Johnson Controls TrueRH Series, TrueRH HT-670 Series Installation Instructions Manual

Page 1
24-7701-187, Rev. B
Product Code Number
Description
ACC-DWCLIP-0
Drywall Clip Mounting Kit (10/bag)
ACC-INSL-0*
Wallbox Mounting Pad (10/bag)
GRD10A-608
Plastic Guard with Baseplate and Mounting Ring
T-4000-119
Allen-head Adjustment Tool (30/bag)
TE-67D0-601**
Door Replacement Kit with Johnson Controls logo
** Contains 10 original style and 10 new style doors.
Installation Instructions HT-670x Issue Date March 2016
TRUERH™ Series HT-670 x Humidity Transmitters

Application Requirements

Configure the transmitter for the output signal required prior to installation. Proceed to the appropriate transmitter section to change the factory setting.

Installation

The humidity transmitter is available in both a wall mount or duct probe package to suit a variety of sensing application needs.

Parts Included

mounting base for U.S. wallbox or surface mounting
No. 6-32 x 7/8 in. oval-head screw (2)
No. 4-40 x 1/4 in. he x-head cover screw (in the
mounting base)
drywall clip mounting kit (includes two each No. 6-20 x 1.25 in. pan-head tapping screws, spring clips, and spacers)
IMPORTANT: The HT-670x Series Humidity Transmitter is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the HT-670x Series Humidity Transmitter could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the HT-670x Series Humidity Transmitter
IMPORTANT: Le HT-670x Series Humidity Transmitter est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du HT-670x Series Humidity Transmitter risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du HT-670x Series Humidity Transmitter.

Accessories

Table 1: Accessories and Replacement Parts for Wall Mount Humidity Transmitters
ACC-INSL-1*
TE-67MB-600
TE-67D0-602**
* These foam pads help prevent drafts from entering the unit through the wall and make installation easier when mounting on an uneven surface.
© 2016 Johnson Controls, Inc. 1 Part No. 24-7701-187, Rev. B www.johnsoncontrols.com
Surface Mounting Pad (10/bag)
Mounting Base Kit
Door Replacement Kit without logo
Page 2

Mounting

BaseCover
1. Loosen (do not remove) the cover screw with a 1/16 in. (1.5 mm) Allen wrench.
2. Swing the cover down from the base.
No. 6
Screws
Cover Screw
Base
Cover Screw
Cover

Location Considerations

IMPORTANT: To avoid damage to the circuit
board and components, do not mount the unit in a location where high concentrations of corrosive vapors are present.
The HT-670x element comes with one mounting base for both surface and wallbox mounting. To mount the HT-670x, release the cover from the mounting base as described in Figure 1.
Figure 2: Wallbox MountingPlace the bottom edge of
the cover against the bottom lip of the base, and rotate it up onto the base. (See Figure 3.)
5. Tighten the cover screw.
Figure 1: Removing the Cover from the Base

Wallbox Mounting: Special Tools Needed

Use a 1/16 in. (1.5 mm) Allen wrench or T-4000-119 Allen-head adjustment tool for mounting.

Wallbox Mounting: Location Considerations

Locate the humidity transmitter on an inside wal l, fr ee from drafts, and out of direct sunlight. The HT-670x is shock and vibration resistant; however, be careful not to drop or mount the unit where it could be exposed to excessive vibration. The following ambient operating conditions apply:
Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0 to 100% Relative Humidity (RH),
noncondensing; 85°F (29°C) maximum dew point
To mount the HT-670x to a wallbox:
1. Pull the cable or wiring through the wallbox and base.
2. Rotate the mounting base, so one of the arrows on the base points up.
3. Fasten the base to the wallbox with the No. 6 screws provided. (See Figure 2.)
Figure 3: Attaching the Cover to the Base
Once installed, the HT-670x cannot be removed from the wall unless the cover screw is loosened as described in Figure 1.
IMPORTANT: Seal the drilled hole or use an ACC-INSL-0 Foam Pad Kit to help reduce drafts entering the unit. (See Table 1.) Drafts could result in false humidity or temperature readings.
Note: These instructions assume a standard 2 x 4 in. (52 x 104 mm) U.S. wallbox is used.
2 TRUERH Series HT-670x Humidity Transmitters Installation Instructions
Page 3

