Johnson Controls TEC3000 User Manual

TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers Technical Bulletin
www.johnsoncontrols.com
2021-01-21
LIT-12013267
Technical Bulletin

Contents

Contents
Introduction.................................................................................................................................................... 5
Product overview............................................................................................................................................ 5
Proportional Fan Coil and Individual Zone Thermostat Controllers............................................. 5
On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers................................... 6
Single- or Two-Stage RTU/Heat Pump with Economizer Thermostat Controllers...................... 7
Model names and code numbers...................................................................................................... 8
Determining correct pairing of CPU Board and Base Board................................................................ 8
Wireless TEC3000 networks.......................................................................................................................... 9
Configuring a wired TEC3000 for MS/TP or N2 bus................................................................................... 9
Wiring the network.............................................................................................................................. 9
End-of-Line termination.................................................................................................................... 10
Setting the network parameters..................................................................................................... 10
Connecting the MS/TP or N2 bus.................................................................................................... 11
MS/TP or N2 thermostat controller mapping................................................................................ 12
Preparation............................................................................................................................................... 12
Adding a thermostat controller............................................................................................................. 12
Adding BACnet MS/TP points................................................................................................................. 12
Adding N2 points..................................................................................................................................... 13
MS/TP or N2 bus points tables................................................................................................................... 13
Thermostat controllers..................................................................................................................... 13
Scheduling..................................................................................................................................................... 37
Commanding objects from a supervisory controller............................................................................... 39
User lockout....................................................................................................................................... 40
Menu and submenu descriptions.............................................................................................................. 40
Setpoints............................................................................................................................................. 40
Dehumidification...................................................................................................................................... 41
Temperature............................................................................................................................................. 42
Schedule Options............................................................................................................................... 43
Display Settings................................................................................................................................. 43
Setup................................................................................................................................................... 44
General...................................................................................................................................................... 44
Input.......................................................................................................................................................... 47
Tuning........................................................................................................................................................ 48
Network Setup (present in TEC30xx-1x-000, TEC36xx-1x-000, and TEC31xx-14-000
models)...................................................................................................................................... 49
Equipment Setup............................................................................................................................... 49
General (Equipment Setup).................................................................................................................... 49
Supply Fan................................................................................................................................................. 50
Reheat........................................................................................................................................................ 51
Economizer............................................................................................................................................... 51
Heat Pump................................................................................................................................................ 51
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers Technical Bulletin
3
Changeover............................................................................................................................................... 52
Commissioning......................................................................................................................................... 52
Trend.......................................................................................................................................................... 52
Status.................................................................................................................................................. 53
System Status........................................................................................................................................... 53
Control Status........................................................................................................................................... 53
Controller Info.......................................................................................................................................... 54
Comms Status (wireless TECs only)....................................................................................................... 54
Update................................................................................................................................................ 54
BAS Only Points........................................................................................................................................ 54
Troubleshooting........................................................................................................................................... 56
Related documentation............................................................................................................................... 61
Product warranty......................................................................................................................................... 62
Software terms............................................................................................................................................. 62
Patents........................................................................................................................................................... 62
Single point of contact................................................................................................................................. 62
Contact information..................................................................................................................................... 62
4
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin

Introduction

This document describes how to configure the various wireless and wired TEC3000 Series Thermostat Controllers for BACnet MS/TP or N2 networked applications, including how to:
Connect to the MS/TP or N2 bus and map a thermostat controller into a Network Automation Engine (NAE)
Add a thermostat controller
Add points
Command and configure from an NAE
Troubleshoot the thermostat controller

Product overview

The technologically advanced TEC3000 Series Thermostat Controllers feature a Building Automation System (BAS) BACnet MS/TP or N2 connectivity that enables remote monitoring and programming for efficient space temperature control. The TEC3000 Series Thermostat Controllers feature an intuitive user interface with backlit color display that makes setup and operation quick and easy. The programming memory of all TEC3000 Series Thermostat Controllers is non-volatile.
In addition, the configuration can be backed up to a USB drive and restored to like models to help expedite the commissioning process. Refer to the TEC3000 Series On/Off or Floating Fan Coil
Thermostats Installation Guide (LIT-12013161), TEC3000 Series Proportional Fan Coil Thermostats Installation Guide (LIT-12013162), or TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide (LIT-12013163) for information on using the USB
drive.
The TEC3000 Series Thermostat Controllers are BACnet MS/TP, N2, or ZFR Wireless networked devices that provide control of:
Rooftop units (with or without economizers, dehumidification, or hot gas bypass)
Heat pumps
Single- and multi-stage heating and cooling equipment
Humidification and dehumidification equipment
Two- or four-pipe fan coils
Cabinet unit heaters
Local hydronic reheat valves
Pressure-dependent Variable Air Volume (VAV) equipment with or without local reheat
Other individual zone equipment using an on/off, floating, or proportional 0 VDC to 10 VDC control input

