TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP
Networked Thermostat Controllers with Dehumidification Capability,
Fan Control, and Occupancy Sensing Capability
Installation Instructions
Part No. 24-9890-1001, Rev. B
Issued June 22, 2010
Supersedes January 27, 2010
Applications
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat Controllers are BACnet® MS/TP
networked devices that provide control of two- or fourpipe fan coils, cabinet unit heaters, or other equipment
using on/off, floating, or proportional 0 to 10 VDC
control input, three speeds of fan control, and
dehumidification capability. The TEC26x6H-4+PIR
Series Thermostat Controllers have occupancy
sensing capability built into the device. These devices
maximize up to 30% energy savings in high-energy
usage light commercial buildings, such as schools and
hotels, during occupied times by using additional
standby setpoints. See the Occupancy Sensor
Operation – TEC26x6H-4+PIR Series Thermostat
Controllers section for more information.
The technologically advanced TEC26x6(H)-4 and
TEC26x6H-4+PIR Series Thermostat Controllers
feature a Building Automation System (B AS) BACnet
MS/TP communication capability that enables remote
monitoring and programming for efficient space
temperature control. Specific models are available to
accommodate commercial and hospitality applications.
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat Controllers feature an intuitive User
Interface (UI) with backlit display that makes setup and
operation quick and easy. The thermostats also emplo y
a unique, Proportional-Integral (PI) time-proportioning
algorithm that virtually eliminates temperature offset
associated with traditional, differential-based
thermostat controllers.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the TEC26x6(H)-4 or TEC26x6H-4+PIR Series
Thermostat Controller:
IMPORTANT: The TEC26x6(H)-4 and
TEC26x6H-4+PIR Series Thermostat Controllers
are intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat could lead to personal
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the thermostat.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat
Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing
•on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
•away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure
that the thermostat controller is located centrally , wh ere
occupant movement is frequent.
1
Capability Installation Instructions
Note: Allow for vertical air circulation to the
Figure 1: Removing the Thermostat Controller
Cover (TEC26x6H-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the Thermost a t Contro ller PCB
F
Tabs
TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat Controllers.
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the
security screw if it is installed on the bottom of the
thermostat controller cover.
Note: Normally, the security screw is packaged
separately in a plastic bag with the thermostat
controller. Skip this step if the screw is not installed
on the bottom of the cover.
2. Pull the bottom edge of the thermostat cover and
open the thermostat as illustrated in Figure 1.
Note: PIR models have a wiring connection
between the cover and the Printed Circuit Board
(PCB). This connection allows for proper wiring of
the occupancy sensor. Carefully remove the wiring
connection from the PCB by pulling up on the
connector block. Do not attempt to remove the
connector block by pulling on the wires.
3. Carefully pull the locking tabs on the right side of
the thermostat mounting base and unlock the PCB.
Open the PCB to the left as illustrated in Figure 2.
PCB
Locking
IG:prcrctbrd
4. Pull approximately 6 in. (152 mm) of wire from the
wall and insert the wire through the hole in the
thermostat mounting base.
5. Align the thermostat mounting base on the wall and
use the base as a template to mark the two
mounting hole locations.
6. Position the thermostat mounting base on the wall
so that the arrow on the base points upward to
indicate the top of the thermostat.
Note: If you need to install the thermostat on an
electrical junction box, use 2-1/2 x 4 in.
(63 x 101 mm) square boxes with mud ring covers,
and avoid smaller 1-1/2 x 4 in. (38 x 101 mm)
square or 3 x 2 in. (76 x 51 mm) boxes. This
procedure ensures you have enough space for
cabling and end-of-line devices, if needed.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
2
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Note: For surface-mount applications, use
durable mounting hardware such as Molly bolt
anchors that cannot be easily pulled out of the
mounting surface.
7. Secure the mounting base to the wall surface using
two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting
screws.
Figure 3: Securing the Thermostat Controller
Mounting Base to the Wall
FIG:mntbs
Figure 4: Removing the Screw Terminal Blocks
!
!
8. Swing the PCB back to the right and carefully snap
it into the locking tabs on the thermostat mounting
base.
9. Remove the screw terminal blocks that are
attached to a disposable adhesive. Figure 4
illustrates the locations of the screw terminal
blocks on the thermostat controller.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat Controllers.
To wire the thermostat:
1. Strip the ends of each wire 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Table 1 and Figure 5 through Figure 9.
Note: For more details on wiring the MS/TP
Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin
(LIT-12011034).
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
Wiring
When an existing thermostat controller is replaced,
remove and label the wires to identify the terminal
functions. When a TEC26x6(H)-4 or TEC26x6H-4+PIR
Series Thermostat is replaced, simply remove the old
screw terminal blocks and reinsert them onto the PCB
of the replacement thermostat.
