equipment covered in this manual is designed for safe and reliable operation when installed and operated
within its’ design specication limits. To avoid personal
injury or damage to equipment or property while installing or operating this equipment, it is essential
that qualied, experience personnel familiar with local
codes and regulations, perform these functions using
good judgment and safe practices. See the following cautionary statements.
ELECTRICAL SHOCK HAZARDS
All power must be disconnected prior
to installation and servicing this equip-
ment. More then one source of power may be present. Disconnect all power sources to avoid electrocution or shock hazards.
HOT PARTS HAZARD
Electric resistance heating elements
must be disconnected prior to servic­ing. Electric heaters may start auto-
matically; disconnect all power and control circuits prior to servicing to avoid burns.
Check that rigging and lifting equip­ment can safely support the unit as-
sembly and component weights.
CAUTION identies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually an instruction will be given, together with a brief explanation.
NOTE is used to highlight additional information which may be helpful to you.
All assemblies must be adequately secured during lifting and rigging by
temporary supports and restraints un-
til equipment is permanently fastened and set in its’ nal location.
All unit temporary and permanent supports must be capable of safely supporting the equipment’s weight and any additional live, seismic or dead loads that may be encountered. All
supports must be designed to meet ap-
plicable local codes and ordinances.
All fastening devices must be designed to mechanically lock the assembly in
place without the capability of loosen-
ing or breaking away due to system operation and vibration.
Secure all dampers when servicing
damper, actuators or linkage. Damp­ers may activate automatically, discon-
nect the control circuits or pneumatic control systems to avoid injury.
Protect adjacent ammable material when brazing. Use ame and heat protection barriers where needed.
Have re extinguisher ready for im-
mediate use.
3
Page 4
FORM 130.13-NOM1 (114)
INSPECTION
Upon receipt of equipment, carefully check all items against the bill of lading to ensure that all equipment has
been received (including shipped loose items). Note any discrepancy on the bill of lading before signing.
Inspect all equipment for any signs of damage caused
during transit. On units with re-heat, check the coil ns and/or ensure that the resistance heat coils are not damaged. Note any visual damage on the bill of lading before signing. Immediately report all visual and concealed damage to the carrier and le a claim with the carrier.
Locate the model number on the nameplate and check
that the correct units have been received. Verify that all
options have been included, such as controls, heating
coils, etc. Also ensure that unit voltage agrees with the building parameters. If a discrepancy is discovered
between what was ordered and received, contact your
local Johnson Controls representative immediately.
DO NOT USE FLOW SENSOR,
CONNECTING TUBES, COIL STU-
BOUTS OR DAMPER SHAFT AS
A HANDLE WHEN LIFTING OR
MOVING EQUIPMENT, AS DAM-
AGE MAY OCCUR.
DO NOT HANDLE EQUIPMENT’S
HEATING ELEMENTS, AS PERMA-
NENT DAMAGE MAY OCCUR.
DO NOT work on damper until associ-
ated actuator is disconnected.
NEVER pressurize equipment above specied test pressure.
PROTECT adjacent ammable ma-
terials when brazing. Use ame and heat protection barriers where needed. Have a re extinguisher at hand and ready for immediate use.
STORAGE
If equipment is to be stored prior to installation, observe the following precautions:
1. Choose a dry storage site that is reasonably level
and sturdy to prevent undue stress or permanent
damage to the equipment. Set equipment off ground if in moisture prone areas.
2. Tag and store in a safe place until needed. Cover
entire equipment with protective tarp or moisture
proof cover. Extend cover under equipment if stored on ground. Secure cover with adequate tie downs and store indoors. Be sure that piping con­nections have protective shipping caps installed.
CHECK assembly and component weights to be sure that the rigging equipment can handle them safely. Note; also check the centers of gravity and any specic rigging instructions.
CHECK for adequate ventilation so fumes do not migrate through ductwork to occupied spaces when welding or cutting around the unit.
4
Page 5
FORM 130.13-NOM1 (114)
PRE-INSTALLATION INSPECTION
DO NOT USE FLOW SENSOR,
CONNECTING TUBES, COIL STU-
BOUTS OR DAMPER SHAFT AS
A HANDLE WHEN LIFTING OR
MOVING EQUIPMENT, AS DAM-
AGE MAY OCCUR.