Proportional Fan Coil and Individual Zone Thermostat Controllers

The TEC3000 Series Proportional Fan Coil and Individual Zone Thermostat Controllers are field­selectable BACnet MS/TP, N2, or ZFR Wireless networked devices that provide control of:
Local hydronic reheat valves
Pressure-dependent VAV equipment with or without local reheat
Technical Bulletin
5TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using a proportional 0 VDC to 10 VDC control input
The networked models feature a BAS BACnet MS/TP, N2, or ZFR Wireless communication capability that enables remote monitoring and programming for efficient space temperature control.
Some models have occupancy-sensing capability built into the device. These thermostat controllers maximize up to 30% energy savings in high-energy usage, light commercial buildings, such as schools and hotels. Savings occur during occupied times by using additional standby setpoints when occupants are not in the room.
All models feature an intuitive UI with backlit display that makes setup and operation quick and easy. Multiple fan configurations are supported for all equipment types.
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 VDC to 10 VDC control)
All models contain a built-in humidity sensor to support dehumidification on two-pipe fan coil units with reheat and four-pipe fan coil units with individual coils or single coil with heating and cooling valves installed. When no heating is required, the thermostat controller monitors space humidity and activates dehumidification control as necessary. Heat, reheat, or both are used as required to prevent over-cooling while achieving humidity setpoint and maintain the space temperature. For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan.

On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers

The TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers are field-selectable BACnet MS/TP, N2, or ZFR Wireless networked devices that provide control of:
Local hydronic reheat valves
Pressure-dependent VAV equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a BAS BACnet MS/TP, N2, or ZFR Wireless communication capability that enables remote monitoring and programming for efficient space temperature control.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to 30% energy savings in high-energy usage, light commercial buildings, such as schools and hotels. Savings occur during occupied times by using additional standby setpoints.
All models feature a UI with backlit color display that makes setup and operation quick and easy. Multiple fan configurations are supported for all equipment types.
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 VDC to 10 VDC control)
All models contain a built-in humidity sensor to support dehumidification on two-pipe fan coil units with reheat and four-pipe fan coil units with individual coils or single coil with heating and cooling
6
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin
valves installed. When no heating is required, the thermostat controller monitors space humidity and activates dehumidification control as necessary. Heat, reheat, or both are used as required to prevent over-cooling while achieving humidity setpoint and maintain the space temperature. For optimal dehumidification performance, use a fan coil unit with a multi-speed or variable-speed fan.

Single- or Two-Stage RTU/Heat Pump with Economizer Thermostat Controllers

The TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers are field-selectable BACnet MS/TP, N2, or ZFR Wireless networked devices that provide control of:
Unitary rooftop units (RTUs)
Unitary RTUs with economizers
Unitary RTUs with heat pumps
Unitary RTUs with economizers and heat pumps
Unitary RTUs with hot gas reheat
Unitary RTUs with hot gas reheat and economizers
The networked models feature a BAS BACnet MS/TP, N2, or ZFR Wireless communication capability that enables remote monitoring and programming for efficient space temperature control.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to 30% energy savings in high-energy usage, light commercial buildings, such as schools and hotels. Savings occur during occupied times by using additional standby setpoints.
All models feature an intuitive UI with backlit color display that makes setup and operation quick and easy. Only the single-speed fan configuration is supported for RTU equipment types.
All models contain a build-in humidity sensor to support dehumidification on RTUs with hot gas reheat and RTUs with auxiliary dehumidifier installed. When no heating is required, the thermostat controller monitors the space humidity and activates dehumidification control as necessary. The controller uses heat, reheat, or both as required to prevent over-cooling while it achieves the humidity setpoint and maintains the space temperature.
Technical Bulletin
7TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers

