Johnson Controls TEC3000 Series Data Sheet

Code No. LIT-1900896
TEC3000 Series Thermostat Controller
Shown with Occupancy Sensor
Issued February 17, 2017
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page

Description

• local hydronic reheat valves
• pressure-dependent VAV equipment with or without local reheat
• two- or four-pipe fan coils
• cabinet unit heaters
• other zoning equipment using an on/off, floating, or 0 to 10 prop
ortional control input
Models also provide single- or two-stage control of unitary rooftop units (RTUs) with or without economizers and heat pumps.
The field-selectable BACnet MS/TP or N2 networked thermostat controllers enable remote monitoring and programming through the building automation system, for efficient space temperature control. The wireless thermostat controllers feature a connection to the ZFR Pro wireless network. All models include a USB port configuration that reduces installation time by allowing simple backup and restore features from a USB drive, which enables rapid cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints.
All models feature an intuitive UI with backlit display that makes setup and operation quick and easy. Multiple fan configurations are supported for fan coil equipment types:
• single-speed
• multi-speed (two or three discrete speeds)
• variable-speed/EC motors (0 to 10 VDC contro
Some models rehea
t, and four-pipe fan coil units with or without reheat. When heating is r and activates dehumidification control as necessary. Heat and/or
t is used as required to maintain the space temperature. For
rehea optimal dehumidification performance, use a fan coil unit multi-
speed or variable-speed fan (VSF). Models are available with or without the Johnson Controls® logo. Refer to the TEC3000 Series Wireless, Stand-Alone, and
Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Product Bulletin (LIT-12011954) for important product
application information.
support dehumidification on two-pipe fan coil units
equired, the thermostat controller monitors
l)

Features

Two Configurable Binary Inputs—Provide additional inputs for
advanced functions such as remote night setback, service or filter alarms, motion detector, and window status.
Wireless Communication Protocol ZFR Pro (TEC-30xx-0x-
Models)
Field-Selectable BACnet MS/TP or N2 Netw
Com
upgr networked communication without changing hardware.
USB Port Configuration—Reduces
simple backup enables rapid cloning of configuration bet
Backlit Liquid Crystal Display (LCD)—Offers real-time cont
st
atus of the environment in easy-to-read, plain text messages with
adjustable backlight that brightens during user interaction.
Reduces installation time and costs.
munication (TEC36xx-0x-000 Models)—Simplifies
ade from N2 networked communication to BACnet MS/TP
and restore features fr
installation time by allowing om a USB drive, which
orked
ween like units.
VDC
with
no
space humidity
that has a
000
the
rol
Configurable Touchscreen UI—Allows facility managers to limit the user
interaction with the thermostat controller display based on
specific energy policies.
End-of-Line Switch—Simplifies the layout and installation communication
Mobile Access Portal (MAP) Gateway Compatib
Stand-Alone and BACnet MS/TP or N2 Networked Models
Onboard Occupancy Sensor (TEC3xx1-0x-000 and
On
Integral Humidity Sensor (TEC3xx2-0x-000 a
Multiple Fan Configurations for Fan Coil Equipment Types
Full Line of Remote TE-6300 Series Temperature Sensors
Built-In Schedule Object—Allows all wired models of
Optimal Start—Allows each thermostat controller to anticipa
Auto-Tuned Control Loops—Reduce commissioning
Load Shed—Commands a load shed input to offset the heating and
Release 4.0 or Later)—Allows the user to view equipment
(MAP
and control conditions using mobile devices.
Offer application flexibility.
TEC3xx3-0x-000 Models)—Provides ener high-
energy usage commercial buildings without additi
installation time or cost.
/Off, Floating, Proportional 0 to 10 VDC, and Single-
Tw
o-Stage Control—Offers additional application flex
providing mor
TEC3xx3-
dehumidification control on two-pipe fan coil units with reh
pipe fan coil units with or without reheat.
four-
Provide field-selectable single-speed, multi-speed, var
iable-speed fan control capabilities.
Support a wide range of remote temperature sensing needs fr single supp
thermostat controllers to be scheduled as stand-alo allows BACnet the building automation system.
heatin
g or cooling needs of a space by starting the equipment early enough to reach the setpoint at the beginning of the occupancy.
elimina and tear of the mechanical devices.
cooling setpoints by a fixed amount on net chang
e rate of the setpoints is adjustable. The load shed feature in place to help satisfy defined in joint appendix JA5, section JA5.2.4 for deman response. The tr and passed
buses.
gy savings in
e advanced control signals.
nd
0x-000 Models)—Monitors space humidity and activates
lier.
MS/TP models to be defined and adjusted through
te change-of-season recommissioning, and reduce wear
worked models. The
the California Title 24 requirements that are
igger for this event is defined in another contro
through the network command.
of
ility
onal
or
ibility by
eat and
and
om a
ne devices;
te the
scheduled
time,
d signal
ller
is
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
1
TEC3000 Series Thermostat Controller Shown with Occupancy Sensor,
Dimensions, in. (mm)
FIG:t hermostat fe atures
USB Port
Display
Cover Screw
1-13/32
(36)
Occupancy
Sensor
4-23/32
(120)
5-5/8 (143)
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page (Continued)

