Functional Devices, Inc.
TR100VA001US
Transformer 96 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount
1.510"
2.550"
3.500"
Specications
VA Rating:
Frequency:
Mounting:
Over Current Protection:
Dimensions:
Wire Length:
Operating Temperature:
MTBF:
Construction:
Weight:
Approvals:
Blk
PRIMARY WIRES SECONDARY WIRES
120V 60Hz 24Vac 100VA
2.000"
Mounting Hole =
.50" x .188"
9.50"
.50"
Wht
Secondary Yel/Wht wire in phase with Primary Blk wire.
2.500"
96
50/60 Hz
Foot & Single Threaded Hub
Circuit Breaker
3.250˝ x 2.500˝ x 3.500˝
(w/ .500˝ NPT Hub)
9.5˝ Typical w/ .5˝ Strip
-30 to 140° F
100,000 Hours @ 77° F
Split-Bobbin
4.06 lbs.
Class 2 UL5085-3 Listed, C-UL, CE, RoHS
Yel/Wht
Yel
3.250"
CB
Transformer
Made in USA
Meets
“Buy American”
of ARRA 2009