Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers are stand-alone and
field-selectable BACnet® MS/TP or N2 networked devices that provide control of the following:
•unitary rooftop units (RTUs)
•unitary RTUs with economizers
•unitary RTUs with heat pumps
•unitary RTUs with economizers and heat pumps
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control.
All models include a USB port configuration that reduces installation time by allowing simple backup and restore
features from a USB drive, which enables rapid cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick
and easy. Only the single-speed fan configuration is supported for fan coil equipment types.
F
IMPORTANT: The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under
normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal
injury or property damage to the controlled equipment or other property, additional precautions must be
designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat
controller.
IMPORTANT: Le TEC3000 Series Thermostat Controller est destiné à transmettre des données entrantes à un
équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement
du thermostat controller risque de provoquer des blessur es ou d'endommager l'équipe ment contrôlé ou un autre
équipement, la conception du système de con tr ôle doit intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en
cas de défaillance ou de dysfonctionnement du thermostat controller.
TEC3000 Series Single- or Two-Stage Economizer Thermostat
Controllers Installation Instructions
1
Page 2
North American Emissions Compliance
Figure 1: Thermostat Controller
Shown without Occupancy Sensor,
Dimensions, in. (mm)
FIG:thermostat f eatures
USB Port
Display
Securit y Sc rew
1-13/32
(36)
4-23/32
(120)
5-5/8
(143)
United States
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide r easonable p rotectio n against harm ful interfe rence in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenn a .
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
Canada
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Installation
Parts Included
•one TEC3000 Series Thermostat Contr oller with integral mounting base
•one installation instructions sheet
Location Considerations
Locate the TEC3000 Series Thermostat Controller:
•on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature, allowing for vertical air circulation to
the TEC
•away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills,
stairwells, and from behind doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated passive infrared (PIR) models, be sure
that the thermostat controller is located centrally,
where occupant movement is frequent.
Use insulating foam pads for installations where wiring
passes through the wall to the thermostat.
Note: Allow for sufficient clearance to insert a USB drive into the USB port.
IMPORTANT: Only connect memory devices to the USB port. Do not use it for charging external devices.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
2
Page 3
Installing the Thermostat Controller
FIG:security screw
FIG:ther mostat cover
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls® T-4000-119 Allen-Head Adjustment Tool (order
separately) to remove the security screw if it is installed on the top of the thermostat controller cover. See
Figure 2.
2. Pull the top edge of the cover and open the thermostat controller as illustrated in Figure 2.
IMPORTANT: The cover is not secured on the bottom. Be careful not to drop the cover.
IMPORTANT: If you are installing more than one thermostat controller, keep track of which cover attaches to
which base.
IMPORTANT: Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid
damage to the electronic circuits of the thermostat controller.
Figure 2: Removing the Security Screw from the Thermostat Controller Cover
(Shown without Occupancy Sensor) (Left) and Removing the Thermostat Controller Cover (Right)
3. Align the thermostat controller mounting base on the wall with the security screw on the top and use the base
as a template to mark the two mounting hole locations. See Fig ur e 3.
Notes:
•If you need to install the thermostat controller on an elec trical junction box, use
2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers and avoid smaller 1-1/2 x 4 in.
(38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures that you have enough
space for cabling, if needed.
•For surface-mounted applications, use durable mounting hardware, such as wall anchors, that cannot be
easily pulled out of the mounting surface.
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the center hole in the
thermostat controller mounting base. See Figure 3.
5. Secure the mounting base to the wall surface using two mounting screws (user supplied) as illustrated in
Figure 3.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
3
Page 4
Note: Be careful not to overtighten the mounting screws.
4-1/16
(103)
FIG:TEC Backpl ane2
3-1/4
(83)
FIG:TEC Backplane1
Figure 3: Mounting Hole Locations, Dimensions, in. (mm) (Left) and Securing the Thermostat Controller
Mounting Base to the Wall (Right)
Wiring
When an existing thermostat controller is replaced, remove and label the wires to identify the terminal functions.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
électrique.
Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly conn ected
wires may result in permanent damage to the equipment.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un
court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
4
Page 5
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not
EOL Switch
EOL Switch
O
N
FIG:TEC Backplane2_EOL Switch
O
N
FIG:close thermos tat cover
exceed the electrical ratings of the TEC3000 Series Thermostat Controller.
IMPORTANT: Use proper ESD precautions during installation and servicing to avoid damage to the electronic
circuits of the thermostat controller.
To wire the thermostat controller:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in
Table 2 and Figure 7.
Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus
Technical Bulletin (LIT-12011034).
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature
readings.
3. Reattach the communication wires to the terminal block.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together before
inserting them into the terminal connectors.
4. Set the bus end-of-line (EOL) termination switch to the desired location on the TEC3630-00-000 and
TEC3631-00-000 models only.
The bus EOL termination switch allows you to designate the thermostat controller as the end of the Field
Controller (FC) Bus and N2 Bus. The default position is OFF. If the thermostat controller is at the end of a daisy
chain of devices on the FC Bus and N2 Bus, set the EOL switch to the ON position. See Figure 4.
Figure 4: EOL Switch Positions (Left) and Installing the Thermostat Controller Cover (Right)
O
N
ON Position
5. Reattach the thermostat controller cover to the mounting base (bottom side first).
OFF Position
FIG:EOL_Swt ch
IMPORTANT: Make sure you reattach the cover that corresponds to its correct base. The CPU board number
needs to match the base board number.
Otherwise, an operation error occurs after you reattach a cover and
base that do not belong together (as shown in Figure 5). See Table 1 for TEC3000 model names and code
numbers.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
1.The two-character code number is listed within the error code to
indicate that the CPU board and base board do not belong together.
However, if the same code number appears as both the CPU board
and base board, there is no error. For example, if 0B is listed as the
CPU board and the base board, the model is the TEC3611.
6. Use a 1/16 in. (1.5 mm) Allen wrench or
Johnson Controls T-4000-1 19 Allen -Head Adjustment
Tool (order separately) to reinstall the security screw
on the top of the thermostat controller cover.
7. Remove the protective plastic cover sheet from the
display.
Code Number
1
Name
Code Number
1
IMPORTANT: If the display is dirty, gently wipe it
clean with isopropyl alcohol or ethyl alcohol. Do not
scrub hard as to avoid damaging the surface. Do not
use other cleaners such as water, ketones, and
aromatic solvents, since they may damage the
polarizer.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
6
Page 7
Table 2: Terminal Identification (See Figure 7 for Wiring Diagram)
Terminal LabelFunction
TEC3330, TEC3331TEC3630, TEC3631
24 V24 V AC hot from the sensor
Y1Cooling stage 1
Y2Cooling stage 2
OADEconomizer
AUXAuxiliary binary output
AUXAuxiliary
W1 OBHeating 1 (RTU mode)/Reversing valve (O/B) (Heat Pump mode)
1
RH
W2 SUPHeating 2 (RTU mode)/Supplemental heat (Heat Pump mode)
OATOutside air temperature
2
COM
GFan
BI2Configurable binary input 2
BI1Configurable binary input 1
SATSupply temperature sensor
R SENZone temperature sensor
NET+Not connectedField bus+/N2+
NET-Not connectedField bus-/N2-
NET COMNot connectedIsolated common for field bus
Power for W1 and W2
Common
1.RH needs to be connected for W1 and W2 to energize. For heating systems with an isolated power
supply, connect RH to the R terminal of the heating system. For systems that switch the hot supply
to the heating commands, jumper to 24 V. For systems that switch the neutral supply to the heating
commands, jumper to COM.
2.The common terminals, which do not include NET COM, are internally connected and can be used
for all inputs and outputs.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
7
Page 8
Note: Only one transformer is required for each TEC.
Thermistor
FIG:Model 3 Wiring_outpu t
24 V
R SEN
24V
NET COM
SAT
OAD
COM
Supply/Aux
Thermistor
Vin
Common
Economizer
24 V
Cool 1
Cool 2
Y1
AUX
TB1
W2 SUP
Y2
G
AUX
FIG:Model 3 Wiring_inpu t
Common
RH
W1 OB
Outdoor Air Temp
Heat 1
Figure 7: Staged Wiring Diagram - Rooftop Unit (See Table 2 for Terminal Identification)
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
8
Page 9
Note: Only one transformer is required for each TEC.
