Installation Instructions HC-67x3 Issue Date June 2, 2014
TRUERH™ Series
HC-67x3 Humidity Controllers
The HC-67x3 Humidity Controllers proportionall y ramp their output as the humidity changes in the proportional band. The setpoint is at the low en d of the proportional band for Direct Acting (DA) and at the high end for Reverse Acting (RA) (shown in Figure 1) for both wall mount and duct probe humidity controllers.
Figure 1: 0 to 10 Volt, RA Application
Configure the controller prior to installation for the following: setpoint, proportional band, ac tion, and output signal. Proceed to the appropriate cont roller section.
Installation
IMPORTANT: The HC-67x3 Series Humidity
Controllers is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the HC-67x3 Series Humidity Controllers could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or prot ect against failure or malfunction of the HC-67x3 S eries Humidity Controllers.
IMPORTANT: Le HC-67x3 Series Humidity Controllers est destiné à transmettre des données entrantes à un équipement dans des condition s normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du HC-67x3 Series Humidity Controllers risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection sup pl ém entaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du HC-67x3 Series Humidity Controllers.
© 2014 Johnson Controls, Inc. 1 Part No. 24-7701-179, Rev. A www.johnsoncontrols.com
The controller is available in both a wall mount or duct probe package to suit a variety of sensing application needs. Refer to the Mounting section for a complete list of the tools required for installation.
Parts Included
mounting base for U.S. wallbox or surface mounting
No. 6-32 x 7/8 in. oval-head screw (2)
No. 4-40 x 1/4 in. hex-head cover screw (in the
mounting base)
drywall clip mounting kit (includes two each No. 6-20 x 1.25 in. pan-head tapping screws, spring clips, and spacers)
Page 2
Product Code Number
Description
TE-67D0-602**
Door Replacement Kit without logo
** Contains 10 original style and 10 new style doors.
BaseCover
1. Loosen (do no t remove) the cover screw with a 1/16 in. (1.5 mm) Allen wrench.
2. Swing the cover down from the base.
No. 6
Screws
Cover Screw
Accessories
Table 1: Accessories and Replacement Parts for the Wall Mount Humidity Controller
ACC-DWCLIP-0 ACC-INSL-0* ACC-INSL-1* GRD10A-608 T-4000-119 TE-67MB-600 TE-67D0-601**
* These foam pads help prevent drafts from entering the unit through the wall and make installation easier when mounting on an uneven surface.
Drywall Clip Mounting Kit (10/bag) Wallbox Mounting Pad (10/bag) Surface Mounting Pad (10/bag) Plastic Guard with Baseplate and Mounting Ring Allen-head Adjustment Tool (30/ba g) Mounting Base Kit Door Replacement Kit with Johnson Controls logo
Mounting
Location Considerations
IMPORTANT: To avoid damage to the
circuit board and components, do not mount the unit in a location where high concentrations of corrosive vapors are present.
The HC-67x3 controller is shipped with one mounting base for both surface and wallbox mounting. To mount the HC-67x3, release the cover from the base as described in Figure 2.
be careful not to drop or mount the unit where it coul d be exposed to excessive vibration. The following am bi ent operating conditions apply:
Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0 to 100% Relative Humidity (RH),
non-condensing; 85°F (29°C) maximum dew point
To mount the HC-67x3 to a wallbox:
1. Pull the cable or wiring through the wallbox and base.
2. Rotate the mounting base, so one of the arrows on the base points up.
Figure 2: Removing the Cover from the Base
Wallbox Mounting: Special Tools Needed
Use a 1/16 in. (1.5 mm) Allen wrench or T-4000-119 Allen-head adjustment tool for mounting.
Wallbox Mounting: Location Considerations
Locate the humidity transmitter on an inside wall, free from drafts, and out of direct sunlight. The HC-67x3 is shock and vibration resistant ; however,
2 TRUERH Series HC-67x3 Humidity Controllers Installation Instructions
3. Fasten the base to the wallbox with the No. 6 screws provided. (See Figure 3.)
Note: These instructions assume a standard 2 x 4 in. (52 x 104 mm) U.S. wallbox is used.
