Johnson Controls TEC26x7VVT-2 Series Catalog Page

Code No. LIT-1900440 Issued November 8, 2006
TEC26x7VVT-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs for VVT Systems

Description

The TEC26x7VVT-2 Series Thermostats are BACnet® Master-Slave/Token-Passing (MS/TP) networked devices that provide control of pressure dependent Variable Air Volume (VAV) equipment with or without local reheat, or other zoning equipment using a floating or proportional 0 to 10 VDC control input for Variable Air Volume and Temperature (VVT) systems. The technologically advanced TEC26x7VVT-2 Series Thermostats feature a Building Automation System (BAS) BACnet MS/TP communication capability that enables remote monitoring and programmability for efficient space temperature control.
The TEC26x7VVT-2 Series Thermostats feature an intuitive user interface with backlit display that makes setup and operation quick and easy. The thermostats also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostats.
Refer to the TEC26x7VVT-2 Series BACnet
MS/TP Networked Thermostats with Two Outputs for VVT Systems Product Bulletin (LIT-12011227) for important product
application information.

Features

• BACnet MS/TP communication — provides compatibility with a proven communication network; BACnet MS/TP is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English plain text messages with constant backlight that brightens during user interaction
• floating or proportional 0 to 10 VDC control — offers additional application flexibility by providing more advanced control signals
• override interface key — allows easy access for temporarily overriding the unoccupied mode
• simplified setpoint adjustment — enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys
• two configurable binary inputs — provide additional inputs for advanced functions such as remote night setback, service or filter alarms, motion detector, and window status
• over 20 configurable parameters — enable the thermostat to adapt to any application, allowing installer parameter access without opening the thermostat cover
• discharge air sensor — monitors unit efficiency
TEC26x7VVT-2 Series BACnet
MS/TP Networked Thermostat with
Two Outputs for VVT Systems

Repair Information

If the TEC26x7VVT-2 Series Thermostat fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.

Selection Chart

Code Number Control Outputs
TEC2627VVT-2 Two Floating TEC2647VVT-2 Two Proportional 0 to 10 VDC

Accessories

Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor TE-6361M-1
SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and Light-Emitting Diode (LED) TE-636S-1 Strap-Mount Temperature Sensor MS-BACEOL-0 RS485 End-of-Line Terminator
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors
The performance specifications are nomina l and confo rm to ac ceptable i ndustry stand ards. For ap plications a t conditio ns beyond the se specifications, consult the local Jo hnson Contro ls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2006 Johnson Controls, Inc.
1
Product Bulletin (LIT-216320) fo r more details.
Duct Mount Air Temperature Sensor
www.johnsoncontrols.com
1 of 2
Code No. LIT-
TEC26x7VVT-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs for VVT Systems (Continued)
4-15/16
(125)
Room Temp
70.0ºF
3-3/8
(86)
1-1/8
(29)
s
n
s
n m d
: G
I F
Thermostat Dimensions, in. (mm)

Technical Specifications

TEC26x7VVT-2 Series BACnet MS/TP Networked Thermostats with Two Outputs for VVT Systems
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal,
Relay/Triac Contact Rating
Floating Control 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Analog Output Rating Proportional Control 0 to 10 VDC into 2k ohm Resistance (Minimum) Auxiliary Output Rating Triac Output 30 VAC, 1.0 A Maximum, 3.0 A In-Rush Digital Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0 .6 mm Diameter) Recommended MS/TP Network Guidelines 32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length Temperature Range Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing Compliance United States UL Listed, File E27734, CCN XAPX,
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 89/336/EEC
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant Shipping Weight 0.75 lb (0.34 kg)
Class 2 or Safety Extra-Low Voltage(SELV)
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
The performance specifications are nomina l and confo rm to ac ceptable i ndustry stand ards. For ap plications a t conditio ns beyond the se specifications, consult the local Jo hnson Contro ls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2006 Johnson Controls, Inc.