Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers are stand-alone and
field-selectable BACnet® MS/TP or N2 networked devices that provide control of the following:
•local hydronic reheat valves
•pressure-dependent variable air volume (VAV) equipment with or without local reheat
•two- or four-pipe fan coils
•cabinet unit heaters
•other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control.
All models include a USB port configuration that reduces installation time by allowing simple backup and restore
features from a USB drive, which enables rapid cloning of configuration between like units.
Part No. 24-10787-6, Rev.
Issued July 2018
F
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick
and easy. Multiple fan configurations are supported for fan coil equipment types:
•single-speed
•multi-speed (two or three discrete speeds)
•variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates
dehumidification control as necessary. Heat and/or reheat is used as required to maintain the space temperature.
For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers with Dehumidification Capability
Installation Instructions
1
Page 2
IMPORTANT: The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under
normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal
injury or property damage to the controlled equipment or other property, additional precaution s must be
designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat
controller.
IMPORT ANT : Le TEC3000 Series Thermosta t Controller est destiné à tr ansmettre de s données entrantes à un
équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement
du thermostat controller risque de provoquer des blessures ou d'endomma ger l'équipement contrôlé ou un autre
équipement, la conception du système de con tr ôle doit intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en
cas de défaillance ou de dysfonctionnement du thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection ag ainst har mful inter fere nce in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment of f
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenna .
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
Canada
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Installation
Parts Included
•one TEC3000 Series Thermostat Controller with integral mounting base
•one installation instructions sheet
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
2
Page 3
Location Considerations
Figure 1: Thermostat Controller
Shown without Occupancy Sensor,
Dimensions, in. (mm)
FIG:thermostat features
USB Port
Display
Securit y Sc r ew
1-13/32
(36)
4-23/32
(120)
5-5/8
(143)
Locate the TEC3000 Series Thermostat Controller:
•on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature, allowing for vertical air circulation to
the TEC
•away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills,
stairwells, and from behind doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated passive infrared (PIR) models, be sure
that the thermostat controller is located centrally,
where occupant movement is frequent.
Use insulating foam pads for installations where
wiring passes through the wall to the thermostat.
Note: Allow for sufficient clearance to insert a USB
drive into the USB port.
IMPORTANT: Only connect memory devices to the USB port. Do not use it for charging external devices.
Installing the Thermostat Controller
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls® T-4000-119 Allen-Head Adjustment Tool (order
separately) to remove the security screw if it is installed on the top of the thermostat controller cover as
illustrated in Figure 2.
2. Pull the top edge of the cover and open the thermostat controller as illustrated in Figure 2.
IMPORTANT: The cover is not secured on the bottom. Be careful not to drop the cover.
IMPORTANT: If you are installing more than one thermostat controller, keep track of which cover attaches to
which base.
IMPORTANT: Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid
damage to the electronic circuits of the thermostat controller.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
3
Page 4
Figure 2: Removing the Security Screw from the Thermostat Controller Cover
FIG:security s crew
FIG:thermo stat cove r
(Shown without Occupancy Sensor) (Left) and Removing the Thermostat Controller Cover (Right)
3. Align the thermostat controller mounting base on the wall with the security screw on the top and use the base
as a template to mark the two mounting hole locations. See Figure 3.
Notes:
• If you need to install the thermostat controller on an electrical junction box, use
2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers and avoid smaller 1-1/2 x 4 in.
(38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures that you have enough
space for cabling, if needed.
•For surface-mounted applications, use durable mounting hardware, such as wall anchors, that cannot be
easily pulled out of the mounting surface.
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the center hole in the
thermostat controller mounting base. See Figure 3.
5. Secure the mounting base to the wall surface using two mounting screws (user supplied) as illustrated in
Figure 3.
Note: Be careful not to overtighten the mounting screws.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
4
Page 5
Figure 3: Mounting Hole Locations, Dimensions, in. (mm) (Left) and
4-1/16
(103)
FIG:TEC Backpl ane2
3-1/4
(83)
FIG:TEC Backplane1
Securing the Thermostat Controller Mounting Base to the Wall (Right)
Wiring
When an existing thermostat controller is replaced, remove and lab el the wires to identify the terminal functions.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
électrique.
Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly conn ected
wires may result in permanent damage to the equipment.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un
court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not
exceed the electrical ratings of the TEC3000 Series Thermostat Controller.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
5
Page 6
IMPORTANT: Use proper ESD precautions during installation and servicing to avoid damage to the electronic
EOL Switch
EOL Switch
O
N
FIG:TEC Backplane2_EOL Switch
O
N
FIG:cl ose ther mosta t cover
circuits of the thermostat controller.
To wire the the r mo st at co nt ro ller :
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in
Table 2 and Figure 6 or Figure 7.
Note: For more details on wirin g the MS/TP Communications Bus, refer to the MS/TP Communications Bus
Technical Bulletin (LIT-12011034).
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature
readings.
3. Reattach the communication wires to the terminal block.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together before
inserting them into the terminal connectors.
4. Set the bus end-of-line (EOL) termination switch to the desired location on the TEC3610-00-000,
TEC3611-00-000, TEC3612-00-000, and TEC3613-00-000 models only.
The bus EOL termination switch allows you to designate the thermostat controller as the end of the Field
Controller (FC) Bus and N2 Bus. The default position is OFF. If the thermostat controller is at the end of a daisy
chain of devices on the FC Bus and N2 Bus, set the EOL switch to the ON position. See Figure 4.
Figure 4: EOL Switch Position (Left) and Installing the Thermostat Controller Cover (Right)
O
N
ON Position
OFF Position
FIG:EOL_Swt ch
5. Reattach the thermostat contro ller cove r to the mounting base (bottom side first).
IMPORTANT: Make sure you reattach the cover that corresponds to its correct base. The CPU board number
needs to match the base board number.
base that do not belong together (as shown in Figure 5). See Table 1 on page 7 for TEC3000 model names and
Otherwise, an operation error occurs after you reattach a cover and
code numbers.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
1.The two-character code number is listed within the error code to
indicate that the CPU board and base board do not belong together.
However, if the same code number appears as both the CPU board
and base board, there is no error. For example, if 0B is listed as the
CPU board and the base board, the model is the TEC3611.
Code Number
6. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool (order
separately) to reinstall the security screw on the top of the thermostat controller cover. See Figure 2 for security
screw placement.
7. Remove the protective plastic cover sheet from the display.
1
IMPORTANT: If the display is dirty, gently wipe it clean with isopropyl alcohol or ethyl alcohol. Do not scrub
hard as to avoid damaging the surface. Do not use other cleaners such as water, ketones, and aromatic
solvents, since they may damage the polarize r.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
7
Page 8
Table 2: Terminal Identification (See Figure 6 and Figure 7 for Wiring Diagrams)
Terminal LabelFunction
TEC3310, TEC3311, TEC3312, TEC3313
Floating FC/VAV and On/Off FC
24 V24 VAC hot from transformer
FAN HFan high
FAN MFan medium
FAN LFan on (single-speed, variable speed), Fan low (multi-speed)
AUXAuxiliary binary output
AUXAuxiliary power
2
COM
CLG OCool open (Floating), Cooling NC (On/Off), Triac
CLG CCool close (Floating), Cooling NO (On/Off), Triac
HTG OHeat open (Floating), Heating NC (On/Off), Triac
HTG CHeat close (Floating), Heating NO (On/Off), Triac
2
COM
VSFVariable speed fan command (configurable 0 to 10 V range)
BI2Configurable binary input 2
BI1Configurable binary input 1
COSChangeover sensor
R SENRemote zone temperature sensor
NET+Not connectedField bus+/N2+
NET-Not connectedField bus-/N2-
NET COMNot connectedIsolated common for field bus
24 VAC common from transformer
Common
1
TEC3610, TEC361 1, TEC3612, TEC3613
Floating FC/VAV and On/Off FC
1
1.There is no support for an On and Off VAV.
2.The common terminals, which do not include NET COM, are internally connected and can be used for all inputs and
outputs.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
8
Page 9
Notes:
Zone Temp
Thermistor
Supply Temp
Switch
FIG:Model 1 Wiring_on _off_out put
24 V
R SEN
24V
NET COM
COS
VSF
COM
Supply Temp
Thermistor
Vin
Common
or
24 V
High
Med
FAN H
AUX
TB1
CLG C
Low
Fan
on
Fan
Common
Hot
Heating
Common
Hot
FAN M
FAN L
AUX
FIG:Model 1 Wiring_on_off_input
N.C.
Common
Hot
Common
Hot
N.O.
•VAV and 2-pipe systems should connect their valve to the heating output.
•Only one transformer is required for each TEC.
Figure 6: On/Off Wiring Diagram (See Table 2 for Terminal Identification)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
9
Page 10
Notes:
FIG:Mode l 1 Wiring_ fl oa ting_out put
Zone Temp
Thermistor
SupplyTemp
Switch
24 V
Vin
Common
R SEN
24V
NET COM
COS
VSF
COM
SupplyTemp
Thermistor
EC Motor
or
24 V
High
Med
FAN H
AUX
TB1
CLG C
Low
Fan
on
Fan
Heating
FAN M
FAN L
AUX
FIG:Model 1 Wiring_floating_ input
Open
Hot
Close
Open
Hot
Close
•For VAV and 2-pipe systems, connect the valve to the heating output.
