Johnson Controls TMZ1600 Installation Instructions Manual

Installation Instructions Issue Date April 12, 2006
Room Sensor with LCD Display (TMZ1600)

Application

The TMZ is compatible with Unitary (UNT) controller and Variable Air Volume (VAV) (Revision D or later) controller and with the VAV for Modular Assembly (VMA1400 Rev. C00 or later and all VMA1200s). Use HVAC PRO Release 8.01 or later to configure the UNT, VAV, and VMA for use with the TMZ. Refer to the Technical Data section for details.
The TMZ connects to the controller via an 8-pin phone jack cable assembly that provides Zone Bus, sensor, and power supply connections.
When the TMZ is used with a compatible Johnson Controls digital controller, verify proper system operation using a Zone Terminal Unit (ZTU), a laptop computer with CBLPRO and HVAC PRO software, or a Palm compatible handheld interface with VMA Balancing Tool (VBT) software.
Both the ZTU and CBLPRO plug into the 6-pin phone jack on the bottom of the TMZ to access the Zone bus.
80 mm
80 mm
(3.2 in.)
(3.2 in.)
RM AIR
OCC
Figure 1: TMZ1600
Segmented
Display
Light-Emitting
Diode (LED)
Temporary
Occupancy
Button
inst

Installation

Install the TMZ in an accessible location where the temperature is representative of general room conditions. Avoid mounting the TMZ near cold or warm air drafts, radiant heat, or direct sunlight.
IMPORTANT: Prevent any statis electric discharge to the TMZ1600 Room Sensor. Static electric discharge can damage the room sensor and void any warranties.
Note: Do not mount the module on an exterior wall.

Parts Included

The following parts are included with the TMZ:
TMZ1600 Room Sensor with Liquid Crystal Display (LCD)
surface base
wallbox mount base (wallplate) with cover screw
(for vertical or horizontal 2 x 4 in. wallbox mounting)
endcaps (2)
hollow plasti c wall anchors (2)
No. 8 x 1-1/4 in. slotted pan-head sheet metal
screws (2), for surface base
No. 6-32 x 1/2 in. flat-head machin e screws (2), for wallplate

Special Tools Needed

For a typical installation, you need the following:
1.5 mm (1/16 in.) Allen wrench o r stat adjustment tool
1/4 in. flat-blade screwdriver
8 mm (5/16 in.) drill bit and drill
© 2006 Johnson Controls, Inc. Part No. 24-8910-7, Rev. C www.johnsoncontrols.com Code No. LIT-6363110
1

Mounting

The TMZ accommodates both surface and 2 x 4 in. wallbox mounting (horizontal or vertical). To mount the TMZ, first remove the base.

Removing the Base

To remove the base from the TMZ:
1. Insert a 1.5 mm (1/16 in.) Allen wrench in the hole located in the top of the TMZ, in the center.
2. Press down gently on the Allen wrench while carefully pulling the mounting base apart from the TMZ.
3. Proceed to the Surface Mounting or Wallbox Mounting section.
31.7 mm (1.25 in.)
7.5 mm
(0.30 in.)
6 mm
(0.24 in.)

Surface Mounting

To mount the TMZ using the surface base:
1. Pull the wiring through the wall.
2. Place the surface base against the wall with the arrow pointing up, and mark the screw holes using the base as a template. Use the top and bottom
Figure 2).
Note:
4.2 mm
(0.17 in.)
holes for mounting (
Do not use t his hole when mountin g the surface base. The screw will inter fere wit h the ins tallati on of the TMZ1600.
8.2 mm (0.32 in.)
4.2 mm
(0.17 in.)
7.5 mm
(0.30 in.)
Use these holes for mounting.
UP
4.2 mm
(0.17 in.)
Figure 2: Surface Base
9.1 mm
(0.36 in.)
8.5 mm
(0.33 in.)
60.9 mm (2.40 in.)
30 mm
(1.18 in.)
surfbase
3. Drill two 8 mm (5/16 in.) holes at the locations you marked.
Note: An ACC-INSL-1 surface mounting pad may be used between the mounting base and the dry wall to accommodate uneven mounting surfaces or block wall drafts.
2 Room Sensor with LCD Display (TMZ1600) Installation Instructions
4. Insert the anchors in the drilled holes, pull the wiring through the surface base, position the surface base, and drive the screws (
Drywall
Figure 3).
e
s
a B
a
b
cb
Figure 3: Mounting the Surface Base

1. 5. Wire the TMZ (refer to the Wiring section in this document).

2. 6. Reattach the TMZ to the surface-mount base.