Model names and code numbers

Table 1: TEC3000 model names and code numbers
Name Code number Name Code number
TEC3012-13 30 TEC3313-14 05 TEC3012-14 31 TEC3322-13 08 TEC3012-16 33 TEC3322-14 09 TEC3013-14 35 TEC3322-16 0B TEC3022-13 38 TEC3323-14 0D TEC3022-14 39 TEC3330-13 10 TEC3022-16 3B TEC3330-14 11 TEC3023-14 3D TEC3330-16 13 TEC3030-13 40 TEC3331-14 15 TEC3030-14 41 TEC3612-13 18 TEC3030-16 43 TEC3612-14 19 TEC3031-14 45 TEC3612-16 1B TEC3112-14 49 TEC3613-14 1D TEC3113-14 4D TEC3622-13 20 TEC3122-14 51 TEC3622-14 21 TEC3123-14 55 TEC3622-16 23 TEC3130-14 59 TEC3623-14 25 TEC3131-14 5D TEC3630-13 28 TEC3312-13 00 TEC3630-14 29 TEC3312-14 01 TEC3630-16 2B TEC3312-16 03 TEC3631-14 2D

Determining correct pairing of CPU Board and Base Board

Important: Make sure you attach the cover that corresponds to its correct base. The CPU board number needs to match the Base board number. Otherwise you encounter an operation error after you reattach a cover and base that do not belong together, as shown in Figure 1.
Figure 1: Error code indicating mismatched boards
Note: The example shown in Figure 1 indicates a TEC3612-16 CPU board that is mounted on
the base of a TEC3312-16.
8
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin

Wireless TEC3000 networks

The TEC3000 includes an embedded wireless router and can only be used on a ZFR182x or ZFR183x Pro Series Wireless Network.
The WRG1830/ZFR183x Pro Series Wireless Field Bus System is similar to the WNC1820/ZFR182x Series wireless system in many ways. But there are several important differences.
The wireless networks (PANs) formed by the ZFR183x and ZFR182x systems are not compatible.
The ZFR182x Series Routers and TEC3000 are not field upgradeable to be compatible with the ZFR1830 Series System.
Important: ZFR182x Pro Series Wireless System compatible TEC30xx-1x-000 models and ZFR183x Pro Series Wireless System compatible TEC31xx-1x-000 models are not compatible with each other and cannot be used under the same PAN ID (network address).
Table 2: ZFR183x Pro Series indoor transmission ranges
Range type Transmission distance
ZFR to ZFR TEC to ZFR
TEC to TEC Recommended 250 ft (75 m) 250 ft (75 m) 50 ft (15.2 m) Maximum, Line of Sight 1000 ft (304.8 m) 1000 ft (304.8 m) 100 ft (30 m)
WRZ to ZFR
In ZFR182x Pro Series networks, place every wireless TEC3000 within 50 ft (15 m) of at least two other TEC3000 or ZFR182x wireless devices.
In ZFR183x Pro Series networks, place every wireless TEC3000 within 250 ft (76.2 m) of at least two other ZFR183x Pro Series wireless TEC3000.
If any wireless TEC3000 is not within 50 ft (15 m) of a ZFR182x Pro Series, or 250 ft (76.2) of a ZFR183x Pro Series system with other compatible wireless TEC, use compatible ZFR182x or ZFR183x Routers as repeaters with applicable accessories to provide multiple wireless data pathways.
Note: Change the address of the wireless TEC. The address on the wireless TEC is invalid from the factory so it must be changed when installed.
A wireless network requires a network coordinator/gateway. See the WNC1800/ZFR182x Pro Series
Wireless Field Bus System Technical Bulletin (LIT-12012356) and WRG1830/ZFR183x Pro Series Wireless Field Bus System Technical Bulletin (LIT-12013553) for more information about the layout of a ZFR182x
or ZFR183x Pro Series Network.

Configuring a wired TEC3000 for MS/TP or N2 bus

The TEC3000 supports network connectivity to a BAS using a BACnet MS/TP or N2 bus. You select BACnet MS/TP or N2 communication through the software.

Wiring the network

N2 and BACnet MS/TP protocols use the same physical connections for an RS-485 connection, that requires three conductors:
NET +
NET -
Technical Bulletin
9TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
NET COM
Connect the TEC3000 in line with other devices on the network.