Surface Mounting: Special Tools Needed

Base
Cover Screw
Cover
1-3/8 in. (35 mm)
Hole
Drywall
Spacer (2) for
3/8 in. (9.5 mm) and 1/2 in.
(12.7 mm ) Thick Drywall
1-3/8 in.
(35 mm)
Hole
Spring Clip (2)
Drywall
Drywall
Spring
Clip (2)
Base
No. 6-20 x 1.25 in.
Pan-head
Tapp ing Screw (2)
hole saw with 1-3/8 in. (35 mm) diameter blade
1/16 in. (1.5 mm) Allen wrench or T-4000-119
Allen-head adjustment tool
drill with 1/8 in. (3 mm ) drill b it To mount the surface model to drywall, refer to
Figure 5 and proceed as follows:
1. Bend the top and bottom edges of mounting base at the perforations until they break off. (See Figure 4.)
2. Drill a 1-3/8 in. (35 mm) hole in the surface where the unit is to be mounted, and pull the wiring through the drilled hole.
3. Mark the location of the two mounting screws, and drill the holes.
4. Insert the spring clips on each side of the drilled 1-3/8 in. (35 mm) hole, and use the spacers if needed as shown in Figure 5. Do not use the spacers for 5/8 in. (16 mm) drywall.
Note: For replacement spring clips, spacers, and screws, order the ACC-DWCLIP-0 Drywall Clip Mounting Kit. (See Table 1.)
Figure 4: Removing the Breakaway Tabs
6. Pull the wiring through the base of the unit.
7. Center the two holes in the base over the two drilled holes, and fasten the base to the drywall using the No. 6 screws provided. (See Figure 5.)
8. Place the bottom edge of the cover against the bottom lip of the base, and rotate it up onto the base as shown in Figure 3.
9. Tighten the cover screw.
Once installed, the HT-670x cannot be removed from the wall unless the cover screw is loosened as described in Figure 1.
IMPORTANT: To prevent drywall damage, do not overtighten the screws.
Figure 5: Surface Mounting to Drywall
TRUERH Series HT-670x Humidity Transmitters Installation Instructions 3
Page 4

Duct Probe Humidity Transmitter Parts Included

Housing
Conduit Hole
Snap-on Cover
Conduit Knockout
(Top and Bott om
of Cover)
Duct
Washer (Cup ped Side
Toward Housing)
Conduit Fitting (Not Provided)
Nut for Conduit Fitting
(Not Provided)
No. 8
Screw
(2)
HT-670x Series transmitter
No 8 x 1 in. Phillips-head sheet metal screw (2)
washer for use with conduit fitting
Note: Conduit fitting and nut are not provided.

