TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or
N2 Networked Thermostat Controllers Catalog Page
Description
The TEC3000 Series Thermostat Controllers are wireless,
stand-alone, and field-selectable BACnet®
Master-Slave/Token-Passing (MS/TP) or N2 networked devices that
provide on/off, floating, and proportional control of the following:
• local hydronic reheat valves
• pressure-dependent VAV equipment with or without local reheat
• two- or four-pipe fan coils
• cabinet unit heaters
• other zoning equipment using an on/off, floating, or 0 to 10
prop
ortional control input
Models also provide single- or two-stage control of unitary rooftop units
(RTUs) with or without economizers and heat pumps.
The field-selectable BACnet MS/TP or N2 networked thermostat
controllers enable remote monitoring and programming through the
building automation system, for efficient space temperature control.
The wireless thermostat controllers feature a connection to the
ZFR Pro wireless network. All models include a USB port configuration
that reduces installation time by allowing simple backup and restore
features from a USB drive, which enables rapid cloning of configuration
between like units.
Some models have occupancy sensing capability built into the device.
These thermostat controllers maximize up to 30% energy savings in
high-energy usage commercial buildings, such as schools and hotels,
during occupied times by using additional standby setpoints.
All models feature an intuitive UI with backlit display that makes setup
and operation quick and easy. Multiple fan configurations are
supported for fan coil equipment types:
• single-speed
• multi-speed (two or three discrete speeds)
• variable-speed/EC motors (0 to 10 VDC contro
Some models
rehea
t, and four-pipe fan coil units with or without reheat. When
heating is r
and activates dehumidification control as necessary. Heat and/or
t is used as required to maintain the space temperature. For
rehea
optimal dehumidification performance, use a fan coil unit
multi-
speed or variable-speed fan (VSF).
Models are available with or without the Johnson Controls® logo.
Refer to the TEC3000 Series Wireless, Stand-Alone, and
Field-Selectable BACnet MS/TP or N2 Networked Thermostat
Controllers Product Bulletin (LIT-12011954) for important product
application information.
support dehumidification on two-pipe fan coil units
equired, the thermostat controller monitors
l)
Features
• Two Configurable Binary Inputs—Provide additional inputs for
advanced functions such as remote night setback, service or filter
alarms, motion detector, and window status.
• Wireless Communication Protocol ZFR Pro (TEC-30xx-0x-
Models)—
• Field-Selectable BACnet MS/TP or N2 Netw
Com
upgr
networked communication without changing hardware.
• USB Port Configuration—Reduces
simple backup
enables rapid cloning of configuration bet
dehumidification control on two-pipe fan coil units with reh
pipe fan coil units with or without reheat.
four-
Provide field-selectable single-speed, multi-speed,
var
iable-speed fan control capabilities.
Support a wide range of remote temperature sensing needs fr
single supp
thermostat controllers to be scheduled as stand-alo
allows BACnet
the building automation system.
heatin
g or cooling needs of a space by starting the equipment early
enough to reach the setpoint at the beginning of the
occupancy.
elimina
and tear of the mechanical devices.
cooling setpoints by a fixed amount on net
chang
e rate of the setpoints is adjustable. The load shed feature
in place to help satisfy
defined in joint appendix JA5, section JA5.2.4 for deman
response. The tr
and passed
buses.
gy savings in
e advanced control signals.
nd
0x-000 Models)—Monitors space humidity and activates
lier.
MS/TP models to be defined and adjusted through
te change-of-season recommissioning, and reduce wear
TEC3000 Series Thermostat Controller Shown with Occupancy Sensor,
Dimensions, in. (mm)
FIG:t hermostat fe atures
USB Port
Display
Cover Screw
1-13/32
(36)
Occupancy
Sensor
4-23/32
(120)
5-5/8
(143)
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or
N2 Networked Thermostat Controllers Catalog Page (Continued)