DO NOT HANDLE EQUIPMENT’S
HEATING ELEMENTS, AS PERMA-
NENT DAMAGE MAY OCCUR.
Ensure that all linkages are connected properly. Check
the linkage that connects the actuator to the damper shaft
to ensure that the nuts are tight.
While viewing the damper from the discharge of the
unit, rotate the shaft fully. The damper should close
fully and there should be no gaps between the damper
gasketing and the inside of the valve.
INSTALLATION
DO NOT USE FLOW SENSOR,
CONNECTING TUBES, COIL STU-
BOUTS OR DAMPER SHAFT AS
A HANDLE WHEN LIFTING OR
MOVING EQUIPMENT, AS DAM-
AGE MAY OCCUR.
DO NOT HANDLE EQUIPMENT’S
HEATING ELEMENTS, AS PERMA-
NENT DAMAGE MAY OCCUR.
All terminal equipment with electric heaters must
be installed in a horizontal plane with respect to the
airow stream. Low height equipment (Model TSL) can be ipped over in the eld to vary or change control section handing.
Clearances
SEQUENCE OF OPERATION
Single Duct
The basic unit consists of a sheet metal casing and an air valve, which is used to modulate the air being delivered
into the occupied zone. Air enters the air valve inlet and exits into the sheet metal casing to be distributed
to the occupied zone through ductwork attached to the
discharge of the unit.
The basic unit can be ordered with either a factory
mounted hot water heating coil or an electric heater.
These re-heat units are used primarily to reheat the air-to-zone temperature when the load in the occupied space drops off.
The primary air is modulated through the FlowStar™ air valve by rotating the damper blade. The air valves come in rectangular and round. The round valves only
come in diameters of 4, 5, 6, 8, 10, 12, 14 and 16 inches;
an adapter must be used for metric ductwork.
All equipment covered in this document, including those with electric heat, are ETL listed for 0.0" clearance to combustibles. Refer to NEC and/or local codes for minimum electrical clearances required for service. Equipment should not make contact with any structure
located above the equipment without appropriate
isolation. Equipment supplied with bottom access panels requires sufcient clearance to access fasteners,
and to lower and slide panel horizontally until clear of
bottom of unit.
Hanging and Mounting Equipment
Although the basic equipment is generally light enough
that it can be supported by the ductwork, Johnson Controls strongly recommends that all equipment be suspended from the upper most ceiling or a structural element of the building, independent of the false ceiling
grid. Suspension devises are eld supplied, sized and designed by others. Johnson Controls will not accept responsibility for unit support. Equipment must be installed in a level horizontal plane. Failure to level
equipment properly may prevent proper operation of
controls. Provisions for proper support in seismically
active regions is the responsibility of others. See table
1 through 4 for unit weights.
5
Page 6
UNIT WEIGHTS
FORM 130.13-NOM1 (114)
TABLE 1 - SINGLE DUCT TERMINAL UNIT WEIGHTS
UNIT SIZE
SINGLE
04 20 (9) 25 (11) 35 (16) 50 (23) 64 (29) 79 (36) 05 20 (9) 25 (11) 35 (16) 50 (23) 64 (29) 79 (36) 06 19 (9) 24 (11) 34 (15) 49 (22) 62 (28) 77 (35} 08 20 (9) 26 (12) 37 (17) 53 (24) 71 (32) 87 (39) 10 25 (11) 32 (15) 44 (20) 62 (28) 78 (35) 96 (44) 12 28 (13 36 (16) 50 (23) 71 (32) 89 (40) 110 (50) 14 35 (16) 44 (20) 59 (27) 84 (38) 106 (48) 131 (59) 16 37 (17) 47 (21) 63 (29) 90 (41) 113 (51) 140 (64) 19 49 (22) 62 (28) 85 (39) 120 (55) 141 (64) 176 (80) 22 51 (23) 65 (29) 90 (41) 127 (58) 148 (67) 185 (84)
TSS TSS w/ SA TSS w/ EH
SINGLE
