Installation Instructions Issue Date April 12, 2006
Room Sensor with LCD Display (TMZ1600)
Application
The TMZ is compatible with Unitary (UNT) controller
and Variable Air Volume (VAV) (Revision D or later)
controller and with the VAV for Modular Assembly
(VMA1400 Rev. C00 or later and all VMA1200s). Use
HVAC PRO Release 8.01 or later to configure the
UNT, VAV, and VMA for use with the TMZ. Refer to
the Technical Data section for details.
The TMZ connects to the controller via an 8-pin phone
jack cable assembly that provides Zone Bus, sensor,
and power supply connections.
When the TMZ is used with a compatible
Johnson Controls digital controller, verify proper
system operation using a Zone Terminal Unit (ZTU), a
laptop computer with CBLPRO and HVAC PRO
software, or a Palm™ compatible handheld interface
with VMA Balancing Tool (VBT) software.
Both the ZTU and CBLPRO plug into the 6-pin phone
jack on the bottom of the TMZ to access the Zone bus.
80 mm
80 mm
(3.2 in.)
(3.2 in.)
RM
AIR
OCC
Figure 1: TMZ1600
Segmented
Display
Light-Emitting
Diode
(LED)
Temporary
Occupancy
Button
inst
Installation
Install the TMZ in an accessible location where the
temperature is representative of general room
conditions. Avoid mounting the TMZ near cold or warm
air drafts, radiant heat, or direct sunlight.
IMPORTANT: Prevent any statis electric
discharge to the TMZ1600 Room Sensor. Static
electric discharge can damage the room sensor and
void any warranties.
Note: Do not mount the module on an exterior wall.
Parts Included
The following parts are included with the TMZ:
•TMZ1600 Room Sensor with Liquid Crystal
Display (LCD)
• surface base
• wallbox mount base (wallplate) with cover screw
(for vertical or horizontal 2 x 4 in. wallbox
mounting)
• endcaps (2)
• hollow plasti c wall anchors (2)
• No. 8 x 1-1/4 in. slotted pan-head sheet metal
screws (2), for surface base
•No. 6-32 x 1/2 in. flat-head machin e screws (2), for
wallplate
Special Tools Needed
For a typical installation, you need the following:
•1.5 mm (1/16 in.) Allen wrench o r stat adjustment
tool
The TMZ accommodates both surface and 2 x 4 in.
wallbox mounting (horizontal or vertical). To mount the
TMZ, first remove the base.
Removing the Base
To remove the base from the TMZ:
1. Insert a 1.5 mm (1/16 in.) Allen wrench in the hole
located in the top of the TMZ, in the center.
2. Press down gently on the Allen wrench while
carefully pulling the mounting base apart from the
TMZ.
3. Proceed to the Surface Mounting or Wallbox Mounting section.
31.7 mm
(1.25 in.)
7.5 mm
(0.30 in.)
6 mm
(0.24 in.)
Surface Mounting
To mount the TMZ using the surface base:
1. Pull the wiring through the wall.
2. Place the surface base against the wall with the
arrow pointing up, and mark the screw holes using
the base as a template. Use the top and bottom
Figure 2).
Note:
4.2 mm
(0.17 in.)
holes for mounting (
Do not use t his hole when mountin g
the surface base. The screw will
inter fere wit h the ins tallati on of the
TMZ1600.
8.2 mm (0.32 in.)
4.2 mm
(0.17 in.)
7.5 mm
(0.30 in.)
Use these holes for mounting.
UP
4.2 mm
(0.17 in.)
Figure 2: Surface Base
9.1 mm
(0.36 in.)
8.5 mm
(0.33 in.)
60.9 mm
(2.40 in.)
30 mm
(1.18 in.)
surfbase
3. Drill two 8 mm (5/16 in.) holes at the locations you
marked.
Note: An ACC-INSL-1 surface mounting pad may be
used between the mounting base and the dry wall to
accommodate uneven mounting surfaces or block wall
drafts.
2 Room Sensor with LCD Display (TMZ1600) Installation Instructions
4. Insert the anchors in the drilled holes, pull the
wiring through the surface base, position the
surface base, and drive the screws (
Drywall
Figure 3).
e
s
a
B
a
b
cb
Figure 3: Mounting the Surface Base
1. 5. Wire the TMZ (refer to the Wiring section in
this document).
2. 6. Reattach the TMZ to the surface-mount base.
Wallbox Mounting
To mount the TMZ using the wallplate and a standard
2 x 4 in. wallbox:
1. Remove the cover screw from the wallplate
Figure 4).
(
2. Pull the wiring through the wallplate.
3. Position the wallplate so that one of the arrows
points up, and fasten the wallplate to the wallbox
using the screws provided.
Note: An ACC-INSL-0 wallbox mounting pad may be
used between the mounting base and the dry wall to
accommodate uneven mounting surfaces or block wall
drafts.
surfmount
80 mm
(3.15 in.)
P
U
UP
119 mm
(4.70 in.)
wallbse
Figure 4: Wallplate (Shown Vertical)
Cover Scre w
(Insert the cover screw
above the other UP arrow
for horizontal mounting.)
Use these holes for
mounting to wallbox.
4. Wire the TMZ (refer to the Wiring section in this
document).
