Johnson Controls TM-2161, TM-2151, TM-2141, TM-2191 Installation Instructions Manual

TM-21x1 Series Room Temperature Module
24- 10225- 12, Rev. C
Installation Instructions
Part No. 24-10225-12, Rev. C
Issued March 2016
Applications
The TM-21x1 Series of Room Temperature Modules are designed for use with the Facility Explorer Series of field controllers. The setpoint dial enables the room occupant to adjust the working setpoint of the controller. On scaled models, the marked adjustment range is 55 to 85°F; the controller determines the actual setpoint temperature. On Warmer/Cooler models, the adjustment range is marked +/- from midpoint of the dial; the controller determines the equivalent setpoint temperature.
With the occupancy button, the occupant can switch the controller’s operating mode between occupied and standby. In addition, the TM-21x1 Series offers the option of a temporary occupied mode during unoccupied mode.
The TM-21x1 Series Room Temperature Module also features a Light-Emitting Diode (LED) that indicates the current operating mode.
IMPORTANT: The TM-21x1 Series Room Temperature Modules are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the TM-21x1 Temperature Module could lead to personal injury or property damage to the controlled equipment or other property, other precautions must be designed into the control system. Incorpora te and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the TM-21x1 Temperature Module.
Installation
Parts Included
Two #6-32 x 7/8 in. (22 mm) wallbox mounting screws are included with the TM-21x1 Module.
Special Tools Needed
For tightening and loosening the TM-1 1x1 Series Room Temperature Module security screw, order the optional Allen-head tool (T-4000-119) fro m th e ne ar es t Johnson Controls® representative.
TM-21x1 Series Room Temperature Module Installation Instructions 1
Dimensions
Figure 1: TM-2141 Dimensions, in. (mm)
3.15 (80 )
4.72
F
I
G
:
2
1
4
1
_
d
i
m
Figure 2: TM-2151 Dimensions, in. (mm)
F
I
G
:
2
1
5
1
_
d
i
m
Mode
LED
Occupancy
Button
4.72
(120)
Figure 3: TM-2161-0002 and TM-2161-0007
Dimensions, in. (mm)
F
I
G
:
2
1
6
1
_
d
i
m
4.72
(120)
Mode
LED
Button
Fan
Speed
Dial
Setpoint
Dial
F
I
G
:
2
1
6
1
_
0
0
0
5
_
d
i
m
4.72
(120)
Mode
LED
Button
Setpoint
Dial
Figure 4: TM-2161-0000 and TM-2161-0005
Dimensions, in. (mm)
TM-2141 Modules
TM-2161 Modules
1.26 (32)
(120)
1.38 (35 )
3.15 (80)
Occupancy
Adjustment
TM-2151 Modules
1.26 (32 )
3.15 (80)
TM-21x1 Series Room Temperature Module Installation Instructions2
1.38 (35 )
3.15 (80)
Occupancy
Adjustment
TM-2191 Modules
Figure 5: TM-2191 Dimensions, in. (mm)
F
I
G
:
2
1
9
1
_
d
i
m
3.15 (80)
1.38 (35)
4.72
(120)
Setpoint
Adjustment
Dial
7. Attach the housing to the base and tighten the security screw with the allen-head tool.
Mounting
Location Considerations
Mount the TM-21x1 Series Room Temperature Module on a wall in the room to be controlled where the occupant can easily read and adjust the setpoint dial or fan speed override adjustment dial. Consider these additional guidelines in determining the best mounting location:
Avoid areas subject to excessive vibration, electrical noise, direct sunlight, or the effects of radiant heat.
Keep electrical wiring as short as possible to minimize temperature error.
Install modules in areas where the temperature is representative of the general room conditions.
Wiring
To wire a controller to the TM-21x1 Series Room Temperature Module, see the appropriate wiring diagram (Figure 6 to Figure 10).
Installing the TM-21x1
To install the TM-21x1 Series Room Temperature Module:
1. Use the Allen-head tool to loosen the security screw located at the top center of the housing.
2. Insert a screwdriver blade or coin into the slot on the top of the housing.
3. Press down gently, and pry the housing away from the base. As the two parts separate, remove the blade or coin and continue to pull the housing away from the base until the housing is free.
4. Pull the wires through the base. Locate the green terminal blocks in the upper right of the base and position the module on the wallbox with the terminal numbers right-side up.
5. Mount the base to the wallbox using the two #6-32 mounting screws (included).
6. Wire the controller to the module. See the Wiring section for correct wiring.
Note: Use 22 AWG (0.65 mm diameter) wire minimum. Do not exceed 164 ft (50 m) between the controller and the temperature module.
Table 1: Nominal Values for 10k ohm Sensors
Temperature Resistance F Cohm
20 -7 48,525 30 -1 34,919 40 4 27,550 50 10 19,898 60 16 12,246 70 21 11,993 80 27 9,222 90 32 7,510 100 38 5,874 110 43 4,871 120 49 3,956 130 54 3,277
TM-21x1 Series Room Temperature Module Installation Instructions 3