Johnson Controls TM9V100C20MP11, TM9V100C16MP11, TM9V080C16MP11, TM9V060B12MP11, TM9V080B12MP11 User Manual

...
0 (0)
Johnson Controls TM9V100C20MP11, TM9V100C16MP11, TM9V080C16MP11, TM9V060B12MP11, TM9V080B12MP11 User Manual

QUICK REFERENCE GUIDE

96%TWO STAGE MULTI-POSITION RESIDENTAL

GAS FURNACES (33” TALL)

NOTES:

1.If the furnace is equipped with NOx screens and is to be used with LP (propane) gas, the screens must be removed prior to start-up.

2.Drip leg in the gas line must be installed.

3.The furnace controls require correct polarity on the power supply and a proper ground.

4.Y & G must be connected to the control board for cooling operation.

5.External filters are required on all configurations.

6.Electrical or gas entry is available on both casing sides.

7.To measure total static pressure, add supply duct pressure to the return duct pressure, add pressure drop across the ‘A’ coil, and add pressure drop across the filter. Ignore negative signs on the readings.

8.Inlet gas pressure should be 7” w.c. for natural gas and 11” w.c. for propane. Nominal manifold gas pressure is 3.5” w.c. for natural gas and 10” w.c. for propane at max. input.

9.For downflow application the vent blower must be rotated 90 left or right as shown.

 

Airflow CFM (Bottom Return without Filters)

 

 

Minimum Wire

 

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

 

0.5" ESP (Nominal)

 

 

 

 

 

Size awg @ 75'

 

Over Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

One-Way

 

Protection

 

*D-A**

 

*C-A**

 

*B-A**

 

*A-B**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V060B12MP11

600

 

 

690

 

 

1000

 

1305

 

 

14

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V080B12MP11

600

 

 

680

 

 

1000

 

1290

 

 

14

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V080C16MP11

850

 

 

905

 

 

1175

 

1670

 

 

14

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V100C16MP11

870

 

 

910

 

 

1160

 

1655

 

 

14

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V100C20MP11

960

 

1155

 

 

1605

 

2215

 

 

12

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V120D20MP11

960

 

1160

 

 

1595

 

2180

 

 

12

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

Total Unit

Air Temp. Rise

 

Air Temp. Rise

Time For 1 ft

3

Natural Gas

Models

Rate

 

 

 

 

 

Amps

 

Max Input °F

 

 

Min Input °F

(1030 Btu/Ft3) Seconds

 

Max

Min

 

 

 

 

 

 

(On Max. Rate)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V060B12MP11

60,000

21,000

 

 

9

 

 

 

35 - 65

 

 

35 - 65

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V080B12MP11

80,000

28,000

 

 

9

 

 

 

35 - 65

 

 

30 - 60

 

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V080C16MP11

80,000

28,000

 

 

12

 

 

35 - 65

 

 

35 - 65

 

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V100C16MP11

100,000

35,000

 

 

12

 

 

35 - 65

 

 

30 - 60

 

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V100C20MP11

100,000

35,000

 

 

14

 

 

35 - 65

 

 

35 - 65

 

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM9V120D20MP11

120,000

42,000

 

 

14

 

 

35 - 65

 

 

35 - 65

 

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other airflows are available. see Tech Guide for all CFM options.

*Cool Tap.

**Adjustment Tap.

This document does not replace the installation instructions, which must be referred to for detailed information.

 

SUPPLY END

 

2” Diameter

RETURN END

.56”

 

 

 

23.8”

3”

Vent Connection

 

 

 

 

 

 

Outlet

 

 

B

Combustion

 

 

 

Air Inlet

 

 

 

 

 

 

.56”

 

.56”

 

24.25”

 

20”

 

 

 

 

 

 

 

Combustion Air Inlet

 

Combustion Air Inlet

 

 

Condensate Drain

Gas Pipe

 

 

 

(Downflow)

Condensate Drain

 

 

Entry

 

 

 

(Downflow)

 

 

Vent Connection

 

 

 

Electrical

 

 

 

Outlet

 

 

 

Entry

Vent Connection

 

 

 

 

 

 

 

 

 

 

Condensate

Outlet

 

 

 

 

 

 

 

Drain

23”

 

 

 

Thermostat

 

 

 

 

Wiring

 

 

 

 

 

Optional Return Air

 

 

 

 

Cutout (Either side)

 

 

28.5”

 

1.5”

 

 

29.5”

 

 

 

 

LEFT SIDE

 

RIGHT SIDE

Follow all national and local codes and standards in addition to this document. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with national codes and all authorities having jurisdiction.

DURING INSTALLATION, DOORS MUST REMAIN ON FURNACE WHEN MOVING

BOR LIFTING.

Clips can be flipped into the up position for coil cabinet or plenum attachment

A-COIL

14”

1”

33”

AFRONT

LED INDICATOR

Slow Green Flash - Normal operation in standby mode. Slow Amber Flash - Normal operation with call for cooling. Two Amber Flashes - Normal operation with call for heat.

Three Amber Flashes - Normal operation, burner is on at end of thermostat cycle.

Six Amber Flashes - Normal operation with call for heat pump heating.

Any Red Flash - Fault condition. NOTE: 4 or 5 flashes may indicate a blown fuse on the circuit board.

Subject to change without notice. Printed in U.S.A.

*438336*

438336-URG-A-0209

Copyright © 2009 by Johnson Controls, Inc. All rights reserved.

Supersedes: Nothing

 

 

 

 

Johnson Controls Unitary Products

5005 York Drive

Norman, OK 73069

CLEARANCES

Application

Upflow

Downflow

Horizontal

Top

1"

0"

0"

 

 

 

 

Vent

0"

0"

0"

 

 

 

 

Rear

0"

0"

0"

 

 

 

 

Side

0"

0"

1"

 

 

 

 

Front*

0"

0"

0"

 

 

 

 

Floor

Combustible

Combustible1

Combustible

Closet

Yes

Yes

Yes

 

 

 

 

Line Contact

No

No

Yes

 

 

 

 

1. For combustible floors only when used with special sub-base.

*24" clearance in front and 18" on side recommended for service access.

All furnaces approved for alcove and attic installation.

DIMENSIONS

Cabinet Size

A (in)

B (in)

All 'B' Cabinet Furnaces

17-1/2"

16-3/8"

 

 

 

All 'C' Cabinet Furnaces

21"

19-7/8"

 

 

 

All 'D' Cabinet Furnaces

24-1/2"

23-3/8"

 

 

 

Loading...
+ 1 hidden pages