Selection Charts

1
Control Output Onboard
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
Occupancy
Capability
Sensor
No No
No No
Yes No
Yes No
Dehumidification
Wireless Thermostat Controller Models
Code Number Johnson Controls
Logo
TEC3010-00-000 Yes On/off or floating fan coil and zoning No No TEC3010-01-000 No On/off or floating fan coil and zoning No No TEC3011-00-000 Yes On/off or floating fan coil and zoning Yes No TEC3011-01-000 No On/off or floating fan coil and zoning Yes No TEC3012-00-000 Yes On/off or floating fan coil and zoning No Y es TEC3012-01-000 No On/off or floating fan coil and zoning No Yes TEC3013-00-000 Yes On/off or floating fan coil and zoning Yes Yes TEC3013-01-000 No On/off or floating fan coil and zoning Yes Yes TEC3020-00-000 Yes 0 to 10 VDC proportional fan coil and zoning No No TEC3020-01-000 No 0 to 10 VDC proportional fan coil and zoning No No TEC3021-00-000 Yes 0 to 10 VDC proportional fan coil and zoning Y es No TEC3021-01-000 No 0 to 10 VDC proportional fan coil and zoning Yes No TEC3022-00-000 Yes 0 to 10 VDC proportional fan coil and zoning No Yes TEC3022-01-000 No 0 to 10 VDC proportional fan coil and zoning No Yes TEC3023-00-000 Yes 0 to 10 VDC proportional fan coil and zoning Y es Yes TEC3023-01-000 No 0 to 10 VDC proportional fan coil and zoning Yes Yes TEC3030-00-000 Yes Single- or two-stage
TEC3030-01-000 No Single- or two-stage
TEC3031-00-000 Yes Single- or two-stage
TEC3031-01-000 No Single- or two-stage
1. Multiple fan configurations are supported for fan coil equipment types.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
2
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page (Continued)
Stand-Alone Thermostat Controller Models
Code Number Johnson Controls
Logo
1
Control Output Onboard
Occupancy Sensor
TEC3310-00-000 Yes On/off or floating fan coil and zoning No No TEC3310-01-000 No On/off or floating fan coil and zoning No No TEC3311-00-000 Yes On/off or floating fan coil and zoning Yes No TEC3311-01-000 No On/off or floating fan coil and zonin g Yes No TEC3312-00-000 Yes On/off or floating fan coil and zoning No Yes TEC3312-01-000 No On/off or floating fan coil and zonin g No Yes TEC3313-00-000 Yes On/off or floating fan coil and zoning Yes Yes TEC3313-01-000 No On/off or floating fan coil and zoning Yes Yes TEC3320-00-000 Yes 0 to 10 VDC proportional fan coil and zoning No No TEC3320-01-000 No 0 to 10 VDC proportional fan coil and zoning No No TEC3321-00-000 Yes 0 to 10 VDC proportional fan coil and zoning Yes No TEC3321-01-000 No 0 to 10 VDC proportional fan coil and zoning Yes No TEC3322-00-000 Yes 0 to 10 VDC proportional fan coil and zoning No Yes TEC3322-01-000 No 0 to 10 VDC proportional fan coil and zoning No Yes TEC3323-00-000 Yes 0 to 10 VDC proportional fan coil and zoning Yes Yes TEC3323-01-000 No 0 to 10 VDC proportional fan coil and zoning Yes Yes TEC3330-00-000 Yes Single- or two-stage
TEC3330-01-000 No Single- or two-stage
TEC3331-00-000 Yes Single- or two-stage
TEC3331-01-000 No Single- or two-stage
1. Multiple fan configurations are supported for fan coil equipment types.
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
No No
No No
Yes No
Yes No
Dehumidification Capability
Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controller Models1 (Part 1 of 2)
Code Number Johnson Controls
Logo
Control Output Onboard
Occupancy
Dehumidification Capability
Sensor
TEC3610-00-000 Yes On/off or floating fan coil and zoning No No TEC3610-01-000 No On/off or floating fan coil and zoning No No TEC3611-00-000 Yes On/off or floating fan coil and zoning Yes No TEC3611-01-000 No On/off or floating fan coil and zonin g Yes No TEC3612-00-000 Yes On/off or floating fan coil and zoning No Yes TEC3612-01-000 No On/off or floating fan coil and zonin g No Yes TEC3613-00-000 Yes On/off or floating fan coil and zoning Yes Yes TEC3613-01-000 No On/off or floating fan coil and zoning Yes Yes TEC3620-00-000 Yes 0 to 10 VDC proportional fan coil and zoning No No TEC3620-01-000 No 0 to 10 VDC proportional fan coil and zoning No No TEC3621-00-000 Yes 0 to 10 VDC proportional fan coil and zoning Yes No TEC3621-01-000 No 0 to 10 VDC proportional fan coil and zoning Yes No TEC3622-00-000 Yes 0 to 10 VDC proportional fan coil and zoning No Yes TEC3622-01-000 No 0 to 10 VDC proportional fan coil and zoning No Yes TEC3623-00-000 Yes 0 to 10 VDC proportional fan coil and zoning Yes Yes TEC3623-01-000 No 0 to 10 VDC proportional fan coil and zoning Yes Yes