End-of-Line termination

When the TEC3000 is the last device on the bus, make sure the end-of-line (EOL) switch on the I/O board is in the On position.
Note: If the EOL switch is not on the I/O board, the thermostat is a stand-alone model.
Figure 2: EOL switch positions

Setting the network parameters

All network configuration is done through the software. On the home screen, click the menu icon. Scroll down to Network Setup for the network settings. Out of the box, the thermostat is configured in BACnet MS/TP mode. To change to the N2 mode, select FC Comm Mode and change to N2. This change reboots the device when you click the save icon.
10
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin
Table 3: Setup menus
Menu parameter Description
BACnet Instance ID This is the instance ID of the device on the BACnet MS/TP bus. BACnet
MS/TP systems use the instance ID for identification of the device. It can be set from 1 to 4,194,302 and is unique to that site. The default is 1.
BACnet Device Address This is the physical MAC address of the BACnet MS/TP device on the bus.
It can be set from 4 to 127. Two devices on the same bus cannot have the same BACnet MS/TP device address. The default is 4.
MSTP Baud Rate This is the baud rate that the TEC communicates on the network. The
default value is Auto, which allows the device to automatically detect the baud rate of the BACnet MS/TP bus and operate at that speed. An incorrect value causes the device to not communicate on the network, and can potentially cause the network to fail. Options for this setting are Auto, 1,200, 9,600, 19,200, 38,400, and 76,800 Baud.
BACnet Encoding Type This is the method of data encoding and is used by the BACnet MS/TP
bus. The default value, ISO 10646 (UCS-2), is the encoding used by the Metasys® platform. When operating on a third-party BAS, refer to the documentation provided with the BAS for the correct encoding type.
N2 Device Address This is the physical MAC address of the N2 device on the bus and can be
set from 1 to 255. Two devices on the same bus cannot have the same N2 device address.

Connecting the MS/TP or N2 bus

About this task: To connect the MS/TP or N2 bus, complete the following steps:
1. Set the MS/TP or N2 address of the TEC3000 Series BACnet MS/TP or N2 Network Temperature and Humidity Thermostat Controller according to the engineering drawings.
Note: For more details on wiring the MS/TP Communications bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Observe the polarity when connecting the bus wires to the thermostat controller.
3. After the bus wires are connected to the first thermostat controller, continue in a daisy­chained fashion to the next thermostat controller.
Note: The bus wiring must be twisted-pair lines. Do not run the bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
Result
Configure the thermostat controller for automatic baud rate detection. Do not exceed the maximum number of devices allowed on a field bus. Ensure that the wiring terminations are set correctly and that all communication wiring is daisy-chained with no T taps.
Technical Bulletin
11TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers

MS/TP or N2 thermostat controller mapping

Preparation

About this task: Before you map a TEC3000 Series field-selectable BACnet MS/TP or N2 Network Thermostat Controller into an NAE:
1. Decide which points within the thermostat controller need to be mapped. Only map the points that need to be viewed or commanded on a regular basis. Excessive point mapping lowers system performance. Suggested points for mapping include Zone Temp, System Mode, Fan Mode, Manual Occupancy Mode, Occupied Heating Setpoint, Occupied Cooling Setpoint, Unoccupied Heating Setpoint, and Unoccupied Cooling Setpoint. In addition, alarm points may be mapped if they are used, and other points may be mapped if required. Use the Engineering view of the MS/TP trunk on the NAE to examine infrequently used points.
Note: Set all thermostat controller configuration parameters as required before you map the points into the NAE. If you alter any thermostat controller configuration parameters after you mapped the points into the thermostat controller, re-map all points individually, because some exposed points might have been added or removed. Be careful when you map configuration parameters, because they should only be mapped if the operator is fully familiar with their use.
2. Verify that a Field bus is defined in the NAE. BACnet MS/TP or N2 devices attach to a Field bus. Refer to the Metasys N2 Communication Bus Technical Bulletin (LIT-636018) for instructions on how to define a Field bus.
3. For Metasys system software earlier than Release 4.0, verify that a BACnet Integration is defined for the Field bus. The thermostat controllers are mapped as BACnet MS/TP devices under a Field bus BACnet Integration. Refer to the BACnet Controller Integration with NAE/
NCE Technical Bulletin (LIT-1201531) or the Metasys N2 Communication Bus Technical Bulletin (LIT-636018) for instructions on how to define a BACnet Integration.
Note: Metasys system Release 7.0.7 or later software is required for correct support of text strings on all network points.
Result
At this point, you can map the thermostat controller and the required points inside the thermostat controller.

