Note: The actual output
voltage may exceed 10 VDC.
Installation Instructions HC-67x3
Issue Date June 2, 2014
TRUERH™ Series
HC-67x3 Humidity Controllers
Application Requirements
The HC-67x3 Humidity Controllers proportionall y
ramp their output as the humidity changes in the
proportional band. The setpoint is at the low en d of
the proportional band for Direct Acting (DA) and at
the high end for Reverse Acting (RA) (shown in
Figure 1) for both wall mount and duct probe
humidity controllers.
Figure 1: 0 to 10 Volt, RA Application
Configure the controller prior to installation for the
following: setpoint, proportional band, ac tion, and
output signal. Proceed to the appropriate cont roller
section.
Installation
IMPORTANT: The HC-67x3 Series Humidity
Controllers is intended to provide an input to
equipment under normal operating conditions. Where
failure or malfunction of the HC-67x3 Series Humidity
Controllers could lead to personal injury or property
damage to the controlled equipment or other property,
additional precautions must be designed into the
control system. Incorporate and maintain other
devices, such as supervisory or alarm systems or
safety or limit controls, intended to warn of or prot ect
against failure or malfunction of the HC-67x3 S eries
Humidity Controllers.
IMPORTANT:Le HC-67x3 Series Humidity
Controllers est destiné à transmettre des données
entrantes à un équipement dans des condition s
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du HC-67x3 Series Humidity
Controllers risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle doit
intégrer des dispositifs de protection sup pl ém entaires.
Veiller dans ce cas à intégrer de façon permanente
d'autres dispositifs, tels que des systèmes de
supervision ou d'alarme, ou des dispositifs de sécurité
ou de limitation, ayant une fonction d'avertissement ou
de protection en cas de défaillance ou de
dysfonctionnement du HC-67x3 Series Humidity
Controllers.
The controller is available in both a wall mount or duct
probe package to suit a variety of sensing application
needs. Refer to the Mounting section for a complete list
of the tools required for installation.
Parts Included
• mounting base for U.S. wallbox or surface mounting
• No. 6-32 x 7/8 in. oval-head screw (2)
• No. 4-40 x 1/4 in. hex-head cover screw (in the
mounting base)
•drywall clip mounting kit (includes two each
No. 6-20 x 1.25 in. pan-head tapping screws, spring
clips, and spacers)
Product Code Number
Description
TE-67D0-602**
Door Replacement Kit without logo
** Contains 10 original style and 10 new style doors.
BaseCover
1. Loosen (do no t
remove) the cover
screw with a 1/16 in.
(1.5 mm) Allen
wrench.
2. Swing the cover
down from the
base.
No. 6
Screws
Cover
Screw
Accessories
Table 1: Accessories and Replacement Parts for the Wall Mount Humidity Controller
* These foam pads help prevent drafts from entering the unit through the wall and make installation easier when mounting
on an uneven surface.
Drywall Clip Mounting Kit (10/bag)
Wallbox Mounting Pad (10/bag)
Surface Mounting Pad (10/bag)
Plastic Guard with Baseplate and Mounting Ring
Allen-head Adjustment Tool (30/ba g)
Mounting Base Kit
Door Replacement Kit with Johnson Controls logo
Mounting
Location Considerations
IMPORTANT: To avoid damage to the
circuit board and components, do not mount the
unit in a location where high concentrations of
corrosive vapors are present.
The HC-67x3 controller is shipped with one
mounting base for both surface and wallbox
mounting. To mount the HC-67x3, release the cover
from the base as described in Figure 2.
be careful not to drop or mount the unit where it coul d be
exposed to excessive vibration. The following am bi ent
operating conditions apply:
• Temperature: 32 to 122°F (0 to 50°C)
• Humidity: 0 to 100% Relative Humidity (RH),
non-condensing; 85°F (29°C) maximum dew point
To mount the HC-67x3 to a wallbox:
1. Pull the cable or wiring through the wallbox and
base.
2. Rotate the mounting base, so one of the arrows on
the base points up.
Figure 2: Removing the Cover from the Base
Wallbox Mounting: Special Tools Needed
Use a 1/16 in. (1.5 mm) Allen wrench or
T-4000-119 Allen-head adjustment tool for
mounting.
Wallbox Mounting: Location Considerations
Locate the humidity transmitter on an inside wall,
free from drafts, and out of direct sunlight. The
HC-67x3 is shock and vibration resistant ; however,
2 TRUERH Series HC-67x3 Humidity Controllers Installation Instructions
3. Fasten the base to the wallbox with the
No. 6 screws provided. (See Figure 3.)
Note: These instructions assume a standard
2 x 4 in. (52 x 104 mm) U.S. wallbox is used.
Figure 3: Wallbox Mounting
4. Place the bottom edge of the cover against the
bottom lip of the base, and rotate it up ont o the
base. (See Figure 4.)
5. Tighten the cover screw.
Base
Cover
Screw
Cover
Base
Cover
Screw
Cover
Figure 4: Attaching the Cover to the Base
Note: Once installed, the unit cannot be remov ed
from the wall unless the cover screw is loosene d as
described in Figure 2.
IMPORTANT: Seal the drilled hole or use an
ACC-INSL-0 Foam Pad Kit to help reduce drafts
entering the unit. (See Table 1.) Drafts could result
in false readings.
needed as shown in Figure 6. Do not use the
spacers for 5/8 in. (16 mm) drywall.
Note: For replacement spring clips, spacers, and
screws, order the ACC-DWCLIP-0 Drywall Clip Mounting
Kit. (See Table 1.)
Surface Mounting: Special Tools Needed
• hole saw with 1-3/8 in. (35 mm) diameter blade
• 1/16 in. (1.5 mm) Allen wrench or
T-4000-119 Allen-head adjustment tool
•drill with 1/8 in. (3 mm) drill bit
To mount the surface model to drywall, refer to
Figure 6 and proceed as follows:
1. Bend the top and bottom edges of mounting
base at the perforations until they break of f.
(See Figure 5.)
2. Drill a 1-3/8 in. (35 mm) hole in the surf ace
where the unit is to be mounted, and pull the
wiring through the drilled hole.
3. Mark the location of the two mounting screws,
and drill the holes.
4. Insert the spring clips on each side of the drilled
1-3/8 in. (35 mm) hole, and use the spacers if
Figure 5: Removing the Breakaway Tabs
5. Pull the wiring through the base of the unit.
6. Center the two holes in the base over the two drilled
holes, and fasten the base to the drywall using t he
No. 6 screws provided. (See Figure 6.)
7. Place the bottom edge of the cover against the
bottom lip of the base, and rotate it up onto the base
as shown in Figure 4.
8. Tighten the cover screw.
9. Once installed, the HE-67xx cannot be removed
from the wall unless the cover screw is loosene d as
described in Figure 2.
IMPORTANT: To prevent drywall damage, do
not overtighten the screws.
TRUERH Series HC-67x3 Humidity Controllers Instal lation Instructions 3