Johnson Controls TEC3312, TEC3320, TEC3311, TEC3330, TEC3323 Installation Instructions Manual

...
TEC3000 Series On/Off or Floating Fan Coil and Individual
(barcode for factory use only)
24-10787-6, Rev. F
*24107876F*
Zone Thermostat Controllers with Dehumidification Capability
Installation Instructions
TEC3310-xx-xxx, TEC3311-xx-xxx, TEC3312-xx-xxx, TEC3313-xx-xxx,TEC3610-xx-xxx, TEC361 1-xx-xxx, TEC3612-xx-xxx, TEC3613-xx-xxx
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers are stand-alone and field-selectable BACnet® MS/TP or N2 networked devices that provide control of the following:
pressure-dependent variable air volume (VAV) equipment with or without local reheat
two- or four-pipe fan coils
cabinet unit heaters
other individual zone equipment using an on/off or floating control input The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control. All models include a USB port configuration that reduces installation time by allowing simple backup and restore features from a USB drive, which enables rapid cloning of configuration between like units.
Part No. 24-10787-6, Rev.
Issued July 2018
F
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick and easy. Multiple fan configurations are supported for fan coil equipment types:
single-speed
multi-speed (two or three discrete speeds)
variable-speed/EC motors (0 to 10 VDC control) Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates dehumidification control as necessary. Heat and/or reheat is used as required to maintain the space temperature. For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers with Dehumidification Capability
Installation Instructions
1
IMPORTANT: The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precaution s must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller.
IMPORT ANT : Le TEC3000 Series Thermosta t Controller est destiné à tr ansmettre de s données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du thermostat controller risque de provoquer des blessures ou d'endomma ger l'équipement contrôlé ou un autre équipement, la conception du système de con tr ôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection ag ainst har mful inter fere nce in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment of f and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna .
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Canada
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
Parts Included
one TEC3000 Series Thermostat Controller with integral mounting base
one installation instructions sheet
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
2
Location Considerations
Figure 1: Thermostat Controller
Shown without Occupancy Sensor,
Dimensions, in. (mm)
FIG:thermostat features
USB Port
Display
Securit y Sc r ew
1-13/32
(36)
4-23/32
(120)
5-5/8 (143)
Locate the TEC3000 Series Thermostat Controller:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature, allowing for vertical air circulation to the TEC
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, stairwells, and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated passive infrared (PIR) models, be sure that the thermostat controller is located centrally, where occupant movement is frequent.
Use insulating foam pads for installations where wiring passes through the wall to the thermostat.
Note: Allow for sufficient clearance to insert a USB drive into the USB port.
IMPORTANT: Only connect memory devices to the USB port. Do not use it for charging external devices.
Installing the Thermostat Controller
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls® T-4000-119 Allen-Head Adjustment Tool (order separately) to remove the security screw if it is installed on the top of the thermostat controller cover as illustrated in Figure 2.
2. Pull the top edge of the cover and open the thermostat controller as illustrated in Figure 2.
IMPORTANT: The cover is not secured on the bottom. Be careful not to drop the cover.
IMPORTANT: If you are installing more than one thermostat controller, keep track of which cover attaches to
which base.
IMPORTANT: Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid damage to the electronic circuits of the thermostat controller.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
3
Figure 2: Removing the Security Screw from the Thermostat Controller Cover
FIG:security s crew
FIG:thermo stat cove r
(Shown without Occupancy Sensor) (Left) and Removing the Thermostat Controller Cover (Right)
3. Align the thermostat controller mounting base on the wall with the security screw on the top and use the base as a template to mark the two mounting hole locations. See Figure 3.
Notes:
If you need to install the thermostat controller on an electrical junction box, use
2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures that you have enough space for cabling, if needed.
For surface-mounted applications, use durable mounting hardware, such as wall anchors, that cannot be
easily pulled out of the mounting surface.
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the center hole in the thermostat controller mounting base. See Figure 3.