•Only one transformer is required for each TEC.
Figure 7: Floating Wiring Diagram (See Table 2 for Terminal Identification)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
10
Page 11
Note: VAV and 2-pipe systems should connect their valve to the heating output.
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjuste d on Actuator)
Floating
Actuator
COS
COM
24V
HTG O
HTG C
FIG:model_1_cln
g_onl
y
FIG:model_ 1_htng_c lng_chngvr
Changeover
Sensor
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjuste d on Actuator)
Floating
Actuator
Supply Air
Temperature Sensor
COS
COM
24V
HTG O
HTG C
FIG:model_1_htng_clng_chngvr_rht
Changeover
Sensor
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjuste d on Actuator)
Heating/Cooling
and On/Off
Duct Heater
Floating
Actuator
Supply Air
Temperature Sensor
1
C
COS
COM
24V
HTG O
HTG C
AUX
AUX
Figure 8: Floating Control (Pressure-Dependent VAV)
Figure 9: Floating Control (Pressure-Dependent VAV with Changeover Sensor/Switch)
Figure 10: Floating Control (Pressure-Dependent VAV with Changeover Sensor/Switch and Reheat)
Note: Power to the AUX contact comes from the reheat coil.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
11
Page 12
Note: VAV and 2-pipe systems should connect their valve to the heating output.
FIG:mode l_1_htn g_clng_h drnc
Room Temperature
Control Thermostat
COS
COM
24V
HTG O
HTG C
FIG:model_1_ htng_cl ng_hdrnc _chngvr
Floating
Heating/Cooling
Valve
Optional Wat er
Supply Sensor
Room Temperature
Control Thermosta t
Supply Water
Temperature Sensor
COS
COM
24V
HTG O
HTG C
Two-Pipe Applications
Four-Pipe Applications
FIG:model_1_onoff
COM
24V
COM
24V
Cooling
Valve
Heating
Valve
Triac Switch
Triac Switch
Triac Switch
Figure 11: Floating Control Two-Pipe Heating and Cooling Hydronic Valve Control Fan Coil Application
Figure 12: Floating Control Two-Pipe Heating and Cooling Hydronic Valve Control with Changeover Fan
Coil Application
Figure 13: Floating Control (On/Off Two-Pipe and Fo ur-Pipe Fan Coil Applications)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
12
Page 13
Note: VAV and 2-pipe systems should connect their valve to the heating output.
Two-Pipe ApplicationsFour-Pipe Applications
FIG:model_1_floating
COM
24V
CLG O
Cooling
Valve
Heating
Valve
CLG C
HTG O
HTG C
COM
24V
HTG O
Heating/Cooling
Valve
HTG C
Triac Switc hTriac Switch
Triac Switc hes
AUX Contact
FIG:Aux Contact Wiring
Load
Hot
19 to 30 VAC
FIG:Binary Input Wiring
BI1
Dry Contact
Bi2
Dry Contact
Figure 14: Floating Control (Floating Two-Pipe and Four-Pipe Fan Coil Applications)
Figure 15: AUX Contact Wiring
Figure 16: Binary Input Wiring
Setup and Adjustments
IMPORTANT: Table 10 provides a full list of TEC3000 menu settings. In the upcoming sections, step-by-step
instructions are included on how to access and adjust the more commonly used menus.
Overview
Figure 17 shows the thermostat controller home screen. You can customize it to show or hide various elements
from the occupant. See Table 3 for a listing of the touchscreen icons and Table 10 to identify the home screen
settings under the Display Settings. When screen customization is used in conjunction with a passcode, the
building owner can control which options the occupant can access and adjust.
IMPORTANT: If lockout levels are used, some icons are hidden. Table 4 provides details of these levels.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
13
Page 14
Figure 17: Thermostat Controller Home Screen
The humidity level appears on the home screen if there is a humidity sensor in the unit, or if the thermostat
controller has a network override written to it.
Customizing the Home Screen
Customizing the Home screen settings include:
• Brightness• Units• Time Zone• Date
• Enable Backlight• Time• Time Format• Date Format
You can also show or hide these items on the Home screen:
• Fan Button• Off Button• Alarm Indication• Date/Time
• Space Temperature • Hold Button• Occupancy Status
• Humidity• Setpoint• Unit Status
To customize the Home screen:
1. Press the Menu icon.
2. Press Display Settings.
3. Enable or disable elements of the home screen as appropriate for the building owner and occupants.
4. Set the passcode on the thermostat controller to prevent the o ccupants from changing settings th at they should
not have access to change.
Touchscreen Icons
Table 3 describes the home screen touchable icons. Press and release a touchscreen icon to activate the TEC.
Additional touchable icons appear based on the menu, and those icons are also descri bed in Table 3.
Table 3: Touchscreen Icons (Part 1 of 3)
IconIcon NameDescription
Displays the configuration screens where various settings may be adjusted.
Menu
Indicates that the thermostat controller has triggered an alarm.
Alarm
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
14
Page 15
Table 3: Touchscreen Icons (Part 2 of 3)
IconIcon NameDescription
Unit Power
On
Off
Network Communication
Arrow
Run/Hold
No Hold/Hold
Powers the thermostat controller on or off.
Note: This icon disables all equipment control, but does not physically power
down the unit.
Indicates that the thermostat controller detected a supervisory controller and both
are online.
Increases or decreases a value depending on the configuration screen.
Displays the current setpoint. Hold mode is enabled by pressing the button.
Displays the current setpoint. Hold mode is not enabled.
Hold/Hold
Right Arrow
Fan Overrides for
Single-speed Fans
On
Auto
Quiet
Fan Overrides for
Variable-speed Fans
On
Auto
Displays the active setpoint. Hold mode is not enabled.
Proceeds to the next screen.
Adjusts the fan override between On, Auto, and Quiet for single-speed fans.
Adjusts the fan override between On, Auto, and Quiet for variable-speed fans.
Quiet
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
15
Page 16
Table 3: Touchscreen Icons (Part 3 of 3)
IconIcon NameDescription
Fan Overrides for
Multi-speed Fans
Low
Medium
High
Auto
Quiet
Home
Back
Adjusts the fan override between Low, Medium, High, Auto, and Quiet for
multi-speed fans.
Returns the display to the main home screen.
Returns to the previous screen.
Save
Delete
Clear
Wrench
Checkmark
Exclamation Point
Saves the current configuration an d pa r ameter settings.
Deletes the scheduled event.
Clears the password entry on the keypad screen.
Indicates that the value is editable.
Indicates that an event or schedule is programmed for a specific day of the week.
Indicates that an error has occurred.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
16
Page 17
User Lockout
You can select from three different levels of access at the local display to manage functionality through the
supervisory controller. This lockout is independent of any display or passcode settings. The existing temporary
occupancy capability is unaffected by this feature. User lockout hides the icons that are not operable. The lockout
levels are described in Table 4.
Table 4: User Lockout Levels
Lockout LevelCapability
State 0
State 1
State 2
Allows full access to Home Screen Display Adjustments and icons (default).
Hides the Menu icon.
Only allows the screen to trigger temporary occupancy. Menu, Unit Power, the Up
and Down arrows, and Run/Hold are hidden.
Using the USB Port
The USB port allows you to quickly and easily load firmware upgrades, backup settings, and r estore settings to the
TEC3000 by using a USB drive. The TEC3000 can recognize eight configuration files or firmware package files.
The USB drive format must be F AT or FAT32. The drive cannot be NTFS or USB 3.0. If you are upgra ding firmware
or copying configuration files, you need the TEC3000 passcode, if it has been set up. Do n ot remove the USB drive
until the firmware upgrade is complete. The TEC3000 may restart and go offline to the NAE after a firmware
upgrade. The upgrade takes approximately three minutes.
Configurations are copied, except for the Communication mode. See Choosing the Communication Mode (TEC3610-00-000, TEC3611-00-000, TEC3612-00-000, and TEC3613-00-000 Models) to configure each device.
Loading the Firmware
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Load Firmware.
6. Select the correct firmware version. The correct file name has the .pkg extension.
7. Press Confirm if you have the correct firmware version.
The firmware is loaded from the USB drive into the T EC3000 operat ing system. The TEC3000 locates the new
firmware only if the new firmware is on the root drive of the USB drive. See Troubleshooting
if the firmware is
not loaded correctly.
8. Remove the USB drive from the TEC3000 controller when the update is complete.
The TEC3000 firmware update is complete when the TEC3000 restarts and returns to the home screen.
Backing Up the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Backup.
A message appears stating that the file is saved locally and on a USB drive.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
17
Page 18
6. Press Confirm to save locally and on USB.
The setting files are named based on the TEC3000 model nam e, date , an d tim e sta m p
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive’s root directory.