WALL
DOU-
BLE
WALL
SINGLE
WALL
DOU-
BLE
WALL
WALL
DOU-
BLE
WALL
TABLE 3 - SINGLE DUCT LOW HEIGHT TERMINAL UNIT WEIGHTS
UNIT SIZE
SINGLE
10 26 (12) 30 (14) 43 (19) 58 (26) 62 (28) 77 (35) 12 28 (13) 35 (16) 49 (22) 68 (31) 74 (34) 93 (42) 14 39 (18) 47 (21) 62 (28) 82 (37) 90 (41) 110 (50) 16 45 (20) 55 (25) 73 (33) 96 (44) 103 (47) 126 (57)
TSL TSL w/ SA TSL w/ EH
WALL
DOUBLE
WALL
SINGLE
WALL
DOUBLE
WALL
SINGLE
WALL
DOUBLE
WALL
TABLE 2 - TSS WATER COIL WEIGHT ADDS
UNIT SIZE
04 4 (2) 5 (2) 8 (4) 12 (5) 05 4 (2) 5 (2) 8 (4) 12 (5) 06 4 (2) 5 (2) 8 (4) 12 (5) 08 4 (2) 6 (3) 9 (4) 13 (6) 10 5 (2) 8 (4) 12 (5) 18 (8) 12 7 (3) 10 (5) 16 (7) 22 (10) 14 9 (4) 14 (6) 21 (10) 30 (14) 16 10 (5) 16 (7) 24 (11) 34 (15) 19 12 (5) 20 (9) 28 (13) 40 (18) 22 13 (6) 22 (10) 32 (15) 44 (20)
Adds for water coils reect actual operating weight.
1 ROW 2 ROW 3 ROW 4 ROW
# OF ROWS
TABLE 4 - TSL WATER COIL WEIGHT ADDS
UNIT SIZE
Adds for water coils reect actual operating weight.
1 ROW 2 ROW 3 ROW 4 ROW
10 9 (4) 12 (5) 15 (7) 18 (8) 12 11 (5) 15 (7) 19 (9) 23 (10) 14 13 (6) 18 (8) 22 (10) 27 (12) 16 15 (7) 21 (9) 27 (12) 32 (15)
# OF ROWS
When requested, equipment is supplied with optional
hanger brackets for use with up to a 3/8" diameter
hanger rod. See submittal drawings for hanger bracket
locations.
Hanger straps may be utilized as an alternate means of
suspending the equipment. Do not secure hanger straps to electric heaters, coils or control enclosures. Hanger
straps can be mounted directly to the sides and bottom of equipment casing, such that they do not interfere with working components or access panels, using screws that
do not penetrate the unit cabinet more than 3/8".
When hanging equipment, always use the support method as prescribed for rectangular duct in the job
specications.
Duct Connections
When fastening ductwork to equip-
ment, DO NOT use fasteners that penetrate equipment cabinet more
than 3/8" [10mm]. Fasteners penetrat­ing the equipment cabinet over 3/8"
[10mm] may come in contact with live
electrical parts or penetrate other com-
ponents within the equipment casing causing damage.
All duct connections should be congured and installed in accordance with SMACNA guidelines and all local code requirements.
6
Page 7
FORM 130.13-NOM1 (114)
Allow a minimum of 1½-duct diameters of straight duct prior to equipment inlet and equipment discharge.
The diameter of the inlet duct for round valves must
be equal to the listed size of the equipment. The round air valve inlet collar of the equipment is 1/8" smaller
then listed size in order to allow the round ductwork to
slip over the air valve inlet collar. DO NOT INSERT DUCTWORK INTO AIR VALVE INLET COLLAR.
When making ductwork connection to air valve inlet collar and insulating air valve inlet, take caution not to
damage or remove the ow sensor connections, which are vital to unit control. Provide insulation around entire inlet collar (all the way to the equipment casing).
Permissible discharge duct connections are straight anged, slip and drive or drive and screw.
If equipment is to be installed in a location with high
humidity, external insulation around the heating coil should be installed.
Sound Critical Applications
Flexible duct connectors are not recommended on equipment discharge. The sagging membrane of these ttings can cause turbulence and higher air velocities that generate noise. Also, lightweight membrane
material allows noise to breakout, which can increase
sound levels in the space below.
Coil Connections
Hot water and steam coils are male sweat connections.