5. Secure the mounting base to the wall surface using two mounting screws (user supplied) as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
4
Figure 3: Mounting Hole Locations, Dimensions, in. (mm) (Left) and
4-1/16
(103)
FIG:TEC Backpl ane2
3-1/4
(83)
FIG:TEC Backplane1
Securing the Thermostat Controller Mounting Base to the Wall (Right)
Wiring
When an existing thermostat controller is replaced, remove and lab el the wires to identify the terminal functions.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly conn ected wires may result in permanent damage to the equipment.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC3000 Series Thermostat Controller.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
5
IMPORTANT: Use proper ESD precautions during installation and servicing to avoid damage to the electronic
EOL Switch
EOL Switch
O N
FIG:TEC Backplane2_EOL Switch
O N
FIG:cl ose ther mosta t cover
circuits of the thermostat controller.
To wire the the r mo st at co nt ro ller :
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 2 and Figure 6 or Figure 7.
Note: For more details on wirin g the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature
readings.
3. Reattach the communication wires to the terminal block. Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together before
inserting them into the terminal connectors.
4. Set the bus end-of-line (EOL) termination switch to the desired location on the TEC3610-00-000, TEC3611-00-000, TEC3612-00-000, and TEC3613-00-000 models only.
The bus EOL termination switch allows you to designate the thermostat controller as the end of the Field Controller (FC) Bus and N2 Bus. The default position is OFF. If the thermostat controller is at the end of a daisy chain of devices on the FC Bus and N2 Bus, set the EOL switch to the ON position. See Figure 4.
Figure 4: EOL Switch Position (Left) and Installing the Thermostat Controller Cover (Right)
O N
ON Position
OFF Position
FIG:EOL_Swt ch
5. Reattach the thermostat contro ller cove r to the mounting base (bottom side first).
IMPORTANT: Make sure you reattach the cover that corresponds to its correct base. The CPU board number needs to match the base board number. base that do not belong together (as shown in Figure 5). See Table 1 on page 7 for TEC3000 model names and
Otherwise, an operation error occurs after you reattach a cover and
code numbers.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
6
Figure 5: Error Code Indicating
Mismatched Boards
Table 1: TEC3000 Model Names and Code Numbers
1
Name
Code Number
CPU Board
Base Board
Name
TEC3310 00 TEC3610 0A TEC3311 01 TEC3611 0B TEC3312 02 TEC3612 0C TEC3313 03 TEC3613 0D TEC3320 04 TEC3620 0E TEC3321 05 TEC3621 0F TEC3322 06 TEC3622 10 TEC3323 07 TEC3623 11 TEC3330 08 TEC3630 12 TEC3331 09 TEC3631 13
1. The two-character code number is listed within the error code to indicate that the CPU board and base board do not belong together. However, if the same code number appears as both the CPU board and base board, there is no error. For example, if 0B is listed as the CPU board and the base board, the model is the TEC3611.
Code Number
6. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool (order separately) to reinstall the security screw on the top of the thermostat controller cover. See Figure 2 for security screw placement.
7. Remove the protective plastic cover sheet from the display.
1
IMPORTANT: If the display is dirty, gently wipe it clean with isopropyl alcohol or ethyl alcohol. Do not scrub
hard as to avoid damaging the surface. Do not use other cleaners such as water, ketones, and aromatic solvents, since they may damage the polarize r.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
7
Table 2: Terminal Identification (See Figure 6 and Figure 7 for Wiring Diagrams)
Terminal Label Function
TEC3310, TEC3311, TEC3312, TEC3313 Floating FC/VAV and On/Off FC
24 V 24 VAC hot from transformer FAN H Fan high FAN M Fan medium FAN L Fan on (single-speed, variable speed), Fan low (multi-speed) AUX Auxiliary binary output AUX Auxiliary power
2
COM CLG O Cool open (Floating), Cooling NC (On/Off), Triac CLG C Cool close (Floating), Cooling NO (On/Off), Triac HTG O Heat open (Floating), Heating NC (On/Off), Triac HTG C Heat close (Floating), Heating NO (On/Off), Triac
2
COM VSF Variable speed fan command (configurable 0 to 10 V range) BI2 Configurable binary input 2 BI1 Configurable binary input 1 COS Changeover sensor R SEN Remote zone temperature sensor NET+ Not connected Field bus+/N2+ NET- Not connected Field bus-/N2- NET COM Not connected Isolated common for field bus
