Johnson Controls TEC26x6(H)-4, TEC26x6H-4+PIR Installation Manual

TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
Installation Instructions
Part No. 24-9890-1001, Rev. B
Issued June 22, 2010
Supersedes January 27, 2010

Applications

The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers are BACnet® MS/TP networked devices that provide control of two- or four­pipe fan coils, cabinet unit heaters, or other equipment using on/off, floating, or proportional 0 to 10 VDC control input, three speeds of fan control, and dehumidification capability. The TEC26x6H-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These devices maximize up to 30% energy savings in high-energy usage light commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints. See the Occupancy Sensor
Operation – TEC26x6H-4+PIR Series Thermostat Controllers section for more information.
The technologically advanced TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers feature a Building Automation System (B AS) BACnet MS/TP communication capability that enables remote monitoring and programming for efficient space temperature control. Specific models are available to accommodate commercial and hospitality applications.
The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers feature an intuitive User Interface (UI) with backlit display that makes setup and operation quick and easy. The thermostats also emplo y a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Location Considerations

Locate the TEC26x6(H)-4 or TEC26x6H-4+PIR Series Thermostat Controller:
IMPORTANT: The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat
Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure that the thermostat controller is located centrally , wh ere occupant movement is frequent.
1
Capability Installation Instructions
Note: Allow for vertical air circulation to the
Figure 1: Removing the Thermostat Controller
Cover (TEC26x6H-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the Thermost a t Contro ller PCB
F
Tabs
TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers.
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
2. Pull the bottom edge of the thermostat cover and open the thermostat as illustrated in Figure 1.
Note: PIR models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor. Carefully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires.
3. Carefully pull the locking tabs on the right side of the thermostat mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
PCB Locking
IG:prcrctbrd
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat mounting base.
5. Align the thermostat mounting base on the wall and use the base as a template to mark the two mounting hole locations.
6. Position the thermostat mounting base on the wall so that the arrow on the base points upward to indicate the top of the thermostat.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
2
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface.
7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
Figure 3: Securing the Thermostat Controller
Mounting Base to the Wall
FIG:mntbs
Figure 4: Removing the Screw Terminal Blocks
!
!
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers.
To wire the thermostat:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1 and Figure 5 through Figure 9.
Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034).
s k
c
l
b
_
l
n m
r
t
: G
I F