Figure 3: Wallbox Mounting
4. Place the bottom edge of the cover against the bottom lip of the base, and rotate it up ont o the base. (See Figure 4.)
5. Tighten the cover screw.
Page 3
Base
Cover Screw
Cover
Base
Cover Screw
Cover
Figure 4: Attaching the Cover to the Base
Note: Once installed, the unit cannot be remov ed
from the wall unless the cover screw is loosene d as described in Figure 2.
IMPORTANT: Seal the drilled hole or use an ACC-INSL-0 Foam Pad Kit to help reduce drafts entering the unit. (See Table 1.) Drafts could result in false readings.
needed as shown in Figure 6. Do not use the spacers for 5/8 in. (16 mm) drywall.
Note: For replacement spring clips, spacers, and screws, order the ACC-DWCLIP-0 Drywall Clip Mounting Kit. (See Table 1.)
Surface Mounting: Special Tools Needed
hole saw with 1-3/8 in. (35 mm) diameter blade
1/16 in. (1.5 mm) Allen wrench or
T-4000-119 Allen-head adjustment tool
drill with 1/8 in. (3 mm) drill bit To mount the surface model to drywall, refer to
Figure 6 and proceed as follows:
1. Bend the top and bottom edges of mounting base at the perforations until they break of f. (See Figure 5.)
2. Drill a 1-3/8 in. (35 mm) hole in the surf ace where the unit is to be mounted, and pull the wiring through the drilled hole.
3. Mark the location of the two mounting screws, and drill the holes.
4. Insert the spring clips on each side of the drilled 1-3/8 in. (35 mm) hole, and use the spacers if
Figure 5: Removing the Breakaway Tabs
5. Pull the wiring through the base of the unit.
6. Center the two holes in the base over the two drilled holes, and fasten the base to the drywall using t he No. 6 screws provided. (See Figure 6.)
7. Place the bottom edge of the cover against the bottom lip of the base, and rotate it up onto the base as shown in Figure 4.
8. Tighten the cover screw.
9. Once installed, the HE-67xx cannot be removed from the wall unless the cover screw is loosene d as described in Figure 2.
IMPORTANT: To prevent drywall damage, do not overtighten the screws.
TRUERH Series HC-67x3 Humidity Controllers Instal lation Instructions 3
Page 4
1-3/8 in. (35 mm)
Hole
Drywall
Spacer (2) for
3/8 in. (9.5 mm) and 1/2 in.
(12.7 mm ) Thick Drywall
1-3/8 in.
(35 mm)
Hole
Spring Clip (2)
Drywall
Drywall
Spring
Clip (2)
Base
No. 6-20 x 1.25 in.
Pan-head
Tapping Screw (2)
Housing
Conduit Hole
Snap-on Cover
Conduit Knockout
(Top and Bottom
of Cover)
Duct
Washer (Cup ped Side
Toward Hou s i n g)
Conduit Fitting (Not Provided)
Nut for Conduit Fitting
(Not Provided)
No. 8
Screw
(2)
Figure 6: Surface Mounting to Drywall
Duct Probe Humidity Controller: Parts Included
HC-6703-6N00P duct probe humidity controlle r
No. 8 x 1 in. Phillips-head sheet metal screw (2)
washer for use with conduit fitting
Note: Conduit fitting and nut are not provided. Duct Probe Humidity Controller:Special Tools
Needed
hole saw with 1 in. (25 mm) diameter blade
2. Use the hole saw to make a 1 in. (25.4 mm) hole in the duct for inserting the probe.
3. Pull the plastic cover off the housing.
drill with 1/8 in. (3 mm) drill bit
1/8 in. (3 mm) flat-blade and No. 2 Phillips
screwdrivers
pliers
gasket, sealer, or other material to seal t he area
between the unit and the duct
Duct Probe Mounting Location Considerations
Place the duct probe humidity controller in a locati on that complies with the following:
Position: Designed for duct mounting in any position, except with the probe tip pointed up.