Thermistor
FIG:Model 3 Wiring_outpu t
24 V
R SEN
24V
NET COM
SAT
OAD
COM
Supply/Aux
Thermistor
Vin
Common
Economizer
24 V
Compressor
1
Compressor
2
Y1
AUX
TB1
W2 SUP
Y2
G
AUX
FIG:Model 3 Wiring_inpu t_heatp ump
Common
RH
W1 OB
Outdoor Air Temp
O/B
Figure 8: Staged Wiring Diagram - Heat Pump (See Table 2 for Terminal Identification)
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
9
Page 10
Figure 9: AUX Contact Wiring
AUX Contact
FIG:Aux Contact Wiring
Load
Hot
19 to 30 VAC
FIG:Binary Input Wiring
BI1
Dry Contact
Bi2
Dry Contact
Figure 10: Binary Input Wiring
Setup and Adjustments
IMPORTANT: Table 10 provides a full list of TEC3000 menu settings. In the upcoming sections, step-by-step
instructions are included on how to access and adjust the more commonly used menus.
Overview
Figure 11 shows the thermostat controller home screen. You can customize it to show or hide various elements
from the occupant. See Table 3 for a listing of the touchscreen icons and Table 10 to identify the home screen
settings under the Display Settings. When screen customization is used in conjunction with a passcode, the
building owner can control which options the occupant can access and adjust.
IMPORTANT: If lockout levels are used, some icons are hidden. Table 4 provides details of these levels.
Figure 11: Thermostat Controller
Home Screen
This model cannot be purchased with a built-in sensor. The only way for the unit to display humidity is if the network
override for humidity is active. If this override is active, the humidity level is displayed on the home screen.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
10
Page 11
Customizing the Home Screen
Customizing the Home screen settings include:
• Brightness• Units• Time Zone• Date
• Enable Backlight• Time• Time Format• Date Format
You can also show or hide these items on the Home screen:
• Fan Button• Off Button• Alarm Indication• Date/Time
• Space Temperature • Hold Button• Occupancy Status
• Humidity• Setpoint• Unit Status
To customize the Home screen:
1. Press the Menu icon.
2. Press Display Settings.
3. Enable or disable elements of the home screen as appropriate for the building owner and occupants.
4. Set the passcode on the thermostat controller to prevent the o ccupants from changing settings th at they should
not have access to change.
Touchscreen Icons
Table 3 describes the home screen touchable icons. Press and release a touchscreen icon to activate the TEC.
Additional touchable icons appear based on the menu, and those icons are also described in Table 3.
Table 3: Touchscreen Icons (Part 1 of 2)
IconIcon NameDescription
Displays the configuration screens where various settings may be adjusted.
Menu
Alarm
Unit Power
On
Off
Network Communication
Arrow
Run/Hold
Indicates that the thermostat controller has triggered an alarm.
Powers the thermostat controller on or off.
Note: This icon disables all equipment control, but does not physically
power down the unit.
Indicates that the thermostat controller detected a supervisory controller and
both are online.
Increases or decreases a value depending on the configuration screen.
Displays the current setpoint. Hold mode is enabled by pressing the button.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
11
Page 12
Table 3: Touchscreen Icons (Part 2 of 2)
IconIcon NameDescription
Displays the current setpoint. Hold mode is not enabled.
No Hold/Hold
Displays the active setpoint. Hold mode is not enabled.
Hold/Hold
Proceeds to the next screen.
Right Arrow
Fan Overrides for
Single-speed Fans
On
Auto
Quiet
Home
Back
Save
Delete
Clear
Adjusts the fan override between On, Auto, and Quiet for single-speed fans.
Returns the display to the main home screen.
Returns to the previous screen.
Saves the current configuration and parameter settings.
Deletes the scheduled event.
Clears the password entry on the keypad screen.
Wrench
Checkmark
Exclamation Point
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Indicates that the value is editable.
Indicates that an event or schedule is programmed for a specific day of the
week.
Indicates that an error has occurred.
12
Page 13
User Lockout
You can select from three different levels of access at the local display to manage functionality through the
supervisory controller. This lockout is independent of any display or passcode settings. The existing temporary
occupancy capability is unaffected by this feature. User lockout hides the icons that are not operable. The lockout
levels are described in Table 4.
Table 4: User Lockout Levels
Lockout LevelCapability
State 0
State 1
State 2
Allows full access to Home Screen Display Adjustments and icons (default).
Hides the Menu icon.
Only allows the screen to trigger temporary occupancy. Menu, Unit Power, the Up
and Down arrows, and Run/Hold are hidden.
Using the USB Port
The USB port allows you to quickly and easily load firmware upgrades, backup settings, and r estore settings to the
TEC3000 by using a USB drive. The TEC3000 can recognize eight configuration files or firmware package files.
The USB drive format must be F AT or F AT32. The drive canno t be NTFS or USB 3.0. If you a re upgrading firm ware
or copying configuration files, you need the TEC3000 passcode, if it has been set up. Do n ot remove the USB drive
until the firmware upgrade is complete. The TEC3000 may restart and go offline to the NAE after a firmware
upgrade. The upgrade takes approximately three minutes.
Configurations are copied, except for the Communication mode. See Choosing the Communication Mode (TEC3630-00-000 and TEC3631-00-000 Models) to configure each device.
Loading the Firmware
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Load Firmware.
6. Select the correct firmware version. The correct file name has the .pkg extension.
7. Press Confirm if you have the correct firmware version.
The firmware is loaded from the USB drive into the T EC3000 operat ing system. The TEC3000 locates the new
firmware only if the new firmware is on the root drive of the USB drive. See Troubleshooting
if the firmware is
not loaded correctly.
8. Remove the USB drive from the TEC3000 controller when the update is complete.
The TEC3000 firmware update is complete when the TEC3000 restarts and returns to the home screen.
Backing Up the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Backup.
A message appears stating that the file is saved locally and on a USB drive.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
13
Page 14
6. Press Confirmto save locally and on USB.
The setting files are named based on the TEC3000 model nam e, date , an d tim e sta m p
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive’s root directory.
See Troubleshooting
if the settings are not backed up correctly.
7. After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Restoring the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration file created from a previous backup operation.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive’s root directory.
7. Press Confirm if you have the correct file name.
The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive, remove the USB drive from the TEC3000.
Choosing the Communication Mode
(TEC3630-00-000 and TEC3631-00-000 Models)
1. Ensure that the TEC screen is on.
2. Press the Menu icon.
3. Press Network Setup.
4. Press FC Comm Mode.
5. Select BACnet or N2 by pressing .
6. Proceed to Step 7 to perform BACnet communication and Step 15 to perform N2 communication.
7. Press
to return to the previous screen.
8. Press BACnet Instance ID.
9. Enter the unique BACnet instance ID through the keypad.
10. Press Save.
11. Press to return to the previous screen.
12. Press BACnet Address.
13. Enter the BACnet MS/TP address through the keypad.
14. Press Save.
15. After selecting N2 in Step 5, press Save.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
14
Page 15
16. Press to return to the previous screen.
17. Press N2 Address.
18. Enter the N2 address through the keypad.
19. Press Save.
Configuring the Thermostat Controller
Use the Menu icon on the home screen to access and change the basic operating parameters of the thermostat
controller. During normal operation, press the Menu icon once to access the following parameters:
• Faults Status• Display Settings• Equipment Setup• Controller Information
• Setpoints• Control Setup• System Status• Commissioning
• Schedule• Network Setup• Control Status• Update
Installer Configuration Menu
The thermostat controller comes from the factory with default settings for all configuration parameters. The UI
menu navigation and default settings are shown in Table 10. Before any outputs turn on, the controller must be
configured for the equipment connected. You need to start from the home screen to perform any of the following
tasks.
Screen Reset
The current screen returns to the home screen if the current screen is not touched for 3 minutes.
Selecting Rooftop or Heat Pump Mode
By default, the thermostat controller is configured for Rooftop mode. This mode is used for up to two discrete
stages of heating (W1, W2) and up to two discr ete stages of cooling (Y1, Y2). Certa in heat pumps do not require an
O/B input and instead take standard W and Y commands as heat or cool commands, internally sequencing the
equipment. For these type of heat pump units, leave the controller in Rooftop mode.