Wiring

When an existing thermostat controller is replaced, remove and label the wires to identify the terminal functions. When a TEC26x6(H)-4 or TEC26x6H-4+PIR Series Thermostat is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat.
IMPORTANT: Because some of the objects may not directly correlate to a previous version (TEC26xx-4), you must rediscover all point objects for the TEC26x6(H)-4 or TEC26x6H-4+PIR version. For detailed information on this mapping, refer to the
TEC BACnet® MS/TP Network Series Thermostat Controllers Technical Bulleti n (L IT-1201159 2 ).
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the MS/TP communication wires to the terminal block.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
5. Reattach the thermostat cover to the mounting base (top side first).
6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat cover.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
3
Table 1: Terminal Identification (See Figure 5.)
Terminal Number
TEC2616-4, TEC2616H-4, TEC2616H-4+PIR (On/Off Control)
1 Fan-H Fan-H F an-H Fan On – High 2 Fan-M Fan-M Fan-M Fan On – Medium 3 Fan-L Fan-L Fan-L Fan On – Low 4 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 VAC from Transformer 5 24 V~ Com 24 V~ Com 24 V~ Com 24 VAC (Common) from Transformer 6 BO5 Aux BO5 Aux BO5 Aux Aux BO (Auxilia ry Output) 7 BO5 Aux BO5 Aux BO5 Aux Aux BO (Auxilia ry Output) 8 BO3 BO3 Blank Open Heat
9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 1 1 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 RS RS RS Remote Sensor 14 Scom Scom Scom Sensor Common 15 BI2 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 UI3 Configurable Universal Input 3
Blank +, –, REF +, –, REF +, –, REF MS/TP Bus
Terminal Label Function
TEC2626-4, TEC2626H-4, TEC2626H-4+PIR TEC2636-4, TEC2636H-4, TEC2636H-4+PIR (On/Off or Floating Control)
TEC2646-4, TEC2646H-4, TEC2646H-4+PIR, TEC2656-4, TEC2656H-4, TEC2656H-4+PIR (Proportional 0 to 10 VDC Control)
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
4
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Figure 5: Wiring the TEC26x6(H)-4 or TEC26x6H-4+PIR Series Thermostat Controller
(See Table 1)
FIG:wrng_26x6(H)(+PIR)
Supervisory
Controller
Contact
• COC/NH
= Cold Water
• COC/NC Normall y Cool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
Three-Pole Right Top Connector
Hot
Com
- OR ­Same 24 VAC
(24 VA C Maximum )
Power Source for Auxiliary Output
(24 VA C Maximum )
BO5
Aux
BO5
Aux
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Power and Fan
Power and Fan
BO5
Aux
BO5
Aux
• Reheat
• Lighting
• Exhaust Fa n
Aux
Aux
Fan
-H
Fan
-M
Fan
-L
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Five-Pole
Eight-Pole Bottom Connector
AO1
UI3
BI1
BI2
BO4/
AO2
1 2 3 4 5
Separate 24 VAC
Left Top Connector
+
Fan
-H
Fan-MFan
-L
24 V~
24 V~
BO5
BO5
Aux
Aux
6 7 8
BO3
Power Source for Auxiliary Output
Aux Contact (Isolated Co m m on)
• On/Off Actuation
REF
BO1/
BO2
RS
Scom
9 10 11 12 13 14 15 16
Remote Inputs
BI1
Scom
BI2
UI3
- OR -
Supply Sensor Changeover Sensor
+ REF
Voltage-Free
Normally Heat Closed Contact
Closed Contact
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
5
Figure 6: Wiring TEC2616(H)-4 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applicat ions
Four-Pipe Applications
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 7: Wiring TEC2626(H)-4 and TEC2636(H)-4 Thermostat Controllers for On/Off Control
Two-Pipe Applications
Four-Pipe Applications
FIG:TEC2626-36h4ooc
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 8: Wiring TEC2626(H)-4 and TEC2636(H)-4 Thermostat Controllers for Floating Control
Four-Pipe Applications
FIG:TEC262 6-36h4fc
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 9: Wiring TEC2646(H)-4 and TEC2656(H)-4 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
FIG:TEC2646-56h4prp
Heating/Cooling
Valve
Com
Hot
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
24 V~
24 V~
FIG:TEC2616h4ooc
24 V~
Two -Pip e Applic ations
24 V~
AO2
BO4
24 V~
24 V~
24 V~
BO2 BO3
AO1
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
6
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions

Connecting the MS/TP Bus

To connect the MS/TP Bus:
1. Set the MS/TP address of the TEC BACnet MS/TP Network Series Thermostat Controller per the engineering drawings and test for bus voltage, polarity, and isolation prior to wiring the MS/TP Bus. Use the Com addr parameter to set the MS/TP address for the thermostat controller.
Note: The wiring rules for the MS/TP Bus diff er from the wiring rules for the N2 Bus. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Observe the polarity when connecting the bus wires to the thermostat controller.
3. After the bus wires are connected to the fir st thermostat controller, continue in a daisy-chained fashion to the next thermostat controller.
Note: The bus wiring must be twisted-pair lines. Do not run the bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
The MS/TP Bus requires proper termination and biasing at each end of a segment (a segment is a physically continuous length of wire). Because the rooftop controller is not equipped with end-of-line termination, a Johnson Controls® MS-BACEOL-0 End-of-Line Terminator (see Table 5; ordered separately) or similar device is recommended to provide this end-of-line termination. An end-of-line terminator is required if a supervisory controller is not at the end of the segment. If a supervisory controller is at the end of the segment, then the end-of-line terminator switch on the supervisory controller must be set in the ON position.
The thermostat controller has automatic baud rate detection. Do not exceed the maximum number of devices allowed on a field bus. Be sure that the wiring terminations are set correctly and that all communication wiring is daisy-chained with no taps.
A small green light under the thermostat controller cover (on the left edge when facing the thermostat controller) indicates the communications mode when the thermostat controller is operating.
The following blink codes may be seen:
Short-Short-Long: Indicates that the baud rate is known and that communication is active.
Short-Short: Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication.
Off: Indicates that there is no power to the thermostat controller or that the MS/TP wiring polarity is reversed.
Long: Indicates that the MS/TP communication daughter board is the wrong type for the main board.