IMPORTANT: Because some of the objects may
not directly correlate to a previous version
(TEC26xx-4), you must rediscover all point objects
for the TEC26x6(H)-4 or TEC26x6H-4+PIR version.
For detailed information on this mapping, refer to the
TEC BACnet® MS/TP Network Series Thermostat
Controllers Technical Bulleti n (L IT-1201159 2 ).
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the
ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the MS/TP communication wires to the
terminal block.
Note: If multiple wires are inserted into the
terminals, be sure to properly twist the wires
together prior to inserting them into the terminal
connectors.
5. Reattach the thermostat cover to the mounting
base (top side first).
6. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
cover.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
1Fan-HFan-HF an-HFan On – High
2Fan-MFan-MFan-MFan On – Medium
3Fan-LFan-LFan-LFan On – Low
424 V~ Hot24 V~ Hot24 V~ Hot24 VAC from Transformer
524 V~ Com24 V~ Com24 V~ Com24 VAC (Common) from Transformer
6BO5 AuxBO5 AuxBO5 AuxAux BO (Auxilia ry Output)
7BO5 AuxBO5 AuxBO5 AuxAux BO (Auxilia ry Output)
8BO3BO3BlankOpen Heat
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
4
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Figure 5: Wiring the TEC26x6(H)-4 or TEC26x6H-4+PIR Series Thermostat Controller
(See Table 1)
FIG:wrng_26x6(H)(+PIR)
–
Supervisory
Controller
Contact
• COC/NH
= Cold Water
• COC/NC
Normall y Cool
= Hot Water
Voltage-Free
Contact
• Door
• Remote
Override
• Filter Alarm
• Service Alarm
Voltage-Free
Contact
• Remote NSB
• Motion
• Window
Three-Pole
Right Top
Connector
–
Hot
Com
- OR Same 24 VAC
(24 VA C Maximum )
Power Source for Auxiliary Output
(24 VA C Maximum )
BO5
Aux
BO5
Aux
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Power and Fan
Power and Fan
BO5
Aux
BO5
Aux
• Reheat
• Lighting
• Exhaust Fa n
Aux
Aux
Fan
-H
Fan
-M
Fan
-L
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Five-Pole
Eight-Pole Bottom Connector
AO1
UI3
BI1
BI2
BO4/
AO2
1 2 3 4 5
Separate 24 VAC
Left Top Connector
+
Fan
-H
Fan-MFan
-L
24 V~
24 V~
BO5
BO5
Aux
Aux
6 7 8
BO3
Power Source for Auxiliary Output
Aux Contact
(Isolated Co m m on)
• On/Off Actuation
REF
BO1/
BO2
RS
Scom
9 10 11 12 13 14 15 16
Remote Inputs
BI1
Scom
BI2
UI3
- OR -
Supply Sensor
Changeover Sensor
+REF
Voltage-Free
Normally Heat
Closed Contact
Closed Contact
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
5
Figure 6: Wiring TEC2616(H)-4 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applicat ions
Four-Pipe Applications
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 7: Wiring TEC2626(H)-4 and TEC2636(H)-4 Thermostat Controllers for On/Off Control
Two-Pipe Applications
Four-Pipe Applications
FIG:TEC2626-36h4ooc
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 8: Wiring TEC2626(H)-4 and TEC2636(H)-4 Thermostat Controllers for Floating Control
Four-Pipe Applications
FIG:TEC262 6-36h4fc
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 9: Wiring TEC2646(H)-4 and TEC2656(H)-4 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
FIG:TEC2646-56h4prp
Heating/Cooling
Valve
Com
Hot
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
24 V~
24 V~
FIG:TEC2616h4ooc
24 V~
Two -Pip e Applic ations
24 V~
AO2
BO4
24 V~
24 V~
24 V~
BO2 BO3
AO1
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
6
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Connecting the MS/TP Bus
To connect the MS/TP Bus:
1. Set the MS/TP address of the TEC BACnet MS/TP
Network Series Thermostat Controller per the
engineering drawings and test for bus voltage,
polarity, and isolation prior to wiring the MS/TP
Bus. Use the Com addr parameter to set the
MS/TP address for the thermostat controller.
Note: The wiring rules for the MS/TP Bus diff er
from the wiring rules for the N2 Bus. For more
details on wiring the MS/TP Communications Bus,
refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Observe the polarity when connecting the bus
wires to the thermostat controller.
3. After the bus wires are connected to the fir st
thermostat controller, continue in a daisy-chained
fashion to the next thermostat controller.