When in heat pump mode, the TEC controls up to two stages of compressors (Y1, Y2) for both heating and cooling.
O/B is controlled through the W1/OB output and one stage of supplemental heat is controlled through th e W2/SUP
output. To configure heat pump mode:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Heat Pump.
4. Press Heat Pump Supported and select Yes.
5. If supplemental heating is installed, pres s Supp Heating Installed and select Yes.
6. Press Reversing Valve Polarity and set appropriately for the O/B input on the equipment based on if the
equipment is normally cooling until the thermostat output is activated or normally heating (typically, Normally
Heat for O and Normally Cool for B).
7. Pressto save and
to return to the previous screen.
Configuring Heating and Cooling Stages
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press General.
4. Press Number of Compressors and adjust the number of compressor inputs on the equipment being
controlled.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
15
Page 16
5. If the thermostat controller is in roofto p mo de , pr es s Number of Heating Stages and adjust the number of
heating inputs on the equipment being controlled.
6. Pressto save and
to return to the previous screen.
Configuring Economizer
If the equipment has an analog (between 0 to 10 V) input for an economizer damper command, configure the
economizer as follows:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Economizer.
4. Press Economizer Installed and select Yes.
5. Press Min Position and set to the percentage that the damper must be kept open to ensure fresh air flow in
the zone.
6. Press Closed Voltage and set to the voltage output at which the damper is fully closed.
7. Press Opened Voltage and set to the voltage output at which the damper is fully opened.
8. Pressto save and
The TEC supports three methods of determining economizer availability. These are Dry Bulb, Single Enthalpy, and
Dual Enthalpy, in increasing order of accuracy. To run an economizer, outdoor air temperature (OAT) is required to
run in Dry Bulb mode. This can be provided by connecting a sensor to the OAT input on the TEC. It also can be
provided by writing to NET-OAT from a Building Automation System (BAS) , which overrides the internal sensor. If
Outdoor Air Humidity ( OAH) is also provided by writing to NET-OAH, then the single enthalpy method is used to
determine if economizer cooling should be used. Finally, if Zone Humidity (ZNH) is also provided by writing to
NET-ZNH, then the dual enthalpy method is used to determine if economizer cooling should be used.
to return to the previous screen.
All network overrides to the TEC work on a timeout basis. If the value is written to, it remains active as long as the
BAS writes a new value within 15 minutes of the first one. If the 15-minute timeout occurs without getting any data
written, the TEC stops using the network data
When operating in Dry Bulb or Single Enthalpy mode, it is necessary to provide a Dry Bulb Setpoint or an OA
Enthalpy Setpoint, respectively. The TEC ships with default values set, but depending on climate it may be
necessary to change these. To access these values:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Economizer.
4. Press Dry Bulb Setpoint or OA Enthalpy Setpoint and adjust according.
5. Pressto save and
to return to the previous screen.
Setting the Control Mode
The Control Mode tells the controller to run in Cooling only, Heating only, or Automatic mode, based on the
temperature in the zone relative to the heating and cooling setpoints. This setting does not override equipment
lockouts, such as low or high outdoor temperature lockouts. To set the Control Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
16
Page 17
4. Press Control Mode and select Cooling, Heating, or Auto as desired.
5. Pressto save and
to return to the previous screen.
Setting the Fan Mode
The Fan Mode informs the controller how to handle the fan. There are two options for fan configuration: a Fan
Mode available to the installer through the menu system, and a fan override available as an option to the e nd user
from the Fan icon on the home screen. See Customizing the Home Screen
disabling end-user controls. The Fan Mode available to the installer is dependent on the fan type. The following
options are provided for single-speed fans:
•On—Fan is continuously on
•Auto—Fan cycles on demand with the stages of heating or cooling (continuous when free cooling with the
economizer is running)
•Smart—Fan cycles on demand with the stages of heating or cooling during unoccupied periods but is
continuously running during occupied/standby periods
The Fan Override icon on the home screen is dependent on the fan type. The following options are provided for
single-speed fans:
•On—Overrides the fan to be continuously on
•Auto—Follows the behavior set as Fan Mode
•Quiet—Follows the behavior set as Auto Mode. The Quiet option has no effect on the RTU/heat pump
equipment as only a single-speed fan is supported.
To set the Fan Mode:
for information on enabling and
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Fan Mode and select On, Auto, or Smart.
5. Pressto save and
to return to the previous screen.
Configuring the Zone Space or Equipment Size
With non-binary outputs, the TEC3000 is configured by default to have a slower temperature response for larger
zones with normal-sized equipment. In installations with small zones and oversized equipment, set the Equipment
Size parameter to Oversized.
To set the Equipment Size parameter:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Use the up and down arrows to navigate to Equipment Size.
5. Press Equipment Setup and select Oversized.
6. Pressto save and
to return to the previous screen.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
17
Page 18
Temperature Setpoints
The thermostat controller provides a flexible setpoint configuration to give power to the building ow ne r wh ile be ing
easy to use by the occupant. In addition to a simple up/down offset adjustment on the home screen for the
occupant, there are six temperature setpoints on the TEC. The six temperature setpoints are Cooling and Heating
setpoints for Occupied, Unoccupied, and Standby modes. To set these setpoints:
1. Press the Menu icon.
2. Press Setpoints.
3. Select the desired setpoint to adjust and change as desired.
4. Pressto save and
to return to the previous screen.
Note: The TEC enforces a 2-degree deadband between heating and cooling setpoints. If a setpoint violates this
standard (for example, cooling setpoint is set to 70 with a heating setpoint already set to 70), the o pposing setpoint
is modified to comply with this deadband (in the previous example, the heating setpoint would automatically
change to 68).
The occupant has access to an up/down adjustment from the home screen. This adjustment applies a fixed offset
(+/-) to the currently active setpoint, and this offset holds until the occupancy state of the controller changes. If the
user taps the setpoint on the home screen, the icon inverts and displays white text on a black icon. The offset is
held throughout all occupancy periods. For example, if the TEC is cooling in Occup ied mode to an oc cupied cooling
setpoint of 72 and you raise the setpoint 2 degrees to 74 from the home screen and then select hold, then the +2
degree offset persists through an occupancy chang e. If the occupancy then changes to un occupied, with a setp oint
of 80 degrees, the effective setpoint is 82 degree s. This allows the occupant to have a small amount of control over
raising or lowering the temperature, but the building owner can still set back setpoints during standby and
unoccupied periods. When the setpoint is in Hold mode, pre ssing the icon again releases the hold and immediately
sets the setpoint offset back to 0.
When the TEC is in Min/Max mode (Setpoints/Occ Setpoint Select are equal to Min and Max Setpoint), the TEC
rejects any attempts to change the present valu e ou ts ide of the valid range. If the present value is outside of the
valid range (for example, if the Occ Setpoint Select is switched from Setpoint Offset to Min and Max Setpoint), the
present value is reset to be in the center of the valid range.
The four modes of setpoint operation are described in Table 5.
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Individual Setpoints
This is the default mode and the original mode of operation that the TEC was released with
(the next three modes are new). In this mode, the TEC has a heating setpoint and a cooling
setpoint. There is a common Setpoint Offset (warmer/cooler adjust) that is applied to each
setpoint simultaneously. The range of setpoint adjustment is two-fold:
• There are large constant range s bounding the individual heating and cooling setpoints.
• There is also a smaller co nfigurable range limit set to the Setpoint Offset point (Control Setup > General > Max Setpoint Offset).
In this mode, the TEC has a heating setpoint and a cooling setpoint. Each setpoint has a
configurable range (Setpoints > Min Cooling Setpoint, Max Cooling Setpoint, Min Heating Setpoint, and Max Heating Setpoint). The configurable range values are bounded
by the larger constant bounds used in Setpoint Offset mode and are constrained in the
following manner: Min must be below Max and Heating must be below Cooling, so in order
from least to greatest, the values are: Min Heating Setpoint, Max Heating Setpoint, Min
Cooling Setpoint, and Max Cooling Setpoint.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
18
Page 19
Table 5: Setpoint Operation
Mode of Setpoint
Details
Operation
Occ Setpoint Select =
Setpoint Offset and
Heat Cool Setpoint Mode =
Common Setpoint
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Offset and Heat Cool Setpoint Mode = Individual Setpoints.