MS/TP Thermostat Controller Mapping

For detailed information on MS/TP Bus objects and thermostat controller mapping, refer to the TEC
BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin (LIT-12011592).
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
7

Setup and Adjustments

Figure 10: Front Cover of Thermostat Controller (TEC26x6H-4+PIR Model Shown)
70.0ºF
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any condition.
Five keys on the thermostat controller make ope ra t ion easy and intuitive.
indicate system activi ty.
FIG:frnt_v w
PIR motio n de te ct or
saves ene r gy using
stand-b y setpoints.
°C
°F
Room Temp

Light-Emitting Diodes (LEDs)

Thermostat User Interface Keys

The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat UI consists of five keys on the front cover (Figure 10). The function of each key is as follows:
MODE key toggles among the system modes available, as defined by selecting the appropriate operation sequence in the Installer Configuration Menu (Off, Heat, Cool, Auto).
FAN key toggles am on g th e fan mode s available, as defined by selecting the appropriate fan menu options defined in the Installer Configuration Menu (Low, Med, High, Auto).
OVERRIDE key (commercial models) overrides the unoccupied mode to occupied at the local user interface for the specified TOccT ime. (T OccTime is defined by selecting the appropriate time period in the Installer Configuration Menu.) If one of the binary inputs is configured to operate as a remote override contact, this OVERRIDE function is disabled. The OVERRIDE key also allows access to the Installer Configuration Menu. See the
Configuring the TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controller
section.
°C/°F key (hospitality models) changes the temperature scale to either Celsius or Fahrenheit and allows access to the Installer Configuration Menu. See the Configuring the TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controller section.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
8
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Note: For hospitality models, binary inputs can override from the unoccupied mode to occupied mode.
UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment.

Backlit Liquid Crystal Display (LCD)

The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers include a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat is left unattended for 45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on.

Integrated PIR Sensor – TEC26x6H-4+PIR Series Thermostat Controllers

The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Stand-By temperature setpoints without user interaction. This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied.

Status Display Menu

The Status Display Menu is displayed during normal thermostat operation. This menu continuously scrolls through the following parameters:
Room Temperature (All Models) and Humidity (TEC2636-4, TEC2636H-4, TEC2636H-4+PIR, TEC2656-4, TEC2656H-4, and TEC2656H-4+PIR Models)
Note: For models with dehumidification capability, the default setting is no humidity reading on the display (%RH disp parameter is set to off.) The %RH disp parameter must be set to on to display the current humidity reading.
System Mode
Occupancy Status (Occupied/Unoccupied/Override)
Applicable Alarms (The backlight lights up as an alarm condition is displayed.)
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature paramet er.

Dehumidification Operation – TEC2636(H)-4 and TEC2656(H)-4 Thermostat Models

Upon detection of room humidity above the adjustable humidity setpoint as sensed by the integral humidity sensor, dehumidification activates.
Note: Dehumidification operation functions only in the Cooling mode; dehumidification operation does not function in either the Off or the Heating mode.
Note: A central network command can globally lock out dehumidification operation to all thermostats.
If the room temperature resides in the dea db an d between the Heating and Cooling setpoint:
the thermostat forces the fan to low speed
the chilled water valve opens to the specified maximum value set by CoolMax
the thermostat stages Heating to maint ain the room temperature at the Cooling setpoint, as sensed by the thermostat
If the room temperature falls below the current Heating setpoint, the thermostat disables dehumidification operation.
If the thermostat is in Cooling demand:
the chilled water valve opens to 100%
the thermostat stages Heating to main tain the room temperature at the Cooling setpoint, as sensed by the thermostat
If the thermostat is in Cooling demand and the room temperature rises 2F°/1C° above the Cooling setpoint, the thermostat automatically disables dehumidification operation. Likewise, if the thermostat is in Cooling demand and the room temperature falls below the current Heating setpoint, the thermostat disables dehumidification operation.

Occupancy Sensor Operation – TEC26x6H-4+PIR Series Thermostat Controllers

A TEC26x6H-4+PIR Series Thermostat Controller (or a TEC26x6(H)-4 Series Thermostat Controller equipped with a PIR accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the thermostat controller is programmed to be Unoccupied , the PIR function does not have an effect on the occupancy strategy.
The thermostat controller automatically switches occupancy levels from Occupied to Stand-By and Unoccupied as required, when local movement is sensed.
Occupancy sensing is enabled only if a PIR cover is installed on the thermostat controller (PIR models) or if a remote input is configured as a remote PIR sensor (MotionNO or MotionNC).