Note: The bus wiring must be twisted-pair lines.
Do not run the bus wiring in the same conduit as
line voltage wiring (30 VAC or above) or other
wiring that switches power to highly inductive loads
(such as contactors, coils, motors, or generators).
The MS/TP Bus requires proper termination and
biasing at each end of a segment (a segment is a
physically continuous length of wire). Because the
rooftop controller is not equipped with end-of-line
termination, a Johnson Controls® MS-BACEOL-0
End-of-Line Terminator (see Table 5; ordered
separately) or similar device is recommended to
provide this end-of-line termination. An end-of-line
terminator is required if a supervisory controller is not
at the end of the segment. If a supervisory controller is
at the end of the segment, then the end-of-line
terminator switch on the supervisory controller must be
set in the ON position.
The thermostat controller has automatic baud rate
detection. Do not exceed the maximum number of
devices allowed on a field bus. Be sure that the wiring
terminations are set correctly and that all
communication wiring is daisy-chained with no taps.
A small green light under the thermostat controller
cover (on the left edge when facing the thermostat
controller) indicates the communications mode when
the thermostat controller is operating.
The following blink codes may be seen:
•Short-Short-Long: Indicates that the baud rate is
known and that communication is active.
•Short-Short: Indicates that the thermostat
controller is scanning for the correct baud rate and
that there is no communication.
•Off: Indicates that there is no power to the
thermostat controller or that the MS/TP wiring
polarity is reversed.
•Long: Indicates that the MS/TP communication
daughter board is the wrong type for the main
board.
MS/TP Thermostat Controller Mapping
For detailed information on MS/TP Bus objects and
thermostat controller mapping, refer to the TEC
BACnet MS/TP Network Series Thermostat Controllers
Technical Bulletin (LIT-12011592).
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
7
Setup and Adjustments
Figure 10: Front Cover of Thermostat Controller (TEC26x6H-4+PIR Model Shown)
70.0ºF
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any condition.
Five keys on the thermostat controller
make ope ra t ion easy and intuitive.
indicate system activi ty.
FIG:frnt_v w
PIR motio n de te ct or
saves ene r gy using
stand-b y setpoints.
°C
°F
Room Temp
Light-Emitting Diodes (LEDs)
Thermostat User Interface Keys
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat UI consists of five keys on the front cover
(Figure 10). The function of each key is as follows:
•MODE key toggles among the system modes
available, as defined by selecting the appropriate
operation sequence in the Installer Configuration
Menu (Off, Heat, Cool, Auto).
•FAN key toggles am on g th e fan mode s available,
as defined by selecting the appropriate fan menu
options defined in the Installer Configuration Menu
(Low, Med, High, Auto).
•OVERRIDE key (commercial models) overrides
the unoccupied mode to occupied at the local user
interface for the specified TOccT ime. (T OccTime is
defined by selecting the appropriate time period in
the Installer Configuration Menu.) If one of the
binary inputs is configured to operate as a remote
override contact, this OVERRIDE function is
disabled. The OVERRIDE key also allows access
to the Installer Configuration Menu. See the
Configuring the TEC26x6(H)-4 and
TEC26x6H-4+PIR Series Thermostat Controller
section.
•°C/°F key (hospitality models) changes the
temperature scale to either Celsius or Fahrenheit
and allows access to the Installer Configuration
Menu. See the Configuring the TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controller
section.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
8
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Note: For hospitality models, binary inputs can
override from the unoccupied mode to occupied
mode.
•UP/DOWN arrow keys change the configuration
parameters and activate a setpoint adjustment.
Backlit Liquid Crystal Display (LCD)
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat Controllers include a 2-line, 8-character
backlit display. Low-level backlighting is present during
normal operation, and it brightens when any user
interface key is pressed. The backlight returns to low
level when the thermostat is left unattended for
45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•The fan LED is on when the fan is on.
•The heat LED is on when heating is on.
•The cool LED is on when cooling is on.
Integrated PIR Sensor –
TEC26x6H-4+PIR Series Thermostat
Controllers
The integrated PIR sensor allows for automatic
switching between fully adjustable Occupied and
Stand-By temperature setpoints without user
interaction. This feature generates incremental energy
savings during scheduled occupied periods while the
space is unoccupied.
Status Display Menu
The Status Display Menu is displayed during normal
thermostat operation. This menu continuously scrolls
through the following parameters:
•Room Temperature (All Models) and Humidity
(TEC2636-4, TEC2636H-4, TEC2636H-4+PIR,
TEC2656-4, TEC2656H-4, and TEC2656H-4+PIR
Models)
Note: For models with dehumidification capability, the
default setting is no humidity reading on the display
(%RH disp parameter is set to off.) The %RH disp
parameter must be set to on to display the current
humidity reading.