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.
Configuring Occupancy
The TEC3000 controller supports a wide variety of occupancy sources to adapt to nearly any application.
•Local stand-alone weekly scheduler
•Remote schedule from BAS
•Occupancy sensor (internal or remote)
•Occupancy binary input (configurable)
•Manual occupancy override
•Temporary occupancy (by interacting with screen while unoccupied)
•Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 6.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
19
Page 20
Enumerations may not match the TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat
Controllers with Dehumidification Capability Installation Instructions (Part No. 24-10787-6), TEC3000 Series
Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability Installation
Instructions
(Part No. 24-10788-0), TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation
Instructions (Part No. 24-10789-5), and T EC3 00 0 Ser ies Field-Selectable BACnet MS/TP or N2 Networked
Thermostat Controllers Technical Bulletin (LIT-12011956) for NAE releases prior to 7.x.
Table 6: Occupancy Determination
Sequence of Operation (Highest to Lowest Priority)Status Indicated
Manual
1.Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current
state of the BI when configured as Occupancy.
2.True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when
the schedule is not Occupied.
3.When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occup ied, the Manual
Occupancy Mode is not No Override, or an Occupancy BI is configured.
4.Built-in occupancy sensing (PIR) or EI configured for Motion NO or Motion NC.
5.Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and
the Schedule is writing Not Set as the schedule.
Selecting Schedule Source
Scheduling
The TEC3000 thermostat controller can operate as a stand-alone unit with an internal schedule or scheduled with
an external schedule. The OCC-CONFIG object sets the method used for scheduling.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
20
Page 21
If the OCC-CONFIG is set to External, the NET-OCC object is used to control the unit externally.
If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object, which sets the
Occupancy Schedule command.
Note: If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set to Schedule, you
can control the unit with the LOCAL-OCC object externally; however, we do not recommend this method.
See Table 7 for scheduling information.
Once the Occupancy Schedule command is set, the effective occupancy is determined by settings shown in the
Occupancy Determination table. See Table 6.
Table 7: BAS Objects for Scheduling
BAS Objects for Scheduling
OCC-CONFIGLOCAL-OCC
(Commanded by
NET-OCCOccupancy Schedule
Command
1
Internal Schedule)
ExternalAny State
(Internal Schedule in
Control)
ScheduleOccupiedNot ApplicableOccupied
UnoccupiedUnoccupied
StandbyStandby
Not SetNot Set
OccupiedOccupied
UnoccupiedUnoccupied
StandbyStandby
Not SetNot Set
1.The effective occupancy can be affected by other factors listed in Table 6.
The occupancy schedule can come from either the weekly scheduler built into the TEC or as an input from the
BAS. The Schedule Source must be selected to tell the controller where to read the occupancy source from. To
select the schedule source:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Schedule Source and select Schedule (Local) or External (BAS).
5. Pressto save and
to return to the previous screen.
This option is also exposed to the BAS through the point OCC-CONFIG. If BAS is configured as the occupancy
source, map the point NET-OCC in and write to that point to control the schedule remotely. If the supervisor goes
offline (as identified by the network icon going away on the home screen of the TEC), the control logic
automatically falls back to the local schedule as the occu pancy source. If that schedule is not set, the default
occupancy is continuously occupied.
Setting the Local Schedule
A weekly occupancy schedule with up to four occupancy events for each day can be set locally on the TEC and
operate independently of a supervisor. To set the schedule:
1. See Selecting Schedule Source
to ensure the schedule source is set to Local.
2. Press the Menu icon.
3. Press Schedule.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
21
Page 22
4. Press Set Schedule.
5. Select the days to which the schedule should apply. Note that if events are already set for the selected days,
they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears
in the event box.
6. Select the event to be set.
7. Set the Occupancy to Not Set, Occupied, Unoccupied, or Standby and press Save.
IMPORTANT: Internally, the TEC 3000 uses a BACnet schedule where daily schedules are independent of the
previous and next days. The default occupancy of the TEC3000 from the factory is set to Occupied. As a result,
a daily event at 12:00 AM must be scheduled if you do not want the controller to transition to Occupied Mode at
midnight.
Figure 12: Selecting the Days (Left) and Selecting the Event (Right)
Figure 13: Setting the Room Occupancy (Left) and Setting the Occupancy Mode (Right)
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
22
Page 23
8. Set the time to the time at which the event should occur and press Save.
Figure 14: Setting the Event Time (Left) and Viewing the Event Time (Right)
9. Press Save to save the event and press the Return icon to return to the main scheduler screen.
Figure 15: Returning to the Main Menu
10. Pressto save and
to return to the previous screen.
Overriding the Occupancy Mode
The TEC supports a manual override of all other schedule sources (for example, Schedule, Occupancy BI, and
temporary occupancy). To override the Occupancy Mode:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Manual Occupancy Mode and select Occupied, Unoccupied, or No Override.
5. Pressto save and
This option is also exposed to the BAS through the point OCCOVRD-MODE.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
to return to the previous screen.
23
Page 24
Enabling Optimal Start
The TEC supports an advanced optimal start algorithm. The algorithm works in conjunction with a local schedule to
pre-heat or pre-cool the zone before scheduled occupancy periods begin, in order to bring the zone to the desired
occupied setpoint when the scheduled occupan cy p er iod b egins. Occu pan t comfort is en sure d while au to matically
minimizing energy usage. This algorithm creates a model of the zone being cont rolled and automatically
determines when to start the equipment before the scheduled transition to Occupied. The start time automatically
adjusts daily to minimize the time between reaching setpoint and entering Occupied state.
Note: Optimal Start does not work when the schedule source is set to External.
To enable this feature:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Optimal Start Enable and select Yes.
5. Pressto save and
to return to the previous screen.
Enabling the Motion Sensor (TEC3x31-00-000 Models)
By default on models with integral motion sensing capability, the motion sensor is enabled with a default timeout of
15 minutes from the last detection of motion in the zone. On models without an integrated sensor, the default
timeout is still 15 minutes, but it only is applied when one of the two configurable binary inputs is set to be a motion
sensor (see Configurable Binary Inputs
for information on configuring the binary inputs). To disable motion se nsing
capabilities, set the Motion Sensor Timeout to 0 minutes. See Table 6 to view the available setpoints. See Table 10
to view the setpoint values. To adjust the motion sensor timeout:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Motion Sensor Timeout and adjust accordingly.
5. Pressto save and
to return to the previous screen.
PID/PRAC+ Automatic Control Tuning
The TEC3000 features advanced proportional-integral-derivative (PID) control algorithms to maximize control
performance while minimizing excessive cycling and wear on the equipment. PID is used in conjunction with a
Multi-Stage Controller (MSC) for all occupied and standby control.
Additionally, the PID features Johnson Controls proprietary PRAC+ (Pattern Recognition Adaptive Control)
automatic tuning, which continuously tunes the controller parameters to automatically optimize the control
performance to match the equipment and zone. For units configured with two sta ges of heating or cooling, PRAC+
is enabled and immediately begins to tune. To reset tuning at any time to the factory defaults:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Press Reset PID Tuning and select Yes.
5. Pressto save and
to return to the previous screen.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
24
Page 25
PRAC+ automatic tuning can also be disabled. When disabled, the controller pa rameters remain at their last values
until automatic tuning is re-enabled. To disable automatic tuning:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Press Temp Control Setup.
5. Select Manual PID T uning (o r any optio n listed in Table 8). PID tuning is active with the Automatic PID Tuning
and Deadband Override parameters.
6. Pressto save and
to return to the previous screen.
As a result of disabling PRAC+ Auto Tuning, you have access to different types of manual tuning that allows
modifications of tuning parameters listed under Control Setup > General in Table 10.
Table 8: TEC3000 Tuning Types
Tuning TypeDescription
Automatic PID TuningAutomatic tuning in an existing TEC3000
Deadband OverrideOverrides the deadband that PRAC+ would normally use. Decouples Deadband control
from PRAC+ Automatic Tuning and Min On Off Equipment Setting.
Manual PID TuningManual tuning of Heating and Cooling PIDs. The manual tuning parameters are listed
under Control Setup > Tuning in Table10.
On/Off ControlBinary control
Note: For more details on PID/PRAC+ Automatic Control Tuning, refer to the Controller Tool Help (LIT-12011147).