Adding a thermostat controller

You must add the thermostat controller before you can map its points. To add the thermostat controller, select either the Field or N2 bus (depending on the selected configuration) and choose Field Device from the Insert menu.
Assisted Definition using Auto Discovery is the easiest way to add a new thermostat controller online; however, this method requires that the thermostat controller that you want to add is connected and ready to communicate. Device addresses must be unique from 4 to 127 for the BACnet MS/TP and 1 to 255 for the N2 network.
Note: Do not use the MAP-ALL functionality when you add the thermostat controller to a Supervisory device, because this adds all TEC3000 Trend Objects which cannot be viewed in the Supervisory device. These trends update every 15 minutes which could cause issues in the Supervisory device.

Adding BACnet MS/TP points

You must map the required points under the thermostat controller device. To map the points, select the thermostat controller device under the BACnet Integration (if required, refresh the tree view to see a newly added thermostat controller device) and choose Field Point from the Insert menu.
12
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin
Assisted Definition using Auto Discovery is the easiest way to add new points online; however, this function requires that the thermostat controller that you want to map is connected and ready to communicate. When mapping points offline, the point type must match the BACnet object type (for example, AV, MV, BI), and the point instance number must match the point BACnet instance number.

Adding N2 points

You must map the required points under the thermostat controller device. To map the points, select the thermostat controller device under the N2 Integration (if required, refresh the tree view to see a newly added thermostat controller device) and choose Field Point from the Insert menu.
Then you need to add the appropriate PRN file based on the TEC model being used as an extension to the device. Multi-state points are defined as ADI points in the PRN file. You must map these using either MI or MO NAE object types. Following the field point addition, object units may need further tailoring of units and enum set values. See Table 4, Table 5 or Table 6 for the enum set values.