PIR Warm-Up Period

When a PIR cover is used and a thermostat controller is powered up, there is a 1-minute warm-up perio d before any local movement can be detected and acknowledged by the PIR sensing device. The local status LEDs for the PIR function are not active, and the sensor is in Stand-By mode for the 1-minute period. The PIR functionality and local movement status LEDs are activated after the 1-minute warm-up period has elapsed after the initial powering of the thermostat controller. If movement is present, the mode changes to Occupied.

PIR Diagnostic LEDs

The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
9

Setpoints

St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Figure 11: Increasing Room Temperature Setpoints
Stand-By
Unoccupied
Stand-By
= 2 Hours
= 6 Hours
Time
Last Mov ement Detected
by PIR Devi ce
Stand-By Time Elapsed = Stand-By Mode
Stand-By
= 2 Hrs
Unoccu pied Time
= 6 Hour s
Last Mov ement Detected
by PIR Devi ce
Stand-By Time Elapsed = Stand-By Mode
= Unoccu pied Mode
FIG:unocc6sb2
First Movement
Detected
by PIR Device
First Movement
Detected by PIR Device
Figure 12: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
The Stand-By setpoints are under the same limitations and restrictions as the Occupied and Unoccupied setpoints. Stand-By setpoints reside between the corresponding Occupied and Unoccupied setpoint values.
The installer must be certain that the difference between the Stand-By and Occupied values can be recovered within a timely fashion to ensure occupancy comfort. In addition, the difference between the two values must be large enough to warrant maximum energy savings.
Hotel and lodging applications can benefit from the addition of an entry door switch wired to one of the binary inputs of the thermostat controller. When a door contact is used and configured, the S t and-By timer and its configuration are no longer active or used. The occupancy toggle between Occupied and Stand-By is then dictated by both the door contact and the PIR sensing device used. If movements are detected by the PIR sensor and the door is closed, the room is considered occupied. The thermostat controller switches back to S tand-By m ode only if the door switch toggles open/closed. Motion is ignored when the door switch indicates an open door.
PIR occupancy functionality is dictated by both the Stand-By timer and Unoccupied timer configuration value and movements present in the area.
Occupied
Unoccupied Time
Unoccupied Time Elapsed
Time
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
10
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hrs
= 0 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed = Stand-By Mode
Unoccupied Time
= 0 Hours
Last Movement Detected
by PIR Device
Stand-By Time Elapsed = Stand-By Mode
FIG:unocc0sb2
First Movement Detected
by PIR Device
Stand-By
= 2 Hrs
First Movement Detected
by PIR Device
Figure 13: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours
Unoccupied Time
Time

Unoccupied Timer Disable

It might be preferable for the local area to stay out of Unoccupied mode and always stay at the Stand-By occupancy level when no activity is present. In instances when areas always need to be on Stand-By status, ready to respond to demand at any given point in time, we recommend disabling the Unoccupied timer . When the local PIR occupancy routine is running at the thermostat controller, the zone drifts into Unoccupied mode when the Unoccupied timer is set above its factory default value of 0.0 hours.
For more information on occupancy sensor operation, refer to the TEC2x45-4, TEC2xx6(H)-4,
TEC2xx6H-4+PIR, and TEC2xx7-4 Series Thermostat Controllers Application Note (LIT-12011594).

Configuring the TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controller

The TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers are shipped with default settings for all configurable parameters. The default settings are shown in Table 4. To reconfigure the parameters via the thermostat, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the center key for approximately 8 seconds.
Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MODE key to proceed through the Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins, press and release the center key to scroll through the parameters listed in Table 4.
3. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option.
4. Press and release the center key to continue scrolling through the parameters.
Note: Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed in Table 4.
When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat reverts to the Status Display Menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water switching or supply air temperature monitoring at the thermostat.
Each input can be configured to the Selection Options included in Table 4.

