Installation Instructions HE-67xx Issue Date March 2016
TRUERH™ Series
Installation
IMPORTANT: Use this HE-67xx Humidity
Element with Temperature Sensor only as an operating control. Where failure or malfunction of the humidity element with temperature sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the humidity element with temperature sensor.
IMPORTANT : Utiliser ce HE-67xx Humidity Element with Temperature Sensor uniquement en tant que dispositif de contrôle de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du humidity element with temperature sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer de s dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autre s dispositifs, tels que des systèmes de supervisio n ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du humidity element with temperature sensor.
The humidity elements are available in both a wall mount or duct probe package to suit a variety of sensing application needs. Refer to the Mounting section for a complete list of the parts included and tools required for installation.
Location Requirements
IMPORTANT: To avoid damage to the circuit
board and components, do not mount the unit in a location where high concentrations of corrosive vapors are present.
Wall Mount Humidity Element
Locate the humidity element on an inside wall, f ree from drafts, out of direct sunlight, and where the element is not exposed to excessive vibration. Be careful not to drop the unit.
Mount the wall mount element at a height of 4 to 6 ft (1.2 to 1.8 m) above the floor and with one of the two mounting direction arrows on the circuit board pointing up. (See Figure 1.) Improper orientation can result in heat-induced error.
Figure 1: Mounting Direction Arrows
and Output Jumper Location
Duct Probe Humidity Element
Place the duct probe humidity element in a location that complies with the following:
Position: Designed for duct mounting in any position, except with the probe tip pointed up.
Duct Diameter: Recommended minimum diameter (round ducts) or width (square duct s) is 12 in. (305 mm).
Air Stratification (when the unit is mounted on the discharge side of the fan): Recommended location is at least 8 ft (2.4 m) downstream from humidification equipment, where duct air and water vapor are sufficiently mixed. Avoid areas where the probe may be exposed to condensation.
© 2016 Johnson Controls, Inc. 1 Part No. 24-9527-7, Rev. C www.johnsoncontrols.com
Page 2
Application Setup
0 to 5 VDC
0 to 10 VDC (Factory Set)
Output
Probe
Base
Circuit Boa r d
Cover
Horizontal Faceplate
No. 8
Screw (2)
Vertical
Faceplate
Button-head
Screw (2)
Drywall
Base
Anchor (2)
The element must be configured for the output signal required prior to installation. Proceed to the appropriate element section to change the facto ry setting.
Wall Mount Humidity Element
To set the output jumper, refer to Figure 1. Remove the cover, and position the output jumper to suit the application. Reinstall the cover.
Duct Probe Humidity Element
Refer to Figure 2 to set the output jumper for the application.
Surface
To mount the unit to drywall, refer to Figure 3 and proceed as follows:
Figure 2: Output Jumper Selection
Mounting
Wall Mount Humidity Element
Parts included are:
wall mount humidity element
No. 8 x 1-1/4 in. pan-head tapping screw (2)
plastic drywall anchor (2)
horizontal and vertical faceplates
Tools required are:
1/16 in. (1.5 mm) Allen wrench or
1/4 in. (7 mm) and 1/8 in. (3 mm) flat-blade
drill with 5/16 in. (8 mm) and 1/2 in. (13 mm)
T-4000-119 Allen-head adjustment tool
screwdrivers
drill bits
Figure 3: Mounting to Drywall
1. Loosen the button-head sc rew on both sides of the plastic cover.
2. Pull the cover off the base.
3. Use the base as a template, and mark the holes for the two anchors and the wiring.
4. Drill a 5/16 in. (8 mm) hole for the each anchor.
5. Drill a 1/2 in. (13 mm) hole in the surface where the unit will be mounted, and pull the wiring through the drilled hole.
6. Feed the wiring through the 1/2 in. (13 mm) hole and the circuit board.
7. Mount the base to the wall usin g the anchors and the No. 8 screws.
2 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions
Page 3
Wallbox
* Items in TE-1800-9600 Wall Plate Adaptor Kit
Base
Mounting
Bracket*
Wal l Plate A dapter*
Humidity Transmitter’s
Circuit Board
Cover
Horizontal Fa c eplate
or
Vertical Faceplate
Wallbox
No. 6-32 x 7/8 in. Pan-head
Machine Screw ( 2)*
No. 6-32 x 5/8 in. Pan-head
Machine Screw ( 2)*
To mount the unit to a wallbox, refer to Figure 4 and proceed as follows:
Note: The TE-1800-9600 Wall Plate Adaptor Kit is
required for this mounting method and must be ordered separately. (See Figure 4 and Table 1.)
Figure 4: Mounting to a Wallbox
1. Attach the mounting bracket f rom the wall plate adaptor kit (TE-1800-9600) to the wallbox, using the two No. 6-32 x 7/8 in. pan-head screws included.