MS/TP or N2 bus points tables

Thermostat controllers

Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
type
Control Mode SYSTEM-MODE MV 29500 MI, ADI 1 TEC3000 Unit Control Mode
Unit Enable UNITEN-MODE MV 29501 MI, ADI 2 Shutdown/Enable
Occupied Cooling Setpoint
Occupied Heating Setpoint
Unoccupied Cooling Setpoint
Unoccupied Heating Setpoint
Standby Cooling Setpoint
Standby Heating Setpoint
Setpoint Offset WC-ADJ AV 29508 AO, ADF 7 (Negative) Max Setpoint Offset.
Hold/Run HOLDRUN-
Humidity Setpoint ZNH-SP AV 29510 AO, ADF 8 0% RH to 100% RH
CLGOCC-SP AV 29502 AO, ADF 1 60°F to 100°F (15.05°C to 37.78°C)
HTGOCC-SP AV 29503 AO, ADF 2 45°F to 85°F (7.22°C to 29.44°C)
CLGUNOCC-SP AV 29504 AO, ADF 3 60°F to 100°F (15°C to 38°C)
HTGUNOCC-SP AV 29505 AO, ADF 4 45°F to 85°F (7°C to 30°C)
CLGSTBY-SP AV 29506 AO, ADF 5 60°F to 100°F (15°C to 38°C)
HTGSTBY-SP AV 29507 AO, ADF 6 45°F to 85°F (7°C to 30°C)
MV 29509 MI, ADI 3 Hold/Run
MODE
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. Auto
2. Cooling
3. Heating
1. Shutdown
2. Enable
*When Occ Setpoint Select = Setpoint Offset. Otherwise, see Table 11 for constraints
1. Hold
2. Run
Technical Bulletin
13TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
type
Network Override
NET-OAT AV 29513 AO, ADF 11 -50°F to 125°F (-46°C to 52°C) Outdoor Air Temperature
Network Override
NET-OAH AV 29514 AO, ADF 12 0% RH to 100% RH Outdoor Air Humidity
Network Override
NET-SAT AV 29515 AO, ADF 13 0°F to 150°F (-18°C to 65°C) Supply Air Temperature
Network Override
NET-ZNH AV 29516 AO, ADF 14 0% RH to 100% RH Zone Humidity
Reset PID Tuning TUNING-RESET MV 29517 MI, ADI 4 No/Yes
Manual Occupancy
OCCOVRD-MODE MV 29518 MI, ADI 5 UI Occ Override Mode
Supervisor
NET-OCC MV 29519 MI, ADI 6 Occ Schedule Occupancy
Occupancy
OCC-CONFIG MV 29520 MI, ADI 7 SE Occupancy Mode Schedule Source
Changeover Mode CGOVR-MODE MV 29523 MI, ADI 8 TEC3000 Unit Control Mode
Passcode
PASSCODE
11
MV 29522 AI, ADF 15 00000 to 99999
Fan Mode FAN-MODE MV 29524 MI, ADI 9 TEC3000 Fan Mode
Fan Override FANOVRD-MODE MV 29525 MI, ADI 10 UI Fan Override
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. No
2. Yes
1. No Override
2. Occupied
3. Unoccupied
1. Occupied
2. Unoccupied
3. Standby
1. Schedule
2. External
1. Auto
2. Cooling
3. Heating
1. On
2. Auto
3. Smart *This point only shows if the unit type is 2-pipe or 4-pipe and the fan type is single- or variable-speed
1. On
2. Auto
3. Quiet *This point only shows if the unit type is 2-pipe or 4-pipe and the fan type is single- or variable-speed
14
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin
Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
type
Aux Mode AUX-MODE MV 29527 MI, ADI 11 TEC3000 Aux Mode
Units TEMP-UNITS MV 29528 MI, ADI 12 Unit Set
Max Setpoint Offset MAXSP-OFFSET AV 29529 AO, ADF 29 0 to 20 delta °F (0 to 11 delta °C) Changeover
Setpoint Unit Status UNIT-S MV 29700 MI, ADI 13 TEC3000 Detailed Control Status2
Operational Space Temperature
Return Air Humidity EFF-ZNH AV 29702 AO, ADF 17 n/a Supply Air
Temperature
CGOVR-SP AV 29530 n/a n/a 40°F to 200°F (4°C to 93°C)
EFF-ZNT AV 29701 AO, ADF 16 n/a
EFF-SAT AV 29703 AO, ADF 18 n/a
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. Not Used
2. Occupied NO
3. Occupied NC
4. Occupied Fan NO
5. Occupied FAN NC
6. On
7. Off
1. IP
2. SI
1. System Fault
2. Airflow Fault
3. Open Window
4. Control Off
5. Unreliable Temperature
6. Dehumidification
7. Idle
8. Cooling
9. Heating
10. Cooling Unavailable
11. Heating Unavailable
12. Cooling Unavailable due to Changeover
13. Cooling Unavailable due to OA Temp
14. Cooling Unavailable due to Control Mode
