Johnson Controls TEC2627-2, TEC2647-2 Installation Instructions And Operators Manual

Page 1
TEC26x7-2 Series BACnet® MS/TP Networked Thermostat s with Two Outputs
Installation Instructions
Part No. 24-9890-242, Rev. A
Issued November 8, 2006
Supersedes January 31, 2006

Applications

The TEC26x7-2 Series Thermostats are BACnet® Master-Slave/Token-Passing (MS/TP) networked devices that provide control of local hydronic re he a t valves, pressure dependent Variable Air V olume (VAV) equipment with or without local reheat, or other zoning equipment using an on/off, floating, or proportional 0 to 10 VDC control input. The technologically advanced TEC26x7-2 Series Thermostats feature a Building Automation System (BAS) BACnet MS/TP communication capability that enables remote monitoring and programmability for efficient space temperature control.
The TEC26x7-2 Series Thermostat s feature an intuitive user interface with backlit display that makes setup and operation quick and easy . Th e thermostat s also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostats.
IMPORTANT: The TEC26x7-2 Series Thermostats are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostat.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Location Considerations

Locate the TEC26x7-2 Series Thermostat:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: Allow for vertical air circulation to the TEC26x7-2 Series Thermostat.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs
Installation Instructions
1
Page 2
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the security screw on the bottom of the thermostat cover.
2. Pull the bottom edge of the thermostat cover and open the thermostat as illustrated in Figure 1.
l
v m
r
_
r v
c
: G
I F
6. Drill a 3/16 in. (5 mm) hole at each of the two marked locations and tap nylon anchors (included with the thermostat) flush to the wall surface.
7. Position the thermostat mounting base on the wall and use the two mounting screws (included with the thermostat) to secure the base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
e
s a
b g n
i
t n u
o m
Figure 1: Removing the Thermostat Cover
3. Carefully pull the locking tabs on the right side of the thermostat mounting base and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 2.
PCB Locking Tabs
d
r a o b
t
i u
c
r
i
c d e
t n
i
r
p
Figure 2: Opening the Thermosta t PCB
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat mounting base.
5. Align the thermostat mounting base on the wall and use the base as a template to mark the two mounting hole locations.
Note: Be sure to position the thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat.
Figure 3: Securing the Thermostat
Mounting Base to the Wall
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat mounting base.
9. Remove the screw terminal blocks as illustrated in Figure 4.
s k
c
l
b
_
l
n m
r
t
: G
I F
Figure 4: Removing the Screw Terminal Blocks
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions2
Page 3

Wiring

When an existing thermostat is replaced, remove and label the wires to identify the terminal functions. When a TEC26x7-2 Series Thermostat is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
!
!
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC26x7-2 Series Thermostat.
making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
To wire the thermostat:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1 and Figure 5 through Figure 18.
Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034).
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the MS/TP communication wires to the terminal block.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
5. Reattach the thermostat cover to the mounting base (top side first).
6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat cover.
Table 1: Terminal Identification (See Figure 5.)
Terminal Number
4 24 V~ Hot 24 V~ Hot 24 VAC from Transformer 5 24 V~ Com 24 V~ Com 24 VAC (Common) from Transformer 6 BO5 Aux BO5 Aux Aux BO (Auxiliary Output) 7 BO5 Aux BO5 Aux Aux BO (Auxiliary Output) 8 BO3 Blank Open Heat 9 BO4 AO2 Close Heat
10 BO1 AO1 Open Cool
1 1 BO2 Blank Close Cool 12 BI1 BI1 Configurable Binary Input 1 13 RS RS Remote Sensor 14 Scom Scom Sensor Common 15 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 Configurable Universal Input 3
Blank +, –, REF +, –, REF MS/TP Bus
TEC2627-2 (On/Off or Floating Control)
Terminal Label Function
TEC2647-2 (Proportional 0to10VDCControl)
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 3
Page 4
Separ at e 24 VAC
Power Source for Auxiliar y Output
(24 VA C Maximu m)
24 V~
24 V~
Hot
Com
BO5
Aux
24 VAC
Thermostat Power
Same 24 VAC
Power Source for Auxiliar y Output
(24 VA C Maximu m)
24 V~
Com
BO5
Aux
24 V~
Hot
24 VAC
Thermostat Power
BO5
Aux
Aux
BO5
Aux
Aux
+
REF
Eight-Pole Bottom Connector
BO4/
AO2
9 10 11 12 13 14 15 16
Independent Contacts
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fan
Remote Inputs
BI1
Voltage-Free Contact
• Remote NSB
• Motion
• Window
Two-Pole Left Top Connector
24 V~
24 V~
Com
Hot
4 5
BO1/
BO2
BI1
AO1
Scom
BI2 UI3
RS
- OR -
Supply S ensor Changeover Sensor
Three-Pole Right Top Connector
BO5
Aux
6 7 8
Scom
BI2
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm Voltage-Free
Contact
• COC/NH Normally Heat Closed Contact
= Cold Water
• COC/NC
Normally Cool
Closed Contact
= Hot Water
BO5
Aux
BO3
UI3
+
Supervisory
Controller
REF
g
n
r w
: G
I F
Figure 5: Wiring the TEC26x7-2 Series Thermostat
(See Table 1.)