Configuring the Sequence of Operation (SeqOpera)

Choose the appropriate sequence of operation. The modes presented are user-dependent on the sequen ce of operation selected. For two-pipe applications using a changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between Cooling Only and Heating Only. See Figure 14
through Figure 19 for sequence of operation examples.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
11
Table 2: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection Option
(0): Cooling Only See Figure 14. 10: Normally Open
(1): Heating Only See Figure 15. 10: N.O. Heating
(2): Cooling and Reheat See Figure 16. 6 and 7: Reheat
(3): Heating and Reheat See Figure 17. 6 and 7: Reheat
Control Curve
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off Control Floating Control Proportional
(N.O.) Cooling 11: Normally Closed (N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
10: N.O. Heating 11: N.C. Heating
10: Open Cooling 11: Closed Cooling
10: Open Heating 11: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 10: Open Heating 11: Closed Heating
Table 3: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection Option
(0): Cooling Only See Figure 14. 10: N.O. Cooling
(1): Heating Only See Figure 15. 8: N.O. Heating
(2): Cooling and Reheat See Figure 16. 6 and 7: Reheat
(3): Heating and Reheat See Figure 17. 6 and 7: Reheat
(4): Cool/Heat Four-Pipe See Figure 18. 8: N.O. Heating
(5): Cool/Heat Four-Pipe and Reheat
Control Curve
See Figure 19. 6 and 7: Reheat
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off Control Floating Control Proportional
11: N.C. Cooling
9: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating
9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
10: Open Cooling 11: Closed Cooling
8: Open Heating 9: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating
8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
6 and 7: 8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
Reheat
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 10: Proportional Heating
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating
9: Proportional Heating 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating 10: Proportional Cooling
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
12
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor tional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 14: Cooling Only,
Two- or Four-Pipe Applications
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 15: Heating Only,
Two- or Four-Pipe Applications
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
or Propor t ional
Outputs
Heating Output Cooling Output
Off
Off
On
On
Figure 16: Cooling with Reheat,
Two- or Four-Pipe Applications
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 17: Heating with Reheat,
Two- or Four-Pipe Applications
Figure 18: Heating/Cooling,
Four-Pipe Applications
Heating Setpoint
Closed
Device
Opened
FIG:htng_clng
Deadband
or Propor t ional
Outputs
Heating Output Cooling Output
Device Closed
Device
Opened
Temperature Incr ease
(Increments of 1F°/0.5C°)
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
(Increments of 1F°/0.5C°)
On/Off, Floating,
On
Temperature Increase
100%
0%
t
h
r
On/Off, Floating,
Temperature In cr ease
(Increments of 1F°/0.5C°)
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Device
Cooling Setpoint
Device
Temperature Increase
(Increm ents of 1F°/0.5C°)
13
Heating Setpoint
Device
Closed
Device Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put Cooling Output
Off
Off
On
On
Figure 19: Heating/Cooling with Reheat, Four-Pipe Applications
Figure 20: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature De vi ation from Setpoint , F°
2.0F°/1. 0C° to
5.0F°/2.5C° Deadband
100%
0%
2.5
2.5
2.0 2.0
1.5
1.50.5 0.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Setpoint
High
FIG:fn_oprtn
Fan
Speed
The fan is of f
between the
heating and
if the
parameter is
set to .
Auto Fan
AS AD
Temperature Incr ease
(Increments of 1F°/0.5C°)