•System Mode
•Occupancy Status
(Occupied/Unoccupied/Override)
•Applicable Alarms (The backlight lights up as an
alarm condition is displayed.)
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature paramet er.
Dehumidification Operation –
TEC2636(H)-4 and TEC2656(H)-4 Thermostat
Models
Upon detection of room humidity above the adjustable
humidity setpoint as sensed by the integral humidity
sensor, dehumidification activates.
Note: Dehumidification operation functions only in the
Cooling mode; dehumidification operation does not
function in either the Off or the Heating mode.
Note: A central network command can globally
lock out dehumidification operation to all thermostats.
If the room temperature resides in the dea db an d
between the Heating and Cooling setpoint:
•the thermostat forces the fan to low speed
•the chilled water valve opens to the specified
maximum value set by CoolMax
•the thermostat stages Heating to maint ain the room
temperature at the Cooling setpoint, as sensed by
the thermostat
If the room temperature falls below the current Heating
setpoint, the thermostat disables dehumidification
operation.
If the thermostat is in Cooling demand:
•the chilled water valve opens to 100%
•the thermostat stages Heating to main tain the room
temperature at the Cooling setpoint, as sensed by
the thermostat
If the thermostat is in Cooling demand and the room
temperature rises 2F°/1C° above the Cooling setpoint,
the thermostat automatically disables dehumidification
operation. Likewise, if the thermostat is in Cooling
demand and the room temperature falls below the
current Heating setpoint, the thermostat disables
dehumidification operation.
Occupancy Sensor Operation –
TEC26x6H-4+PIR Series Thermostat
Controllers
A TEC26x6H-4+PIR Series Thermostat Controller (or a
TEC26x6(H)-4 Series Thermostat Controller equipped
with a PIR accessory cover) provides advanced
occupancy logic.
Note: The PIR strategy is an occupied strategy. If the
thermostat controller is programmed to be Unoccupied ,
the PIR function does not have an effect on the
occupancy strategy.
The thermostat controller automatically switches
occupancy levels from Occupied to Stand-By and
Unoccupied as required, when local movement is
sensed.
Occupancy sensing is enabled only if a PIR cover is
installed on the thermostat controller (PIR models) or if
a remote input is configured as a remote PIR sensor
(MotionNO or MotionNC).
PIR Warm-Up Period
When a PIR cover is used and a thermostat controller
is powered up, there is a 1-minute warm-up perio d
before any local movement can be detected and
acknowledged by the PIR sensing device. The local
status LEDs for the PIR function are not active, and the
sensor is in Stand-By mode for the 1-minute period.
The PIR functionality and local movement status LEDs
are activated after the 1-minute warm-up period has
elapsed after the initial powering of the thermostat
controller. If movement is present, the mode changes
to Occupied.
PIR Diagnostic LEDs
The diagnostic LEDs inside the PIR lens brighten when
movement is detected within the first 30 minutes after
powerup. The LEDs do not light up or brighten after the
initial 30-minute period.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
9
Setpoints
St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Figure 11: Increasing Room Temperature Setpoints
Stand-By
Unoccupied
Stand-By
= 2 Hours
= 6 Hours
Time
Last Mov ement Detected
by PIR Devi ce
Stand-By Time Elapsed
= Stand-By Mode
Stand-By
= 2 Hrs
Unoccu pied Time
= 6 Hour s
Last Mov ement Detected
by PIR Devi ce
Stand-By Time Elapsed
= Stand-By Mode
= Unoccu pied Mode
FIG:unocc6sb2
First Movement
Detected
by PIR Device
First Movement
Detected by PIR Device
Figure 12: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
The Stand-By setpoints are under the same limitations
and restrictions as the Occupied and Unoccupied
setpoints. Stand-By setpoints reside between the
corresponding Occupied and Unoccupied setpoint
values.
The installer must be certain that the difference
between the Stand-By and Occupied values can be
recovered within a timely fashion to ensure occupancy
comfort. In addition, the difference between the two
values must be large enough to warrant maximum
energy savings.
Hotel and lodging applications can benefit from the
addition of an entry door switch wired to one of the
binary inputs of the thermostat controller. When a door
contact is used and configured, the S t and-By timer and
its configuration are no longer active or used. The
occupancy toggle between Occupied and Stand-By is
then dictated by both the door contact and the
PIR sensing device used. If movements are detected
by the PIR sensor and the door is closed, the room is
considered occupied. The thermostat controller
switches back to S tand-By m ode only if the door switch
toggles open/closed. Motion is ignored when the door
switch indicates an open door.