Configurable Binary Inputs
The thermostat controller supports up to two configurable binary inputs (BIs) that can be used to add additional
features to the system. Configurable Binary Inputs are accessed through Settings > Control Setup > Inputs. Both
BIs can be configured to support the following options:
•Disabled—Sets the binary input to an unused state. When disabled, you can use the binary input for
monitoring-only without affecting the thermostat functionality.
•Open Window—Sensor to shut down control if a window is opened. The controller disables control 60 seconds
after detecting an opened window.
•Open Door—Works in conjunction with the Motion NO/Motion NC sensor to control occupancy
•Fan Lock—Air Proof switch input to shut down control if no airflow is detected within 10 seconds of turning the
fan on. Fan Lock must be manually reset from the Faults menu.
•Service—Input from the equipment to display a service warning on the thermostat
•Dirty Filter—Input from the equipment to display a dirty filter fault on the thermostat
•Motion NC—External motion sensor with a closed contact output when no motion is detected
•Motion NO—External motion sensor with an open contact output when no motion is detected
•Temp Occ—Trigger to place controller into Temporary Occupancy mode
•Occupancy—Direct override of Occupied and Unoccupied
•Supply Fan Status—Input from the equipment to display a Supply Fan Fault. When Fan Alarm Action is set to
Shutdown and the Supply Fan Fault is active, the TEC3000 disables the fan, heating, and cooling. When the
Fan Alarm Action is set to Enable and the Supply Fan Fault is active, the TEC3000 allows the fan, heating, and
cooling to operate during the Supply Fan Fault.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
25
Page 26
Setting both BIs to the same function is supported for all except Occupancy, Fan Lock, Open Door, and Open
Window. If both BIs are set the same for those four, BI2 is ignored and only BI1 is used.
The Open Door option works in conjunction with a motion sensor, either built into the TEC or connected to another
BI configured for Motion NO/NC mode. When the door is open, motion detected by the sensor is ignored.
Note: Opening the door does not stop an Occupied period started by the motion sensor prior to opening the door.
The polarity of the inputs are provided in Table 9.
Table 9: Input Polarities
BI ConfigurationContact OpenContact Closed
OccupancyUnoccupiedOccupied
Temp OccNo T rigger Active
Open DoorDoor Open, UnoccupiedDoor Closed, Occupied
Open WindowWindow Open, Control Shut DownWindow Closed, Control Running
Supply Fan StatusSupply Fan OffSupply Fan On
1.Configurations that support both BIs configured for the same feature of the action that occurs when either
of the BIs enter that state.
Note: Supply Fan Status and Fan Lock are not compatible with each other. The TEC3000 only co ntrols one fan so
it cannot accept feedback from two fan sources. When configuring BI-1 and BI-2, choose either Supply Fan Status
or Fan Lock, but not both.
Aux Control
The TEC has an auxiliary output that can be configured to operate in a few different ways. The Aux Mode supports
seven different options:
•Not Used—Output is always off
•Occupied NO—Output is normally open, but closes when occupied
•Occupied NC—Output is normally closed, but opens when occupied
•Occupied Fan NO—Output is normally open, but is closed when occupied with the fan running
•Occupied Fan NC—Output is normally closed, but is open when occupied with the fan running
•On—Output is turned on (relay closed), used by a BAS to directly control the AUX output
•Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Aux Mode and set accordingly.
5. Pressto save and
to return to the previous screen.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
26
Page 27
This option is also exposed to the BAS through the point AUX-MODE.
Commissioning Mode
The thermostat controller has a built-in commissioning mode, which is designed to allow you to quickly test
equipment wiring and functionality. Commissioning mode temporarily disables the control logic, and allows you to
manually command any individual output. Commissioning is designed to be the last step of the installation process
after configuring the controller for the equipment being controlled, and the available options in commissioning
mode are dependent on the controller configuration. To enter commissioning mode:
1. Press the Menu icon.
2. Select Commissioning.
3. Confirm that the selection was intentional. (The control is overridden upon selecting Confirm).
Individual outputs can be commanded through this interface. For binary outputs, the options are Off or On; for
analog outputs, they can be commanded from 0 to 100%. Whenever a control output is turned on, the fan is
engaged for safety purposes. To command an output from the Commissioning menu:
1. Select the output to command. Adjust the value to the desired output and press Save. Th e outp ut immed iately
changes to that value.
2. Restore the value to the original setting and press Save once again to complete testing that output.
Pressing the back icon from the main commissioning menu or allowing the menu system to time out and return to
the home screen ends commissioning and puts the control logic back in control of the outputs.
Sensor Priority
The TEC3000 supports various sources of sensor data for use in control or display, including internal sensors,
remote sensors (connected using an analog input), or network commanded sensors. The TEC uses the highest
priority connected input (network commands followed by remote sensors and then internal se nsors) for control and
display. Not all sources are available for all sensors.
Network commands operate on a timeout basis. When a network point is written to by a supervisor, the point
becomes the highest priority for 15 minutes. If a new up date is written within 15 minutes, the timer is restarted for
another 15 minutes.
Available Fault Diagnostics
•Supply Fan Faults—The TEC3000 supports a configurable Supply Fan Status feedback input that turns on
when the Supply Fan Status does not match the Supply Fan Command, and can be configured to disable
heating, cooling, and fan commands. The alarm delay is adjustable through the Fan Alarm delay setting. If the
delay is set to 0 or the binary input is not defined, this feature becomes disabled.
•Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the
limit is exceeded, an alarm turns on. This feature is intended to be used as a maintenance reminder. Setting
the runtime limit to 0 disables this feature.
•Supply Air Temperature Diagnostics—The TEC3000 supports diagnostics when you have a Supply Air
Temperature installed. The TEC3000 monitors the supp ly air. If you call for cooling or heating and the
temperature does not fall or rise by at least the supply air temperature alarm offset value within the supply air
temperature alarm delay, an alarm is generated. If the monitoring occurs while cooling, a cooling ineffective
alarm is generated. If the monitoring occurs while heating, a heating ineffective alarm is generated. If you set
the supply air temperature offset value set to 0, this alarm is disabled.
•Zone Temperature Alarm—When enabled, the user can set a low and high temperature alarm; and if the zone
temperature rises or falls below those limits, an alarm is generated.
•Trends—Built-in tren ds exist for many of the inputs and o utputs for the TEC3000. These trends a re viewable at
the TEC. The analog graph displays data in 15-minute increments over the previous 24 hours or a table with
the last 25 data points. Binary trends display 25 samples taken at every change of state.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
27
Page 28
Menus and Submenus
In the following table, the * indicates that the menus depend on your configuration.
Table 10: Menus and Submenus (Part 1 of 9)
Level 1Level 2
(LCD Screen Name)
SetpointsOcc Cooling Setpoint72°F (22°C)55 to 85°F (13 to 30°C)
Occ Heating Setpoint68°F (20°C)55 to 85°F (13 to 30°C)
Unocc Cooling Setpoint80ºF (27°C)55 to 85°F (13 to 30°C)
Unocc Heating Setpoint60°F (15°C)55 to 85°F (13 to 30°C)
Stby Cooling Setpoint74°F (23°C)55 to 85°F (13 to 30°C)
Stby Heating Setpoint66°F (19°C)55 to 85°F (13 to 30°C)
Occ Setpoint SelectSetpoint OffsetMin and Max Setpoint or Setpoint Offset
Heat Cool Setpoint ModeIndividual
Max Heating Setpoint*68°F (20°C)The range (in degrees) from the Min
Min Heating Setpoint*60°F (15°C)45°F (7.22°C) to Max Heating Setpoint
Max Cooling Setpoint*80ºF (27°C)Min Cooling Setpoint to 100°F (37.77°C)
Min Cooling Setpoint*72°F (22°C)The range (in degrees) from the Max
Max Setpoint*80ºF (27°C)Min Setpoint to 100°F (37.77°C)
Min Setpoint*60°F (15°C)45°F (7.22°C) to Max Setpoint
Level 3
(Default Values)
Setpoints
Available Values
Common Setpoint or Individual Setpoint
Heating Setpoint temperature to the Min
Cooling Setpoint temperature minus 1°F
(0.55°C). (The cooling temperature
always needs to be 1°F [0.55°C] above
the heating temperature.)