Use appropriate brazing alloy for system temperature
and pressure. Refer to unit construction submittal drawing for specic connection size. MAXIMUM HYDRONIC SYSTEM OPERATING PRESSURE MUST NOT EXCEED 300 PSIG. MAXIMUM STEAM SYSTEM PRESSURE MUST NOT EXCEED 15 PSIG.
Minimum circuit ampacity (MCA) designates the maximum operating load of the equipment for sizing wire feeders. Fuse size of the internal fuse if supplied. Maximum Overcurrent Protection (MOP) designates
the largest breaker or fuse in the electrical service panel
that can be used to protect the equipment.
Use Copper conductors only.
OPERATION
Start-Up
Thorough safety precautions should always be taken
when performing startup and service. Only qualied individuals should perform these tasks.
Check that all electrical work is nished and properly terminated. Check that all electrical connections are tight and that the proper voltage is connected.
3 Phase Balancing
AC power imbalance must not exceed 2%. Be sure that
the following guides are met:
1. AC power is within 10% of rated voltage at rated
frequency. (See equipment nameplate for rat-
ings).
2. AC power is within 5% of rated frequency at rated voltage.
3. A combined variation in the voltage and frequency of 10% (sum of absolute values) of rated values, provided the frequency variation does not exceed 5% of rated frequency.
Equipment with electric heat requires a minimum of 0.1" w.g. downstream static pressure.
Electrical
All eld wiring must comply with NEC and all local codes. Electrical and/or control wiring diagrams are located on the control enclosure box. All electric heaters are staged per specications.
The installing electrician should rotate the incoming electric service by phase to help balance the building
electrical load.
Prior to start-up, the project control sequence/wiring diagram should be obtained and thoroughly understood. If factory supplied analog or DDC controls are utilized, refer to the applicable Operation Manual for start-up and balancing information.
7
Page 8
FORM 130.13-NOM1 (114)
MAINTENANCE
Optional Damper Actuator
An optional factory mounted oating type actuator
is available, which mounts directly to the damper
operating shaft. The actuator is not provided with and
does not require any limit switches but is electronically
protected against overload.
Manual Override
A button on the side of the actuator cover disengages the gear train so the drain shaft can be moved manually. Releasing the button will re-engage the gear train.
Mechanical Angle of Rotation Stops
The adjustable stops may be field adjusted to halt the rotation of the damper blade before the damper
blade reaches the damper stops. The actuator can be indenitely stalled in any position without harm.
1. Loosen the two end stop screws using a No. 2 Phillips head screwdriver, being careful not to unscrew the captive nut under the slot.
2. Move the stops (in 2.5° steps) to the desired posi­tion and retighten the screws.
External Terminal Strip
Checkout Instructions
1. Disconnect actuator from the controller.
2. Apply 24 VAC to the COM and CW terminals on the actuator. Actuator should rotate in a clockwise direction.
3. Apply 24 VAC to the COM and CCW terminals on the actuator. Actuator should rotate in a counter clockwise direction.
4. If actuator moves in both directions, it is opera­tional.
5. If the actuator does not rotate, it may be at an end stop or there is a problem with the damper.
6. Loosen the set screw to free the actuator from the damper shaft. Check to make sure that the damper shaft rotates freely.
7. Check to make sure that actuator is not against stop. Repeat steps 2 and 3.
8. If actuator does not rotate, replace.
Damper Shaft
There is an indicator on the end of the damper shaft that can be used to determine the position of the damper
blade. If the indicator is horizontal, the damper is completely open. The damper shaft is ½" diameter.
The external terminal strip is located on the top of the actuator. Connections are numbered. The terminals are designed for 26 to 16 gauge wires. For most
installations, 18 or 16 gauge wire will work well with the actuator (see table 5 for maximum wire lengths).
TABLE 5 - MAXIMUM WIRE LENGTHS
WIRE SIZE MAX FEET
16 GA 1225 FT 18 GA 725 FT 20 GA 400 FT 22 GA 200 FT
Overload Protection
The actuators are electronically protected against
mechanical overload. In the actuator, an electronic
circuit maintains the current at a level that will not damage the motor while providing adequate holding
torque.