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions4
Page 5
Floating Actuator
Room Temperature Control Thermostat
(Minimum and Maximum Pos i t ion
Adjusted on Actuator)
Figure 6: Wiring the TEC2627-2 Thermostat for Floating Control
(Pressure-Dependent VAV Cooling Only)
UI3 COS
24 V~ Com
24 V~ Hot BO1 Open
BO2 Close
y
l n
o
_ g
n
l
c _
7
2 6
2
c
e
t
: G
I F
Proportional
Actuator
0 to 10
VDC
UI3 COS
24 V~ Com
Room Temperature Control Thermostat
(Minimum and Maximum Position
Adjusted on Actuator)
24 V~ Hot
AO1
Figure 7: Wiring the TEC2647-2 Thermostat for Proportional 0 to 10 VDC Control
(Pressure-Dependent VAV Cooling Only)
Changeover
Sensor
Floating
Actuator
Room Temperature Control Thermostat
(Minimum and Maximum Positio n
Adjusted on A ct uator)
Supply Air
Temperature Sensor
UI3 COS
24 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
y
l
n
o _
g
n
l
c _
7
4 6
2
c
e
t
: G
I F
r
v
g n
h
c _
g
n
l
c _
g
n
t
h _
7
2 6
2
c
e
t
: G
I F
Figure 8: Wiring the TEC2627-2 Thermostat for Floating Control
(Pressure-Dependent VAV Heating/Cooling with Changeover)
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 5
Page 6
Changeover
Sensor
Supply Air
Tempe r at ur e Sensor
Proportional
Actuator
0 to 10
VDC
UI3 COS
24 V~ Com
Room Temperature Control Thermostat
(Mini m u m an d Ma ximum Pos i t ion
Adjusted on Actuator)
24 V~ Hot
AO1
Figure 9: Wiring the TEC2647-2 Thermostat for Proportional 0 to 10 VDC Control
(Pressure-Dependent VAV Heating/Cooling with Changeover)
Supply Air
Tempe r ature Sensor
UI3 COS
24 V~ Com
24 V~ Hot
BO1 Op en
BO2 Close
BO5-Aux BO5-Aux
1
C
Changeover
Sensor
Room Temperature Control Thermostat
Floating
Actuator
Heating/Cooling
and On/Off
Duct Heater
(Minimum and Max i m um P os i t ion
Adjusted on A ct uator)
r
v
g n
h
c _
g
n
l
c
_
g n
t h
_
7 4
6
2
c
e
t
: G
I F
t
h
r
_
r
v
g n
h
c _
g
n
l
c _
g
n
t
h _
7
2 6
2
c
e
t
: G
I F
Figure 10: Wiring the TEC2627-2 Thermostat for Floating Control
(Pressure-Dependent VAV Heating Cooling with Changeover and Reheat)
Changeover
Sensor
Room Temperature Control Thermostat
Proportional
Actuator
Heating/Cooling
and On/Off
Duct Heater
(Minim u m an d Ma ximum Pos i tion
Adjuste d on Actuator)
Supply Air
Tempe r at ur e Sensor
UI3 COS
24 V~ Com
24 V~ Hot
AO1
AO2 BO5-Aux BO5-Aux
0 to 10
VDC
1
C
Figure 11 : Wiring the TEC2647-2 Thermostat for Proportional 0 to 10 VDC Control
(Pressure-Dependent VAV Heating/Cooling with Changeover and Reheat)
t
h
r
_
r
v
g n
h
c
_
g n
l
c
_
g n
t h
_
7 4
6
2
c
e
t
: G
I F
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions6
Page 7
UI3 COS
24 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
Room Temperature Control Therm ostat
Figure 12: Wiring the TEC2627-2 Thermostat for Floating Control