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
Heating Setpoint temperature plus
1°F (0.55°C) to the Max Cooling Setpoint
temperature.
*These values only appear when Heat
Cool Setpoint Mode == Individual
Setpoints and Occ Setpoint Select ==
Min and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
*These values only appear when Heat
Cool Setpoint Mode == Common
Setpoint and Occ Setpoint Select == Min
and Max Setpoint.
1
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
28
Page 29
Table 10: Menus and Submenus (Part 2 of 9)
Level 1Level 2
(LCD Screen Name)
ScheduleSchedule Options
Set Schedule
Optimal Start EnableNoYes or No
Temp Occ Duration120 minutes0 to 300 minutes
Motion Sensor Timeout15 minutes15 to 240 minutes
Manual Occupancy ModeNo OverrideNo Override, Occupied, Unoccupied
Schedule SourceLocalLocal or BAS
Display SettingsPasscode EnableNoYes or No
Passcode*NA0000 to 9999
Brightness Setting80 to 10 (most dim to brightest)
Enable Backlight TimeoutYesYes/No
UnitsIPIP or SI
TimeN/A
Time ZoneCentralAll World Time Zones
Set Time Format24 hour24 hour or 12 hour
DateN/A
Set Date FormatYYYY-MM-DDYYYY-MM-DD, or Day, Month DD, YYYY,
LanguageEnglishEnglish, French, Spanish
Show Fan IconYesYes or No
Show TempYesYes or No
Show HumidityYesYes or No
Show Off IconYesYes or No
Show Hold IconYesYes or No
Show SetpointYesYes or No
Show AlarmsYesYes or No
Show Occ StatusYesYes or No
Show Unit StatusYesYes or No
Show Date/TimeYesYes or No
Control SetupGeneral
Control ModeAutoAuto, Cooling, or Heating
Unit EnableEnableEnable or Shutdown
Fan ModeSmartOn, Auto, and Smart
Max Setpoint Offset30 to 20 degrees (°F or °C based on Units
Fan On Delay30 seconds0 to 120 seconds
Fan Off Delay30 seconds0 to 120 seconds
Level 3
Available Values
(Default Values)
—See Scheduling
*Passcode Enable = Yes
—
—
or MM-DD-YYYY
setting under Display Settings menu)
1
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
29
Page 30
Table 10: Menus and Submenus (Part 3 of 9)
Level 1Level 2
(LCD Screen Name)
Control Setup
(Cont)
Frost ProtectionYesYes or No
Aux ModeNot UsedNot Used, Occupied NO, Occupied NC,
Load Shed Rate Limit0.066°F 0 to 1°F (0 to 0.5°C)
Load Shed Adjust4°F0 to 8°F (0 to 4°C)
Fan Alarm Delay0 seconds0 to 300 seconds
Fan Alarm Action (when Fan Alarm
Delay is greater than 0)
Fan Alarm Reset (when Fan Alarm
Delay is greater than 0)
Fan Runtime Limit0 hours0 to 9,000 hours
Fan Runtime Reset (when Fan
Runtime Limit is greater than 0)
Supply Air Temperature Alarm Offset0°F0 to 10°F (0 to 5.5°C)
Supply Air Temperature Alarm Delay
(when Supply Air Temp Alarm Offset
is greater than 0)
Inputs
BI1 ConfigDisabledDisabled, Open Window, Open Door, Fan
BI2 ConfigDisabledDisabled, Open Window, Open Door, Fan
Supply Temp Offset*0-5 to 5 (°F or °C based on Units setting
Zone Temp SensorNickelNickel, Platinum, A99B, 2.25k ohm NTC,
Zone Temp Offset0-5 to 5 (°F or °C based on Units setting
OA Temp Offset0-5 to 5 (°F or °C based on Units setting
OA Temp SensorNickelNickel, Platinum, A99B, 2.25k ohm NTC,
Reset SensorsFalseTrue or False
Zone Temp Alarm EnabledNoYes or No
Zone Temp Low Limit55°F32 to 150°F (0 to 65.56°C)
Zone Temp High Limit90°F32 to 150°F (0 to 65.56°C)
when the T emp Control Setup is equal to
the Deadband Override or Manual PID
Tuning. When the Temp Control Setup
equals the On/Off Control, the Deadband
is used for the On/Off range of the stage
equipment. This parameter is hidden
when Temp Control Setup equals
Automatic PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when the Temp
control equals Manual PID Tuning.
1
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
31
Page 32
Table 10: Menus and Submenus (Part 5 of 9)
Level 1Level 2
(LCD Screen Name)
Control Setup
(Cont)
Network SetupFC Comm ModeBACnet/MSTPBACnet/MSTP, N2
Cool Period*60 seconds30 to 120 seconds
Econ Prop Band*160°F5 to 10°F (-15 to -1.11°C)
Econ Integral Time*729 seconds300 to 1,600 second s
Econ Process Range*40°F10 to 100°F (-12.22 to 37.77°C)
Econ Saturation Time*600 seconds60 to 900 seconds
Econ Time Constant*720 seconds360 to 1,440 seconds
Econ Process Dead Time*72 seconds20 to 120 seconds
BACnet Encoding Type
BACnet/MSTP Communication Mode
Level 3
(Default Values)
ISO 10646
(UCS-2)
Available Values
*Values only appear when the Temp
control equals Manual PID Tuning.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Values only appear when Auto
Economizer Tuning is Disabled.
*Value only appears when Temp Control
Setup is not equal to On Off Control
* BACnet/MSTP communication mode
* N2 Communication mode
* BACnet/MSTP communication mode
* BACnet/MSTP communication mode
ISO 10646 (UCS-2), ANSI X3.4
(US-ASCII)
1
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
32
Page 33
Table 10: Menus and Submenus (Part 6 of 9)
Level 1Level 2
(LCD Screen Name)
Equipment Setup General
Number of CompressorOne-StageNot Used, One-Stage, Two-Stage
Lead/Lag Equalize RuntimeNoYes or No
Number of Heating Stages*Two-StageNot Used, One-Stage, Two-Stage
Compressor Min On Time180 seconds0 to 360 seconds
Compressor Min Off Time180 seconds0 to 360 seconds
Heating Min On Time120 seconds0 to 360 seconds
Heating Min Off Time120 seconds0 to 360 seconds
Equipment Setup
(Cont)
Supp Min On Time120 seconds0 to 360 seconds
Supp Min Off Time120 seconds0 to 360 seconds
Cooling Lockout Temp40°F (4°C)0 to 100°F (-18 to 38°C)
Heating Lockout Temp80°F (27°C)0 to 100°F (-18 to 38°C)
Unoccupied Off Delay10 minutes0 to 10 minutes
Economizer
Economizer InstalledFalseTrue or False
Economizer Min Pos*20%0 to 100%
Closed Voltage*2 VDC0 to 10 VDC
Open Voltage*10 VDC0 to 10 VDC
Dry Bulb Sepoint68°F (20°C)0 to 100°F (-18 to 38°C)
Outdoor Enthalpy Setpoint27 Btu/lb0 to 100 Btu/lb dry air
Heat Pump
Heat Pump SupportedFalseTrue or False
Supp Heating Installed*TrueTrue or False
Comp Low Lockout Temp*32°F (0°C)-20 to 100°F (-29 to 38°C)
Supp High OA Lockout Temp*50°F (10°C)-20 to 100°F (-29 to 38°C)
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
33
Page 34
Table 10: Menus and Submenus (Part 7 of 9)
Level 1Level 2
(LCD Screen Name)
TrendEFF-ZNT—-50 to 250°F (-45.56 to 121.11°C)
EFF-SETPOINT
EFF-ZNH
B1 Status
B2 Status
EFF-OAT
EFF-SAT
FANSPD-S
CLG1-C
CLG2-C
HTG1-C
HTG2-C
OAD-O
TrendHTG-O
CLG-O
Level 3
Available Values
(Default Values)
—45 to 100°F (7.22 to 37.78°C)
—0 to 100%RH
—On or Off
—On or Off
—-50 to 250°F (-45.56 to 121.11°C)
—-50 to 250°F (-45.56 to 121.11°C)
—On or Off
—On or Off
—On or Off
—On or Off
—On or Off
—0 to 100%
—0 to 100%
—0 to 100%
1
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
34
Page 35
Table 10: Menus and Submenus (Part 8 of 9)
Level 1Level 2
(LCD Screen Name)
System StatusOccupancy SourceOccupancy SensorOccupancy BI
Unit StatusIdleSystem Fault
Supply Air Temperature75°F-50 to 250°F (-45 to 121°C)
Cooling OAT LockoutInactiveActive or Inactive
Heating OAT LockoutInactiveActive or Inactive
Comp Low OAT LockoutInactiveActive or Inactive
Supp High Lockout TempInactiveActive or Inactive
Zone Temp SourceInternal SensorUnreliable
Control StatusCooling % Command0%0 to 100%
Heating % Command0%0 to 100%
Supplemental % Command0%0 to 100%
Supplemental Heat CommandOff On or Off
FanOnOn or Off
Controller InfoModel NameTEC3x3x-xx
Software Versionx.x.x.xxxx—
Unit NameTECxxxxx—
Device Name—User-Supplied
Device DescriptionTEC3000
Level 3
(Default Values)
Available Values
Temp Occ BI
Temp Occ
Occ Override
Local Schedule
BAS Schedule
Occupancy Sensor
Airflow Fault
Open Window
Control Off
Unreliable Temperature
Dehumidification
Idle
Cooling
Heating
Cooling Unavailable
Heating Unavailable
Cooling Unavailable due to Changeover
Cooling Unavailable due to OA Temp
Cooling Unavailable due to Control Mode
Heating Unavailable due to Changeover
Heating Unavailable due to OA Temp
Heating Unavailable due to Control Mode
Internal Sensor
Remote Sensor
Network Override
Input Not Installed
—
—
1
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
35
Page 36
Table 10: Menus and Submenus (Part 9 of 9)
Level 1Level 2
(LCD Screen Name)
CommissioningSupply Air Temperatur eDisplay Current
Heat Command0%0 to 100%
Cool Command0%0 to 100%
Supply FanNoYes or No
AuxNoYes or No
UpdateView Versionx.x.x.xxxxCurrent Release of Software
Load Firmware
Restore*
Backup*—File list from USB drive or local storage
1.If the value is outside min/max limits, it is reassigned to the midpoint between min and max.