See Troubleshooting
if the settings are not backed up correctly.
7. After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Restoring the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration file created from a previous backup operation.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive’s root directory.
7. Press Confirm if you have the correct file name.
The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive, remove the USB drive from the TEC3000.
Choosing the Communication Mode
(TEC3610-00-000, TEC3611-00-000, TEC3612-00-000, and
TEC3613-00-000 Models)
1. Ensure the TEC screen is on.
2. Press the Menu icon.
3. Press Network Setup.
4. Press FC Comm Mode.
5. Select BACnet or N2 by pressing .
6. Proceed to Step 7 to perform BACnet communication and Step 15 to perform N2 communication.
7. Press
8. Press BACnet Instance ID.
9. Enter the unique BACnet® instance ID using the keypad. This value should be dif f erent to the other controlle rs
on the site.
10. Press Save.
11. Press to return to the previous screen.
12. Press BACnet Address.
13. Enter the BACnet MS/TP address through the keypad.
to return to the previous screen.
14. Press Save.
15. After selecting N2 in Step 5, press Save.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
18
Page 19
16. Press to return to the previous screen.
17. Press N2 Address.
18. Enter the N2 address through the keypad.
19. Press Save.
Configuring the Thermostat Controller
Use the Menu icon on the home screen to access and change the basic operating parameters of the thermostat
controller. During normal operation, press the Menu icon once to access the following parameters:
• Faults Status• Display Settings• Equipment Setup• Controller Information
• Setpoints• Control Setup• System Status• Commissioning
• Schedule• Network Setup• Control Status• Update
Installer Configuration Menu
The thermostat controller comes from the factory with default settings for all configuration parameters. The UI
menu navigation and default settings are shown in Table 10. Before any outputs turn on, the controller must be
configured for the equipment connected. You need to start from the home screen to per form any of the following
tasks.
Screen Reset
The current screen returns to the home screen if the current screen is not touched for 3 minutes.
Selecting the Unit Type
There are three unit types. They are:
•4-pipe—This unit type has both heating and cooling coils pl us a supply fan. This config uration can also be used
on configurations that are heating or cooling only.
•2-pipe—This unit type has a single set of pipes that can serve hot or chilled water plus a supply fan. The
Supply Temp Type allows for the conn ection of an analog sensor or an aquastat to a binary input. Based on th e
water temperature or aquastat state, the unit controls heating or cooling.
•VAV—This unit type is designed for a pressure-dependent zone damper and the supply fan outputs are
disabled. The TEC senses the supply air temperature coming from the unit. The Supply Temp Type setting
allows for the connection of an analog sensor or binary duct thermostat. Based on the air temperature or duct
thermostat state, the zone damper controls for heating or cooling. Th e TEC does n ot control the unit d elivering
the air. The logic needs to be part of another controller.
By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or
Pressure-Dependent VAV mode:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press General.
4. Press Unit Type and select 2-pipe, 4-pipe, or VAV.
5. Pressto save and
to return to the previous screen.
Note: Selecting VAV reboots the controller in order to apply the change.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
19
Page 20
Selecting the Heating and Cooling Device Type
By default, the thermostat is configured for On-Off (2-position) control. This can be changed to Floating
(Incremental) mode when the Unit Type is not set to VAV. For VAV mode, only floating actuators are supported
and this option is unavailable. To change the Heating/Cooling Device Type:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press General.
4. Press Htg/Clg Device Type and select On-Off or Floating. Changing this option reboots the controller in
order to apply the change.
5. Pressto save and
to return to the previous screen.
When in Floating mode, the Actuator Stroke Time must also be set to match the equipment. To set the actuator
stroke time:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press General.
4. Press Actuator Stroke Time and adjust accordingly.
5. Pressto save and
to return to the previous screen.
Configuring the Supply Fan - Fan Coil Only
On fan coil units (2-pipe or 4-pipe), three different types of supply fans are supported. These are single-speed fa ns,
multi-speed fans (up to three discrete speeds), and VSF using a 0 to 10 V control signal and an optional bin ary on/
off command. Note that fan control is not available when in VAV mode. To select the fan type:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Supply Fan Type and select Single Speed, Multi-Speed, or Variable Speed.
5. Pressto save and
to return to the previous screen.
For multi-speed fan control, you can adjust the point when the medium or high speed turns on. The fan speed is
based on the load on the cooling/heating device, and is a percentage between 0 and 100. By default, the Med
Speed On Cmd is 33% and the High Speed On Cmd is 66%. When only two fan speeds are used, you must set the
High Speed On Cmd to 100% to disable the third speed and set the Med Speed On Cmd to 50%. To adjust these
values:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Medium Speed On Cmd and adjust accordingly.
5. Press High Speed On Cmd and adjust accordingly.
6. Pressto save and
to return to the previous screen.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
20
Page 21
For VSF control, the output is configurable for any range between 0 V and 10 V. The parameters are Start Voltage,
Full Speed Voltage, and Minimum Command. Start Voltage is the volta ge output at which the fan begins running,
and Full Speed Voltage is the voltage output at which the fan reaches full speed. Minimum Command is the
percentage of the range between the Start Voltage and the Full Speed Voltage. The fan does not go below the
minimum command when the fan is turned on. By default, the Start Voltage is 2 V, the Full Speed Voltage is 10 V,
and the Minimum Command is 20%.
When the variable speed fan is off, the FAN bina ry output is off an d the voltage a t th e VSF outp ut is 0 V. When the
fan turns on, the FAN binary output turns on and the voltage at the VSF output begins controlling the fan. When the
VSF is configured for reverse acting mode (Start Voltage is above Full Sp eed Voltage), the VSF output goes to th e
lesser of 10 V and 1 V above the Start Voltage when the fan is turned off.
To configure the variable speed parameters:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Supply Fan.
4. Press Start Voltage and adjust accordingly.
5. Press Full Speed Voltage and adjust accordingly.
6. Press Minimum Command and adjust accordingly.
7. Pressto save and
to return to the previous screen.
Setting the Control Mode
The Control Mode informs the controller to run in Cooling only, Heating only, or Automatic mode, based on the
temperature in the zone relative to the heating and cooling setpoints. Control Mode does not override equipment
lockouts or changeover. To set the Control Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Control Mode and select Cooling, Heating, or Auto as desired.
5. Pressto save and
to return to the previous screen.
Setting the Fan Mode - Fan Coil Only
The Fan Mode informs the controller how to handle the fan. There are two options for fan configuration: a Fan
Mode available to the installer through the menu system, and a fan override available as an option to the end user
from the Fan icon on the home screen. See Customizing the Home Screen
disabling end-user controls. The Fan Mode available to the installer is dependent on the fan type. The following
options are provided for single-and variable-speed fans:
•On—Fan is continuously on
•Auto—Fan cycles on demand with the controller entering cooling, heating, or dehumidification modes
for information on enabling and
•Smart—Fan cycles on demand with the controller entering cooling or heating modes during unoccupied
periods but is continuously running during occupied and standby periods
The following Fan Mode options are provided for multi-speed fans:
•Low—Fan is continuously on low
•Medium—Fan is continuously on medium
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
21
Page 22
•High—Fan is continuously on high
•Auto—Fan cycles on demand with the controller entering cooling, heating, or dehumidification modes
•Smart—Fan cycles on demand with the controller entering cooling or heating modes during unoccupied
periods but is continuously running during occupied and standby periods
The Fan Override icon on the home screen is dependent on the fan type. The following options are provided for
single- and variable-speed fans:
•On—Overrides the fan to be continuously on
•Auto—Follows the behavior set as Fan Mode
•Quiet—Follows the behavior set as Fan Mode, but prevents the fan from ever going above minimum speed.
The Quiet option has no effect on equipment with single-speed fans.
The following Fan Override options are provided for multi-speed fans:
•Low—Fan is continuously on low
•Medium—Fan is continuously on medium
•High—Fan is continuously on high
•Auto—Follows the behavior set as Fan Mode
•Quiet—Follows the behavior set as Fan Mode, but prevents the fan from ever going above minimum speed
To set the Fan Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Fan Mode and select On, Auto, or Smart.
5. Pressto save and
to return to the previous screen.
Configuring the Zone Space or Equipment Size - Floating Actuators, Multi-Speed Fans, and
Variable-Speed Fans Only
With non-binary outputs, the TEC3000 is configured by default to have a slower temperature response for larger
zones with normal-sized equipment. In installations with small zones and oversized equipment, set the Equipment
Size parameter to Oversized.
To set the Equipment Size parameter:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Use the up and down arrows to navigate to Equipment Size.
5. Press Equipment Setup and select Oversized.
6. Pressto save and
to return to the previous screen.