PIR occupancy functionality is dictated by both the
Stand-By timer and Unoccupied timer configuration
value and movements present in the area.
Occupied
Unoccupied Time
Unoccupied Time Elapsed
Time
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
10
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hrs
= 0 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time
= 0 Hours
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
FIG:unocc0sb2
First Movement Detected
by PIR Device
Stand-By
= 2 Hrs
First Movement Detected
by PIR Device
Figure 13: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours
Unoccupied Time
Time
Unoccupied Timer Disable
It might be preferable for the local area to stay out of
Unoccupied mode and always stay at the Stand-By
occupancy level when no activity is present. In
instances when areas always need to be on Stand-By
status, ready to respond to demand at any given point
in time, we recommend disabling the Unoccupied timer .
When the local PIR occupancy routine is running at the
thermostat controller, the zone drifts into Unoccupied
mode when the Unoccupied timer is set above its
factory default value of 0.0 hours.
For more information on occupancy sensor operation,
refer to the TEC2x45-4, TEC2xx6(H)-4,
TEC2xx6H-4+PIR, and TEC2xx7-4 Series Thermostat
Controllers Application Note (LIT-12011594).
Configuring the TEC26x6(H)-4 and
TEC26x6H-4+PIR Series Thermostat Controller
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series
Thermostat Controllers are shipped with default
settings for all configurable parameters. The default
settings are shown in Table 4. To reconfigure the
parameters via the thermostat, follow the steps in this
section.
1. To access the Installer Configuration Menu, press
and hold the center key for approximately
8 seconds.
Note: If the Password parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the UP/DOWN arrow
keys to indicate the configured password, then
press the MODE key to proceed through the
Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins,
press and release the center key to scroll through
the parameters listed in Table 4.
3. When the desired parameter is displayed, use the
UP/DOWN arrow keys to choose the desired
selection option.
4. Press and release the center key to continue
scrolling through the parameters.
Note: Pressing the FAN key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 4.
When the thermostat is in the Installer Configuration
Menu and left unattended for approximately 8 seconds,
the thermostat reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
The UI3 input provides changeover of hot/cold water
switching or supply air temperature monitoring at the
thermostat.
Each input can be configured to the Selection Options
included in Table 4.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequen ce
of operation selected. For two-pipe applications using a
changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between
Cooling Only and Heating Only. See Figure 14
through Figure 19 for sequence of operation examples.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
11
Table 2: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 14.10: Normally Open
(1): Heating OnlySee Figure 15.10: N.O. Heating
(2): Cooling and ReheatSee Figure 16.6 and 7: Reheat
(3): Heating and ReheatSee Figure 17.6 and 7: Reheat
Control
Curve
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off ControlFloating ControlProportional
(N.O.) Cooling
11: Normally Closed
(N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling
11: N.C. Cooling
10: N.O. Heating
11: N.C. Heating
10: Open Cooling
11: Closed Cooling
10: Open Heating
11: Closed Heating
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
10: Open Heating
11: Closed Heating
Table 3: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 14.10: N.O. Cooling
(1): Heating OnlySee Figure 15.8: N.O. Heating
(2): Cooling and ReheatSee Figure 16.6 and 7: Reheat
(3): Heating and ReheatSee Figure 17.6 and 7: Reheat
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
6 and 7:
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
Reheat
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
10: Proportional Heating
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
9: Proportional Heating
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
10: Proportional Cooling
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
12
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor tional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 14: Cooling Only,
Two- or Four-Pipe Applications
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 15: Heating Only,
Two- or Four-Pipe Applications
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
or Propor t ional
Outputs
Heating Output
Cooling Output
Off
Off
On
On
Figure 16: Cooling with Reheat,
Two- or Four-Pipe Applications
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 17: Heating with Reheat,
Two- or Four-Pipe Applications
Figure 18: Heating/Cooling,
Four-Pipe Applications
Heating Setpoint
Closed
Device
Opened
FIG:htng_clng
Deadband
or Propor t ional
Outputs
Heating Output
Cooling Output
Device
Closed
Device
Opened
Temperature Incr ease
(Increments of 1F°/0.5C°)
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
(Increments of 1F°/0.5C°)
On/Off, Floating,
On
Temperature Increase
100%
0%
t
h
r
On/Off, Floating,
Temperature In cr ease
(Increments of 1F°/0.5C°)
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Device
Cooling Setpoint
Device
Temperature Increase
(Increm ents of 1F°/0.5C°)
13
Heating Setpoint
Device
Closed
Device
Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat
Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put
Cooling Output
Off
Off
On
On
Figure 19: Heating/Cooling with Reheat, Four-Pipe Applications
Figure 20: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature De vi ation from Setpoint , F°
2.0F°/1. 0C° to
5.0F°/2.5C°
Deadband
100%
0%
2.5
2.5
2.02.0
1.5
1.50.50.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Setpoint
High
FIG:fn_oprtn
Fan
Speed
The fan is of f
between the
heating and
if the
parameter is
set to .