Level 3
Available Values
(Default Values)
—
Temperature
—File list from USB drive
—File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar models
to expedite the commissioning process.
*Configuration can be backed up to the
USB drive and restored to similar models
to expedite the commissioning process.
1
T roubleshooting
Table 11: Fault List (Part 1 of 3)
FaultsProbable CausesSolutions
Remote Zone Temp FailThe External Zone Temperature sensor
has been disconnected or has failed.
Supply Temp FailThe External Supply Temperature
sensor has been disconnected or has
failed.
Outdoor Temp FailThe External Outdoor Air Temperature
sensor has been disconnected or has
failed.
Internal Sensor FailAn internal sensor has failed on the
TEC.
1. Check the wiring of the sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
1. Check the wiring of the sensor.
2. If intentionally disconnected, result fault by
entering the menu, enter Control Setup, and
select Inputs to reset the sensors.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
1. Check the wiring of sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
36
Page 37
Table 11: Fault List (Part 2 of 3)
FaultsProbable CausesSolutions
OA Lockouts DisabledThe Local Outdoor Air Temperature
sensor has become disconnected or
failed or a network Outdoor Air
T emperature sensor has timed out, and
the TEC is no longer shutting down
equipment based on the OA lockout
setpoints.
Econ UnavailableThe Outdoor Air Temperature sensor is
not installed, has failed, or has been
disconnected and the TEC can no
longer control the economizer.
Dehum UnavailableDehumidification is unavailable
because the zone humidity sensor has
failed or the humidity reading is not
reliable.
ServiceEquipment connected to the BI
configured for a Service alarm is
triggering the alarm.
Dirty FilterEquipment connected to the BI
configured for a Dirty Filter alarm is
triggering the alarm.
Calibration CorruptFactory calibration data is lost or is not
installed.
Zone Temp UnreliableAll sources of zone temperature are
unreliable, including the onboard
sensor.
Open WindowThe switch connected to the BI
configured for Open Window is sensing
that the window is opened, and control
has shut down.
Fan LockThe switch connected to the BI
configured for Fan Lock did not sense
airflow within 10 seconds of starting the
fan, and control has been shut down.
Humidity UnreliableThe zone humidity reading was reliable
and has now failed.
1. If the source of outdoor air temperature was a
locally connected sensor, follow the steps for
the Outdoor Temp Fail alarm.
2. If the source of outdoor air temperature was a
BAS, check the BAS to ensure that it is still
online and is providing the TEC with the
temperature reading. If removal of the BAS
mapping was intentional, reset sensors
through the menu.
Follow the same steps as Outdoor Temp Fail
alarm.
1. If the source of zone humidity was a BAS,
check the BAS to ensure that it is still online,
and providing the TEC with the humidity
reading. If removal of the BAS mapping was
intentional, reset the sensors through the
menu.
2. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Service the equipment b y way of the
manufacturer's recommendation.
Replace the filter in the equipment as explained in
the manufacturer's instructions.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
1. Close the window to resume control.
2. Check sensor functionality with an ohmmeter,
and verify the wiring to the TEC.
3. Order replacement units and return the
affected devices to Johnson Controls under
the RMA program.
1. Inspect equipment to ensure fan functions.
2. Check sensor functionality with an ohmmeter,
and verify wiring to the TEC.
3. Reset fault by entering the menu, selecting
Fault Status, and selecting the Fan Lock.
4. If problems persist, order replacement units
and return the affected devices to Johnson
Controls under the RMA program.
1. If the source of zone humidity was the
onboard sensor, contact Johnson Controls
product sales and support.
2. If the source of zone humidity was a BAS,
check the BAS to ensure that it is still online
and providing the TEC with the humidity
reading. If removal of the BAS mapping was
intentional, reset sensors through the menu.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
37
Page 38
Table 11: Fault List (Part 3 of 3)
FaultsProbable CausesSolutions
Controller FaultThe controller has detected an internal
fault that it cannot recover.
An unknown error has prevented the
controller from turning on.
Touchscreen UnavailableThe touchscreen components have
failed to initialize.
Board MismatchThe baseboard and CPU board are
paired incorrectly . An error message
appears on the TEC indicating the
model number of the baseboard and
CPU board.
Firmware MismatchThe previous upgrade has not
completed.
The previous downgrade has not
completed because the previous
version is no longer supported.
USB MalfunctionA USB drive has malfunctioned and
Supply Fan Runtime Limit
Extended
Heating IneffectiveThe Supply Air Temperature has not
Cooling IneffectiveThe Supply Air Temperature has not
Supply Fan FaultThe Supply Fan Status configured for
Zone Temperature Too ColdThe Zone Temperature has decreased
Zone Temperature Too HotThe Zone Te mper ature ha s increase d
drawn more than the maximum allowed
current.
The Supply Fan Runtime has exceeded
the configured Supply Fan Runti m e
Limit.
increased above the configured Supply
Air Temperature Alarm Offset while
heating has been active for at least the
Supply Air Temperature Alarm Delay.
decreased below the configured Supply
Air Temperature Alarm Offset while
cooling has been active for at least th e
Supply Air Temperature Alarm Delay.
either BI1 or BI2 has not proved within
the configured Fan Alarm Delay.
below the configured Zone Temp Lo w
Limit.
above the configured Zone Temp High
Limit.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
1. Reboot the controller.
2. If problems persist, order replacement units
and return the affected devices to Johnson
Controls under the RMA program.
Match the baseboard to its corresponding CPU
board. See Figure 5 for info rmation on ensuring
that you have the CPU board and base board
paired correctly.
1. Upgrade the TEC3000 to the latest released
version.
2. Upgrade the TEC3000 to the current version
again.
Reboot the TEC3000 to clear the fault.
1. Attempt to insert and use the USB drive
again.
2. Try a new USB drive.
3. If problems persist, order replacement units
and return the affected devices to Johnson
Controls under the RMA program.
1. Service the Supply Fan.
2. Reset the Supply Fan runtime.
Verify that the heating elements on the rooftop
are functioning properly.
Verify that the cooling elements on the rooftop are
functioning properly.