Coil
The frequency of required cleaning is dependent on the
operating hours of the system, lter maintenance and efciency as well as dirt load.
Important: Coils may become exter­nally dirty as result of normal opera-
tion. Dirt on the surface of the coil reduces its ability to transfer heat that can result in reduced performance, and increased operating energy cost. If the dirt on the surface of the coil becomes wet, microbial growth (mold)
can result, possibly causing unpleas-
ant odors and serious health related indoor air quality problems.
Fin edges are sharp. Fins are fragile;
care must be exercised to avoid damag-
ing ns. Do not use solutions to clean coils; drain pans are not present to remove collected solution.
8
Page 9
FORM 130.13-NOM1 (114)
Cleaning
1. Disconnect all electrical power to the equipment, tag and lock out power source.
2. Gain access to coil either through ductwork or optional coil access panel.
3. Use soft brush and vacuum to remove loose debris from sides of coil. Do not use uid or solvents to
clean coils, as no provisions for collecting liquids
exist on this type of equipment.
4. Straighten any coil ns that may have been dam­aged during cleaning process with n comb.
5. Replace ductwork or access panel and restore electrical power to equipment.
Electric Heat
Johnson Controls electric heaters require little or no
maintenance.
Electric heaters come equipped with a primary auto-reset limit switch. These limit switches provide protection against overheating. The auto-reset limits switches
automatically cut the heater off when overheating occurs, and turns the heater back on when the elements
have cooled down. Electric heaters also come equipped with a secondary one-time trip limit switch. Should
the secondary limit switches trip, they will need to be replaced with a limit switch that has the same trip
temperature as the one-time trip limit switch that was originally supplied with the electric heater. An optional
manual reset secondary is available, which can be reset
by depressing the reset switch.
Minimum Operating Conditions
Airow must be at least 70 CFM per kW. A minimum of 0.1" w.g. external pressure is required.
Electric Heater Rack Replacement
JOHNSON CONTROLS HEATERS
1. Turn off power supply before servicing.
2. Locate T-Plate inside on heater control enclo­sure.
3. Before removing wires from the element rack T-Plate, mark where the wires are connected so
that they can be reconnected correctly on the new
element rack.
4. Remove the wires and screws holding the heater T-plate in the control enclosure and remove ele­ment rack.
5. Insert new element rack into control enclosure and
replace screws to secure the element rack to control
enclosure.
6. Replace wires.
7. Close control enclosure cover before turning on the power.
Electric Heater Element Replacement
TUTCO HEATERS
1. Turn off power supply before servicing.
2. Disconnect eld wiring from Electric Heater Con­trol Enclosure.
3. Disconnect Amp Plug Connectors if equipped.
4. Remove 4 mounting screws from inside Electric Heater Control Enclosure.
5. Slide entire heater assembly out of Single Duct Terminal.
6. Remove wires and any jumpers from heater ele-
ment terminal ends, noting which wire and jumper
goes to which terminal.
7. Remove ¼" hex head screws located near terminal ends.
8. Remove ¼" hex head screws from opposite of terminal end on heater rack.
9. Remove elements and replace with new ones.
10. Reassemble, replace wires correctly.
11. Close control enclosure cover before turning on power.
9
Page 10
ELECTRIC HEATER TROUBLESHOOTING GUIDE
FORM 130.13-NOM1 (114)
TABLE 6 - HEATER TROUBLESHOOTING GUIDE
Check wiring diagrams to ensure that heater is properly wired.
SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
HEATER DOES NOT OPERATE
LOW OR HIGH TEMPERATURE RISE
SHORT CYCLING
HEATER WITH SSR DOES NOT
OPERATE
JOHNSON CONTROLS AND TUTCO
No Power Check Disconnect.
Check Control Signal (i.e. 24 VAC).
No Control Voltage
Blown Fuse Replace fuse.
Open Limit (primary or secondary)
Airow Incorrect Direction Check sensing tube, rotate if needed.
Low Airow Static Pressure Increase airow.
Damaged Elements
Incompatible Thermostat or Controller
Problems with Additional Stages
Incorrect CFM
Improper Airow
Low CFM
Incorrect Signal Applied Verify signal input.
Interface Board Fuse Blown Replace fuse.