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
3
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page (Continued)
Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controller Models1 (Part 2 of 2)
Code Number Johnson Controls
Logo
TEC3630-00-000 Yes Single- or two-stage
TEC3630-01-000 No Single- or two-stage
TEC3631-00-000 Yes Single- or two-stage
TEC3631-01-000 No Single- or two-stage
1. Multiple fan configurations are supported for fan coil equipment types.
Accessories (Order Separately)
Product
Description
Code Number
TEC-WALLPLT Wallplate for retrofitting existing installations or concealing mounting surface damage; can be used with any TEC3000 Series
MS-WNC1820-0A WNC1800-0SZ with base, 120 to 230 VAC power, ZFR1820 ProCordFlag, with 3 ft (0.9 m) cable MS-WNC1823-0A WNC1800-0SZ with base, 120 to 230 VAC power, ZFR1823 ProCordWall, with 10 ft (3 m) cable MS-WNC1820-0B WNC1800-0SZ with base, 24 VAC power, ZFR1820 ProCordFlag, with 3 ft (0.9 m) cable MS-WNC1823-0B WNC1800-0SZ with base, 24 VAC power, ZFR1823 ProCordWall, with 10 ft (3 m) cable MS-ZFR1821-0B ZFR1821 Pro Flag Repeater, 24 V AC/DC power, with 3 ft (0.9 m) cable MS-ZFR1822-0B ZFR1822 Pro Wall Mount Repeater, 24 VAC/DC power , with 10 ft (3 m) cable MS-ZFR1821-0 ZFR1821 Pro Flag Router, with 3 ft (0.9 m) cable MS-ZFR1822-0 ZFR1822 Pro Wall Mount Router, with 10 ft (3 m) cable ZFR-CBLEXT-0 10 ft (3 m) extension cable accessory, RJ12 F-F coupler ZFR-WALLCOVER ZFR Repeater wallplate cover ZFR-USBHA-0 Wireless USB dongle
TE-6300 Series T-4000-119 Allen-head adjustment tool (30 per bag)
1. See Johnson Controls TE-6300 Series T emperature Sensors table for ordering details regarding Johnson Controls TE-6300 Series Remote Temperature Sensors.
1
Thermostat Controller
Remote temperature sensors
Control Output Onboard
Occupancy Sensor
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
No No
No No
Yes No
Yes No
Dehumidification Capability
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
4
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page (Continued)
Johnson Controls TE-6300 Series Temperature Sensors (Order Separately) (Part 1 of 2)
Sensor Type Mounting Style Probe Length Product
Nickel (1k ohm)
Platinum (1k ohm)
Platinum Equivalent
Thermistor (2.2k ohm)
Adjustable Averaging 8 ft (2.4 m) TE-6315M-1
Duct 4 in. (102 mm) TE-631GM-1
Flange 4 in. (102 mm) TE-631GV-2
Flush N/A TE-6310F-0
Outside air 3 in. (76 mm) TE-6313P-1 Strap-mount 3 in. (76 mm) TE-631S-1 Wall Well 6 in. (152 mm) TE-631AM-2
Adjustable 8 in. (203 mm) TE-6351-A Duct 4 in. (102 mm) TE-635GM-1
Flange 4 in. (102 mm) TE-635GV-2
Flush N/A TE-6350F-0
Strap-mount 3 in. (76 mm) TE-635S-1 Outside air 3 in. (76 mm) TE-6353P-1 Wall Well 6 in. (152 mm) TE-635AM-2
1k ohm averaging
100 ohm averaging
Adjustable 8 in. (203 mm) TE-6341A-1 Duct 8 in. (203 mm) TE-6341P-1 Flange 4 in. (102 mm) TE-634GV-2
Outside air 3 in. (76 mm) TE-6343P-1 Wall Well 8 in. (203 mm) TE-6342M-1
1
2
2
1
1
2
8 in. (203 mm) TE-6311A-1
17 ft (5.2 m) TE-6316M-1
8 in. (203 mm) TE-6311M-1
18 in. (457 mm) TE -631JM-1
8 in. (203 mm) TE-6311V-2
N/A TE-6314P-1
8 in. (203 mm) TE-6312M-1
8 in. (203 mm) TE-6351M-1
18 in. (457 mm) TE -635JM-1
8 in. (203 mm) TE-6351V-2
N/A TE-6324P-1
8 in. (203 mm) TE-6352M-1 10 ft (3 m) TE-6327P-1 20 ft (6.1 m) TE-6328P-1 10 ft (3 m) TE-6337P-1 20 ft (6.1 m) TE-6338P-1
8 in. (203 mm) TE-6341V-2
N/A TE-6344P-1
6 in. (152 mm) TE-634AM-2
Code Number
TE-6315V-2
TE-6316V-2
TE-6311P-1
TE-6310F-1
TE-6351P-1
TE-6350F-1
1
1
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
5
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page (Continued)
Johnson Controls TE-6300 Series Temperature Sensors (Order Separately) (Part 2 of 2)
Sensor Type Mounting Style Probe Length Product
Thermistor (10k ohm) Type II
1. Two TE-6001-8 Element Holders come with the plat inum-equivalent averaging sensors. Order separately to use with a nickel averaging sensor.
2. Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.
Adjustable 8 in. (203 mm) TE-6361A-1 Duct 4 in. (102 mm) TE-636GM-1
8 in. (203 mm) TE-6361M-1
18 in. (457 mm) TE-636JM-1
Flange 4 in. (102 mm) TE-636GV-2
8 in. (203 mm) TE-6361V-2
Flush N/A TE-6360F-0
Outside air 3 in. (76 mm) TE-6363P-1 Strap-mount 3 in. (76 mm) TE-636S-1 Well 6 in. (152 mm) TE-636AM-2
8 in. (203 mm) TE-6362M-1