Selection Charts
1
Control OutputOnboard
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
Occupancy
Capability
Sensor
NoNo
NoNo
YesNo
YesNo
Dehumidification
Wireless Thermostat Controller Models
Code NumberJohnson Controls
Logo
TEC3010-00-000YesOn/off or floating fan coil and zoningNoNo
TEC3010-01-000NoOn/off or floating fan coil and zoningNoNo
TEC3011-00-000YesOn/off or floating fan coil and zoningYesNo
TEC3011-01-000NoOn/off or floating fan coil and zoningYesNo
TEC3012-00-000YesOn/off or floating fan coil and zoningNoY es
TEC3012-01-000NoOn/off or floating fan coil and zoningNoYes
TEC3013-00-000YesOn/off or floating fan coil and zoningYesYes
TEC3013-01-000NoOn/off or floating fan coil and zoningYesYes
TEC3020-00-000Yes0 to 10 VDC proportional fan coil and zoningNoNo
TEC3020-01-000No0 to 10 VDC proportional fan coil and zoningNoNo
TEC3021-00-000Yes0 to 10 VDC proportional fan coil and zoningY esNo
TEC3021-01-000No0 to 10 VDC proportional fan coil and zoningYesNo
TEC3022-00-000Yes0 to 10 VDC proportional fan coil and zoningNoYes
TEC3022-01-000No0 to 10 VDC proportional fan coil and zoningNoYes
TEC3023-00-000Yes0 to 10 VDC proportional fan coil and zoningY esYes
TEC3023-01-000No0 to 10 VDC proportional fan coil and zoningYesYes
TEC3030-00-000YesSingle- or two-stage
TEC3030-01-000NoSingle- or two-stage
TEC3031-00-000YesSingle- or two-stage
TEC3031-01-000NoSingle- or two-stage
1. Multiple fan configurations are supported for fan coil equipment types.
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or
N2 Networked Thermostat Controllers Catalog Page (Continued)
Stand-Alone Thermostat Controller Models
Code NumberJohnson Controls
Logo
1
Control OutputOnboard
Occupancy
Sensor
TEC3310-00-000YesOn/off or floating fan coil and zoningNoNo
TEC3310-01-000NoOn/off or floating fan coil and zoningNoNo
TEC3311-00-000YesOn/off or floating fan coil and zoningYesNo
TEC3311-01-000NoOn/off or floating fan coil and zonin gYesNo
TEC3312-00-000YesOn/off or floating fan coil and zoningNoYes
TEC3312-01-000NoOn/off or floating fan coil and zonin gNoYes
TEC3313-00-000YesOn/off or floating fan coil and zoningYesYes
TEC3313-01-000NoOn/off or floating fan coil and zoningYesYes
TEC3320-00-000Yes0 to 10 VDC proportional fan coil and zoningNoNo
TEC3320-01-000No0 to 10 VDC proportional fan coil and zoningNoNo
TEC3321-00-000Yes0 to 10 VDC proportional fan coil and zoningYesNo
TEC3321-01-000No0 to 10 VDC proportional fan coil and zoningYesNo
TEC3322-00-000Yes0 to 10 VDC proportional fan coil and zoningNoYes
TEC3322-01-000No0 to 10 VDC proportional fan coil and zoningNoYes
TEC3323-00-000Yes0 to 10 VDC proportional fan coil and zoningYesYes
TEC3323-01-000No0 to 10 VDC proportional fan coil and zoningYesYes
TEC3330-00-000YesSingle- or two-stage
TEC3330-01-000NoSingle- or two-stage
TEC3331-00-000YesSingle- or two-stage
TEC3331-01-000NoSingle- or two-stage
1. Multiple fan configurations are supported for fan coil equipment types.
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
RTU/heat pump with economizer
NoNo
NoNo
YesNo
YesNo
Dehumidification
Capability
Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controller Models1 (Part 1 of 2)
Code NumberJohnson Controls
Logo
Control OutputOnboard
Occupancy
Dehumidification
Capability
Sensor
TEC3610-00-000YesOn/off or floating fan coil and zoningNoNo
TEC3610-01-000NoOn/off or floating fan coil and zoningNoNo
TEC3611-00-000YesOn/off or floating fan coil and zoningYesNo
TEC3611-01-000NoOn/off or floating fan coil and zonin gYesNo
TEC3612-00-000YesOn/off or floating fan coil and zoningNoYes
TEC3612-01-000NoOn/off or floating fan coil and zonin gNoYes
TEC3613-00-000YesOn/off or floating fan coil and zoningYesYes
TEC3613-01-000NoOn/off or floating fan coil and zoningYesYes
TEC3620-00-000Yes0 to 10 VDC proportional fan coil and zoningNoNo
TEC3620-01-000No0 to 10 VDC proportional fan coil and zoningNoNo
TEC3621-00-000Yes0 to 10 VDC proportional fan coil and zoningYesNo
TEC3621-01-000No0 to 10 VDC proportional fan coil and zoningYesNo
TEC3622-00-000Yes0 to 10 VDC proportional fan coil and zoningNoYes
TEC3622-01-000No0 to 10 VDC proportional fan coil and zoningNoYes
TEC3623-00-000Yes0 to 10 VDC proportional fan coil and zoningYesYes
TEC3623-01-000No0 to 10 VDC proportional fan coil and zoningYesYes
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or
N2 Networked Thermostat Controllers Catalog Page (Continued)
Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controller Models1 (Part 2 of 2)