See SSR Troubleshooting (next page)
Check transformer and transformer fus-
ing (if applicable), replace if necessary.
Replace limits or reset as applicable.
Check for continuity across limit to de-
termine if open, replace as necessary.
Check for open or damaged elements and replace as necessary.
Check Wiring.
Check for compatibility.
Check location of thermostat; may be
installed in a “too hot” or “too cold loca-
tion. Check heat outputs on controller.
Check contactors for open coil.
Check for damaged elements.
Check for blocked duct or location of heater.
Check for even airow across the face of the element section.
Check for blocked duct.
Verify installation per SMACNA and ASHRAE guidelines.
Check for dirty lters.
See remedies for “Improper Airow”.
Check air velocity of 70 CFM per kW.
10
Page 11
PROPORTIONAL HEAT CONTROL
(SSR) TROUBLESHOOTING GUIDE
Johnson Controls Heaters
FORM 130.13-NOM1 (114)
Lethal voltages are present in the heater control enclosure. Use extreme caution when taking measurements in these units. Always disconnect power before removing or re-applying any connections.
1. Before applying power, verify wiring matches
diagram in cover of heater control enclosure, and that correct line voltage has been wired to heater
line block.
2. Verify 24 VAC +15% or -10% between P1 and P2 of interface circuit board (ETPHCI, ETPHCV2, etc., depending on input).
3. The table below lists responses to input signal by interface model as explained in step 4. If any of
these inputs cannot be obtained, refer to the litera­ture on the device that is supposed to provide the
input. Otherwise, proceed to step 4.
INTERFACE
MODEL ETPHCI 12.0 mA 4.0 mA 20.0 mA Sig, Com
ETPHCV2 6.0 VDC 2.0 VDC
ETPHCC 50% 0 VAC 24 VAC Sig, Com
ETPHCC1 50% 0 VAC 24 VAC
“PULSE”
INPUT
FULL
OFF
INPUT
4. Apply Full Off Input per table above. If the unit is three phase, verify that the LED on the SSR (solid state relay) is off. If the unit is single phase, measure voltage between P4 and P6 and verify 0.3 VDC + or - 0.3 VDC. Replace the interface circuit board if the voltage is higher than specied, or the LED is on.
5. Apply Full On Input per table above. If the unit is three phase, verify that the LED on the SSR (solid state relay) is on. If the unit is single phase, mea­sure voltage between P4 and P6 and verify between 3 and 5 VDC.
FULL
ON
INPUT
10.0
VDC
INPUTS
Sig, Com
+18,
Com
6. If the module provided is an ETPHCC or ET­PHCC1, go to step 7. Apply “Pulse” Input per table above. If the unit is three phase, verify that the LED on the SSR (solid state relay) is ashing at an interval of about one second. If the unit is single phase, the voltage between P4 and P6 of the interface board should vary between the Full Off and Full On voltages in steps 4 and 5 in intervals of about one second.
Some voltmeters will not respond this quickly, so the value of the voltages may not appear to be correct; however, if the voltage appears to be changing
at regular intervals, it may be as-
sumed that this function is operating properly.
This completes the low voltage portion of the unit
test. Go to step 8.
7. For the ETPHCC or ETPHCC1, the associated
consignment controller must be directed to output
a 50% On pulse width modulation signal. For three phase, verify that the LED is pulsing at regular intervals. The rate of the pulse is based on the output from the consignment controller. If the unit is single phase, the DC voltage between P4 and P6
of the interface board should vary between the full
Off and full On voltages in steps 4 and 5.
Some voltmeters will not respond this quickly, so the value of the voltages may not appear to be correct; however, if the voltage appears to be changing
at regular intervals, it may be as-
sumed that this function is operating properly.
11
Page 12
8. If the heater always remains energized when power is applied, remove the wire from P4 of the interface circuit board. If the heat remains on, there is a wiring error or the SSR is defective.
Remove Power From the Unit Before Proceeding With the Next Step.
9. If the heater is always de-energized when power
is applied, remove the line and load connections to the proportional heat control and temporarily
tie them together. If the system is a three phase arrangement, do the phases one at a time.
Always remove power from the unit before moving to the next phase).