Auto Fan
AS AD
Temperature Incr ease
(Increments of 1F°/0.5C°)
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer
Configuration menu to set the available Fan Mode
options. Use the FAN key to select the desired Fan
Mode option.
Heating
cooling se t points
When selection option (2): Low-Med-High-Auto is
chosen in the Fan Menu parameter, the fan operates
as shown in Figure 20. When selection option
(3): Low-High-Auto is chosen in the Fan Menu
parameter, the fan operates at only the low and high
settings, ignoring the medium setting (Figure 20). This
operation applies to the occupied mode when the fan is
set to Auto.
Cooling
Setpoint
14
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 1 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
PswrdSets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
Com addrMS/TP address at the thermostat;
coincides with the address assigned
at the supervisory controller.
Default: 254BI1Configuration of Binary Input 1.
Default: None
BI2Configuration of Binary Input 2.
Default: None
Range: 0 to 1,000
Range: 004 to 127
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is closed, until the TOccTime expires.
(Window): Cancels the thermostat heating or cooling action when a
window is open. The fan operation is only affected if the Fan Menu
parameter is set to (4): On-Auto and Auto is the selected fan mode.
A Window alarm appears, indicating that the window needs to be
closed to resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to MotionNO
or MotionNC. (See the BI1 parameter earlier in this table.) The
occupancy is now dictated via BI1 and BI2. Any motion detected
sets the zone to Occupied status. The zone remains permanently in
occupied mode until the door contact switch opens momentarily. The
thermostat then enters stand-by mode. If more movements are
detected, the occupied mode resumes. While the door is opened,
any movements detected by the remote PIR sensor or the PIR
accessory cover are ignored. Use a Normally Closed contact
switching device. Contact opened = Door opened,
Contact closed = Door closed.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
15
Table 4: Installer Configuration Menu (Part 2 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
UI3Configuration of Universal Input 3.
Default: None
MenuScroGives the option of having the
display continuously scroll the
parameters.
Default: onAutoModeEnables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat cover.)
Default: onC or FProvides temperature scale options
for display.
Default: °F%RH dispDisplays the current humidity
reading (TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models).
Default: offLockoutSelectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
(None): No function is associated with an input.
(COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water
changeover switching. Valid only for two-pipe systems.
• A water temperature greater than 78.0°F (25.6°C) indicates hot
• A water temperature less than 75.0°F (23. 9°C) indicates cold
Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between
Cooling Only and Heating Only. The changeover sensor does not
operate in Cooling and Reheat, Heating and Reheat, or Cool/Heat
Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring
(off): The scroll is inactive.
(on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale
(°F): Fahrenheit scale
(on): Displays the current humidity reading in % RH.
(off): Does not display the current humidity reading.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
16
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 3 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Pipe NoSelectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTypDefines the control output for the
SeqOperaDetermines the sequence of
Fan MenuSets the Fan Mode options.
DHumiLCKLocks out the dehumidification
%RH set
1
type of valves used in the
installation (TEC2626-4,
TEC2626H-4, TEC2626H-4+PIR,
TEC2636-4, TEC2636H-4, and
TEC2636H-4+PIR models).
Default: Floating
operation.
Default: 1
Default: 4
capability (TEC2636-4,
TEC2636H-4, TEC2636H-4+PIR,
TEC2656-4, TEC2656H-4, and
TEC2656H-4+PIR models).
Default: on
Sets the dehumidification setpoints
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 50.0% RH
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating
valves.
(0): Cooling Only (Off-Cool). The default is Cool.
(1): Heating Only (Off-Heat). The default is Heat.
(2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto.
(3): Heating and Reheat (Off-Heat). The default is Heat.
(4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Auto.
(5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Auto.
* Auto can be disabled with the AutoMode parameter.Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling
and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H). The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. The default is Auto.
(off): Dehumidification is locked out.
(on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
17
Table 4: Installer Configuration Menu (Part 4 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
1
DehuHyst
DehuCool
St-By TMSets stand-by timer value when
Unocc TMSets Unoccupied Timer Value when
Sets the dehumidification hysteresis
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
1
Sets the maximum dehumidification
cooling output (TEC2636-4,
TEC2636H-4, TEC2636H-4+PIR,
TEC2656-4, TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 100%
used with occupancy sensor; time
delay between moment where
occupancy sensor detected the last
movement in the area and the time
which the thermostat stand-by mode
and setpoints become active.