Duct Probe Humidity Transmitter Special Tools Needed

hole saw with 1 in. (25 mm) diameter blade
drill with 1/8 in. (3 mm ) drill b it

Duct Probe Humidity Transmitter Location Considerations

Place the duct probe humidity transmitter in a location that complies with the following:
Position: Designed for duct mounting in any position, except with the probe tip pointed up.
Duct Diameter: Recommended minimum diameter (round ducts) or width (square ducts) is 12 in. (305 mm).
Air Stratification (when the unit is mounted on the discharge side of the fan): Recommended location is at least 8 ft (2.4 m) downstream from humidification equipment, where duct air and water vapor are sufficiently mixed. Avoid areas where the probe may be exposed to condensation.
To mount the duct probe humidity transmitter, refer to Figure 6, and proceed as follows:
1. Remove any excess insulation from the duct that prevents the probe from extending a minimum of 3 in. (76 mm) into the air stream.
2. Use the hole saw to make a 1 in. (25.4 mm) hole in the duct to insert the probe.
Figure 6: Mounting and Assembly
4. Insert the probe into the duct, and mark the location of the holes for the mounting screws.
5. Remove the unit, and drill a 1/8 in. (3 mm) hole for each mounting screw.
IMPORTANT: Remove the unit before drilling to prevent any metal remnants from falling onto the circuit board.
Seal any holes created during installation to help reduce drafts and produce more accurate humidity readings.
6. Use a gasket, sealer, or other means to seal the area around the 1 in. (25.4 mm) hole between the unit and the duct.
7. Reinsert the probe, and secure the housing to the duct using the two No. 8 screws provided.
3. Pull the plastic cover off the housing.
4 TRUERH Series HT-670x Humidity Transmitters Installation Instructions
Page 5
!
-
-
+
+
Output
Power
Common
Measuring Device:
R = 5k ohm
(Minimum)
Power Supply:
20 to 30 VAC
or
14 to 30 VDC
-
-
+
+
Power
Measuring Device:
R 50 x (Supply
Voltage - 15.5)
Power Supply:
16 to 30 VDC
Note: Output is not used .
Common
Circuit Boa r d
0 to 10 VDC (Factory Set)
4 to 20 mA
Output
Disengage the tabs
to remov e the
circuit board.

Wiring

CAUTION: Risk of Electric Shock.
Disconnect the power supply befor e m aking electrical connections to avoid electric shock.
MISE EN GARDE: Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
When wiring the HT-670x, consider the following:
Do not run low-voltage wiring in the same conduit as line-voltage wiring or other conductors that supply highly inductive loads.
Make all wiring connections in accordance with the National Electrical Code and all local regulations.

Wall Mount Humidity Transmitter

Depending on the application, refer to Figure 7 or Figure 8 to wire the wall mount model.
1. Proceed with the terminal connections.

Duct Probe Humidity Transmitter

Depending on the application, refer to Figure 10 or Figure 11 to wire the duct probe model.
1. Route the wires from the equipment to the unit through the conduit hole in the housing. (See Figure 6.)
2. Break out the appropriate knockout from the cover, shown in Figure 6, using pliers to accommodate the wiring or conduit.
IMPORTANT: If using a conduit fitting (not provided), a washer is provided to support the fitting in the housing. If the washer is not used, the fitting could stress the plastic housing.
3. Press the cover onto the base.

Setup and Adjustments

Wall Mount Humidity Transmitter

To set the output jumper, refer to Figure 9. Rem ove the circuit board, and position the output jumper to suit the application. Reinstall the circuit board.
Figure 7: Wiring with Output Jumper
Set for 0 to 10 VDC
Figure 8: Wiring with Output Jumper
Set for 4 to 20 mA Once installed, the unit cannot be
removed from the wall unless the cover screw is loosened as described in Figure 1.
TRUERH Series HT-670x Humidity Transmitters Installation Instructions 5
Figure 9: Setting the Output Jumper

Duct Probe Humidity Transmitter

Refer to Figure 10 to set the output jumper for 0 to 10 VDC.
Page 6
Probe
Output
Power
Ground
(Common)
+
-
-
+
Measuring
Device:
R = 5,000 ohms
(Minimum)
Power Supply:
20 to 30 VAC
or
14 to 30 VDC
0 to 10 VDC (Factory Set)
Output
Probe
Power
Ground
(Common)
+
-
­+
Power Supply:
16 to 30 VDC
Measuring
Device:
R 50 x (Supply
Voltage - 15.5)
<
Output 4 to 20 mA
Note: Output is not used.
Figure 10: Output Jumper Set for 0 to 10 VDC
Refer to Figure 3 to set the output jumper for 4 to 20 mA.

