Johnson Controls TM9V100C20MP11, TM9V100C16MP11, TM9V080C16MP11, TM9V060B12MP11, TM9V080B12MP11 User Manual

...
NOTES:
SUPPLY END
RETURN END
LEFT SIDE
Combustion Air Inlet
Condensate Drain (Downflow)
Vent Connection Outlet
Thermostat
Wiring
29.5”
28.5”
RIGHT SIDE
Condensate Drain (Downflow)
14”
1”
1.5”
23”
Combustion Air Inlet
Gas Pipe
Entry
Electrical
Entry
Condensate
Drain
Optional Return Air Cutout (Either side)
FRONT
A
33”
Clips can be flipped into the up position for coil cabinet or plenum attachment
A-COIL
Follow all national and local codes and standards in addition to this document. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with national codes and all authorities having jurisdiction.
B
24.25”
.56”
.56”
20”
3”
23.8”
.56”
Combustion Air Inlet
2” Diameter Vent Connection Outlet
B
DURING INSTALLATION, DOORS MUST REMAIN ON FURNACE WHEN MOVING OR LIFTING.
Vent Connection Outlet
QUICK REFERENCE GUIDE
96%TWO STAGE MULTI-POSITION RESIDENTAL
GAS FURNACES (33” TALL)
1. If the furnace is equipped with NOx screens and is to be used with LP (propane) gas, the screens must be removed prior to start-up.
2. Drip leg in the gas line must be installed.
3. The furnace controls require correct polarity on the power supply and a proper ground.
4. Y & G must be connected to the control board for cooling operation.
6. Electrical or gas entry is available on both casing sides.
Airflow CFM (Bottom Return without Filters)
Models
TM9V060B12MP11 TM9V080B12MP11 TM9V080C16MP11 TM9V100C16MP11 TM9V100C20MP11 TM9V120D20MP11
*D-A** *C-A** *B-A** *A-B**
600 690 1000 1305 14 15 600 680 1000 1290 14 15 850 905 1175 1670 14 15 870 910 1160 1655 14 15 960 1155 1605 2215 12 20 960 1160 1595 2180 12 20
0.5" ESP (Nominal)
7. To measure total static pressure, add supply duct pressure to the return duct pressure, add pressure drop across the ‘A’ coil, and add pressure drop across the filter. Ignore negative signs on the readings.
8. Inlet gas pressure should be 7” w.c. for natural gas and 11” w.c. for propane. Nominal manifold gas pressure is 3.5” w.c. for natural gas and 10” w.c. for propane at max. input.
9. For downflow application the vent blower must be rotated 90 left or right as shown.
Minimum Wire
Size awg @ 75'
One-Way
Maximum
Over Current
Protection
This document does not replace the installation instructions, which must be referred to for detailed information.
Input
Models
TM9V060B12MP11 60,000 21,000 9 35 - 65 35 - 65 62
Subject to change without notice. Printed in U.S.A. 438336-URG-A-0209 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing
TM9V080B12MP11 80,000 28,000 9 35 - 65 30 - 60 46 TM9V080C16MP11 80,000 28,000 12 35 - 65 35 - 65 46 TM9V100C16MP11 100,000 35,000 12 35 - 65 30 - 60 37 TM9V100C20MP11 100,000 35,000 14 35 - 65 35 - 65 37 TM9V120D20MP11 120,000 42,000 14 35 - 65 35 - 65 31
Other airflows are available. see Tech Guide for all CFM options. * Cool Tap. ** Adjustment Tap.
Slow Green Flash - Normal operation in standby mode. Slow Amber Flash - Normal operation with call for cooling. Two Amber Flashes - Normal operation with call for heat. Three Amber Flashes - Normal operation, burner is on at end of
thermostat cycle. Six Amber Flashes - Normal operation with call for heat pump
heating. Any Red Flash - Fault condition. NOTE: 4 or 5 flashes may indi-
cate a blown fuse on the circuit board.
LED INDICATOR
Rate
Max Min
Johnson Controls Unitary Products
Total Unit
Amps
Air Temp. Rise
Max Input °F
*438336*
5005 York Drive
Norman, OK 73069
Air Temp. Rise
Min Input °F
Time For 1 ft3 Natural Gas
(1030 Btu/Ft
3
) Seconds
(On Max. Rate)
CLEARANCES
Application Upflow Downflow Horizontal
Top 1" 0" 0"
Vent 0" 0" 0"
Rear 0" 0" 0"
Side 0" 0" 1"
Front* 0" 0" 0"
Floor Combustible
Closet Yes Yes Yes
Line Contact No No Yes
1. For combustib le floors only when used with special sub-base.
* 24" clearance in front and 18" on side recommended for
service access.
All furnaces approved for alcove and attic installation.
Combustible
1
Combustible
DIMENSIONS
Cabinet Size A (in) B (in)
All 'B' Cabinet Furnaces 17-1/2" 16-3/8" All 'C' Cabinet Furnaces 21" 19-7/8" All 'D' Cabinet Furnaces 24-1/2" 23-3/8"
Furnace is multi-position and may be installed in any of the configurations shown.
Ensure that all PVC venting has at least 1/4” per foot slope towards the furnace.
The furnace condensate pan is self priming and contains an internal trap.
.Do not install an external condensate trap
When drain hose routing changes are required (shown in red), be sure to cap
all unused openings. If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate, which will cause the furnace to not operate.
Move rain gutter hose
to this position.
HORIZONTAL LEFT
Move pressure switch
hose to this position.
NOTE: May require the
longer hose that is
provided with wider
cabinets.
Change condensate drain
connection to the 90° fitting provided.
Move condensate drain hose to this position.
Move rain gutter hose to this position
NOTE: May require hose extension that
is provided with wider cabinets.
UPFLOW
DOWNFLOW
Move condensate drain
hose to this position.
For downflow applications, the gas
valve must be rotated upwards.
Inducer must be rotated 90° in
either direction for this installation.
HORIZONTAL RIGHT
Move pressure switch
hose to this position.
Change condensate drain
connection to the 90° fitting provided.
Move rain gutter hose
to this position.
Move condensate drain
hose to this position.
Move rain
gutter hose
to this position.
Move pressure switch
hose to this position.
NOTE: May require the
longer hose that is provided
with wider cabinets.
AIRFLOW
AIRFLOW
MOST COMMON INSTALLATION CONFIGURATIONS (MORE OPTIONS AVAILABLE WHICH IS COVERED IN THE INSTALLATION MANUAL)WITH INDUCER ROTATION,
Rain
Gutter
Hose
Pressure
Switch
Hose
Condensate Drain Hose
For 100 & 120K input furnaces, the condensate
drain is factory set toward the left casing outlet.
For 060 & 080K input furnaces, the condensate
drain is factory set toward the right casing outlet.
MULTI-POSITION CONFIGURATION INFORMATION:
1
2
3
4
1
2
5
4
3
1
2
3
4
In upflow and downflow installation - Condensate drain hose may go out either side.
AIRFLOW
5
Move rain gutter hose
to this position.
Loading...