Johnson Controls TEC26x6 Series Catalog Page

Code No. LIT-1900620
TEC26x6(H)-4 Series
Thermostat Controller
TEC26x6H-4+PIR Series
Thermostat Controller
Issued December 1, 2009
TEC26x6 Series
BACnet® MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers are BACnet® Master-Slave/Token-Passing (MS/TP) networked devices that provide control of two­or four-pipe fan coils, cabinet unit heaters, or other equipment using on/off, floating, or proportional 0 to 10 VDC control input, three speeds of fan control, and dehumidification capability. The TEC26x6H-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These devices maximize up to 30% energy savings in high-energy usage light commercial buildings, such as schools and hotels, during occupied times by using additional Stand-By setpoints.
The technologically advanced TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers feature a Building Automation System (BAS) BACnet MS/TP communication capability that enables remote monitoring and programming for efficient space temperature control. Specific models are available to accommodate commercial and hospitality applications.
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers feature an intuitive User Interface (UI) with backlit display that makes setup and operation quick and easy. The thermostats also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers.
Refer to the TEC26x6(H)-4 and
TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin (LIT-12011587) for important product
application information.
Features
• BACnet MS/TP communication — provides compatibility with a proven communication network; BACnet MS/TP is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers
• onboard occupancy sensor (Passive Infrared [PIR] Models) — provides energy savings without additional installation time and cost
• password protection option — protects against unwanted thermostat controller tampering
• integral humidity sensing capability (dehumidification models) — increases occupancy comfort by providing dehumidification
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English plain text messages with constant backlight that brightens during user interaction
• on/off, floating, or proportional 0 to 10 VDC control — offers additional application flexibility by providing more advanced control signals
• three speeds of fan control — provide easy FAN speed selection via the interface key, to meet the application requirements
Selection Chart
TEC26x6(H)-4 and TEC26x6H-4+PIR Thermostat Controller Models (Part 1 of 2)
Code Number Control Outputs Onboard
Occupancy Sensor
TEC2616-4 Two On/Off No No Commercial Market TEC2616H-4 Two On/Off No No Hospitality Market TEC2616H-4+PIR Two On/Off Yes No Hospitality Market TEC2626-4 Two On/Off or Fl oating No No Commercial Market TEC2626H-4 Two On/Off or Floating No No Hospitality Market TEC2626H-4+PIR Two On/Off or Floating Yes No Hospitality Market
Dehumidification Capability
• single/dual setpoint adjustment — enables user setpoint options to accommodate application
• override interface key (commercial models) — allows easy access for temporarily overriding the unoccupied mode
• temperature scale selector key (hospitality models) — offers guests the ability to select a Fahrenheit (°F) or Celsius (°C) temperature scale display
• two configurable binary inputs — provide additional inputs for advanced functions such as remote night setback, service or filter alarms, motion detector, and window status
• over 20 configurable parameters — enable the thermostat to adapt to any application, allowing installer parameter access without opening the thermostat cover
• optional discharge air sensor — monitors unit efficiency
Repair Information
If a TEC26x6(H)-4 or TEC26x6H-4+PIR Series Thermostat fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.
Application
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
1 of 3
www.johnsoncontrols.com
TEC26x6 Series BACnet® MS/TP Networked Thermostat Controllers with
4-15/16
(125)
3-3/8
(86)
1-1/8
(29)
(125)
(86)
(36)
70.0ºF
Room Temp
Room Temp
°C
°F
TEC26x6(H)-4 and TEC26x6H-4+PIR Thermostat Controller Dimensions, in. (mm)
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
TEC26x6(H)-4 and TEC26x6H-4+PIR Thermostat Controller Models (Part 2 of 2)
Code Number Control Outputs Onboard
Occupancy Sensor
TEC2636-4 Two On/Off or Floating No Yes Commercial Market TEC2636H-4 Two On/Off or Floating No Yes Hospitality Market TEC2636H-4+PIR Two On/Off or Floating Yes Yes Hospitality Market TEC2646-4 Two Proportional 0 to 10 VDC No No Commercial Market TEC2646H-4 Two Proportional 0 to 10 VDC No No Hospitality Market TEC2646H-4+PIR Two Proportional 0 to 10 VDC Yes No Hospitality Market TEC2656-4 Two Proportional 0 to 10 VDC No Yes Commercial Market TEC2656H-4 Two Proportional 0 to 10 VDC No Yes Hospitality Market TEC2656H-4+PIR Two Proportional 0 to 10 VDC Yes Yes Hospitality Market
Dimensions
Dehumidification Capability
Application
4-15/16
70.0ºF
°C
°F
3-3/8
1-3/8
FIG:dmnsns_tec26x6
Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor TE-6361M-1
SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TE-636S-1 Strap-Mount Temperature Sensor MS-BACEOL-0 RS485 End-of-Line Terminator
TEC-6-PIR TEC-6H-PIR
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors ar e available; refer to the TE-6300 Series Temperature Sensors Product
2. The TEC-6-PIR and TEC-6H-PIR Accessory Covers can be used to replace the existing cover on a non-PIR TEC26x6(H)-4 Series Thermostat Controller to
1
2
2
Bulletin (LIT-216320) for more details. provide occupancy sensing capability.
Duct Mount Air Temperature Sensor
Commercial Fan Coil Cover for Occupancy Sensor Hospitality Fan Coil Controller Cover for Occupancy Sensor
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
2 of 3
www.johnsoncontrols.com
TEC26x6 Series BACnet® MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
Technical Specifications
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers
with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal,
Relay/Triac Contact Rating
Analog Output Rating
Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Auxiliary Output
Rating Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC)
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AW G (0.6 mm Diameter) Recommended MS/TP Network Guidelines 32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length Temperature Range Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Compliance United States UL Listed, File E27734, CCN XAP X, Under UL 873, Temperature Indicating and Regulating Equipment
Shipping Weight TEC26x6(H)-4 Models: 0.75 lb (0.34 kg)
On/Off and Floating Control
Proportional Control 0 to 10 VDC into 2k ohm Resistance (Minimum)
Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 2004/108/EC BACnet International BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific Controller (B-ASC) Australia and New
Zealand
Class 2 or Safety Extra-Low Voltage (SELV) 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3. 0 A In-Rush, Class 2 or SELV
Thermistor Sensors
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
TEC26x6H-4+PIR Models: 0.77lb (0.35 kg)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
www.johnsoncontrols.com
3 of 3
Loading...