Code NumberJohnson Controls
Logo
TEC3630-00-000YesSingle- or two-stage
TEC3630-01-000NoSingle- or two-stage
TEC3631-00-000YesSingle- or two-stage
TEC3631-01-000NoSingle- or two-stage
1. Multiple fan configurations are supported for fan coil equipment types.
Accessories (Order Separately)
Product
Description
Code Number
TEC-WALLPLTWallplate for retrofitting existing installations or concealing mounting surface damage; can be used with any TEC3000 Series
MS-WNC1820-0AWNC1800-0SZ with base, 120 to 230 VAC power, ZFR1820 ProCordFlag, with 3 ft (0.9 m) cable
MS-WNC1823-0AWNC1800-0SZ with base, 120 to 230 VAC power, ZFR1823 ProCordWall, with 10 ft (3 m) cable
MS-WNC1820-0BWNC1800-0SZ with base, 24 VAC power, ZFR1820 ProCordFlag, with 3 ft (0.9 m) cable
MS-WNC1823-0BWNC1800-0SZ with base, 24 VAC power, ZFR1823 ProCordWall, with 10 ft (3 m) cable
MS-ZFR1821-0BZFR1821 Pro Flag Repeater, 24 V AC/DC power, with 3 ft (0.9 m) cable
MS-ZFR1822-0BZFR1822 Pro Wall Mount Repeater, 24 VAC/DC power , with 10 ft (3 m) cable
MS-ZFR1821-0ZFR1821 Pro Flag Router, with 3 ft (0.9 m) cable
MS-ZFR1822-0ZFR1822 Pro Wall Mount Router, with 10 ft (3 m) cable
ZFR-CBLEXT-010 ft (3 m) extension cable accessory, RJ12 F-F coupler
ZFR-WALLCOVERZFR Repeater wallplate cover
ZFR-USBHA-0Wireless USB dongle
TE-6300 Series
T-4000-119Allen-head adjustment tool (30 per bag)
1. See Johnson Controls TE-6300 Series T emperature Sensors table for ordering details regarding Johnson Controls TE-6300 Series Remote
Temperature Sensors.
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet® MS/TP or
N2 Networked Thermostat Controllers Catalog Page (Continued)
Johnson Controls TE-6300 Series Temperature Sensors (Order Separately) (Part 2 of 2)
Sensor TypeMounting StyleProbe LengthProduct
Thermistor
(10k ohm)
Type II
1. Two TE-6001-8 Element Holders come with the plat inum-equivalent averaging sensors. Order separately to use with a nickel averaging sensor.
2. Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.
Adjustable8 in. (203 mm)TE-6361A-1
Duct4 in. (102 mm)TE-636GM-1
8 in. (203 mm)TE-6361M-1
18 in. (457 mm)TE-636JM-1
Flange4 in. (102 mm)TE-636GV-2
8 in. (203 mm)TE-6361V-2
FlushN/ATE-6360F-0
Outside air3 in. (76 mm)TE-6363P-1
Strap-mount3 in. (76 mm)TE-636S-1
Well6 in. (152 mm)TE-636AM-2
8 in. (203 mm)TE-6362M-1
Repair Information
If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller,
contact the nearest Johnson Controls representative.
Code Number
TE-6361P-1
TE-6360F-1
Technical Specifications
TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers (Part 1 of 2)
Power Requirements19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safetyextra-low voltage (SELV)
Analog Output Rating
(Proportional Control Models)
Relay Contact Rating
(On/Off, Floating, or Staged
Economizer Control Models)
Fan Relay Output Rating
(On/Off, Floating, and
Proportional Control Models)
Auxiliary Output Rating/Triac
Output (On/Off, Floating, and
Proportional Control Models)
Binary InputsDry contact across terminal COM to terminals BI1, BI2, or COS
Analog InputsNickel, platinum, A99B, 2.25k ohm negative temperature coefficient (NTC), 10k ohm NTC, 10k ohm NTC Type 3
Temperature Sensor TypeLocal 1k ohm platinum sensor
Wire Size18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
MS/TP Network GuidelinesUp to 100 devices maximum per Network Automation Engine (NAE);
Wireless BandDirect-sequence, spread-spectrum, 2.4 GHz ISM band
Transmission Power10 mW maximum
Transmission Range50 ft (15.2 m) practical average indoor
Temperature
Range
AccuracyTemperature±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Minimum Deadband2F°/1C° between heating and cooling
Backlit Display-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating Control40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control54.0°F/12.0°C to 100.0°F/38.0°C
Humidity
(On/Off, Floating,
and Proportional
Control Models)
0 to 10 VDC into 2k ohm resistance (minimum)
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3. 0 A in-rush, Class 2 or SELV
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
across terminal COM to terminals R SEN or COS
4,000 ft (1,219 m) maximum cable length (repeaters can be added to extend this length)
250 ft (76.2 m) maximum indoor line of sight
±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)