Default: 0.5 hours
used with occupancy sensor; time
delay between the moment where
the thermostat toggles to stand-by
mode and the time which the
thermostat unoccupied mode and
setpoints become active.
Default: 0.0 hours
Range: 2.0 to 20.0% RH
Range: 20.0 to 100.0%Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Range: 0.5 to 24.0hours, in 0.5 hour increments
0.0 hours or Factory Value: Setting this parameter to its default 0
value disables the occupied timer and prevents the thermostat from
drifting from stand-by mode to unoccupied mode when occupancy
sensor functions are used.
Range: 0.0 to 24.0hours in 0.5 hour increments
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
18
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 5 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Default: 78.0°F/25.6°CUnocc HTSets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°CUnocc CLSets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°CHeat maxSets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°CCool minSets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°CPbandProportional Band used by the PI
temperature control loop of the
thermostat.
Pband is not converted with C or F
scale and is always shown with a
range of 3 to 10.
Default: 3 (3F°/1.7C°)
Set typeProvides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
ValueF Scale Pband/C Scale Pband
33.0F°/1.7C°
44.0F°/2.2C°
55.0F°/2.8C°
66.0F°/3.3C°
77.0F°/3.9C°
88.0F°/4.4C°
99.0F°/5.0C°
1010.0F°/5.6C°
Note: The use of a larger proportional band is not to use the
thermostat as a discharge air controller device. The use of a larger
proportional band can be used to solve issues for flawed HVAC
design with basic sizing and thermostat location errors that cannot
be worked around.
(temporar): Local changes to the heating or coolin g setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
Note: When adjusting the
temperature, press the UP/DOWN arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN arrow keys
to change the temperature
in 5.0F°/5.0C° increments.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
19
Table 4: Installer Configuration Menu (Part 6 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Spt FuncDetermines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
TOccTimeSets the duration of the Tempor ary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in
the Main User Menu (when the
thermostat is in the Unoccupied
mode)
• a temporary heating or cooling
setpoint
Default: 2.0 hrs
DeadbandSets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Cal RSSets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C°
Cal RHSets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 0.0% RH
(Attch Stp): Single Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. Both the heating and
cooling setpoints are changed simultaneously, while respecting the
minimum configured deadband. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. The heating and cooling
setpoints can be separated individually, allowing the minimum
configured deadband to expand. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Range: -15.0% RH to 15.0% RH (adjustable in 1% RH increments)
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
20
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 7 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Aux contDetermines the auxiliary contact
function and configuration.
Default: 0
Auto FanAffects the auto mode of operation
for the following Fan Menu
parameter selection options only:
• (2): Low-Med-High-Auto
• (3): Low-High-Auto
Default: AS
FL timeSets the maximum actuator stroke
timing (floating CntrlTyp
TEC2626-4, TEC2626H-4,
TEC2626H-4+PIR, TEC2636-4,
TEC2636H-4, and
TEC2636H-4+PIR models).
Default: 1.5 minCphSets the maximum number of cycles
per hour (TEC2616-4,
TEC2616H-4, TEC2616H-4+PIR,
and on/off CntrlTyp TEC2626-4,
TEC2626H-4, TEC2626H-4+PIR,
TEC2636-4, TEC2636H-4, and
TEC2636H-4+PIR models).
Default: 4RA/DAChoice of reverse or direct acting
analog output signal (TEC2646-4,
TEC2646H-4, TEC2646H-4+PIR,
TEC2656-4, TEC2656H-4, and
TEC2656H-4+PIR models)
Default: DA
(AS AD): The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only
re-activated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperat ure error from the setpoint.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
Range: 3 to 8 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC
(DA): Direct acting, 0 to 100% = 0 to 10 VDC
(0)Not used,
or used for
reheat
(1)Auxiliary
N.O.
(2)Auxiliary
N.C.
(3)Auxiliary
N.O.
(4)Auxiliary
N.C.
(5)Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network
variable.
If the sequence of operation is set to
reheat (2, 3, or 5), ignore this parameter.
Occupied = contact
closed
Unoccupied = contact
open
Occupied = contact open
Unoccupied = contact
closed
Occupied and fan On =
contact closed
Unoccupied and fan On or
Off = contact open
Occupied and fan On =
contact open
Unoccupied and fan On or
Off = contact closed
The output
aligns with
occupancy.
The output
aligns with
occupancy
and the
fan on
command.
The output
aligns with
the
secondary
network
occupancy
command.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
21
Table 4: Installer Configuration Menu (Part 8 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
ReheatSets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 disDisplays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
1.When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0): 15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
Used as a diagnostic/service help, to troubleshoot and diagnose
sensor operation.