24 VAC common from transformer
Common
1
TEC3610, TEC361 1, TEC3612, TEC3613 Floating FC/VAV and On/Off FC
1
1. There is no support for an On and Off VAV.
2. The common terminals, which do not include NET COM, are internally connected and can be used for all inputs and outputs.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
8
Notes:
Zone Temp Thermistor
Supply Temp
Switch
FIG:Model 1 Wiring_on _off_out put
24 V
R SEN
24V
NET COM
COS
VSF
COM
Supply Temp
Thermistor
Vin
Common
or
24 V
High
Med
FAN H
AUX
TB1
CLG C
Low
Fan
on
Fan
Common Hot
Heating
Common Hot
FAN M
FAN L
AUX
FIG:Model 1 Wiring_on_off_input
N.C.
Common Hot
Common Hot
N.O.
VAV and 2-pipe systems should connect their valve to the heating output.
Only one transformer is required for each TEC.
Figure 6: On/Off Wiring Diagram (See Table 2 for Terminal Identification)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
9
Notes:
FIG:Mode l 1 Wiring_ fl oa ting_out put
Zone Temp Thermistor
SupplyTemp
Switch
24 V
Vin
Common
R SEN
24V
NET COM
COS
VSF
COM
SupplyTemp
Thermistor
EC Motor
or
24 V
High
Med
FAN H
AUX
TB1
CLG C
Low
Fan
on
Fan
Heating
FAN M
FAN L
AUX
FIG:Model 1 Wiring_floating_ input
Open Hot
Close
Open Hot
Close
For VAV and 2-pipe systems, connect the valve to the heating output.
Only one transformer is required for each TEC.
Figure 7: Floating Wiring Diagram (See Table 2 for Terminal Identification)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
10
Note: VAV and 2-pipe systems should connect their valve to the heating output.
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjuste d on Actuator)
Floating
Actuator
COS
COM
24V HTG O HTG C
FIG:model_1_cln
g_onl
y
FIG:model_ 1_htng_c lng_chngvr
Changeover
Sensor
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjuste d on Actuator)
Floating Actuator
Supply Air
Temperature Sensor
COS
COM
24V
HTG O
HTG C
FIG:model_1_htng_clng_chngvr_rht
Changeover
Sensor
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjuste d on Actuator)
Heating/Cooling
and On/Off
Duct Heater
Floating Actuator
Supply Air
Temperature Sensor
1
C
COS COM 24V HTG O HTG C AUX
AUX
Figure 8: Floating Control (Pressure-Dependent VAV)
Figure 9: Floating Control (Pressure-Dependent VAV with Changeover Sensor/Switch)
Figure 10: Floating Control (Pressure-Dependent VAV with Changeover Sensor/Switch and Reheat)
Note: Power to the AUX contact comes from the reheat coil.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
11
Note: VAV and 2-pipe systems should connect their valve to the heating output.
FIG:mode l_1_htn g_clng_h drnc
Room Temperature Control Thermostat
COS
COM
24V
HTG O
HTG C
FIG:model_1_ htng_cl ng_hdrnc _chngvr
Floating
Heating/Cooling
Valve
Optional Wat er Supply Sensor
Room Temperature Control Thermosta t
Supply Water
Temperature Sensor
COS
COM
24V HTG O HTG C
Two-Pipe Applications
Four-Pipe Applications
FIG:model_1_onoff
COM
24V
COM
24V
Cooling
Valve
Heating
Valve
Triac Switch
Triac Switch
Triac Switch
Figure 11: Floating Control Two-Pipe Heating and Cooling Hydronic Valve Control Fan Coil Application
Figure 12: Floating Control Two-Pipe Heating and Cooling Hydronic Valve Control with Changeover Fan
Coil Application
Figure 13: Floating Control (On/Off Two-Pipe and Fo ur-Pipe Fan Coil Applications)
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
12
Note: VAV and 2-pipe systems should connect their valve to the heating output.
