Johnson Controls TEP Series, TEA Series Catalog Page

Code No. LIT-1922220
TEP/TEA Series Platinum
Temperature Sensors
Issued December 11, 2002
TEP/TEA Series
Platinum Temperature Sensors and TQ-6000 Accessory Transmitter
The TEP and TEA Series Platinum Temperature Sensors come in probe (TEP Series) and averaging (TEA Series) configurations with 100-ohm or 1,000-ohm elements. These sensors have metal electrical boxes and are designed for use with building automation systems and application specific controllers. Use them also whenever platinum is specified for general purpose temperature sensing applications.
Probe Sensors: The TEP Series Probe Sensors have platinum wire elements in bronze sheaths. Easily field-install them with TE-6001 Hardware Assemblies.
Averaging Sensors: The TEA Series Averaging Sensors are complete sensor/hardware assemblies. Each consists of a platinum equivalent averaging-type sensor, either 10 or 20 ft (305 or 610 cm) long, encased in an aluminum sheath attached to a handibox, and shipped with two element holders for easy mounting and wiring.
Transmitter: The TQ-6000 is a 2-wire current loop type transmitter that works with the 100­ohm platinum sensors to send a 4 to 20 mA temperature control signal long distances without the loss of accuracy due to lead wire resistance.
Features
• probe and averaging sensors available to cover a wide variety of applications
• current transmitter option allows longer wire runs
• metal electrical boxes provide an alternative to plastic for meeting code requirements
• sensor element options offer choice of 100 or 1,000 ohms
Applications
The TEP/TEA sensors can be used in a wide variety of general purpose temperature sensing applications or wherever platinum is specified.
Selection Chart
Code Number Description
TEP-J000000 Probe sensors, 100 ohms at 32°F (0°C) TEP-L000000 Probe sensors, 1,000 ohms at 32°F (0°C) TEA-J000000 Averaging sensors, 10 foot sensor length, 100 ohms at
TEA-K000000 Averaging sensors, 20 foot sensor length, 100 ohms at
TEA-L000000 Averaging sensors, 10 foot sensor length, 1,000 ohms at
TEA-M000000 Averaging sensors, 20 foot sensor length, 1,000 ohm at
TQ-6000-1 Transmitter, 2-wire, 4 to 20 mA
32°F (0°C)
32°F (0°C)
32°F (0°C)
32°F (0°C)
Repair Information
If the Platinum Temperature Sensors or TQ-6000 Accessory Transmitter fail to operate within its specifications, replace the unit. For a replacement unit, contact the nearest Johnson Controls® representative.
Accessories
Code Number Description
TE-6001-8 Temperature element holder for use with all averaging
sensors (nickel and platinum)
Technical Specifications
Elements Platinum (or equivalent) resistance type Accuracy ±1F° at 70°F (±0.56C° at 21.1°C) Reference
Resistance at 32°F (0°C)
Temperature Range -50 to 275°F (-46 to 135°C) Shipping
Weight
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
TEP/TEA Temperature Sensing Elements
100 ohms TEP-J000000, TEA-J000000,
TEA-K000000
1,000 ohms TEP-L000000, TEA-L000000,
TEA-M000000
TEP-J/L000000 0.2 lb (0. 0 9kg) TEA-J/L000000 1.0 lb (0.45kg) TEA-K/M000000 1.1 lb (0.5kg)
TQ-6000 Temperature Transmitter
Output 4 to 20 mA DC scaled over the 0 to 100°F (-18 to 38°C)
Sensing Element
Calibration Accuracy
Adjustments Zero and span, ±5% of span Supply Voltage 8.5 to 35 VDC, voltage effect: ±0.001% of span per volt Warmup Drift ±0.1% of span max. assuming V
Loop Resistance
Linearity Referenced to actual sensor temperature (±0.1% of sp an ) Ambient
Operating Temperature
Storage Temperature
sensor range Requires 100 ohms (TEP/TEA Series Platinum or
equivalent) ±0.1% of span at calibration temperature 32°F (0°C)
= 250 ohms: stable within 30 minutes
and R
loop
The maximum allowable resistance of the signal-carrying loop (with load resistor R calculated with the following formula:
max = (V
R
loop
32 to 122°F (0 to 50°C), calibrated at 75°F (23.9°C); Drift less than 0.007% per 1°F (0.56°C) per 1°C change in ambient temperature over usable range
-67 to 212°F (-55 to 100°C)
-8.5) / 0.02 amps
supply
supply
and extension wires) is
load
www.johnsoncontrols.com
1 of 1
= 24 VDC
Loading...