2. Feed the wiring through th e mounting bracket, the wall plate adapter, the base, and the hole in the circuit board.
3. Use the No. 6-32 x 5/8 in. pan-head sc rews to secure the base of the humidity element to the wall plate adaptor and the mounting bracket.
Duct Probe Humidity Element
Parts included are:
duct probe humidity element
No 8 x 1 in. Phillips-head sheet metal screw (2)
washer for use with conduit fitting
Note: Conduit fitting and nut are not provided. Tools required are:
hole saw with 1 in. (25 mm) diameter blade
drill with 1/8 in. (3 mm) drill bit
No. 2 Phillips screwdriver
pliers
gasket, sealer, or other material to seal the area
between the unit and the duct
TRUERH Series HE-67xx Humidity Element with Te m perature Sensor Installation Instructions 3
Page 4
Housing
Conduit Hole
Snap-on Cover
Conduit Knockout
(Top and Bott om
of Cover)
Duct
Washer (Cupped Side
Toward Housing)
Conduit Fitting (Not Provided)
Nut for Conduit Fitting
(Not Provided)
No. 8
Screw
(2)
!
T erminal Block TB1
(Humidity Transmitter
Connection)
T erminal Block TB2
(Temperature S en s or
Connection)
Wiring
Opening
UP
UP
Sensor
Sensor
PWR
COM
OUT
Terminal
Wiring
To mount the duct probe humidity element, ref er t o Figure 5 and proceed as follows:
Figure 5: Duct Probe Humidity Element
Assembly and Mounting
1. Remove any excess insulation from the duct that prevents the probe from extending a minimum of 3 in. (76 mm) into the air stream.
2. Use the hole saw to make a 1 in. (25. 4 mm) hole in the duct for inserting the probe.
3. Pull the plastic cover off the housing.
4. Insert the probe into the du ct , and use the housing as a template to mark the location of the holes for the mounting screws.
5. Remove the unit, and drill a 1/8 in. (3 mm) hole for each mounting screw.
Wiring
WARNING: Risk of Electric Shock.
Disconnect the power supply before making electrical connections. Contact wit h compon ents carry ing hazardous voltage can cause electric shock and may result in severe personal inj ury or deat h.
AVERTISSEMENT : Risque de décharge électrique. Débrancher l'alimentation avant de réaliser
tout branchement élect rique. Tout contact av ec des composants conducteurs de tensions dangereuses risque d'entraîner une déc harge él ectriqu e et de provoquer des blessures graves, voire mortelles.
Observe the following when wiring either ty pe of element:
Do not run low voltage wiring in the same conduit as line voltage wiring or other conductors that supply highly inductive loads.
Use 18 or 24 AWG wire.
Make all wiring connections in accordance with t he
National Electrical Code and all local regulations.
Wall Mount Humidity Element
To wire a wall mount model:
1. Connect the wires to the appropriate positions on the terminal block. (See Figure 6.)
IMPORTANT: Remove the unit before drilling to prevent any metal remnants from falling onto the circuit board.
Seal any holes created during installation to help reduce drafts and for more accurate humidity readings.
6. Use a gasket, sealer, or oth er m eans to seal the area around the 1 in. (25.4 mm) hole between the unit and the duct.
7. Reinsert the probe, and se cure the housing to the duct using the two No. 8 screws provided.
4 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions
Figure 6: Wiring the Wall Mount Humidity Element
2. Place the cover over the base, an d tighten the button-head screw (shown in Figure 3) on either side of the unit to secure.
3. Choose the appropriate faceplate (vertical or horizontal), depending on the mounting positio n of the unit.
4. Remove the adhesive-backed paper from the faceplate, and apply to the cover.
Page 5
Label
Output
Selection
0
-
5
V
0
-
1
0
V
P
W
R
C
O
M
O
U
T
T
E
M
P
T
E
M
P
Terminal
Designation
Input 18-30 VAC, 12-30 VD C Ouput 0- 5 or 0-10 VDC
DATE
PAR T NUMBER
Probe
GRD10A-608
Duct Probe Humidity Element
To wire a duct probe model:
1. Route the wires from the controller to the unit through the conduit hole in the housing.
IMPORTANT: If using a conduit fitting (not provided), a washer is provided to support the fitting in the housing. If the washer is not used, the fitting could stress the plastic housing.
2. Break out the appropriat e knockout from the cover (shown in Figure 5) with pliers to accommodate the wiring or conduit if used.
3. Connect the wires to the appropriate terminals of the wiring block. (See Figure 7.)
Troubleshooting
If the humidity element is not functioning properly:
1. Verify the unit is mounted in a locat i on that is indicative of space humidity and temperature (away from drafts, moisture, sunlight, etc.).
2. Use a humidity tester with accuracy greater than the element (±2% between 20 and 80% for 2% models; ±3% between 20 and 80% for 3% models), such as an optical dew point hygrometer, to determine the percent of Relative Humidity (RH).