Configuring Automatic Fan Speed

Use the Fan Menu parameter in the Installer Configuration menu to set the available Fan Mode options. Use the FAN key to select the desired Fan Mode option.
Heating
cooling se t points
When selection option (2): Low-Med-High-Auto is chosen in the Fan Menu parameter, the fan operates as shown in Figure 20. When selection option (3): Low-High-Auto is chosen in the Fan Menu parameter, the fan operates at only the low and high settings, ignoring the medium setting (Figure 20). This operation applies to the occupied mode when the fan is set to Auto.
Cooling
Setpoint
14
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 1 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Pswrd Sets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu. Com addr MS/TP address at the thermostat;
coincides with the address assigned
at the supervisory controller.
Default: 254 BI1 Configuration of Binary Input 1.
Default: None
BI2 Configuration of Binary Input 2.
Default: None
Range: 0 to 1,000
Range: 004 to 127
(None): No function is associated with an input. (Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat remains in the occupied mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat remains in the occupied mode if the contact is closed, until the TOccTime expires.
(Window): Cancels the thermostat heating or cooling action when a window is open. The fan operation is only affected if the Fan Menu parameter is set to (4): On-Auto and Auto is the selected fan mode. A Window alarm appears, indicating that the window needs to be closed to resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input. (Door Dry): Door contact only has an effect if BI1 is set to MotionNO
or MotionNC. (See the BI1 parameter earlier in this table.) The occupancy is now dictated via BI1 and BI2. Any motion detected sets the zone to Occupied status. The zone remains permanently in occupied mode until the door contact switch opens momentarily. The thermostat then enters stand-by mode. If more movements are detected, the occupied mode resumes. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover are ignored. Use a Normally Closed contact switching device. Contact opened = Door opened, Contact closed = Door closed.
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat when the input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
15
Table 4: Installer Configuration Menu (Part 2 of 8)
Parameter
Description and Default Selection Options Appearing on Display
UI3 Configuration of Universal Input 3.
Default: None
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on AutoMode Enables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat cover.)
Default: on C or F Provides temperature scale options
for display.
Default: °F %RH disp Displays the current humidity
reading (TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models).
Default: off Lockout Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
(None): No function is associated with an input. (COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems.
• A water temperature greater than 78.0°F (25.6°C) indicates hot
• A water temperature less than 75.0°F (23. 9°C) indicates cold Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/Heat
Four-Pipe and Reheat applications. (SS): Supply Air Sensor Monitoring
(off): The scroll is inactive. (on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale (°F): Fahrenheit scale
(on): Displays the current humidity reading in % RH. (off): Does not display the current humidity reading.
Lockout Level
water is present. water is present.
Function
Mode Setting
(0) Access Access Access Access (1) Access Access No Access Access (2) No Access No Access Access Access (3) No Access No Access No Access Access (4) No Access No Access Access No Access (5) No Access No Access No Access No Access
Fan Setting
Local Override
Occupied T emperature Setpoints
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
16
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 3 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Pipe No Selectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTyp Defines the control output for the
SeqOpera Determines the sequence of
Fan Menu Sets the Fan Mode options.
DHumiLCK Locks out the dehumidification
%RH set
1
type of valves used in the
installation (TEC2626-4,
TEC2626H-4, TEC2626H-4+PIR,
TEC2636-4, TEC2636H-4, and
TEC2636H-4+PIR models).
Default: Floating
operation.
Default: 1
Default: 4
capability (TEC2636-4,
TEC2636H-4, TEC2636H-4+PIR,
TEC2656-4, TEC2656H-4, and
TEC2656H-4+PIR models).
Default: on
Sets the dehumidification setpoints
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 50.0% RH
(2.0 Pipes): Limits the number of sequences of operation available from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5, and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.) 24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating valves.
(0): Cooling Only (Off-Cool). The default is Cool. (1): Heating Only (Off-Heat). The default is Heat. (2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto. (3): Heating and Reheat (Off-Heat). The default is Heat. (4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Auto. (5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Auto. * Auto can be disabled with the AutoMode parameter. Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H). The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. The default is Auto.
(off): Dehumidification is locked out. (on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
17
Table 4: Installer Configuration Menu (Part 4 of 8)
Parameter
Description and Default Selection Options Appearing on Display
1
DehuHyst
DehuCool
St-By TM Sets stand-by timer value when
Unocc TM Sets Unoccupied Timer Value when
Sets the dehumidification hysteresis
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
1
Sets the maximum dehumidification
cooling output (TEC2636-4,
TEC2636H-4, TEC2636H-4+PIR,
TEC2656-4, TEC2656H-4, and
TEC2656H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 100%
used with occupancy sensor; time
delay between moment where
occupancy sensor detected the last
movement in the area and the time
which the thermostat stand-by mode
and setpoints become active.
Default: 0.5 hours
used with occupancy sensor; time
delay between the moment where
the thermostat toggles to stand-by
mode and the time which the
thermostat unoccupied mode and