(Heating/Cooling Hydronic Valve Control)
c n
r d
h
_ g
n
l
c
_ g
n
t
h
_ 7
2
6 2
c
e
t
: G
I F
UI3 COS
24 V~ Com
24 V~ Hot
AO1
0 to 10
VDC
Room Temperature Control Therm ostat
c
n
r
d
h _
g
n
l
c _
g
n
t
h _
7
4 6
2
c
e
t
: G
I F
Figure 13: Wiring the TEC2647-2 Thermostat for Proportional 0 to 10 VDC Control
(Heating/Cooling Hydronic Valve Control)
Optional Wat er Supply S ensor
Room Temperature Control Therm ostat
Floating
Heating/Cooling
Valve
UI3 COS
24 V~ Com
24 V~ Hot BO1 Open BO2 Close
Supply Water
Tempe r at ur e Sensor
r
v
g n
h
c
_
c n
r d
h
_ g
n
l
c
_ g
n
t
h
_ 7
2
6 2
c
e
t
: G
I F
Figure 14: Wiring the TEC2627-2 Thermostat for Floating Control
(Heating/Cooling Hydronic Valve Control with Changeover)
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 7
Page 8
UI3 COS
24 V~ Com
24 V~ Hot Optional Wat er Supply S ensor
Proportional
Heating/Cooling
Valve
AO1
0 to 10
VDC
Room Temperature Control Therm ostat
Supply Water
Tempe r at ur e Sensor
Figure 15: Wiring the TEC2647-2 Thermostat for Proportiona l 0 to 10 VDC Co nt rol
(Heating/Cooling Hydronic Valve Control with Changeover)
24 V~
or
24 V~
Hot
Two -Pip e Applic ations
24 V~
Com
Cooling
Valve
Heating
Valve
or
or
Four-Pipe Applications
24 V~
Hot
Com
r
v g
n
h
c
_
c n
r d
h
_ g
n
l
c
_ g
n
t
h
_ 7
4
6 2
c
e
t
: G
I F
f
f o n o 7 2 6 2 C E T
Figure 16: Wiring the TEC2627-2 Thermostat for On/Off Control
Heating/Cooling
Valve
Two -Pip e Applic ations
Figure 17: Wiring the TEC2627-2 Thermostat for Floating Control
BO1
BO2
24 V~
Hot
24 V~
Com
Cooling
Valve
Heating
Valve
BO1
BO2 BO3
BO4
Four-Pipe Applications
24 V~
Hot
24 V~
Com
g n
i
t a o
l
f 7
2 6 2 C E T
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions8
Page 9
AO1
Com
Hot
24 V~
24 V~
Cooling
Valve
Heating/Cooling
Valve
Heating
Valve
Two -Pip e Applic ations
Figure 18: Wiring the TEC2647-2 Thermostat for Proportional Control
Table 2: MS/TP Bus Objects (Part 1 of 4)
Point Name Thermostat Point
(Type/Address)
Room Temp
Room Temp Override
Outdoor Temperature
Sequence of Operation
System Mode
Occupancy
PI Heating Demand PI Cooling Demand Supply Temperature
AUX (BO5) Status
AUX (BO5) Output
1, 2
3
3, 4
3
3
3
5
5
5
5
3
Heating (BO3 and BO4) Valve Status (TEC2627-2 Model)
5
AV 6 -40.0°F/-40.0°C to
BV 7 0 = Normal
AV 8 -40.0°F/-40.0°C to
MSV 39 1 = Cooling Only
MSV 13 1 = Off
MSV 12 1 = Resume Schedule
AV 54 0 to 100% AV 55 0 to 100% AI 11 -40.0°F/-40.0°C to
BI 65 0 = Off
BV 47 0 = Off
MSV 66 For On/Off Control:
AO1
Hot
24 V~
AO2
Four-Pipe Applications
Range
122.0°F/50.0°F
1 = Override
122.0°F/50.0°F
2 = Heating Only 3 = Cooling and Reheat 4 = Heating and Reheat 5 = Cool/Heat Four-Pipe 6 = Cool/Heat Four-Pipe and Reheat
2 = Cool 3 = Heat 4=Auto