Note: The humidity tester and the element must
sense the air at the same temperature. Before testing, be sure to wait 30 to 60 minutes for the tester to stabilize to ambient temperature and humidity. A temperature difference of as little as 1F° (0.6C°) can cause a difference in measured RH of over 2.5% RH.
3. Calculate the percent of RH i ndicated by the element as follows:
For 0 to 10 VDC output, multiply the output voltage
by 10. For example: 7.5 VDC x 10 = 75% RH
For 0 to 5 VDC output, multiply the output voltage
by 20. For example: 3.5 VDC x 20 = 70% RH
Note: ±0.9F° (±0.5C°) corresponds to an error of
about ±2% RH at 25°C if RH is at a high level, e.g., 70%.
Figure 7: Wiring the Duct Probe Humidity Element
4. Press the cover onto the base.
4. Compare the RH readings between the humidity tester and the element. If the difference is more than the sum of the allowable errors, replace the element.
Ordering Information
Refer to Table 1 for accessories for the wall mount humidity elements (none for the duct probe models), and contact the nearest Johnson Controls representative.
See Table 2 for product specifications for the humidit y elements.
Table 1: Accessories for the Wall Mount Humidity Elements
Product Code Number Description
Plastic Guard with Baseplate and Mounting Ring
T-4000-119 Allen-head Adjustment Tool (30/ba g) TE-1800-9600 Wall Plate Adaptor Kit required for wallbox mounting
TRUERH Series HE-67xx Humidity Element with Te m perature Sensor Installation Instructions 5
Page 6
T
Current Draw
°
Electrical Connections
3-position and 2-position screw terminal bloc ks
Conditions
Conditions
Shipping Weight
Agency Compliance
European Single Point of Contact:
NA/SA Single Point of Contact:
APAC Single Point of Contact:
Technical Data
Product Power Requirements 14 to 30 VDC or 20 to 30 VAC at 50/60 Hz, Class 2
Acceptable Wire Gauge 16 to 24 AWG wire (18 AWG wire recommended) Humidity Element
at 77
F (25°C)
Temperature Sensors Thin-film Nickel: Accuracy: ±0.34°F (0.18°C) at 70°F (21°C)
Silicon: Accuracy: ±1°F (0.6°C) at 70°F (21°C)
Thin-film Platinum: Accuracy: ±0.65°F at 70°F (±0.36°C at 21°C)
RUERH Series HE-67xx Humidity Element with T emperature Sensor
3 mA with no load, 25 mA maximum
Signal: 0 to 5 VDC or 0 to 10 VDC, 1,000 ohm maximum load Accuracy: HE-67x2: ±2% RH for 20 to 80% RH at 77°F (25°C)
±4% RH for 10 to 20% and 80 to 90% RH at 77°F (25°C) HE-67x3: ±3% RH for 20 to 80% RH at 77°F (25°C) ±5% RH for 10 to 20% and 80 to 90% RH at 77°F (25° C)
Temperature Coefficient: -0.1 to 0.05% RH/°C at 5°C (41°F) t o
-0.07 to -0.21% RH/°C at 65°C (149°F)
Reference Resistance: 1,000 ohms at 70°F (21°C) Resistance Change: Approximately 3 ohms/°F (5 ohms/°C)
Reference Resistance: 1,035 ohms at 77°F (25°C) Resistance Change: Approximately 4 ohms/°F (8 ohms/°C)
Reference Resistance: 1,000 ohms at 32°F (0°C) Resistance Change: Approximately 2 ohms/°F (4 ohms/°C)
Ambient Operating
32 to 140°F (0 to 60°C) 0 to 100% RH, 85°F (29.4°C) maximum dew point
Survival Operating Conditions
Ambient Storage
-20 to 140°F (-29 to 60°C) 0 to 100% RH, 85°F (29.4°C) maximum dew point
-40 to 140°F (-40 to 60°C) 0 to 100% RH, 85°F (29.4°C) maximum dew point
Materials Wall Mount: Beige plastic cover with metal base and metal foil face plates
Duct Probe: White plastic cover with dark gray pl as tic housing and probe
Dimensions Wall Mount (H x W x D): 1.81 x 2.12 x 3.12 in. (46 x 54 x 79 mm)
Duct Probe (H x W x D): 3.28 x 3.25 x 8.27 in. (83 x 83 x 210 mm) Probe (L x D): 6.25 x 0.98 in. (159 x 25 mm)
0.6 lb (0.3 kg) Duct Probe Material: 94-5V flammability rated per UL 94
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
6 TRUERH Series HE-67xx Humidity Element with Temperature Sensor Installation Instructions
Page 7
Building Efficiency
All other marks herein are the marks of t heir respective owners. © 2016 Johnson Controls, Inc.
TRUERH Series HE-67xx Humidity Element with Te m perature Sensor Installation Instructions 7