Changeover
Pressure-Dependent VAV systems and 2-pipe fan coils require changeover detection in order to switch seasonal
operation between heating and cooling modes. Th e TEC supports the following methods for changeover:
automatic changeover using an analog sensor (thermistor), automa tic changeover using a bi nary switch, or remote
changeover from a BAS and manual changeover.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
22
Page 23
For automatic changeover, a supply temperature sensor or switch must be connected to the Changeover Sensor
(COS) input of the TEC. Changeover Mode must be set to Auto, and Supply Temp Type must be set for Analog
Sensor, Cooling N.C. (cooling when switch is closed), or Heating N.C. (heating when switch is closed). When an
analog sensor is used, the changeover setpoint can be adjusted. The changeover logic applies a 10-degree
Fahrenheit differential to the setpoint. The system switches to cooling mode when the temperature drops be low the
changeover setpoint and remains in cooling mode until the measur ed tempe rature has r isen 10 de grees above the
changeover setpoint.
To configure automatic changeover:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Changeover.
4. Press Changeover Mode and select Auto.
5. Press Supply Temp Type and select Analog Sensor, Cooling N.C., or Heating N.C.
6. Pressto save and
to return to the previous screen.
Additionally, the thermostat controller supports manual changeover. To configure manual changeover:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press General.
4. Press Changeover.
5. Press Changeover Mode and select Heating or Cooling.
6. Pressto save and
to return to the previous screen.
You need to ensure that the Supply Temp type is set to Analog Sensor. The Changeover Mode is also exposed to
the BAS through the CGOVR-MODE and can be commanded from the BAS.
On 2-pipe/VAV systems without an automatic changeover, or on 4-pipe systems, you can use COS as a
monitor-only point for reading an analog sensor. By setting the controller in 4-pipe mode, or selecting Heating or
Cooling for Changeover Mode, the controller defaults to monitor-only mode for the COS and exposes the value to
the network as the supply temperature.
Dehumidification Control - Fan Coil Only
The TEC3000 controller support dehumidification control on fan coil devices under three configurations:
•4-pipe fan coil
•4-pipe fan coil with reheat
•2-pipe fan coil (with changeover in cooling mode) with reheat
For optimal dehumidification performance, a 4-pipe unit with floating/incremental or 0 to 10 V control and a multispeed or variable-speed fan is recommended.
Dehumidification operates when the zone humidity increases abo ve the zone humidity setp oint and the controller is
in the Idle or Cooling state. Dehumidification does not operate during heating and stops if the zone temperature
drops below the heating setpoint. When dehumidification is active, the cooling device controls to the humidity
setpoint, and the heating device reheats the zone in order to keep the temperature at the cooling setpoint. While in
the dehumidification mode, a multi-speed or variable-speed fan runs at the lowest possible speed to maximize
condensation and moisture removal across the cooling coil.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
23
Page 24
To enable dehumidification control:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Dehum Enable and select Yes.
5. Pressto save and
to return to the previous screen.
This point is also exposed to the BAS through the point DEHUM-EN.
To adjust the de hu m idification setpoint:
1. Press the Menu icon.
2. Press Setpoints.
3. Press Dehumidification and adjust accordingly.
4. Pressto save and
to return to the previous screen.
This point is also exposed to the BAS through the point DEHUM-SP.
Temperature Setpoints
The thermostat controller provides a flexible setpoint configuration to give power to the building owner while being
easy to use by the occupant. In addition to a simple up/down offset adjustment on the home screen for the
occupant, there are six temperature setpoints on the TEC. The six temperature setpoints are Cooling and Heating
setpoints for Occupied, Unoccupied, and Standby modes. To set these setpoints:
1. Press the Menu icon.
2. Press Setpoints.
3. Select the setpoint to adjust and change as desired.
4. Pressto save and
to return to the previous screen.
Note: The TEC enforces a 2-degree deadband between heating and cooling setpoints. If a setpoint violates this
standard (for example, cooling setpoint is set to 70 with a heating setpoint already set to 70), the o pposing setpoint
is modified to comply with this deadband (in the previous example, the heating setpoint would automatically
change to 68).
The occupant has access to an up/down adjustment from the home screen. This adjustment applies a fixed offset
(+/-) to the currently active setpoint, and this offset holds until the occupancy state of the controller changes. If the
user taps the setpoint on the home screen, the icon inverts and displays white text on a black icon. The offset is
held throughout all occupancy periods. For example, if the TEC is cooling in Occup ied mode to an oc cupied cooling
setpoint of 72 and you raise the setpoint 2 degrees to 74 from the home screen and then select hold, then the +2
degree offset persists through an occupancy chang e. If the occupancy then changes to un occupied, with a setp oint
of 80 degrees, the effective setpoint is 82 degree s. This allows the occupant to have a small amount of control over
raising or lowering the temperature, but the building owner can still set back setpoints during standby and
unoccupied periods. When the setpoint is in Hold mode, pre ssing the icon again releases the hold and immediately
sets the setpoint offset back to 0.
When the TEC is in Min/Max mode (Setpoints/Occ Setpoint Select are equal to Min and Max Setpoint), the TEC
rejects any attempts to change the present valu e ou ts ide of the valid range. If the present value is outside of the
valid range (for example, if the Occ Setpoint Select is switched from Setpoint Offset to Min and Max Setpoint), the
present value is reset to be in the center of the valid range.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
24
Page 25
The four modes of setpoint operation are described in Figure 5.
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Individual Setpoints
Occ Setpoint Select =
Setpoint Offset and
Heat Cool Setpoint Mode =
Common Setpoint
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Common Setpoint
This is the default mode and the original mode of operation that the TEC was released with
(the next three modes are new). In this mode, the TEC has a heating setpoint and a cooling
setpoint. There is a common Setpoint Offset (warmer/cooler adjust) that is applied to each
setpoint simultaneously. The range of setpoint adjustment is two-fold:
• There are large constant ranges bounding the individual heating and cooling setpoints.
• There is also a smaller configurable range limit set to the Setpoint Offset point (Control Setup > General > Max Setpoint Offset).
In this mode, the TEC has a heating setpoint and a cooling setpoint. Each setpoint has a
configurable range (Setpoints > Min Cooling Setpoint, Max Cooling Setpoint, Min Heating Setpoint, and Max Heating Setpoint). The configurable range values are bounded
by the larger constant bounds used in Setpoint Offset mode and are constrained in the
following manner: Min must be below Max and Heating must be below Cooling, so in order
from least to greatest, the values are: Min Heating Setpoint, Max Heating Setpoint, Min
Cooling Setpoint, and Max Cooling Setpoint.
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Offset and Heat Cool Setpoint Mode = Individual Setpoints.
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.
Configuring Occupancy
The TEC3000 controller supports a wide variety of occupancy sources to adapt to nearly any application.
•Local stand-alone weekly scheduler
•Remote schedule from BAS
•Occupancy sensor (internal or remote)
•Occupancy binary input (configurable)
•Manual occupancy override
•Temporary occupancy (by interacting with the screen while in unoccupied mode)
•Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 6.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
25
Page 26
Enumerations may not match the TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat
Controllers with Dehumidification Capability Installation Instructions (Part No. 24-10787-6), TEC3000 Series
Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability Installation
Instructions (Part No. 24-10788-0), TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers
Installation Instructions (Part No. 24-10789-5), and TEC3000 Series Field-Selectable BACnet MS/TP or N2
Networked Thermostat Controllers Technical Bulletin (LIT-12011956) for NAE releases prior to 7.x.
Table 6: Occupancy Determination
Sequence of Operation (Highest to Lowest Priority)Status Indicated
Manual
1.Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current
state of the BI when configured as Occupancy.
2.True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when
the schedule is not Occupied.
3.When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occup ied, the Manual
Occupancy Mode is not No Override, or an Occupancy BI is configured.
4.Built-in occupancy sensing (PIR) or EI configured for Motion NO or Motion NC.
5.Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and
the Schedule is writing Not Set as the schedule.
Selecting Schedule Source
Scheduling
The TEC3000 thermostat controller can operate as a stand-alone unit with an internal schedule or scheduled with
an external schedule. The OCC-CONFIG object sets the method used for scheduling.
If the OCC-CONFIG is set to External, the NET-OCC object is used to control the unit externally.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
26
Page 27
If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object, which sets the
Occupancy Schedule command.
Note: If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set to Schedule, you
can control the unit with the LOCAL-OCC object externally; however, we do not recommend this method.
See Table 7 for scheduling information.
Once the Occupancy Schedule command is set, the effective occupancy is determined by settings shown in the
Occupancy Determination table. See Table 6.
Table 7: BAS Objects for Scheduling
BAS Objects for Scheduling
OCC-CONFIGLOCAL-OCC
(Commanded by
NET-OCCOccupancy Schedule
Command
1
Internal Schedule)
ExternalAny State
(Internal Schedule in
Control)
ScheduleOccupiedNot ApplicableOccupied
UnoccupiedUnoccupied
StandbyStandby
Not SetNot Set
OccupiedOccupied
UnoccupiedUnoccupied
StandbyStandby
Not SetNot Set
1.The effective occupancy can be affected by other factors listed in Table 6.
The occupancy schedule comes from either the weekly scheduler built into the TEC or as an input from the BAS.
The Schedule Source must be selected to tell the controller where to read the occupancy source from. To select
the schedule source:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Schedule Source and select Schedule (Local) or External (BAS).
5. Pressto save and
to return to the previous screen.