Duct Diameter: Recommended minimum di am eter (round ducts) or width (square ducts) is 12 i n. (305 mm).
Air Stratification (when the unit is mounted on t he discharge side of the fan): Recommended location is at least 8 ft (2.4 m) downstream from the humidification equipment, where duct ai r and water vapor are sufficiently mixed. Avoid areas where the probe may be exposed to condensation.
To mount the duct probe humidity controller, ref er to Figure 7, and proceed as follows:
1. Remove any excess insulation from the duct that prevents the probe from extending a minimum of 3 in. (76 mm) into the air stream.
4 TRUERH Series HC-67x3 Humidity Controllers Installation Instructions
4. Insert the probe into the duct, and mark the
5. Remove the unit, and drill a 1/8 in. (3 mm) hole for
6. Use a gasket, sealer, or other means to seal the
7. Reinsert the probe, and secure the housing to the
Figure 7: Mounting and Assembly
location of the holes for the mounting screws.
each mounting screw.
IMPORTANT: Remove the unit before drilling to prevent any metal remnants from falling ont o the circuit board. Seal any holes created during installation to help reduce drafts and for more accurate humidity readings.
area around the 1 in. (25.4 mm) hole between the unit and the duct.
duct using the two No. 8 screws provided.
Page 5
!
Proportional
Band
Potentiometer
Output Common Power
20
15
10
5 2
6 to 9 VDC
0 to 10 VDC (Factory Set)
Output
Reverse (Factory Set)
Direct
Action
Setpoint
40
60
80
SP
20
Proportional Band
PB
5
2
20
15
10
Power Ground (Common) Output
Probe
Setpoint
Adjustment
Lever
Quick-mount
Installation Base
Pull Tab
Access Door
Manual Override
LED Dis play
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE: Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Make all wiring connections using No. 18 AWG wire and in accordance with the National Electrical Code and all local regulations.
Wall Mount Humidity Controller
To wire the wall mount model, refer to Figure 8, and proceed with the terminal connections.
Figure 9: Settings on a Duct Probe
Humidity Controller
Figure 8: Wiring and Proportional Band Setting
Duct Probe Humidity Controller
To wire the duct probe model, refer to Figure 9, and proceed as follows:
IMPORTANT: If using a conduit fitting (not provided), use the washer provided to support the fitting in the housing. If the washer is not used, the fitting could stress the plastic housing.
1. Route the wires from the equipment to the unit through the conduit hole in the housing shown in Figure 7.
2. Break out the appropriate knockout from the cover, shown in Figure 7, using pliers to accommodate the wiring or conduit.
3. Press the cover onto the base.
Setup and Adjustments
Wall Mount Humidity Controller
Setpoint
Adjust the setpoint using the setpoint adj ust m ent lever shown in Figure 10. To open the access door, push down on the pull-tab, and pull the door open.
IMPORTANT: To prevent unauthorized adjustment of the setpoint, install an optional plastic guard. (See Table 1 for ordering informat i on.)
Figure 10: Accessing the Setpoint
TRUERH Series HC-67x3 Humidity Controllers Instal lation Instructions 5
Page 6
Disengage the tabs
to remove the
circuit board.
Reverse (Factory Set)
Direct
Action
0 to 10 VDC (Factory Set)
6 to 9 VDC
Output
Circuit Bo ar d
Disengage the tabs
to remove the
circuit board.
Reverse (Factory Set)
Direct
Action
0 to 10 VDC (Factory Set)
6 to 9 VDC
Output
Circuit Bo ar d
Jumpers
To set the jumpers, refer to Figure 11. Turn the circuit board over, and position the action and output j um pers to suit the application. Reinstall the circuit board.
