Johnson Controls TG9S040A08MP11, TG9S060A10MP11, TG9S060B12MP11, TG9S080B12MP11, TG9S080C16MP11 Quick Reference Manual

...
NOTES:
1. Refer to the condensate management and drain hose plumbing for different configurations in this document. No hose clamps are needed for the condensate pan hook up.
2. Drip leg in the gas line must be installed.
3. The furnace controls require correct polarity on the power supply and a proper ground.
4. Y & G must be connected to the control board for cooling operation.
6. Inlet gas pressure for natural gas should be 7” and that for propane should be 11” w.c. Nominal manifold gas pressure is 3.5” for natural gas and 10” w.c. for propane.
7. If thermoplastic evaporator ‘A’ coil drain pans are to be installed in the up-flow/horizontal configuration, then extra 2” minimum spacing may be needed to ensure against drain pan distortion.
8. External filters required on all configurations.
9. Electrical entry is available on both sides of the casing.
10. All 33”, 95% furnaces are approved for single-pipe and 2­pipe systems. For single pipe systems it is recommended to install the combustion air coupling provided and install approximately 18” of PVC pipe on the furnace.
11. Do not install an external condensate trap on these fur­naces, as it will prevent the unit from operating correctly.
Models
Airflow CFM (Bottom Return without Filters)
Minimum Wire Size awg @ 75'
One-Way
Total Unit
Amps
Maximum
Over Current
Protection
0.5" ESP (Nominal)
Low Med-Lo Med-Hi High
(T,G)G9S040A08MP11 581 653 818 950 14 8.0 15 (T,G)G9S060A10MP11
769 917 1038 1103 14 10.0 15
(T,G)G9S060B12MP11
713 872 1082 1243 14 10.0 15 (T,G)G9S080B12MP11 854 1008 1179 1370 14 10.0 15 (T,G)G9S080C16MP11
838 1250 1465 1671 14 11.5 15 (T,G)G9S080C22MP11
1285 1586 1937 2162 12 17.0 20 (T,G)G9S100C16MP11 819 1224 1477 1706 14 11.5 15 (T,G)G9S100C20MP11
1183 1430 1712 1934 12 17.0 20 (T,G)G9S120D16MP11
876 1254 1495 1805 14 11.5 15 (T,G)G9S120D20MP11 1190 1430 1739 1977 12 17.0 20 (T,G)G9S130D20MP11
1198 1459 1786 2047 12 17.0 20
Models
Maximum
Vent Equivalent
1
Factory Heating Speed Setting
2
Temperature
Rise Range
Time For 1 ft
3
Natural Gas
(1030 Btu/Ft
3
)
Seconds On (Rate)
2" 3"
(T,G)G9S040A08MP11 65’ 90’ Med-Hi 30°F-60°F 93 (T,G)G9S060A10MP11 65’ 90’ High 30°F-60°F 62 (T,G)G9S060B12MP11 65’ 90’ Med-Hi 30°F-60°F 62 (T,G)G9S080B12MP11 65’ 90’ High 35°F-65°F 46 (T,G)G9S080C16MP11 65’ 90’ High 35°F-65°F 46 (T,G)G9S080C22MP11 65’ 90’ Med-Hi 35°F-65°F 46 (T,G)G9S100C16MP11 30’ 90’ High 35°F-65°F 37 (T,G)G9S100C20MP11 30’ 90’ Med-Hi 35°F-65°F 37 (T,G)G9S120D16MP11 30’ 90’ High 40°F-70°F 30 (T,G)G9S120D20MP11 30’ 90’ Med-Hi 35°F-65°F 30 (T,G)G9S130D20MP11 N/A 85’ High 45°F-75°F 28
1. For venting purposes, one 90° sweep elbow is equal to 5 Ft. of venting length, one 90° standard elbow is equal to 10 equiva-
lent feet of vent length. Vent termination elbows are included in these calculations, minimum required vent length is 5 ft.
2. Must be changed if not in rise range.
This document does not replace the installation instructions, which must be referred to for detailed information.
CLEARANCES
* 24" clearance in front and 18" on side recommended for
service access.