setpoints become active.
Default: 0.0 hours
Range: 2.0 to 20.0% RH
Range: 20.0 to 100.0% Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Range: 0.5 to 24.0 hours, in 0.5 hour increments
0.0 hours or Factory Value: Setting this parameter to its default 0 value disables the occupied timer and prevents the thermostat from drifting from stand-by mode to unoccupied mode when occupancy sensor functions are used.
Range: 0.0 to 24.0 hours in 0.5 hour increments
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
18
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 5 of 8)
Parameter
Description and Default Selection Options Appearing on Display
St-By HT Sets Stand-by heating setpoint
when used with occupancy sensor;
value is between occupied and
unoccupied heating setp oi n ts.
Default: 69.0°F/20.6°C St-By CL Sets Stand-by cooling setpoint limit
when used with occupancy sensor;
value is between occupied and
unoccupied cooling setpoints.
Default: 78.0°F/25.6°C Unocc HT Sets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C Pband Proportional Band used by the PI
temperature control loop of the
thermostat.
Pband is not converted with C or F
scale and is always shown with a
range of 3 to 10.
Default: 3 (3F°/1.7C°)
Set type Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Value F Scale Pband/C Scale Pband 3 3.0F°/1.7C° 4 4.0F°/2.2C° 5 5.0F°/2.8C° 6 6.0F°/3.3C° 7 7.0F°/3.9C° 8 8.0F°/4.4C° 9 9.0F°/5.0C° 10 10.0F°/5.6C° Note: The use of a larger proportional band is not to use the
thermostat as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat location errors that cannot be worked around.
(temporar): Local changes to the heating or coolin g setpoints are temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are permanently stored in the thermostat memory.
Note: When adjusting the temperature, press the UP/ DOWN arrow keys to change the temperature in
0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
19
Table 4: Installer Configuration Menu (Part 6 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Spt Func Determines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
TOccTime Sets the duration of the Tempor ary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in the Main User Menu (when the thermostat is in the Unoccupied mode)
• a temporary heating or cooling setpoint
Default: 2.0 hrs
Deadband Sets the minimum deadband
between the heating and cooling setpoints.
Default: 2.0F°/1.0C°
Cal RS Sets the desired room air sensor
calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.
Default: 0.0F°/0.0C°
Cal RH Sets the desired humidity sensor
calibration (offset). The offset can be added to or subtracted from the actual displayed room humidity (TEC2636-4, TEC2636H-4, TEC2636H-4+PIR, TEC2656-4, TEC2656H-4, and TEC2656H-4+PIR models). This parameter can be used only if the dehumidification sequence is enabled.
Default: 0.0% RH
(Attch Stp): Single Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. Both the heating and cooling setpoints are changed simultaneously, while respecting the minimum configured deadband. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. The heating and cooling setpoints can be separated individually, allowing the minimum configured deadband to expand. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Range: -15.0% RH to 15.0% RH (adjustable in 1% RH increments)
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
20
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 7 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Aux cont Determines the auxiliary contact
function and configuration.
Default: 0
Auto Fan Affects the auto mode of operation
for the following Fan Menu
parameter selection options only:
(2): Low-Med-High-Auto
(3): Low-High-Auto
Default: AS
FL time Sets the maximum actuator stroke
timing (floating CntrlTyp
TEC2626-4, TEC2626H-4,
TEC2626H-4+PIR, TEC2636-4,
TEC2636H-4, and
TEC2636H-4+PIR models).
Default: 1.5 min Cph Sets the maximum number of cycles
per hour (TEC2616-4,
TEC2616H-4, TEC2616H-4+PIR,
and on/off CntrlTyp TEC2626-4,
TEC2626H-4, TEC2626H-4+PIR,
TEC2636-4, TEC2636H-4, and
TEC2636H-4+PIR models).
Default: 4 RA/DA Choice of reverse or direct acting
analog output signal (TEC2646-4,
TEC2646H-4, TEC2646H-4+PIR,
TEC2656-4, TEC2656H-4, and
TEC2656H-4+PIR models)
Default: DA
(AS AD): The fan is on Auto during occupied periods. The Med and High speeds operate automatically on a temperature error from the setpoint. The Low speed operates Auto on demand. When there is no demand, the Low speed shuts down. The Low speed is only re-activated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on Auto during unoccupied periods. The Low, Med, and High speeds operate automatically on a temperat ure error from the setpoint.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
Range: 3 to 8 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC (DA): Direct acting, 0 to 100% = 0 to 10 VDC
(0) Not used,
or used for reheat
(1) Auxiliary
N.O.
(2) Auxiliary
N.C.
(3) Auxiliary
N.O.
(4) Auxiliary
N.C.
(5) Auxiliary On/Off control through the
auxiliary network command. The output can be commanded through the network for any required auxiliary functions via a separate and dedicated network variable.
If the sequence of operation is set to reheat (2, 3, or 5), ignore this parameter.
Occupied = contact closed
Unoccupied = contact open
Occupied = contact open Unoccupied = contact
closed Occupied and fan On =
contact closed Unoccupied and fan On or
Off = contact open Occupied and fan On =
contact open Unoccupied and fan On or
Off = contact closed
The output aligns with occupancy.
The output aligns with occupancy and the fan on command.
The output aligns with the secondary network occupancy command.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
21
Table 4: Installer Configuration Menu (Part 8 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Reheat Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
1. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and hold the UP or DOWN arrow key to change the numeric value in increments of ten.
(1): 10 seconds (six cycles per minute), for various equipment with solid-state relays that withstand short duty cycles such as electric heat.
(0): 15 minutes (four cycles per hour), for various equipment with mechanical relays or contactors controlling mechanical reheat systems.
Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation.