Figure 11: Jumper Settings
Proportional Band
To set the proportional band, see Figure 8. Use a 1/8 in. (3 mm) flat-blade screwdriver to turn the potentiometer to the position desired.
Duct Probe Humidity Controller
Setpoint, Proportional Band, and Jumpers
Refer to Figure 9 to change the setpoint, proportional band, or the action and output jumpers for the application desired.
1. Use a 1/8 in. (3 mm) flat-blade screwdriver to turn the setpoint or proportional band potentiometer to the desired setting.
2. Select the appropriate control action and output setting using the jumpers.
Troubleshooting
If the humidity controller is not functioni ng properly:
1. Verify the unit is mounted in a location that is indicative of space humidity (away from drafts and sunlight, for example).
2. Check all supply voltage connections, and make sure the wiring is correct. (Refer to Figure 8 and Figure 9.)
3. Check the proportional band and setpoint settings. If the humidity control equipment is cycling excessively, the proportional band setting may be too low.
4. Verify the jumper positions. If the unit is not delivering an output, make sure the jumpers are appropriately selected for the application.
5. Replace the unit if the troubleshooting suggestions fail to remedy the problem.
Repairs and Replacement
The HC-67x3 units are not field repairable. As with any electrical device, keep the air vents clean and free from dust or obstruction. The HC-67x3 controlle rs have been designed for maintenance-free operat i on. Sturdy packaging, solid-state components, and high-quality element construction combine for a long-lasting, high performance sensor. To order replacement parts, contact the nearest Johnson Controls representative.
6 TRUERH Series HC-67x3 Humidity Controllers Installation Instructions
Page 7
Product
T
RH Series HC-67x3 Humidity Controllers
Power Requirements
Control Action
Jumper selectable, direct or revers e ( factory set for reverse acting)
Output Range
impedance
Proportional Band: Adjustable from 2 to 20% RH
Temperature Coefficient
-0.1 to 0.05% RH/°C at 5°C (41°F) to -0.07 to -0.21% RH/°C at 65°C (149°F)
Electrical Connections
3-position screw terminal block
Conditions
Survival Operating
Ambient Storage
Conditions
-40 to 176°F (-40 to 80°C) 0 to 100% RH, non-condensing; 85°F ( 29°C) m axim um de w point
Materials
Dimensions
Wall Mount (H x W x D): 3.20 x 3.20 x 1 .34 in. (81 x 81 x 34 mm)
Building Efficiency
Technical Specifications
14 to 30 VDC at 10 mA or 20 to 30 VAC, 50/60 Hz at 15 mA with no load, Class 2
Jumper selectable, 0 to 10 VDC (factory set) or 6 to 9 VDC; 5 k ohm minimum load
RUE
Humidity
Element: All-Polymer™ element Sensing Range: 0 to 100% RH, non-condensing Setpoint: Adjustable from 20 to 80% RH
Ambient Operating
32 to 122°F (0 to 50°C) 0 to 100% RH, non-condensing; 85°F (29° C) maximum dew point
-22 to 140°F (-30 to 60°C)
Conditions
0 to 100% RH, non-condensing; 85°F (29°C ) maximum dew point
Wall Mount: White plastic enclosure for surf ac e or wallbox mounting, including hardware Duct Probe: Light gray plastic cover with dark gray plastic housing and probe
Duct Probe (H x W x D): 3.25 in. x 3.25 in. x 8.27 in. (83 mm x 83 mm x 210 mm) Probe (L x D): 6.25 in. x 0.98 in. (159 mm x 25 mm)
Shipping Weight
Agency Compliance
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
0.7 lb (0.3 kg) Duct Probe Material: 94-5 V flammability rated per UL 94
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of t heir respective owners. © 2014 Johnson Controls, Inc.
TRUERH Series HC-67x3 Humidity Controllers Instal lation Instructions 7