15. Heating Unavailable due to Changeover
16. Heating Unavailable due to OA Temp
17. Heating Unavailable due to Control Mode
18. Load Shed Active
19. Dehumidifying – Reheat
20. Dehumidifying – Fan Only
21. Dehum Unavail By Dew Point
Technical Bulletin
15TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
type
Operational Outdoor Air Temperature
Active Setpoint EFF-SETPOINT AV 29705 AO, ADF 20 n/a CV Operating
Cooling Setpoint CV Operating
Heating Setpoint Occupancy Status EFF-OCC MV 29708 MI, ADI 14 TEC3000 Occupancy Status
Occupancy Input Source
Changeover State CGOVR-S n/a n/a MA, ADI 16 TEC3000 Changeover Status
Fan % Command FANSPD-% AV 29711 AO, ADF 23 0% to 100% Fan Speed FANSPD-S MV 29712 MI, ADI 18 Supply Fan Status
Cool/Dehum PID Control
Heat PID Cmd HTGPID-% AV 29717 AO, ADF 26 0% to 100% Reheat PID Cmd RHPID-% AV 29720 AO, ADF 27 0% to 100% Load Shed Active LOADSHED-EN MV 29728 MI, ADI 19 No/Yes
Load Shed Rate Limit
Load Shed Adjust LOADSHED-RL-
Occupancy Override Duration
EFF-OAT AV 29704 AO, ADF 19 n/a
EFFCLG-SP AV 29706 AO, ADF 21 n/a
EFFHTG-SP AV 29707 AO, ADF 22 n/a
OCCSOURCE-S MV 29709 MI, ADI 15 TEC3000 Occupancy Source
CLGPID-% AV 29714 AO, ADF 25 0% to 100%
LOADSHED-RL AV 29725 AO, ADF 30 0°F to 1°F/min (0°C to 0.5°C/min)
AV 29726 AO, ADF 31 0 to 8 delta °F (0 to 5 delta °C)
ADJ TEMPOCC-LEN AV 29727 AO, ADF 32 0 minutes to 300 minutes
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. Occupied
2. Temp Occupancy
3. Unoccupied
4. Standby
5. Occupied-Override
6. Unoccupied-Override
1. Occupancy BI
2. Temp Occ BI
3. Temp Occ
4. Occ Override
5. Local Schedule
6. BAS Schedule
7. Occupancy Sensor
1. Changeover Disabled
2. Cooling Mode
3. Heating Mode
4. Supply Temperature Unreliable
1. Off
2. On
3. Low
4. Medium
5. High
1. No
2. Yes
16
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin
Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
type
Lockout Level LOCL-LVL MV 29531 MI-ADI 20 States (0-2)
Unoccupied Off
UNOCC-OFF-DLY AV 29532 AO, ADF 33 0 minutes to 10 minutes
Delay Heat Prop Band HTG-PROP-BAND AV 29535 AO, ADF 34 5 to 30 delta °F (2.8 to 16.7 delta °C) Heat Integral Time HTG-INT-TIME AV 29536 AO, ADF 35 300 seconds to 1600 seconds Heat Process Range HTG-PROC-
AV 29537 AO, ADF 36 10 to 100 delta °F (5.6 to 56 delta °C)
RANGE
Heat Saturation
HTG-SAT-TIME AV 29538 AO, ADF 37 60 seconds to 900 seconds
Time Heat Time Constant HTG-TIME-
AV 29539 AO, ADF 38 360 seconds to 1440 seconds
CONST
Heat Process Dead
HTG-DEAD-TIME AV 29540 AO, ADF 39 20 seconds to 120 seconds
Time Heat Period HTG-PERIOD AV 29541 AO, ADF 40 30 seconds to 120 seconds Cool Prop Band CLG-PROP-BAND AV 29542 AO, ADF 41 5 to 30 delta °F (2.8 to 16.7 delta °C) Cool Integral Time CLG-INT-TIME AV 29543 AO, ADF 42 300 seconds to 1600 seconds Cool Process Range CLG-PROC-
AV 29544 AO, ADF 43 10 to 100 delta °F (5.6 to 56 delta °C)
RANGE
Cool Saturation
CLG-SAT-TIME AV 29545 AO, ADF 44 60 seconds to 900 seconds
Time Cool Time Constant CLG-TIME-CONST AV 29546 AO, ADF 45 360 seconds to 1440 seconds Cool Process Dead
CLG-DEAD-TIME AV 29547 AO, ADF 46 20 seconds to 120 seconds
Time Cool Period CLG-PERIOD AV 29548 AO, ADF 47 30 seconds to 120 seconds Deadband DEADBAND AV 29556 AO, ADF 55 1.4 to 3 delta °F (0.78 to 1.66 delta °C) Min Heating
MINHTG-SP AV 29559 AO, ADF 56
Setpoint
Max Heating
MAXHTG-SP AV 29560 AO, ADF 57 Present value of Min Heating Setpoint
Setpoint
Min Cooling
MINCLG-SP AV 29561 AO, ADF 58 Present value of Max Heating Setpoint
Setpoint
Max Cooling
MAXCLG-SP AV 29562 AO, ADF 59 Min Cooling Setpoint present to 100°F
Setpoint
Occ Setpoint Select OCCSP-SEL MV 29563 AO, ADF 60 Occ Setpoint Select