5. Attach the TMZ to the wallplate, and replace and
tighten the cover screw with a 1.5 mm (1/16 in.)
Allen wrench or stat adjustment tool.
3. 6. Install the endcaps provided by snapping them
onto the wallplate.
Room Sensor with LCD Display (TMZ1600) Installation Instructions 3
Wiring
!
CAUTION: Risk of Property Damage.
Do not run low voltage cable in the same conduit or
wiring troughs with high voltage wires. Running low
and high voltage wires in the same conduit or wiring
troughs may damage the equipment or cause
system malfunction.
Table 1 describes the pinouts for each phone jack on
the TMZ.
Table 1: TMZ Phone Jack Pinouts
8-Pin Phone Jack on
TMZ
Pin Signal Pin Signal
6-Pin Phone Jack on
TMZ
Note: All terminals are power limited. Electrical
wiring must conform to local codes and should be
done by certified personnel only.
To connect the TMZ to a UNT, VAV, or VMA
controller, connect an 8-pin phone jack cable
assembly from the 8-pin phone jack on the TMZ
Figure 5) to the 8-pin phone jack on the controller.
(
C17
D5
C16
8-pin
Phone
Jack
6-pin
Phone
Jack
C9
+
VR1
To ZTU or Laptop PC via CBLPR O Interface
L1
U5
D4
D6
C6
J5
Z1
D2
Q1
RT1
(30 m [100 ft] Maxim um )
J1
U2
C8
C4
Q4
U4
R28
D7
D8
D9
Y2
Q3
Y1
Q2
J6
tmzwire
T o 8-pin
Phon e Jack
on Controller
(30 m [100 ft]
Maximum)
Figure 5: TMZ1600 Cable Connections
!
CAUTION: Risk of Property Damage.
Do not insert a 6-pin connector or anything other
than an RJ-45 8-pin connector into the 8-pin jack on
the back of the TMZ1600 Room Sensor to prevent
damaging the phone jack..
1 Not Used 1 Not Used
2 Not Used 2 Supply: 24 VAC
3 AI1, Zone
Temperature Sensor
3 Supply/Zone Bus
Common
4 AI1, Sensor Common 4 Not Used
5 Supply: 24 VAC 5 Zone Bus
6 Supply/Zone Bus
6 Not Used
Common
7 Not Used
8 Zone Bus
Figure 6 illustrates the cable and phone jack pinouts
used to connect the TMZ to a controller:
8
Controller Phone Plug
7
(Tab Notch Up)
6
5
4
3
d
d
e
e
s
U
t
o
N
M
s
1
O
I
U
C
A
t
I
o
A
N
1 2 3 4 5 6 7 8
TMZ160 0 Phone Pl ug
(Tab Notch Up)
d
n
e
o
ly
s
p
p
u
S
+
m
U
B
m
t
Z
o
o
C
N
2
1
8-Pin Pho ne Jack
(Tab Notch Down)
Termi nal 1 is to the
extreme left as you face
the phone jack ope ning,
tab not c h down.
cblfab
Note: This may not be typical of prefabricated phone
cable. A telephone system cable is wired opposite of the
zone sensor requirements.
Figure 6: Cable and Phone Jack Pinouts
4 Room Sensor with LCD Display (TMZ1600) Installation Instructions
Operation
A
Basic Operation
The TMZ1600 has five control buttons. Their basic
functions are described in
Table 2.
Table 2: TMZ1600 Button Functions
Button Function
Menu Cycles through the following display options: room air temperature, outdoor air temperature, comfort
setpoint temperature, and fan operation.
In Password mode*, cycles through these additional display options: comfort setpoint temperature access
status, fan access status, Temporary Occupancy duration, heating setpoint temperature, and cooling
setpoint temperature.
Down
Arrow
Up Arrow
°F/°C Toggles temperature display between degrees Fahrenheit (°F) and degrees Celsius (°C).
Temporary
Occupancy
* Press and hold the Menu and °F/°C buttons simultaneously for 10 seconds to access Password mode.
LCD Display Symbols
Figure 7 shows the relative size and location of the
LCD Display symbols:
Displays the comfort setpoint temperature if pushed while room air temperature is displayed.
Lowers the setpoint temperature when setpoint is displayed and blinking.
Toggles fan operation mode between On and Auto when the fan mode is displayed and blinking.
In Password mode*, sets user access to UnLK.
Displays the comfort setpoint temperature if pushed while room air temperature is displayed.
Raises the setpoint temperature when the setpoint is displayed and blinki ng.
Toggles fan operation mode between On and Auto when the fan mode is displayed and blinking.
In Password mode*, sets user access to LOCK.
Toggles the controller between Standby or Unoccupied mode and Tempora ry Occupancy mode. The LightEmitting Diode (LED) above this button lights when Temporary Occupancy mode is active.
During power up, the full range of LCD Display
symbols appears for approximately 10 seconds or
more, followed by Err6 if the controller has not started
OUT
RM
IR
OFF
TMP
-
UN
OCC
SBy
communication yet. The TMZ repeats this sequence
until the default display (RM AIR) appears.
Table 3 describes the LCD display symbols.
Figure 7: LCD Display Symbols
Room Sensor with LCD Display (TMZ1600) Installation Instructions 5
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.