FORM 130.13-NOM1 (114)
Make sure there is no danger of the temporary
connection shorting to another component or the
chassis. Briey reapply power. If the section of heat under test now energizes, the SSR is defective.
If heater still will not energize, one of the heater
safety devices (limits, safety contactor or airow switch) or elements is defective.
12
Page 13
PROPORTIONAL HEAT CONTROL
(SSR) TROUBLESHOOTING GUIDE
Tutco Heaters, All Power Modules
FORM 130.13-NOM1 (114)
13
Page 14
FORM 130.13-NOM1 (114)
PROPORTIONAL HEAT CONTROL
(SSR) TROUBLESHOOTING GUIDE
Tutco Heaters, R820 SCR’s
14
Page 15
CALIBRATION CHARTS

Flow Star Calibration Chart

Model TSS
FlowStar Calibration Chart
(For dead-end differential pressure transducers)
FORM 130.13-NOM1 (114)
Model TSS
400 SERIES
(PNEUMATIC)
STANDARD CON-
UNIT
SIZE
4 43 250 35 250 30 43 55 250 250 5 68 350 50 350 48 65 88 350 350 6 75 490 60 550 53 75 97 435 530
8 145 960 115 1000 105 145 190 840 1000 10 235 1545 185 1600 165 235 305 1355 1600 12 340 2250 285 2300 240 340 440 1975 2300 14 475 3100 390 3100 335 475 615 2750 3100 16 625 4100 520 4100 440 625 805 3595 4100 19 1180 6500 1025 6500 845 1180 1510 6375 6500 22 1730 8000 1450 8000 1260 1730 2200 8000 8000
Notes:
1. Minimum and maximum airow limits are dependent on the specic DDC controller supplied. Contact the control vendor to obtain the minimum and maximum differential pressure limits (inches w.g.) of the transducer utilized with the DDC controller.
2. Maximum CFM is limited to value shown in General Selection Data.
3. FlowStar™ differential pressure tubing connections: High side indicated by red tubing; Low side indicated by black tubing.
4. Electric heat will not operate below 0.03” w.g. differential pressure
TROLLER
MIN. MAX. MIN. MAX.
7000 SERIES
ANALOG
ELECTRONIC
DDC CONSIGNMENT CONTROLS
(See Notes Below)
MIN. MAX.
Min. transducer differential
pressure (in. w.g.)
0.015 0.03 0.05 1.0 ≥1.5
Max. transducer differential
pressure (in. w.g.)
15
Page 16
FlowStar Calibration Chart
(For dead-end differential pressure transducers)

Model TSL
NOTE: Maximum and minimum CFM limits are dependent on the type of controls that are utilized. Refer to the table below for specic values. When DDC controls are furnished by others, the CFM limits are dependent on the specic control vendor that is employed. After obtaining the differential pressure range from the vendor, the maximum and minimum CFM limits can be obtained from the chart to the left (many controllers are capable of controlling minimum setpoint down to 0.015”w.g.)
400 SERIES
(PNEUMATIC)
STANDARD
UNIT SIZE
10 235 1545 170 1600 170 235 305 1370 1600 12 340 2250 240 2300 240 340 435 1955 2300 14 495 3100 350 3100 350 495 640 2855 3100 16 660 4100 465 4100 465 660 850 3800 4100
Notes:
1. Minimum and maximum airow limits are dependent on the specic DDC controller supplied. Contact the control vendor to obtain the minimum and maximum differential pressure limits (inches w.g.) of the transducer utilized with the DDC controller.
2. Maximum CFM is limited to value shown in General Selection Data.
3. FlowStar™ differential pressure tubing connections: High side indicated by red tubing; Low side indicated by black tubing.
4. Electric heat will not operate below 0.03” w.g. differential pressure
CONTROLLER
MIN. MAX. MIN. MAX.
7000 SERIES
ANALOG
ELECTRONIC
DDC CONSIGNMENT CONTROLS
(See Notes Below)
MIN. MAX.
Min. transducer differential
pressure (in. w.g.)
0.015 0.03 0.05 1.0 ≥1.5
Max. transducer differential
pressure (in. w.g.)
Form 130.13-NOM1 (114) Supersedes:130.13-NOM1 (808)
Loading...