This option is also exposed to the BAS through the point OCC-CONFIG. If BAS is configured as the occupancy
source, map the point NET-OCC in and write to that point to control the schedule remotely. If the supervisor goes
offline (as identified by the network icon going away on the home screen of the TEC), the control logic
automatically falls back to the local schedule as the occu pancy source. If that schedule is not set, the default
occupancy is continuously occupied.
Setting the Local Schedule
A weekly occupancy schedule with up to four occupancy events for each day can be set locally on the TEC and
operate independently of a supervisor. To set the schedule:
1. See Selecting Schedule Source
to ensure the schedule source is set to Local.
2. Press the Menu icon.
3. Press Schedule.
4. Press Set Schedule.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
27
Page 28
5. Select the days to which the schedule should apply. Note that if events are already set for the selected days,
they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears
in the event box. See Figure 18.
6. Select the event to be set. See Figure 18.
7. Set the Occupancy to Not Set, Occupied, Unoccupied, or Standby and press Save.
IMPORTANT: Internally, the TEC 3000 uses a BACnet schedule where daily schedules are independent of the
previous and next days. The default occupancy of the TEC3000 from the factory is set to Occupied. As a result,
a daily event at 12:00 AM must be scheduled if you do not want the controller to transition to Occupied Mode at
midnight.
Figure 18: Selecting the Days (Left) and Selecting the Event (Right)
Figure 19: Setting the Room Occupancy (Left) and Setting the Occupancy Mode (Right)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
28
Page 29
8. Set the time to the time at which the event should occur and press Save.
Figure 20: Setting the Event Time (Left) and Viewing the Event Time (Right)
9. Press Save to save the event and press the Return icon to return to the main scheduler screen.
Figure 21: Returning to the Main Menu
10. Pressto save and
to return to the previous screen.
Overriding the Occupancy Mode
The TEC supports a manual override of all other schedule sources (for example, Schedule, Occupancy BI, and
temporary occupancy). To override the Occupancy Mode:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Manual Occupancy Mode and select Occupied, Unoccupied, or No Override.
5. Pressto save and
This option is also exposed to the BAS through the point OCCOVRD-MODE.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
to return to the previous screen.
Capability Installation Instructions
29
Page 30
Enabling Optimal Start
The TEC supports an advanced optimal start algorithm. The algorithm works in conjunction with a local schedule to
pre-heat or pre-cool the zone before scheduled occupancy periods begin, in order to bring the zone to the desired
occupied setpoint when the scheduled occupan cy p er iod b egins. Occu pan t comfort is en sure d while au to matically
minimizing energy usage. This algorithm creates a model of the zone being cont rolled and automatically
determines when to start the equipment before the scheduled transition to Occupied. The start time automatically
adjusts daily to minimize the time between reaching setpoint and entering Occupied state.
Note: Optimal Start does not work when the schedule source is set to External.
To enable this feature:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Optimal Start Enable and select Yes.
5. Pressto save and
to return to the previous screen.
Enabling the Motion Sensor (TEC3x11-00-000, TEC3x13-00-000 Models)
By default on models with integral motion sensing capability, the motion sensor is enabled with a default timeout of
15 minutes from the last detection of motion in the zone. On models without an integrated sensor, the default
timeout is still 15 minutes, but it only is applied when one of the two configurable binary inputs is set to be a motion
sensor (see Configurable Binary Inputs
for information on configuring the binary inputs). To disable motion se nsing
capabilities, set the Motion Sensor Timeout to 0 minutes. See Table 6 to view the available setpoints. See Table 10
to view the setpoint values. To adjust the motion sensor timeout:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Motion Sensor Timeout and adjust accordingly.
5. Pressto save and
to return to the previous screen.
PID/PRAC+ Automatic Control Tuning
The TEC3000 features advanced proportional-integral-derivative (PID) control algorithms to maximize control
performance while minimizing excessive cycling and wear on the equipment. PID is used in conjunction with a
Multi-Stage Controller (MSC) for all occupied and standby control.
Additionally, the PID features Johnson Controls proprietary PRAC+ (Pattern Recognition Adaptive Control)
automatic tuning, which continuously tunes the controller parameters to automatically optimize the control
performance to match the equipment and zone. By default, PRAC+ is enabled and immediately begins to tune. To
reset tuning at any time to the factory defaults:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Press Reset PID Tuning and select Yes.
5. Pressto save and
to return to the previous screen.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
30
Page 31
PRAC+ automatic tuning can also be disabled. When disabled, the controller pa rameters remain at their last values
until automatic tuning is re-enabled. To disable automatic tuning:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Press Temp Control Setup.
5. Select Manual PID Tuning (or any option listed in Table 8).
6. Pressto save and
to return to the previous screen.
As a result of disabling PRAC+ Automatic Tuning, you have access to different types of manual tuning that allows
modifications of tuning parameters listed under Control Setup > General in Table 8.
Table 8: TEC3000 Tuning Types
Tuning TypeDes cription
Automatic PID TuningAutomatic tuning in an existing TEC3000
Deadband OverrideDirectly specify the deadband used by the PID algorithm
Manual PID TuningManual tuning of Heating and Cooling PIDs. The manual tuning parameters are listed
On/Off ControlBinary control
under Control Setup > Tuning in Table 10.
Note: For more details on PID/PRAC+ Automatic Control Tuning, refer to the Controller Tool Help (LIT-12011147).
Configurable Binary Inputs
The thermostat controller supports up to two configurable binary inputs (BIs) that can be used to add additional
features to the system. Configurable Binary Inputs are accessed through Settings > Control Setup > Inputs. Both
BIs can be configured to support the following options:
•Disabled—Sets the binary input to an unused state. When disabled, you can use the binary input for
monitoring-only without affecting the thermostat functionality.
•Open Window—Sensor to shut down control if a window is opened. The controller disables control 60 second s
after detecting an opened window.
•Open Door—Works in conjunction with the Motion NO/Motion NC sensor to control occupancy
•Fan Lock—Air Proof switch input to shut down control if no airflow is detected within 10 seconds of turning the
fan on. Fan Lock must be manually reset from the Faults menu.
•Service—Input from the equipment to display a service warning on the thermostat
•Dirty Filter—Input from the equipment to display a dirty filter fault on the thermostat
•Motion NC—External motion sensor with a closed contact output when no motion is detected
•Motion NO—External motion sensor with an open contact output when no motion is detected
•Temp Occ—Trigger to place controller into Temporary Occupancy mode
•Occupancy—Direct override of Occupied and Unoccupied
•Supply Fan Status—Input from the equipment to display a Supply Fan Fault. When Fan Alarm Action is set to
Shutdown and the Supply Fan Fault is active, the TEC3000 disables the fan, heating, and cooling. When the
Fan Alarm Action is set to Enable and the Supply Fan Fault is active, the TEC3000 allows the fan, heating, and
cooling to operate during the Supply Fan Fault.
Setting both BIs to the same function is supported for all except Occupancy, Fan Lock, Open Door, and Open
Window. If both BIs are set the same for those four, BI2 is ignored and only BI1 is used.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
31
Page 32
The Open Door option works in conjunction with a motion sensor, either built into the TEC or connected to another
BI configured for Motion NO/NC mode.
When the door is open, motion detected by the sensor is ignored. Note that opening the door does not stop an
Occupied period started by the motion sens or prio r to op e nin g th e do or.
The polarity of the inputs are provided in Table 9.
Table 9: Input Polarities
BI ConfigurationContact OpenContact Closed
OccupancyUnoccupiedOccupied
Temp OccNo Tr igger Active
Open DoorDoor Open, UnoccupiedDoor Closed, Occupied
Open WindowWindow Open, Control Shut DownWindow Closed, Control Running
Supply Fan StatusSupply Fan OffSupply Fan On
1.Configurations that support both BIs configured for the same feature of the action that occurs when either of
The TEC has an auxiliary output that can be configured to operate in a few different ways. The Aux Mode supports
seven different options:
•Not Used—Output is always off
•Occupied NO—Output is normally open, but closes when occupied
•Occupied NC—Output is normally closed, but opens when occupied
•Occupied Fan NO—Output is normally open, but is closed when occupied with the fan running
•Occupied Fan NC—Output is normally closed, but is open when occupied with the fan running
•On—Output is turned on (relay closed), used by a BAS to directly control the AUX output
•Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Aux Mode and set accordingly.
5. Pressto save and
This option is also exposed to the BAS through the point AUX-MODE.
to return to the previous screen.
When the Reheat installed parameter is set to True, the Aux output is used for Reheat Output. The setting for the
Aux Mode is ignored when reheat is enabled.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
32
Page 33
Commissioning Mode
The thermostat controller has a built-in commissioning mode, which is designed to allow you to quickly test
equipment wiring and functionality. Commissioning mode temporarily disables the control logic, and allows you to
manually command any individual output. Commissioning is designed to be the last step of the installation process
after configuring the controller for the equipment being controlled, and the available options in commissioning
mode are dependent on the controller configuration. To enter commissioning mode:
1. Press the Menu icon.
2. Select Commissioning.
3. Confirm that the selection was intentional. (The control is overridden upon selecting Confirm).
Individual outputs can be commanded through this interface. For binary outputs, the options are Off or On; for
analog outputs, they can be commanded from 0 to 100%. Whenever a control output is turned on, the fan is
engaged for safety purposes. To command an output from the Commissioning menu:
1. Select the output to command. Adjust the value to the desired output and press Save. The ou tp ut immed iately
changes to that value.