Troubleshooting

If the humidity transmitter is not functioning properly:
1. Verify the unit is mounted in a location that is indicative of space humidity (away from drafts or sunlight, for example).
2. Check all supply voltage connections, and make sure the wiring is correct. (Refer to Figure 10 or Figure 11 for the duct probe transmitter and Figure 7 or Figure 8 for the wall mount transmitter.)
3. Verify the jumper positions. If the unit is not delivering an output, make sure the output jumper is selected for the appropriate application.
4. Replace the unit if the troubleshooting suggestions fail to remedy the problem.

Repairs and Replacemen t

The HE-67xx units are not field repairable. As with any electrical device, keep the air vents clean and free from dust or obstruction. The HT-670x controllers have been designed for maintenance-free operation. Sturdy packaging, solid-state components, and high-quality element construction combine for a long-lasti ng, hi gh performance sensor. To order replacement parts, contact the nearest Johnson Controls representative.
Figure 11: Output Jumper Setting for 4 to 20 mA
6 TRUERH Series HT-670x Humidity Transmitters Installation Instructions
Page 7

Technical Specifications

Product
T
RH Series HT-670x Humidity Transmitters
Power Requirements
16 to 30 VDC at 20 mA, Class 2
Conditions
0 to 100% RH, noncondensing; 85°F (29°C) maximum dew point
Survival Operating Conditions
-20 to 140°F (-29 to 60°C) 0 to 100% RH, noncondensing; 85°F (29°C) maximum dew point
Ambient Storage
Duct Probe: White plastic cover with dark gray plastic housing and probe
Probe (L x D): 6.25 x 0.98 in. (159 x 25 mm)
Shipping Weight
0.7 lb (0.3 kg)
Agency Compliance
Duct probe material: 94-5 V flammability rated per UL 94
JOHNSON CONTROLS
JOHNSON CONTROLS
JOHNSON CONTROLS
Building Efficiency
If 0 to 10 VDC output jumper position is used: 20 to 30 VAC, 50/60 Hz at 15 mA or 14 to 30 VDC at 6 mA, Class 2
If 4 to 20 mA output jumper position is used:
RUE
Output Range (Jumper Selectable)
Humidity Transmitter Accuracy
Humidity Element Temperature Coefficient Electrical Connections Ambient Operating
Conditions Materials
Dimensions
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulti ng from misapplication or misuse of its products.
European Single Point of Contact:
0 to 10 VDC (5 k ohm minimum load impedance) or 4 to 20 mA DC (2-wire current loop) Maximum load impedance = 50 x (supply voltage—15.5)
HT-67x2: ±2% RH for 20 to 80% RH at 77°F (25°C) ±4% RH for 10 to 20% and 80 to 90% RH at 77°F (25°C)
HT-67x3: ±3% RH for 20 to 80% RH at 77°F (25°C) ±5% RH for 10 to 20% and 80 to 90% RH at 77°F (25°C)
All-Polymer™ element
-0.1 to 0.05% RH/°C at 5°C (41°F) to -0.07 to -0.21% RH/°C at 65°C (149°F) 3-position screw terminal block 32 to 122°F (0 to 50°C)
-40 to 176°F (-40 to 80°C) 0 to 100% RH, noncondensing; 85°F (29°C) maximum dew point
Wall Mount: White plastic enclosure for surface or standard wallbox mounting, including hardware
Wall Moun t (H x W x D): 3.20 x 3.20 x 1.34 in. (81 x 81 x 34 mm) Duct Probe (H x W x D): 3.25 x 3.25 x 8.27 in. (83 x 83 x 210 mm)
NA/SA Single Point of Contact:
APAC Single Point of Contact:
WESTENDHOF 3 45143 ESSEN GERMANY
507 E MICHIGAN ST MILWAUKEE WI 53202 USA
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
TRUERH Series HT-670x Humidity Transmitters Installation Instructions 7