Two-Pipe Applications Four-Pipe Applications
FIG:model_1_floating
COM
24V
CLG O
Cooling
Valve
Heating
Valve
CLG C
HTG O
HTG C
COM
24V
HTG O
Heating/Cooling
Valve
HTG C
Triac Switc h Triac Switch
Triac Switc hes
AUX Contact
FIG:Aux Contact Wiring
Load
Hot
19 to 30 VAC
FIG:Binary Input Wiring
BI1
Dry Contact
Bi2
Dry Contact
Figure 14: Floating Control (Floating Two-Pipe and Four-Pipe Fan Coil Applications)
Figure 15: AUX Contact Wiring
Figure 16: Binary Input Wiring
Setup and Adjustments
IMPORTANT: Table 10 provides a full list of TEC3000 menu settings. In the upcoming sections, step-by-step
instructions are included on how to access and adjust the more commonly used menus.
Overview
Figure 17 shows the thermostat controller home screen. You can customize it to show or hide various elements from the occupant. See Table 3 for a listing of the touchscreen icons and Table 10 to identify the home screen settings under the Display Settings. When screen customization is used in conjunction with a passcode, the
building owner can control which options the occupant can access and adjust.
IMPORTANT: If lockout levels are used, some icons are hidden. Table 4 provides details of these levels.
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
13
Figure 17: Thermostat Controller Home Screen
The humidity level appears on the home screen if there is a humidity sensor in the unit, or if the thermostat controller has a network override written to it.
Customizing the Home Screen
Customizing the Home screen settings include:
• Brightness • Units • Time Zone • Date
• Enable Backlight • Time • Time Format • Date Format
You can also show or hide these items on the Home screen:
• Fan Button • Off Button • Alarm Indication • Date/Time
• Space Temperature • Hold Button • Occupancy Status
• Humidity • Setpoint • Unit Status
To customize the Home screen:
1. Press the Menu icon.
2. Press Display Settings.
3. Enable or disable elements of the home screen as appropriate for the building owner and occupants.
4. Set the passcode on the thermostat controller to prevent the o ccupants from changing settings th at they should not have access to change.
Touchscreen Icons
Table 3 describes the home screen touchable icons. Press and release a touchscreen icon to activate the TEC. Additional touchable icons appear based on the menu, and those icons are also descri bed in Table 3.
Table 3: Touchscreen Icons (Part 1 of 3)
Icon Icon Name Description
Displays the configuration screens where various settings may be adjusted.
Menu
Indicates that the thermostat controller has triggered an alarm.
Alarm
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
14
Table 3: Touchscreen Icons (Part 2 of 3)
Icon Icon Name Description
Unit Power On
Off
Network Communication
Arrow
Run/Hold
No Hold/Hold
Powers the thermostat controller on or off. Note: This icon disables all equipment control, but does not physically power
down the unit.
Indicates that the thermostat controller detected a supervisory controller and both are online.
Increases or decreases a value depending on the configuration screen.
Displays the current setpoint. Hold mode is enabled by pressing the button.
Displays the current setpoint. Hold mode is not enabled.
Hold/Hold
Right Arrow
Fan Overrides for Single-speed Fans
On
Auto
Quiet Fan Overrides for
Variable-speed Fans
On
Auto
Displays the active setpoint. Hold mode is not enabled.
Proceeds to the next screen.
Adjusts the fan override between On, Auto, and Quiet for single-speed fans.
Adjusts the fan override between On, Auto, and Quiet for variable-speed fans.
Quiet
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
15
Loading...
+ 33 hidden pages