2. Restore the value to the original setting and press Save once again to complete testing that output.
Pressing the back icon from the main commissioning menu or allowing the menu system to time out and return to
the home screen ends commissioning and puts the control logic back in control of the outputs.
Sensor Priority
The TEC3000 supports various sources of sensor data for use in control or display, including internal sensors,
remote sensors (connected using an analog input), or network commanded sensors. The TEC uses the highest
priority connected input (network commands followed by remote sensors and then internal se nsors) for control and
display. Not all sources are available for all sensors.
Network commands operate on a timeout basis. When a network point is written to by a supervisor, the point
becomes the highest priority for 15 minutes. If a new up date is written within 15 minutes, the timer is restarted for
another 15 minutes.
Available Fault Diagnostics
•Supply Fan Faults—The TEC3000 supports a configurable Supply Fan Status feedback input that turns on
when the Supply Fan Status does not match the Supply Fan Command, and can be configured to disable
heating, cooling, and fan commands. The alarm delay is adjustable through the Fan Alarm delay setting. If the
delay is set to 0 or the binary input is not defined, this feature becomes disabled.
•Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the
limit is exceeded, an alarm turns on. This feature is intended to be used as a maintenance reminder. Setting
the runtime limit to 0 disables this feature.
•Supply Air Temperature Diagnostics—The TEC3000 supports diagnostics when you have a Supply Air
Temperature installed. The TEC3000 monitors the supply air. If you call for cooling or heating and the
temperature does not fall or rise by at least the supply air temperature alarm offset value within the supply air
temperature alarm delay, an alarm is generated. If the monitoring occurs while cooling, a cooling ineffective
alarm is generated. If the monitoring occurs while heating, a heating ineffective alarm is generated. If you set
the supply air temperature offset value set to 0, this alarm is disabled.
•Zone Tempera tu re Alarm—When enabled, the user can se t a low and high temperature alarm; and if the zone
temperature rises or falls below those limits, an alarm is generated.
•Trends—Built-in tr ends exist for many of the inputs and outputs for the TEC3000. These tren ds are viewable at
the TEC. The analog graph displays data in 15-minute increments over the previous 24 hours or a table with
the last 25 data points. Binary trends display 25 samples taken at every change of state.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
33
Page 34
Menus and Submenus
In the following table, the * indicates that the menus depend on your configuration.
Table 10: Menus and Submenus (Part 1 of 9)
Level 1Level 2
(LCD Screen Name)
SetpointsOcc Cooling Setpoint72°F (22°C)55 to 85°F (13 to 30°C)
Occ Heating Setpoint68°F (20°C)55 to 85°F (13 to 30°C)
Unocc Cooling Setpoint80ºF (27°C)55 to 85°F (13 to 30°C)
Unocc Heating Setpoint60°F (15°C)55 to 85°F (13 to 30°C)
Stby Cooling Setpoint74°F (23°C)55 to 85°F (13 to 30°C)
Stby Heating Setpoint66°F (19°C)55 to 85°F (13 to 30°C)
Dehumidification*50% RH0 to 100% RH
Occ Setpoint SelectSetpoint OffsetMin and Max Setpoint or Setpoint Offset
Heat Cool Setpoint ModeIndividual
Max Heating Setpoint*68°F (20°C)The range (in degrees) from the Min
Min Heating Setpoint*60°F (15°C)45°F (7.22°C) to Max Heating Setpoint
Max Cooling Setpoint*80ºF (27°C)Min Cooling Setpoint to 100°F (37.77°C)
Min Cooling Setpoint*72°F (22°C)T he range (in degrees) from the Max
Max Setpoint*80ºF (27°C)Min Setpoint to 100°F (37.77°C)
Min Setpoint*60°F (15°C)45°F (7.22°C) to Max Setpoint
Level 3
(Default Values)
Setpoints
Available Values
*Dehumidification Enable = True
Common Setpoint or Individual Setpoint
Heating Setpoint temperature to the Min
Cooling Setpoint temperature minus 1°F
(0.55°C). (The cooling temperature
always needs to be 1°F [0.55°C] above
the heating temperature.)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select
== Min and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select
== Min and Max Setpoint.
Heating Setpoint temperature plus
1°F (0.55°C) to the Max Cooling Setpoint
temperature.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select
== Min and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
1
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
34
Page 35
Table 10: Menus and Submenus (Part 2 of 9)
Level 1Level 2
(LCD Screen Name)
ScheduleSchedule Options
Set Schedule
Optimal Start EnableNoYes or No
Temp Occ Duration120 minutes0 to 300 minutes
Motion Sensor Timeout15 minutes0 to 240 minutes
Brightness Setting80 to 10 (most dim to brightest)
Enable Backlight TimeoutYesYes or No
UnitsIPIP or SI
TimeN/A
Time ZoneCentralAll World Time Zones
Set Time Format24 hour24 hour or 12 hour
DateN/A
Set Date FormatYYYY-MM-DDYYYY-MM-DD, or Day, Month DD, YYYY,
LanguageEnglishEnglish, French, Spanish
Show Fan IconYesYes or No
Show TempYesYes or No
Show HumidityYesYes or No
Show Off IconYesYes or No
Show Hold IconYesYes or No
Show SetpointYesYes or No
Show AlarmsYesYes or No
Show Occ StatusYesYes or No
Show Unit StatusYesYes or No
Show Date/TimeYesYes or No
Control SetupGeneral
Control ModeAutoAuto, Cooling, or Heating
Unit EnableEnableEnable or Shutdown
Fan Mode*SmartOn, Auto, and Smart for single- and
Max Setpoint Offset30 to 20 degrees (°F or °C based on Units
Fan On Delay*30 seconds0 to 120 seconds
Level 3
Available Values
(Default Values)
—See Scheduling
0 = PIR sensor disabled
*Passcode Enable = Yes
or MM-DD-YYYY
variable-speed fans. Low, Medium, High,
Auto, and Smart for multi-speed units.
* Fan coil units only
setting under Display Settings menu)
* Fan coil units only
1
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
35
Page 36
Table 10: Menus and Submenus (Part 3 of 9)
Level 1Level 2
(LCD Screen Name)
Control Setup
(Cont)
Fan Off Delay*30 seconds0 to 120 seconds
Frost ProtectionYesYes or No
Dehumidification Enable*NoYes or No
Aux ModeNot UsedNot Used, Occupied NO, Occupied NC,
Load Shed Rate Limit0.066°F 0 to 1°F (0 to 0.5°C)
Load Shed Adjust4°F0 to 8°F (0 to 4°C)
Fan Alarm Delay0 seconds0 to 300 seconds
Fan Alarm Delay0 seconds0 to 300 seconds
Fan Alarm Action*EnableEnable or Shutdown
Fan Alarm Reset*NoYes or No
Fan Runtime Limit0 hours0 to 9,000 hours
Fan Runtime Reset*NoYes or No
Supply Air Temperature Alarm Offset0°F0 to 10°F (0 to 5.5°C)
Supply Air Temperature Alarm Delay*300 seconds300 to 3,600 seconds
Unocc Low Speed FanDisableEnable or Disable
Inputs
BI1 ConfigurationDisabledDisabled, Open Window, Open Door, Fan
BI2 ConfigurationDisabledDisabled, Open Window, Open Door, Fan
negative temperature coefficient (NTC),
10k ohm NTC, 10k ohm NTC Type 3
* SAT Mode = Analog Sensor,
non four-pipe
under Display Settings menu)
* Analog Sensor
10k ohm NTC, 10k ohm NTC Type 3
under Display Settings menu)
1
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
36
Page 37
Table 10: Menus and Submenus (Part 4 of 9)
Level 1Level 2
(LCD Screen Name)
Control Setup
(Cont)
Humidity Offset0% RH-15% to 15% RH
Reset SensorsFalseTrue or False
Zone Temp Alarm EnabledNoYes or No
Zone Temp Low Limit55°F32 to 150°F (0 to 65.56°C)
Zone Temp High Limit90°F32 to 150°F (0 to 65.56°C)
Tuning
Temp Control Setup*Automatic PID
Reset PID TuningNoYes or No
Deadband*0.7 to 1.5°F1.0°F (-17.22 °C)
Auto Economizer TuningEnableDisable or Enable
Heat Prop Band*160°F5 to 10°F (-15 to -1.11°C)
Heat Integral Time*729 seconds300 to 1,600 seconds
Heat Process Range*40°F10 to 100°F (-12.22 to 37.77°C)
Heat Saturation Time*600 seconds60 to 900 seconds
Heat Time Constant*720 seconds360 to 1,440 seconds
Heat Process Dead Time*72 seconds20 to 120 seconds
Heat Period*60 seconds30 to 120 seconds
Cool Prop Band*160°F5 to 10°F (-15 to -1.11°C)
Cool Integral Time*729 seconds300 to 1,600 seconds
Level 3
(Default Values)
Tuning
Available Values
Automatic PID Tuning, Manual PID
Tuning, Deadband Override, On/Off
Control
* Available when Heating/Cooling Device
Type = On-Off and Supply Fan Type =
Single
*Functionally, this is the PID deadband
when the T emp Control Setup is equal to
the Deadband Override or Manual PID
Tuning. When the Temp Control Setup
equals the On/Off Control, the Deadband
is used for the On/Off range of the stage