Wallbox Mounting

To mount the TMZ using the wallplate and a standard 2 x 4 in. wallbox:
1. Remove the cover screw from the wallplate
Figure 4).
(
2. Pull the wiring through the wallplate.
3. Position the wallplate so that one of the arrows points up, and fasten the wallplate to the wallbox using the screws provided.
Note: An ACC-INSL-0 wallbox mounting pad may be used between the mounting base and the dry wall to accommodate uneven mounting surfaces or block wall drafts.
surfmount
80 mm
(3.15 in.)
P U
UP
119 mm
(4.70 in.)
wallbse
Figure 4: Wallplate (Shown Vertical)
Cover Scre w (Insert the cover screw above the other UP arrow for horizontal mounting.)
Use these holes for mounting to wallbox.
4. Wire the TMZ (refer to the Wiring section in this document).
5. Attach the TMZ to the wallplate, and replace and tighten the cover screw with a 1.5 mm (1/16 in.) Allen wrench or stat adjustment tool.
3. 6. Install the endcaps provided by snapping them onto the wallplate.
Room Sensor with LCD Display (TMZ1600) Installation Instructions 3
Wiring
!
CAUTION: Risk of Property Damage.
Do not run low voltage cable in the same conduit or wiring troughs with high voltage wires. Running low and high voltage wires in the same conduit or wiring troughs may damage the equipment or cause system malfunction.
Table 1 describes the pinouts for each phone jack on the TMZ.
Table 1: TMZ Phone Jack Pinouts
8-Pin Phone Jack on
TMZ
Pin Signal Pin Signal
6-Pin Phone Jack on
TMZ
Note: All terminals are power limited. Electrical
wiring must conform to local codes and should be done by certified personnel only.
To connect the TMZ to a UNT, VAV, or VMA controller, connect an 8-pin phone jack cable assembly from the 8-pin phone jack on the TMZ
Figure 5) to the 8-pin phone jack on the controller.
(
C17
D5
C16
8-pin
Phone
Jack
6-pin
Phone
Jack
C9
+
VR1
To ZTU or Laptop PC via CBLPR O Interface
L1
U5
D4
D6
C6
J5
Z1
D2
Q1
RT1
(30 m [100 ft] Maxim um )
J1
U2
C8
C4
Q4
U4
R28
D7
D8
D9
Y2
Q3
Y1
Q2
J6
tmzwire
T o 8-pin
Phon e Jack on Controller (30 m [100 ft]
Maximum)
Figure 5: TMZ1600 Cable Connections
!
CAUTION: Risk of Property Damage.
Do not insert a 6-pin connector or anything other than an RJ-45 8-pin connector into the 8-pin jack on the back of the TMZ1600 Room Sensor to prevent damaging the phone jack..
1 Not Used 1 Not Used 2 Not Used 2 Supply: 24 VAC 3 AI1, Zone
Temperature Sensor
3 Supply/Zone Bus
Common
4 AI1, Sensor Common 4 Not Used 5 Supply: 24 VAC 5 Zone Bus 6 Supply/Zone Bus
6 Not Used
Common
7 Not Used 8 Zone Bus
Figure 6 illustrates the cable and phone jack pinouts used to connect the TMZ to a controller:
8
Controller Phone Plug
7
(Tab Notch Up)
6 5
4 3
d
d
e
e
s U
t
o N
M
s
1
O
I
U
C
A
t
I
o
A
N
1 2 3 4 5 6 7 8
TMZ160 0 Phone Pl ug
(Tab Notch Up)
d
n
e
o
ly
s
p
p
u S
+
m
U
B
m
t
Z
o
o
C
N
2 1
8-Pin Pho ne Jack
(Tab Notch Down)
Termi nal 1 is to the extreme left as you face the phone jack ope ning, tab not c h down.
cblfab
Note: This may not be typical of prefabricated phone cable. A telephone system cable is wired opposite of the zone sensor requirements.
Figure 6: Cable and Phone Jack Pinouts
4 Room Sensor with LCD Display (TMZ1600) Installation Instructions

Operation

A

Basic Operation

The TMZ1600 has five control buttons. Their basic functions are described in
Table 2.
Table 2: TMZ1600 Button Functions
Button Function
Menu Cycles through the following display options: room air temperature, outdoor air temperature, comfort
setpoint temperature, and fan operation. In Password mode*, cycles through these additional display options: comfort setpoint temperature access
status, fan access status, Temporary Occupancy duration, heating setpoint temperature, and cooling setpoint temperature.
Down Arrow
Up Arrow
°F/°C Toggles temperature display between degrees Fahrenheit (°F) and degrees Celsius (°C). Temporary
Occupancy
* Press and hold the Menu and °F/°C buttons simultaneously for 10 seconds to access Password mode.

LCD Display Symbols

Figure 7 shows the relative size and location of the LCD Display symbols:
Displays the comfort setpoint temperature if pushed while room air temperature is displayed. Lowers the setpoint temperature when setpoint is displayed and blinking. Toggles fan operation mode between On and Auto when the fan mode is displayed and blinking. In Password mode*, sets user access to UnLK. Displays the comfort setpoint temperature if pushed while room air temperature is displayed. Raises the setpoint temperature when the setpoint is displayed and blinki ng. Toggles fan operation mode between On and Auto when the fan mode is displayed and blinking. In Password mode*, sets user access to LOCK.
Toggles the controller between Standby or Unoccupied mode and Tempora ry Occupancy mode. The Light­Emitting Diode (LED) above this button lights when Temporary Occupancy mode is active.
During power up, the full range of LCD Display symbols appears for approximately 10 seconds or more, followed by Err6 if the controller has not started
OUT RM
IR
OFF
TMP
-
UN OCC SBy
communication yet. The TMZ repeats this sequence until the default display (RM AIR) appears.
Table 3 describes the LCD display symbols.
Figure 7: LCD Display Symbols
Room Sensor with LCD Display (TMZ1600) Installation Instructions 5