All furnaces approved for alcove and attic installation.
DIMENSIONS
LED INDICATOR
Slow Green Flash
• Normal operation
Slow Amber Flash
• Normal operation with call for heat
Any Red Flash = Fault condition Any Rapid 4 Flash = Potential fault codes / conditions
SUPPLY END
RETURN END
LEFT SIDE
Combustion Air Inlet
Condensate Drain (Downflow)
Vent Connection Outlet
Thermostat
Wiring
29.5”
28.5”
RIGHT SIDE
Condensate Drain (Downflow)
14”
1”
1.5”
23”
Combustion Air Inlet
Gas Pipe
Entry
Electrical
Entry
Condensate
Drain
Optional Return Air Cutout (Either side)
FRONT
A
33”
Clips can be flipped into the up position for coil cabinet or plenum attachment
A-COIL
Follow all national, local codes and standards in addition to this document. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes andall authorities having jurisdiction.
B
24.25”
.56”
.56”
20”
3”
23.8”
.56”
Combustion Air Inlet
2” Diameter Vent Connection Outlet
B
DURING INSTALLATION, DOORS MUST REMAIN ON FURNACE WHEN MOVING OR LIFTING.
Vent Connection Outlet
Application Upflow Downflow Horizontal
Top 1" 0" 0" Vent 0" 0" 0" Rear 0" 0" 0" Side 0" 0" 1"
Front* 0" 0" 0"
Floor Combustible
Combustible
1
1. For combustible floors only when used with special sub-base.
Combustible
Closet Yes Yes Yes
Line Contact No No Yes
Cabinet Size A (in) B (in)
All 'A' Cabinet Furnaces 14-1/2" 13-3/8" All 'B' Cabinet Furnaces 17-1/2" 16-3/8" All 'C' Cabinet Furnaces 21" 19-7/8" All 'D' Cabinet Furnaces 24-1/2" 23-3/8"
QUICK REFERENCE GUIDE
95.5% SINGLE STAGE MULTI-POSITION
RESIDENTAL GAS FURNACES (33” TALL)
Subject to change without notice. Published in U.S.A. 401260-URG-E-0509 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 401260-URG-D-0808
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
*401260*
Furnace is multi-position and may be installed in any of the configurations shown.
Ensure that all PVC venting has at least 1/4” per foot slope towards the furnace.
The furnace condensate pan is self priming and contains an internal trap.
.Do not install an external condensate trap
When drain hose routing changes are required (shown in red), be sure to cap all unused openings. If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate, which will cause the furnace to not operate.
Move rain gutter hose to this position
HORIZONTAL LEFT
Move pressure switch hose to this position. NOTE: May require the longer hose that is provided with wider cabinets
Change condensate drain connection to the 90° fitting provided
Move condensate drain hose to this position
Move rain gutter hose to this position NOTE: May require hose extension that is provided with wider cabinets
UPFLOW
DOWNFLOW
Move condensate drain hose to this position
Move rain gutter hose to this position
Inducer must be rotated 90° in either direction for this installation
HORIZONTAL RIGHT
Move pressure switch hose to this position
Change condensate drain connection to the 90° fitting provided
Move rain gutter hose to this position
Move condensate drain hose to this position
Move rain gutter hose to this position
Move pressure switch hose to this position. NOTE: May require the longer hose that is provided with wider cabinets.
AIRFLOW
AIRFLOW
AIRFLOW
AIRFLOW
MOST COMMON INSTALLATION CONFIGURATIONS (MORE OPTIONS AVAILABLE WHICH IS COVERED IN THE INSTALLATION MANUAL)WITH INDUCER ROTATION,
Rain Gutter Hose
Pressure Switch Hose
Condensate Drain Hose
For 100, 120 & 130K input furnaces, the condensate
drain is factory set toward the left casing outlet
For 040, 060 & 080K input furnaces, the condensate
drain is factory set toward the right casing outlet
MULTI-POSITION CONFIGURATION INFORMATION:
1
2
3
4
1
2
5
4
3
1
2
3
4
In upflow and downflow installation - Condensate drain hose may go out either side.
NOTE: Only side venting on 130K unit.