Min Setpoint MIN-SP AV 29564 AO, ADF 61
Max Setpoint MAX-SP AV 29565 AO, ADF 62
Heat Cool Setpoint Mode
HTGCLGSP­MODE
MV 29566 MI, ADI 24 Heat Cool Setpoint Mode
Common Setpoint COMMON-SP AV 29567 AO, ADF 62 55°F to 90°F (12.77°C to 32.22°C)
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. State 0
2. State 1
3. State 2
2
45°F (7.22°C) to Max Heating Setpoint Present Value
2
(MINHTG-SP) to present value of Min Cooling Setpoint (MINCLG-SP)minus 1
(MAXHTG-SP) plus 1 to present value of Max Cooling Setpoint (MAXCLG-SP)
(37.78°C)
2
1. Setpoint Offset
2. Min and Max Setpoint
3
45°F to 85°F (7°C to 30°C)
60°F to 100°F (16°C to 38°C)
3
3
1. Common Setpoint
2. Individual Setpoints
2
2
Technical Bulletin
17TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
type
Fan Mode 2 FAN-MODE2 MV 29568 MI, ADI 27 TEC3000 Fan Mode 2
Fan Override 2 FAN-OVRD2 MV 29569 MI, ADI 28 UI Fan Override 2
Temp Control Setup TEMPCTRL-
SETUP
Control State TEMPCTRL-
SETUP2
Network Override Zone Temperature
Signal Strength Signal Strength MV 29724 n/a n/a Wireless Signal Strength
PAO1 Output / Cooling Valve % Command
PAO2 Output / Heating Valve % Command
AO1 Output / Fan Speed Percent Command
NET-ZNT AV 29571 AO, ADF 63 -50°F to 120°F (-45°C to 49°C)
CLG-O AO 86914 AO, AO 1 0% to 100%
HTG-O AO 86915 AO, AO 2 0% to 100%
VSF-O AO 86905 AO, AO 3 0% to 100%
MV 29533 MI, ADI 21 TEMP_CONTROL_SETUP
MV 29570 MI, ADI 26 TEMP_CONTROL_SETUP_SUBSET
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. Auto
2. Smart
3. Low
4. Medium
5. High *This point only shows if the unit type is 2-pipe or 4-pipe and the fan type is multispeed
1. Auto
2. Quiet
3. Low
4. Medium
5. High *This point only shows if the unit type is 2-pipe or 4-pipe and the fan type is multispeed
1. Automatic PID Tuning
2. Deadband Override
3. Manual PID Tuning
4. On Off Control (available on units
with single-speed fan and On/Off actuators configured)
1. Automatic PID Tuning
2. Deadband Override
3. Manual PID Tuning (available on
units with a multi-speed, variable speed fan, or floating actuators configured)
1. None
2. Weak
3. Average
4. Strong
18
TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Technical Bulletin
Table 4: Points for TEC3612-1x-000, TEC3613-1x-000, TEC3012-1x-000, TEC3013-1x-000, TEC3112-14-000, and TEC3113-14-000
Point description Point name Object
4
BO1 Command /
CLGO-C BO 86908 BO, BO 1 Inactive/Active
type
BO1 Cool NO/
4
Open
BO2 Command /
FANL-C BO 86909 BO, BO 2 Inactive/Active BO2 Fan Low Command
BO3 Command /
FANM-C BO 86910 BO, BO 3 Inactive/Active BO3 Fan Medium Command
BO4 Command /
FANH-C BO 86911 BO, BO 4 Inactive/Active BO4 Fan High Command
BO5 Command /
HTGO-C BO 86912 BO, BO 5 Inactive/Active BO5 Heat NO/
4
Open
5
BO6 Command / BO6 Cool NC/Close
BO7 Command /
CLGC-C BO 87101 BO, BO 6 Inactive/Active
5
HTGC-C BO 87102 BO, BO 7 Inactive/Active BO7 Heat NC/
5
Close
AUX Command /
AUX BO 86913 BO, BO 8 Inactive/Active BO8 AUX
BI1 Sensor / Binary
BI1-S BI 30827 BI, BI 1 Inactive/Active Input 1
BI2 Sensor / Binary
BI2-S BI 30828 BI, BI 2 Inactive/Active Input 2
Schedule Schedule Schedule 10133 n/a n/a n/a Local Occupancy LOCAL-OCC MV 6 n/a n/a Occ Schedule
Calendar Calendar Calendar 10019 n/a n/a n/a Dehumidification
DEHUM ENABLE MV 29736 n/a n/a No/Yes Enable
Unocc Dehum Enable
UNOCC DEHUM
ENABLE
MV 29737 n/a n/a No/Yes
InstanceIDPoint
type
Point address
Unit (IP), enum set/range
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Inactive
2. Active
1. Occupied
2. Unoccupied
3. Standby
4. Not Set
1. No
2. Yes
1. No
2. Yes
Technical Bulletin
19TEC3000 Color Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers
Loading...
+ 43 hidden pages