Troubleshooting
See Table 6 for Display messaging. See Table 7 for
troubleshooting details.
Accessories
All the accessories in Table 5 include mounting
hardware; contact the nearest Johnson Controls®
representative to order any of these parts.
Note: Review the technical specifications of the
accessories prior to their use in an application.
Repair Information
If a TEC26x6(H)-4 or TEC26x6H-4+PIR Series
Thermostat fails to operate within its specifications,
replace the unit. For a replacement thermostat, cont act
the nearest Johnson Controls representative.
Table 5: Accessories (Order Separat ely)
Code NumberDescription
SEN-600-1Remote Indoor Air Temperature Sensor
1
TE-6361M-1
SEN-600-4Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-636S-1Strap-Mount Temperature Sensor
MS-BACEOL-0RS485 End-of-Line Terminator
TEC-6-PIR
TEC-6H-PIR
1.Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2.The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC26x6-4 Series Thermostat
Controller to provide occupancy sensing capability.
3.TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC26x6H-4 Series Thermostat
Controller to provide occupancy sensing capability.
2
Duct Mount Air Temperature Sensor
Cover with Occupancy Sensor
3
Cover with Occupancy Sensor for Hospitality Models
Table 6: Display Messages
DisplayFunction
ServiceIndicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
FilterIndicates that the filte r(s) is dirty in accordance with the programmable Binary Input (BI2).
WindowIndicates that an outside window or door is open and has cancelled the thermostat heating or cooling
action in accordance with the programmable Binary Input (BI1).
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
22
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 7: Troubleshooting Details
1
SymptomProbable Causes
Multiple
Symptoms
Poor PerformanceSee the probable causes listed in the Multiple Symptoms section earlier in this table.
Thermostat Goes
Offline
Thermostat Does
Not Come Online
Excessive bus errors may be occurring.
A device may have been added or changed with a duplicate address (may not be the same address as
some devices having problems, and may have happened sometime before the problem was noticed).
Wiring errors or wire problems may exist.
The baud rate may have been changed on some devices on the network, but not all devices.
Max_Master may have been changed incorrectly (may have happened sometime before the problem
was noticed).
A download may be in progress.
There may be a fault at a device.
A repeater may be needed or may be configured incorrectly.
There may be a duplicate device object name or instance.
Excessive bus traffic may exist (bus overload).
The baud rate may be set too low.
There may be too many devices on the network.
There may be unaccounted devices on the network (not mapped to the NAE).
There may be unusually slow devices on the network or devices that are slow to respond.
See the probable causes listed in the Multiple Symptoms section earlier in this table.
A power failure or other failure may have occurred at the thermostat.
Communication may have been disabled at the thermostat.
See the probable causes listed in the Multiple Symptoms section earlier in this table.
A thermostat may be connected to the wrong bus.
A baud rate may be specified in the new thermostat that is incompatible with the running network.
No device on the network is configured to us e a specific baud rate (normally the NAE), but all devices
are set to use auto baud. At least one device, typically the bus supervisor (NAE), must have an
assigned baud rate. Set the baud rate in the bus supervisor and set all other devices to auto baud.
1.For common MS/TP troubleshooting information, refer to the MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
Technical Specifications
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers
with Dehumidification Capability, Fan Control and Occupancy Sensing Capability (Part 1 of 2)
Power Requirements19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Relay/Triac
Contact Rating
Analog Output
Rating
Fan Relay Output Rating19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Auxiliary
Output Rating
Binary InputsVoltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Analog InputsResistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Sensor TypeLocal 10k ohm Negative Temperatur e Coefficient (NTC) Thermistor
On/Off and
Floating Control
Proportional
Control
Triac Output19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Safety Extra-Low Voltage (SELV)
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance (Minimum)
Temperature Coefficient (NTC) Thermistor Sensors
23
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers
with Dehumidification Capability, Fan Control and Occupancy Sensing Capability (Part 2 of 2)
Wire Size18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
MS/TP Network Guidelines32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length
Temperature
Range
AccuracyTemperature±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband2F°/1C° between Heating and Cooling
Ambient
Shipping WeightTEC26x6(H)-4 Models: 0.75 lb (0.34 kg)
Backlit Display-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control54.0°F/12.0°C to 100.0°F/38.0°C
Humidity±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Operating32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
CanadaUL Listed, File E27734, CCN XAPX7,
EuropeCE Mark – Johnson Controls, Inc., declares that the BACnet Thermostats are
Australia and
New Zealand
BACnet
International
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
in compliance with the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
24
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Published in U.S.A.www.johnsoncontrols.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.