equipment. This parameter is hidden
when Temp Control Setup equals
Automatic PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
1
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
37
Page 38
Table 10: Menus and Submenus (Part 5 of 9)
Level 1Level 2
(LCD Screen Name)
Control Setup
(Cont)
Network SetupFC Comm ModeBACnet/MSTPBACnet/MSTP, N2
Cool Process Range*40°F10 to 100°F (-12.22 to 37.77°C)
Cool Saturation Time*600 seconds60 to 900 seconds
Cool Time Constant*720 seconds360 to 1,440 seconds
Cool Process Dead Time*72 seconds20 to 120 seconds
EFF-SETPOINT
EFF-ZNH
B1 Status
B2 Status
EFF-OAT
EFF-SAT
FANSPD-S
CLG1-C
CLG2-C
HTG1-C
HTG2-C
OAD-O
HTG-O
CLG-O
Level 3
Available Values
1
(Default Values)
* Fan coil units only, variable-speed fan
* Fan coil units only, multi-speed fan
* Fan coil units only, multi-speed fan
* VAV units with reheat installed
*Fan coil units with reheat installed
* Reheat installed
* Reheat installed
* Non 4-Pipe units
* Changeover Mode = Auto
* Supply temp type = analog sensor
10k ohm NTC, 10k ohm NTC Type 3
* Supply temp type = analog sensor
* Supply temp type = analog sensor
—-50 to 250°F (-45.56 to 121.11°C)
—45 to 100°F (7.22 to 37.78°C)
—0 to 100%RH
—On or Off
—On or Off
—-50 to 250°F (-45.56 to 121.11°C)
—-50 to 250°F (-45.56 to 121.11°C)
—On or Off
—On or Off
—On or Off
—On or Off
—On or Off
—0 to 100%
—0 to 100%
—0 to 100%
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
40
Page 41
Table 10: Menus and Submenus (Part 8 of 9)
Level 1Level 2
(LCD Screen Name)
System StatusOccupancy SourceLocal ScheduleOccupancy BI
Unit StatusCoolingSystem Fault
Supply Air Temperature75°F-50 to 250°F (-45 to 121°C)
Changeover StateSupply
Zone Temp SourceInternal SensorUnreliable
Control StatusCooling % Command0%0 to 100%
Heating % Command0%0 to 100%
Reheat % Command0%0 to 100%
Cool Stage 1OffOn or Off
Heat Stage 1OffOn or Off
Reheat Stage 1OffOn or Off
Fan % Command0%0 to 100%
FanOnOn or Off when Supply Fan Type =
Level 3
(Default Values)
Temperature
Unreliable
Available Values
Temp Occ BI
Temp Occ
Occ Override
Local Schedule
BAS Schedule
Occupancy Sensor
Airflow Fault
Open Window
Control Off
Unreliable Temperature
Dehumidification
Idle
Cooling
Heating
Cooling Unavailable
Heating Unavailable
Cooling Unavailable due to Changeover
Cooling Unavailable due to OA Temp
Cooling Unavailable due to Control Mode
Heating Unavailable due to Changeover
Heating Unavailable due to OA Temp
Heating Unavailable due to Control Mode
Changeover Disabled
Cooling Mode
Heating Mode
Supply Temperature Unreliable
Internal Sensor
Remote Sensor
Network Override
Input Not Installed
Single-speed or Variable-speed
Off, Low, Medium, or High when Supply
Fan Type = Multi-speed
1
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
41
Page 42
Table 10: Menus and Submenus (Part 9 of 9)
Level 1Level 2
(LCD Screen Name)
Controller InfoModel NameTEC3x1x-xx—
Software Versionx.x.x.xxxx—
Unit NameTECxxxxx—
Device Name—User-Supplied
Device DescriptionTEC3000
CommissioningSupply Air Temperatur eDisplay Current
Heat Command0%0 to 100%
Cool Command0%0 to 100%
Supply FanNoYes or No
AuxNoYes or No
UpdateView Versionx.x.x.xxxxCurrent Release of Software
Load Firmware
Restore*
Backup*
Level 3
Available Values
(Default Values)
—
—
Temperature
—File list from USB drive
—File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar
models to expedite the commissioning
process.
—File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar
models to expedite the commissioning
process.
1
1.If the value is outside min/max limits, it is reassigned to the midpoint between min and max.
Troubleshooting
Table 11: Fault List (Part 1 of 3)
FaultsProbable CausesSolutions
Remote Zone Temp FailThe External Zone T emperature sensor
has been disconnected or has failed.
Supply Temp FailThe External Supply Temperature
sensor has been disconnected or has
failed.
Internal Sensor FailAn internal sensor has failed on the
TEC.
1. Check the wiring of the sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
1. Check the wiring of the sensor.
2. If intentionally disconnected, result fault by
entering the menu, enter Control Setup, and
select Inputs to reset the sensors.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
42
Page 43
Table 11: Fault List (Part 2 of 3)
FaultsProbable CausesSolutions
Dehum UnavailableDehumidification is unavailable
because the zone humidity sensor has
failed or the humidity reading is not
reliable.
ServiceEquipment connected to the BI
configured for a Service alarm is
triggering the alarm.
Dirty FilterEquipment connected to the BI
configured for a Dirty Filter alarm is
triggering the alarm.
Calibration CorruptFactory calibration data is lost or is not
installed.
Changeover FailThe Supply Temperature Sensor is not
installed, has failed, or has been
disconnected and the TEC can no
longer detect changeover mode to cool
or heat.
Zone Temp UnreliableAll sources of zone temper at ure are
unreliable, including the onboard
sensor.
Open WindowThe switch connected to the BI
configured for Open Window is sensing
that the window is opened, and control
has shut down.
Fan LockThe switch connected to the BI
configured for Fan Lock did not sense
airflow within 10 seconds of starting the
fan, and control has been shut down.
Humidity UnreliableThe zone humidity reading was reliable
and has now failed.
Controller FaultThe controller has detected an internal
fault that it cannot recover.
An unknown error has prevented the
controller from turning on.
1. If the sourc e of zone humidity was a BAS,
check the BAS to ensure that it is still online
and is providing the TEC with the humidity
reading. If removal of the BAS mapping was
intentional, reset the sensors through the
menu.
2. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Service the equipment by way of the
manufacturer's recommendation.
Replace the filter in the equipment as explained in
the manufacturer's instructions.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Follow the same steps as Supply Temp Fail
alarm.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
1. Close the window to resume control.
2. Check sensor functionality with an ohmmeter,
and verify the wiring to the TEC.
3. Order replacement units and return the
affected devices to Johnson Controls under
the RMA program.
1. Inspect equipment to ensure fan functions.
2. Check sensor functionality with an ohmmeter,
and verify wiring to the TEC.
3. Reset fault by entering the menu, selecting
Fault Status, and selecting the Fan Lock.
4. Order replacement units and return the
affected devices to Johnson Controls under
the RMA program.
1. If the source of zone humidity was the
onboard sensor, contact Johnson Controls
product sales and support.
2. If the source of zone humidity was a BAS,
check the BAS to ensure that it is still online
and providing the TEC with the humidity
reading. If removal of the BAS mapping was
intentional, reset sensors through the menu.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
43
Page 44
Table 11: Fault List (Part 3 of 3)
FaultsProbable CausesSolutions
Touchscreen UnavailableThe touchscreen components have
failed to initialize.
Board MismatchThe baseboard and CPU board are
paired incorrectly . An error message
appears on the TEC indicating the
model number of the baseboard and
CPU board.
Firmware MismatchThe previous upgrade has not
completed.
The previous downgrade has not
completed because the previous
version is no longer supported.
USB MalfunctionA USB drive has malfunctioned and
drawn more than the maximum allowed
current.
Supply Fan Runtime Limit
Extended
Heating IneffectiveThe Supply Air Temperature has not
Cooling IneffectiveThe Supply Air Temperature has not
Supply Fan FaultThe Supply Fan Status configured for
Zone Temperature Too Cold The Zone Temperature has decreased
Zone Temperature Too HotThe Zone Temperature has increased
The Supply Fan Runtime has exceeded
the configured Supply Fan Runti m e
Limit.
increased above the configured Supply
Air Temperature Alarm Offset while
heating has been active for at least the
Supply Air Temperature Alarm Delay.
decreased below the configured Supply
Air Temperature Alarm Offset while
cooling has been active for at least th e
Supply Air Temperature Alarm Delay.
either BI1 or BI2 has not proved within
the configured Fan Alarm Delay.
below the configured Zone Temp Lo w
Limit.
above the configured Zone Temp High
Limit.