Troubleshooting

See Table 6 for Display messaging. See Table 7 for troubleshooting details.

Accessories

All the accessories in Table 5 include mounting hardware; contact the nearest Johnson Controls® representative to order any of these parts.
Note: Review the technical specifications of the accessories prior to their use in an application.

Repair Information

If a TEC26x6(H)-4 or TEC26x6H-4+PIR Series Thermostat fails to operate within its specifications, replace the unit. For a replacement thermostat, cont act the nearest Johnson Controls representative.
Table 5: Accessories (Order Separat ely)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor
1
TE-6361M-1 SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TE-636S-1 Strap-Mount Temperature Sensor MS-BACEOL-0 RS485 End-of-Line Terminator
TEC-6-PIR TEC-6H-PIR
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2. The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC26x6-4 Series Thermostat Controller to provide occupancy sensing capability.
3. TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC26x6H-4 Series Thermostat Controller to provide occupancy sensing capability.
2
Duct Mount Air Temperature Sensor
Cover with Occupancy Sensor
3
Cover with Occupancy Sensor for Hospitality Models
Table 6: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filte r(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat heating or cooling
action in accordance with the programmable Binary Input (BI1).
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
22
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Table 7: Troubleshooting Details
1
Symptom Probable Causes
Multiple Symptoms
Poor Performance See the probable causes listed in the Multiple Symptoms section earlier in this table.
Thermostat Goes Offline
Thermostat Does Not Come Online
Excessive bus errors may be occurring. A device may have been added or changed with a duplicate address (may not be the same address as
some devices having problems, and may have happened sometime before the problem was noticed). Wiring errors or wire problems may exist. The baud rate may have been changed on some devices on the network, but not all devices. Max_Master may have been changed incorrectly (may have happened sometime before the problem
was noticed). A download may be in progress. There may be a fault at a device. A repeater may be needed or may be configured incorrectly. There may be a duplicate device object name or instance.
Excessive bus traffic may exist (bus overload). The baud rate may be set too low. There may be too many devices on the network. There may be unaccounted devices on the network (not mapped to the NAE). There may be unusually slow devices on the network or devices that are slow to respond. See the probable causes listed in the Multiple Symptoms section earlier in this table. A power failure or other failure may have occurred at the thermostat. Communication may have been disabled at the thermostat. See the probable causes listed in the Multiple Symptoms section earlier in this table. A thermostat may be connected to the wrong bus. A baud rate may be specified in the new thermostat that is incompatible with the running network. No device on the network is configured to us e a specific baud rate (normally the NAE), but all devices
are set to use auto baud. At least one device, typically the bus supervisor (NAE), must have an assigned baud rate. Set the baud rate in the bus supervisor and set all other devices to auto baud.
1. For common MS/TP troubleshooting information, refer to the MS/TP Communications Bus Technical Bulletin
(LIT-12011034).

Technical Specifications

TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control and Occupancy Sensing Capability (Part 1 of 2)

Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Relay/Triac Contact Rating
Analog Output Rating
Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Auxiliary
Output Rating Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Sensor Type Local 10k ohm Negative Temperatur e Coefficient (NTC) Thermistor
On/Off and Floating Control
Proportional Control
Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Safety Extra-Low Voltage (SELV) 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance (Minimum)
Temperature Coefficient (NTC) Thermistor Sensors
23
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control and Occupancy Sensing Capability (Part 2 of 2)
Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended MS/TP Network Guidelines 32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length Temperature
Range
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling Ambient
Conditions Compliance United States UL Listed, File E27734, CCN XAPX,
Shipping Weight TEC26x6(H)-4 Models: 0.75 lb (0.34 kg)
Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark – Johnson Controls, Inc., declares that the BACnet Thermostats are
Australia and New Zealand
BACnet International
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
C-Tick Mark, Australia/NZ Emissions Compliant
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific Controller (B-ASC)
TEC26x6H-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet® MS/TP Networked Thermostat Controllers with
24
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
Loading...