1. Verify that the Supply Fan is operating when
turned on.
2. Verify that the Supply Fan Status wiring is
connected correctly.
Verify that the TEC and the RTU heating are
enabled and functioning.
Verify that the TEC and the RTU cooling are
enabled and functioning.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
38
Page 39
Table 12: Troubleshooting Details1 (Part 1 of 2)
SymptomProbable CausesSolutions
The controller displays Idle with a Unit
Status of Cooling Unavailable due to
OA Temp despite being above cooling setpoint, or with a status of Heating
Unavailable due to OA Temp despite
being below the setpoint.
The controller displays Idle with a Unit
Status of Cooling Unavailable due to
Control Mode despite being above
cooling setpoint, or with a status of
Heating Unavailable due to Control
Mode despite being below the
setpoint.
The controller displays Idle with a Unit
Status of Cooling Unavailable
despite being above cooling setpoint,
or with a status of Heating Unavailable despite being below the
setpoint.
The heat pump does not sequence
properly.
The heat pump heats when it should be
cooling, and cools when it should heat.
The staged equipment shuts off above
the cooling setpoint or below the
heating setpoint when the PID is
running on the TEC. If the unit is in On/
Off Control mode, this does not apply.
The staged equipment cycles too
rapidly or too slowly when the PID is
running on the TEC.
The controller provides an error when
trying to upgrade firmware.
The zone space temperature increases
or decreases too much when the unit is
active in unoccupied mode.
The TEC3000 zone temperature does
not change fast enough compared to
the measured zone temperature from a
verification device (a calibrated
sensor).
The outdoor air temperature is too
warm for heating or too cold for
cooling.
The Control Mode is set to Cooling
Mode, but the controller is requesting
heating.
The Control Mode is set to Heating
Mode, but the controller is requesting
cooling.
The Number of Compressors set to Not
Used and the controller is requesting
cooling, or Number of Heating Stages
is set to Not Used.
The heat pump requires traditional
wiring (Y1, Y2, W1, W2, and G) and
handles the reversing valve internally,
but Heat Pump Supported is set to Yes.
The heat pump requires thermostat to
control the reversing valve (Y1, Y2,
O/B, and G) but the Heat Pump
Supported is set to No.
Reversing Valve polarity is incorrectly
set.
The PID control algorithm minimizes
overshoot and energy usage for the
particular equipment and zone, and
may cycle the equipment prior to
reaching setpoint.
The control band around the setpoint is
determined by the minimum on/off
times and is set incorrectly for the
equipment, zone, or user preference.
There is a tradeoff between reduced
control band size and increased
energy usage and equipment wear
from increased cycling.
The firmware on the USB drive is
below the minimum required version.
Error code 1025.
The heating and cooling equipment are
too big for the unoccupied space.
The TEC3000 is configured by default
for larger spaces with normal-sized
equipment when a proportional device
is active.
1. If Cooling and Heating Lockout
Setpoints are inadequate, adjust
the setpoints.
2. Wait for the outdoor conditions to
be favorable for heating or cooling.
Change the Control Mode to Auto or
Heating.
Change the Control Mode to Auto or
Cooling.
Adjust the number of compressors and
number of heating stages to match the
configuration of the unit.
Consult the equipment documentation
to verify wiring configuration, then set
Heat Pump Supported to No.
Consult the equipment documentation
to verify wiring configuration, then set
Heat Pump Supported to Y es.
Consult the equipment documentation
to verify reversing valve polarity, then
adjust the Reversing Valve Polarity
menu option accordingly.
Expected behavior.
1. Veri fy tha t e qui pment minimum on/
off times are set correctly .
2. If the default deadband around the
setpoint does not provide the
desired temperature control, set
Temp Control Setup to Deadband
Override and set the Deadband
parameter to the desired value.
Please use firmware version 3.0.2.xxxx
or higher.
A reboot is required to clear the
Firmware Mismatch fault that occurs.
Decrease the Unoccupied Off Delay
parameter from 10 minutes to a more
appropriate time for the equipment
configuration.
Select Control Setup >Tuning > Equipment Size > Oversized.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
39
Page 40
Table 12: Troubleshooting Details1 (Part 2 of 2)
SymptomProbable CausesSolutions
The controller provides an error when
trying to back up settings.
The controller provides an error when
trying to restore settings from a
backup.
The controller is unable to access a
USB drive.
The controller displays Board Mismatch.
The controller displays Controller Fault.
The Bell icon is displayed on the TEC
home page.
Partial Restore Complete is displayed
when trying to restore settings from a
backup file.
The temperature displayed is lower
than the actual room temperature.
The Online icon does not appear for a
networked controller.
Some icons are hidden.Lockout levels are used or the icons
The USB drive is defective.Try a different USB drive.
The USB drive is defective.Try a different USB drive.
The Restore file is corrupt.Try restoring a different backup file.
The Restore file is from an
incompatible model TEC.
The drive is formatted as NTFS or
another unsupported format. The TEC
supports FAT and FAT32 formats only.
The USB drive is defective.Try a different USB drive.
The I/O board that the display board is
currently attached to does not match
the one that initially shipped with the
display board.
A hardware failure is causing the two
boards to incorrectly identify
themselves.
An internal fault was detected and the
controller was unable to recover.
The fault has been detected on the
TEC.
Not all of the items in the backup file
have been restored. This error can be
caused by a value being out of the
minimum or maximum range in the
backup file. It may also occur if there
are inconsistencies in the reliability of a
setting in the backup file and on the
TEC device.
Cold air drafts are entering the back of
the TEC.
Air is being forced through the TEC
from a nearby vent.
There is improper field bus wiring.Refer to the MS/TP Communications
are hidden due to the display settings.
Ensure that the backup file being
restored was from the same model
TEC.
Reformat the USB drive, or try a
different USB drive with a supported
format.
Attach the display board to the correct
I/O board.
Order replacement units and return the
affected devices to Johnson Controls
under the RMA program.
Order replacement units and return the
affected devices to Johnson Controls
under the RMA program.
See Table 1 1 for TE C fault causes and
resolution.
1. Create a Backup file on a USB
drive for the TEC that is showing
the issue.
2. Edit the backup file created in step
1 on a PC to reflect the desired
settings.
3. Verify that the modified values are
within minimum and maximum
range in the backup file.
4. Restore the settings from the newly
edited backup file on the TEC.
Seal any holes behind the TEC to
reduce drafts.
Move the location of the TEC or
change the venting to prevent air from
being forced through the TEC.
Bus Technical Bulletin (LIT-12011034).
See Table 4 for lockout level s and
access details.
1.For common MS/TP troubleshooting information, refer to the MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
Repair Information
If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a
replacement thermostat controller, contact the nearest Johnson Controls representative.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
40
Page 41
Technical Specifications
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers
Power Requirements19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
USB Port Power Rating120 to 250 mA current draw supported
Relay Contact Rating19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Binary InputsVoltage free contacts across terminal COM to terminals BI1 or BI2
Analog InputsNickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3
across terminal COM to terminals R SEN
Temperature Sensor TypeLocal 1k ohm platinum sensor
Wire Size18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
MS/TP Network GuidelinesUp to 100 devices maximum for each Network Automation Engine (NAE);
Temperature
Range
AccuracyTemperature±0.9F°/±0.5C° at 70.0°F/21 .0°C typical calibrated
Minimum Deadband2F°/1C° between heating and cooling
Occupancy Sensor Motion
Detection (Occupancy Sensing
Models)
Ambient
Conditions
Compliance BACnet
Shipping
Weight
Backlit Display-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating Control40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control54.0°F/12.0°C to 100.0°F/38.0°C
Operating32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
Storage-22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
International
United StatesUL Listed, File E27734, CCN XAPX, Under UL60730
CanadaUL Listed, File E27734, CCN XAPX7, Under E60730
EuropeCE Mark – Johnson Controls declares that this product is in compliance
Australia and
New Zealand
Models without
Occupancy
Sensor
Models with
Occupancy
Sensor
4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP T echnical Bulletin for
the Metasys, FX, or Verasys system installed.
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
BACnet T esting Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific
Controller (B-ASC)
FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Industry Canada, ICES-003
with the essential requirements and other relevant provisions of the EMC Directive
and the RoHS Directive.
RCM Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
41
Page 42
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.