Repair Information

If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative.
Code Number
TE-6361P-1
TE-6360F-1

Technical Specifications

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers (Part 1 of 2)
Power Requirements 19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safetyextra-low voltage (SELV) Analog Output Rating
(Proportional Control Models) Relay Contact Rating
(On/Off, Floating, or Staged Economizer Control Models)
Fan Relay Output Rating (On/Off, Floating, and Proportional Control Models)
Auxiliary Output Rating/Triac Output (On/Off, Floating, and Proportional Control Models)
Binary Inputs Dry contact across terminal COM to terminals BI1, BI2, or COS Analog Inputs Nickel, platinum, A99B, 2.25k ohm negative temperature coefficient (NTC), 10k ohm NTC, 10k ohm NTC Type 3
Temperature Sensor Type Local 1k ohm platinum sensor Wire Size 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended MS/TP Network Guidelines Up to 100 devices maximum per Network Automation Engine (NAE);
Wireless Band Direct-sequence, spread-spectrum, 2.4 GHz ISM band Transmission Power 10 mW maximum Transmission Range 50 ft (15.2 m) practical average indoor
Temperature Range
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Minimum Deadband 2F°/1C° between heating and cooling
Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Humidity (On/Off, Floating, and Proportional Control Models)
0 to 10 VDC into 2k ohm resistance (minimum)
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3. 0 A in-rush, Class 2 or SELV
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
across terminal COM to terminals R SEN or COS
4,000 ft (1,219 m) maximum cable length (repeaters can be added to extend this length)
250 ft (76.2 m) maximum indoor line of sight
±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
6
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or N2 Networked Thermostat Controllers Catalog Page (Continued)
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers (Part 2 of 2)
Occupancy Sensor Motion Detection (Occupancy Sensing Models)
Ambient Conditions
Compliance BACnet
Shipping Weight
Operating 32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing Storage -22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
International United States UL Listed, File E27734, CCN XAPX, under UL60730
Canada UL Listed, File E27734, CCN XAPX7 under E60730
Europe CE Mark—Johnson Controls declares that this product is in compliance with the essential req uirements and other
Australia and New Zealand
Models without Occupancy Sensor
Models with Occupancy Sensor
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m); based on a clear line of sight
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific Controller (B-ASC)
Transmission complies with FCC Part 15.247 regulations for low power unlicensed transmitte rs; transmitter identification FCC: OEJ-WRZRADIO
Industry Canada (IC) RSS-210; transmitter identification ZFR1810-1: IC: 279A-WRZRADIO
relevant provisions of the Radio Equipment Directive (RED), the Low Voltage Directive (LVD), the EMC Directive, and the RoHS Directive.
RCM Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2017 Johnson Controls.
7