Johnson Controls TEC-6-PIR, TEC-6H-PIR, TEC-3-PIR, TEC-7-PIR Installation Instructions Manual

Page 1
Passive Infrared (PIR) Accessory Covers
24- 9890- 870, Rev. E
Installation Instructions
TEC-3-PIR, TEC-6-PIR, TEC-6H-PIR, and TEC-7-PIR
Part No. 24-9890-870, Rev. E
Issued March 2016
Applications
The Passive Infrared (PIR) Accessory Covers with embedded PIR motion detectors are specifically designed to work with compatible Johnson Controls® TEC and T60x Series Equipment Controllers. These accessory covers are designed to retrofit previously installed controllers, or to serve as replacement covers.
When equipped with a PIR Accessory Cover, the controller provides advanced active occupancy logic, which automatically switches occupancy levels from Occupied to Unoccupied or Standby as required by the presence of local activity. This added occupancy sensing capability provides energy savings during occupied hours without sacrificing occupant comfort.
A PIR Accessory Cover is suited for the following applications:
lodging Fan Coil Unit (FCU) applications
TEC Zoning Control System zones
conference rooms
classroom units
any commercial offices that have random occupancy schedules during occupied hours, as dictated by the function of the tenant
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
any controlled piece of HVAC equipment that may yield energy savings with the introduction of a new automatic standby level of occupancy
Passive Infrared (PIR) Accessory Covers Installation Instructions 1
Page 2
Installation
!
!
Figure 1: Wiring to the PIR Connector on the
Controller Base, and Attaching the
PIR Accessory Cover
FIG:cvr_rmv l
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
MISE EN GARDE : Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Make all wiring connections in
accordance with the National Electrical Code and local regulations. Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid damaging the electronic circuits.
To install a PIR accessory cover:
1. Remove the security screw on the bottom of the existing controller cover.
6. Use the configuration menu to make the appropriate parameter settings related to the specific application, as identified in the controller
installation instructions. See the Configuration Parameters section for more details.
The PIR motion detector may take up to 60 seconds after the initial warm-up period to detect movement consistent with the detection pattern. Blinking Light-Emitting Diodes (LEDs) located on PIR accessory cover beneath the motion detector aid in commissioning. The LEDs blink while an occupant is in the field of detection pattern for a period of 30 minutes after powerup.
Configuration Parameters
When installing a PIR accessory cover on a controller, set the following configuration parameters to appropriate values: PIR Func, BI1, St-By HT, and St-By CL. Each PIR accessory cover requires additional parameters to configure according to the compatible controller model (Table 1).
2. Open the existing cover by pulling upward on the bottom edge of the controller cover, and remove the cover.
3. Insert the polarized connector on the bottom left corner of the PIR accessory cover into the PIR connector located on the controller base (Figure 1).
4. Hinge the PIR accessory cover into position (Figure 1).
5. Snap the PIR accessory cover into place and reinstall the security screw.
Passive Infrared (PIR) Accessory Covers Installation Instructions2
For further information on configuration parameter settings, refer to the appropriate installation instructions for the specific controller model.
For application information details on the PIR sequence of operation, refer to the documentation listed in Table 2.
Mounting
Location Considerations
The typical detection pattern for the PIR sensor is shown in Figure 2. Consider this pattern when positioning the controller.
Page 3
Figure 2: Typical Detection Pattern
PIR TRIGGER ZONE
45°
FLOOR
20 ft
61 m
60°
60°
30°
FIG:pir_dtctn_pttrns
30°
5-1/2 ft
166 cm
5-1/2 ft
166 cm
Table 1: PIR Accessory Cover Code Numbers and Configuration Parameter Settings
Code Number Compatible Controller Series Configuration Parameter Settings
TEC-3-PIR T600xxx-4, T600xxx-4+PIR, T606MSx-4,
T606MSx-4+PIR, TEC2x0x-4, TEC2x0x-4+PIR, TEC2613-4, and TEC2613-4+PIR
TEC-6-PIR TEC20x6-2, TEC2xx6-4, and TEC2x45-4 The PIR accessory cover is auto-detected. Set the Occupied TEC-6H-PIR T60xDFH-4, T60xDFH-4+PIR,
TEC20x6H-2, TEC2xx6H-4, and TEC2xx6H-4+PIR
TEC-7-PIR TEC20x7-2, TEC2xx7-4, and
TEC26x7-4+PIR
TEC2647Z-2, TEC2647Z-2+PIR, TEC2647Z-3, and TEC2647Z-3+PIR
The PIR accessory cover is auto-detected. Set the Occupied Setpoints, Unoccupied Setpoints, and Unoccupied Timer (Unocc TM) to the desired comfort levels.
Setpoints, Standby Setpoints, Unoccupied Setpoints, Unoccupied Timer (Unocc TM), and Standby Timer (St-By TM) to the desired comfort levels.
Set the PIR Function (PIR Func) parameter to enable PIR. Set the Unoccupied Setpoints and Standby Setpoints to the desired comfort levels.
Table 2: PIR Application Documents
Code Number Document Title Document
Number
T60xDFH-4 and T60xDFH-4+PIR T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with
Dehumidification and Occupancy Sensing Capability Application Note
TEC2x45-4, TEC2xx6-4, TEC2xx6H-4, TEC2xx6H-4+PIR,
TEC2x45-4, TEC2xx6(H)-4, TEC2xx6H-4+PIR, TEC2xx7-4, and TEC26x7-4+PIR Series Thermostat Controllers Application Note
TEC2xx7-4, TEC26x7-4+PIR
LIT-12011569
LIT-12011594
Passive Infrared (PIR) Accessory Covers Installation Instructions 3
Page 4
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Repair Information
If the PIR accessory cover fails to operate within its specifications, replace the unit. For a replacement cover, contact the nearest Johnson Controls representative.
Technical Specifications
PIR Accessory Covers
Power Requirements 5 VDC Maximum; Current Draw of 7 mA Supplied by the
Ambient Operating Limits Temperature 32 to 122°F (0 to 50°C)
Humidity 0 to 95% RH, Noncondensing;
Ambient Storage Limits Temperature -22 to 122°F (-30 to 50°C)
Humidity 0 to 95% RH, Noncondensing Motion Detector Local Passive Infrared Sensor Dimensions
(Including Controller) Compliance United States UL Listed, File E27734, CCN XAPX
Canada UL Listed, File E27734, CCN XAPX7
Europe CE Mark – Johnson Controls, Inc., declares that this product is in
Australia and
New Zealand Shipping Weight 0.1 lb (0.05 kg)
Johnson Controls TEC or T60x Series Equipment Controller
85°F (29°C) Maximum Dew Point
4-15/16 in. H x 3-3/8 in. W x 1-13/32 in. D (125 mm H x 86 mm W x 36 mm D)
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
compliance with the essential requirements and other relevant provisions of the EMC Directive and the RTTE Directive.
RCM Mark, AS/NZS CISPR 22 Compliant Supplier Code Number N10696
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
Passive Infrared (PIR) Accessory Covers Installation Instructions4