1. Reboot the controller.
2. If problems persist, or de r rep l a c em ent units
and return the affected devices to Johnson
Controls under the RMA program.
Match the baseboard to its corresponding CPU
board. See Repair Information
ensuring that you have the CPU board and base
board paired correctly.
1. Upgrade the TEC3000 to the latest released
version.
2. Upgrade the TEC3000 to the current version
again.
Reboot the TEC3000 to clear the fault.
1. Attempt to insert and use the USB drive
again.
2. Try a new USB drive.
3. If problems persist, or de r rep l a c em ent units
and return the affected devices to Johnson
Controls under the RMA program.
1. Service the Supply Fan.
2. Reset the Supply Fan runtime.
Verify that the heating elements on the rooftop
are functioning properly.
Verify that the cooling elements on the rooftop are
functioning properly.
1. Verify that the Supply Fan is operating when
turned on.
2. Verify that the Supply Fan Status wiring is
connected correctly.
Verify that the TEC and the RTU heating are
enabled and functioning.
Verify that the TEC and the RTU cooling are
enabled and functioning.
for information on
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
44
Page 45
Table 12: Troubleshooting Details1 (Part 1 of 2)
SymptomProbable CausesSolutions
The controller displays Idle with a
Unit Status of Cooling
Unavailable due to Changeover
despite being above cooling
setpoint, or with a status of
Heating Unavailable due to
Changeover despite being below
the setpoint.
The controller displays Idle with a
Unit Status of Cooling
Unavailable due to Control Mode
despite being above cooling
setpoint, or with a status of
Heating Unavailable due to
Control Mode despite being below
the setpoint.
The staged equipment shuts off
above the cooling setpoint or below
the heating setpoint when the PID
is running on the TEC. If the unit is
in On/Off Control mode, this does
not apply.
The staged equipment cycles too
rapidly or too slowly when the PID
is running on the TEC.
The controller provides an error
when trying to upgrade firmware.
The TEC3000 zone temperature
does not change fast enough
compared to the measured zone
temperature from a verification
device (a calibrated sensor).
The 2-pipe fan coil/VAV system
does not have a changeover
sensor and switch connected, or
the sensor/switch has failed.
The changeover temperature is
sensing a hot supply, but the
controller is requesting cooling.
Changeover temperature is
sensing a cold supply, but the
controller is requesting heating.
The Control Mode is set to
Cooling Mode, but the controller
is requesting heating.
The Control Mode is set to
Heating Mode, but the controller
is requesting cooling.
The PID control algorithm
minimizes overshoot and energy
usage for the particular
equipment and zone, and may
cycle the equipment prior to
reaching setpoint.
The control band around the
setpoint is determined by the
minimum on/off times and is set
incorrectly for the equipment,
zone, or user preference. There
is a tradeoff between reduced
control band size and increased
energy usage and equipment
wear from increased cycling.
The firmware on the USB drive is
below the minimum required
version.
Error code 1025.
The TEC3000 is configured by
default for larger spaces with
normal-sized equipment when a
proportional device is active.
1. Check the wiring of the supply temperature
sensor/switch.
2. Verify that the changeover is set up correctly
for the type of sensor attached (sensor or
switch).
1. Verify that the supply is not in heating mode. If
it is, nothing can be done from the TEC.
2. Check the wiring of the supply temperature
sensor or switch.
3. Check the placement of the supply
temperature sensor or switch.
4. Verify that the changeover is set up correctly
for the type of sensor attached (sensor or
switch).
1. Verify that the supply is not in cooling mode. If
it is, nothing can be done from the TEC.
2. Check the wiring of the supply temperature
sensor or switch.
3. Check the placement of supply temperature
sensor or switch.
4. Verify that the changeover is set up correctly
for the type of sensor attached (sensor or
switch).
Change the Control Mode to Auto or Heating.
Change the Control Mode to Auto or Cooling.
Expected behavior.
1. V erify that equipment minimum on/off times are
set correctly.
2. If the default deadband around the setpoint
does not provide the desired temperature
control, set Temp Control Setup to Deadband
Override and set the Deadband parameter to
the desired value.
Please use firmware version 3.0.2.xxxx or higher.
A reboot is required to clear the Firmware
Mismatch fault that occurs.
Select Control Setup >Tuning > Equipment Size > Oversized.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
45
Page 46
Table 12: Troubleshooting Details1 (Part 2 of 2)
SymptomProbable CausesSolutions
The zone space temperature
increases or decreases too much
when the unit is active in
unoccupied mode.
The controller provides an error
when trying to back up settings.
The controller provides an error
when trying to restore settings from
a backup.
The controller is unable to access a
USB drive.
The controller displays Board Mismatch.
The controller displays Controller Fault.
The Bell icon is displayed on the
TEC home page.
Partial Restore Complete is
displayed when trying to restore
settings from a backup file.
The temperature displayed is lower
than the actual room temperature.
The Online icon does not appear
for a networked controller.
Some icons are hidden.Lockout levels are used or the
The heating and cooling
equipment are too big for the
unoccupied space.
The USB drive is defective.Try a different USB drive.
The USB drive is defective.Try a different USB drive.
The Restore file is corrupt.Try restoring a different backup file.
The Restore file is from an
incompatible model TEC.
The drive is formatted as NTFS
or another unsupported format.
The TEC supports FAT and
FAT32 formats only.
The USB drive is defective.Try a different USB drive.
The I/O board that the display
board is currently attached to
does not match the one that
initially shipped with the display
board.
A hardware failure is causing the
two boards to incorrectly identify
themselves.
An internal fault was detected
and the controller was unable to
recover.
The fault has been detected on
the TEC.
Not all of the items in the backup
file have been restored. This
error can be caused by a value
being out of the minimum or
maximum range in the backup
file. It may also occur if there are
inconsistencies in the reliability of
a setting in the backup file and on
the TEC device.
Cold air drafts are entering the
back of the TEC.
Air is being forced through the
TEC from a nearby vent.
There is improper field bus
wiring.
icons are hidden due to the
display settings.
Decrease the Unoccupied Off Delay parameter
from 10 minutes to a more appropriate time for the
equipment configuration.
Ensure that the backup file being restored was
from the same model TEC.
Reformat the USB drive, or try a different USB
drive with a supported format.
Attach the display board to the correct I/O board.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
See Table 11 for TEC fault causes and resolution.
1. Create a Backup file on a USB drive for the
TEC that is showing the issue.
2. Edit the backup file created in the previous
step on a PC to reflect the desired settings.
3. Verify that the modified values are within
minimum and maximum range in the backup
file.
4. Restore the settin gs from the newly edited
backup file on the TEC.
Seal any holes behind the TEC to reduce drafts.
Move the location of the TEC or change the
venting to prevent air from being forced through
the TEC.
Refer to the MS/TP Communications Bus
Technical Bulletin (LIT-12011034).
See Table 4 for lockout levels and access details.
1.For common MS/TP troubleshooting information, refer to the MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
46
Page 47
Repair Information
If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a
replacement thermostat controller, contact the nearest Johnson Controls representative.
Technical Specifications
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability (Part 1 of 2 )
Power Requirements19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
USB Port Power Rating120 to 250 mA current draw supported
Relay Contact
Rating
Fan Relay Output Rating19 to 30 VAC, 1.0 A maximum, 15 mA minimu m, 3.0 A in-rush
Auxiliary Output Rating/Triac
Output
Binary InputsDry contact across terminal COM to terminals BI1, BI2, or COS
Analog InputsNickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
Temperature Sensor TypeLocal 1k ohm platinum sensor
Wire Size18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
MS/TP Network GuidelinesUp to 100 devices maximum for each Network Automati on Engine (NAE);
Temperature
Range
AccuracyTemperature±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Minimum Deadband2F°/1C° between heating and cooling
Occupancy Sensor Motion
Detection (Occupancy Sensing
Models)
Ambient
Conditions
Compliance BACnet
On/Off or
Floating Control
Backlit Display-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating Control40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control54.0°F/12.0°C to 100.0°F/38.0°C
Humidity±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Operating32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
Storage-22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
International
United StatesUL Listed, File E27734, CCN XAPX, Under UL60730
CanadaUL Listed, File E27734, CCN XAPX7, Under E60730
EuropeCE Mark – Johnson Controls declares that this product is in compliance
Australia and
New Zealand
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
terminal COM to terminals R SEN or COS
4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP Technical Bulletin for
the Metasys, FX, or Verasys system installed.
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability (Part 2 of 2 )
Shipping
Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
Models without
Occupancy
Sensor
Models with
Occupancy
Sensor
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
European Single Point of Contact:NA/SA Single Point of Contact:APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Published in U.S.A.www.johnsoncontrols.com
JOHNSON CONTROLS
507 E MICHIGAN ST
MIL WAUKEE WI 53202
USA
Capability Installation Instructions
48
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.