2 = Occupied 3 = Unoccupied 4 = Temporary Occupied
122.0°F/50.0°F
1=On
1=On
1=Open 2 = Closed
For Floating Control: 1 = Stopped 2=Opening 3=Closing
24 V~
Com
l
a n o
i
t
r o p o
r p 7 4 6 2 C E T
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 9
Page 10
Table 2: MS/TP Bus Objects (Part 2 of 4)
Point Name Thermostat Point
(Type/Address)
Cooling (BO1 and BO2) Valve Status (TEC2627-2 Model)
BI1 Status
BI2 Status
UI3 Status
5, 6
5, 6
5, 6
Window Alarm
Filter Alarm
5
Service Alarm
Occupied Heat Setpoint
Occupied Cool Setpoint
Unoccupied Heat Setpoint
Unoccupied Cool Setpoint
Keypad Lockout
BI1 Configuration
BI2 Configuration
UI3 Configuration
Menu Scroll
Temperature Scale
5
5
5
3, 7
3, 7
3, 7
3, 7
3
3
3
3
3
3
MSV 67 For On/Off Control:
BI 62 0 = Deactivated
BI 63 0 = Deactivated
BI 64 0 = Deactivated
BI 58 0 = Off
BI 59 0 = Off
BI 60 0 = Off
AV 49 40.0°F/4.5°C to
AV 50 54.0°F/12.0°C to
AV 51 40.0°F/4.5°C to
AV 52 54.0°F/12.0°C to
MSV 40 1 = Level 0
MSV 16 1 = None
MSV 17 1 = None
MSV 18 1 = None
BV 19 0 = No Scroll
BV 21 0 = °C
Range
1 = Open 2 = Closed
For Floating Control: 1 = Stopped 2 = Opening 3=Closing
1 = Activated
1 = Activated
1 = Activated
1=On
1=On
1=On
90.0°F/32.0°C
100.0°F/37.5°C
90.0°F/32.0°C
100.0°F/37.5°C
2=Level1 3=Level2 4=Level3 5=Level4 6=Level5
2=RemNSB 3=MotionNO 4=MotionNC 5 = Window
2 = Door Dry 3 = Override 4 = Filter 5=Service
2 = COC/NH 3 = COC/NC 4=COS 5=SS
1=ScrollActive
1=°F
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions10
Page 11
Table 2: MS/TP Bus Objects (Part 3 of 4)
Point Name Thermostat Point
(Type/Address)
Out 1 (BO1 and BO2) Configuration
AUX (BO5) Configuration
Heating Setpoint Limit
Cooling Setpoint Limit
Setpoint Type
3
Temporary Occupancy Time
Door Time
Deadband
3
3
Reheat Time Base (BO5)
Control Type (TEC2627-2 Model)
3
3
3
3
3
3
3
MSV 23 1 = False
MSV 24 1 = Not Used
AV 27 40.0°F/4.5°C to
A V 28 54.0°F/12.0°C to
BV 29 0 = Permanent
MSV 30 1 = 0 Hours
MSV 31 1 = 1 Minute
AV 32 2F°/1C° to
BV 33 0 = 15 Minutes
BV 35 0 = On/Off
Range
2=True
2=NOwithOcc 3 = NC withOcc 6 = Network Controlled
90.0°F/32.0°C
100.0°F/37.5°C
1 = Temporary
2=1Hour 3=2Hours 4=3Hours 5=4Hours 6=5Hours 7=6Hours 8=7Hours 9=8Hours 10 = 9 Hours 11 = 10 Hours 12 = 11 Hours 13 = 12 Hours 14 = 13 Hours 15 = 14 Hours 16 = 15 Hours 17 = 16 Hours 18 = 17 Hours 19 = 18 Hours 20 = 19 Hours 21 = 20 Hours 22 = 21 Hours 23 = 22 Hours 24 = 23 Hours 25 = 24 Hours
2=2Minutes 3=3Minutes 4=4Minutes 5=5Minutes 6=6Minutes 7=7Minutes 8=8Minutes 9=9Minutes 10 = 10 Minutes
5F°/2.5C°
1 = 10 Seconds
1 = Floating
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 1 1
Page 12
Table 2: MS/TP Bus Objects (Part 4 of 4)
Point Name Thermostat Point
(Type/Address)
3
Floating Motor Timing (TEC2627-2 Model)
On/Off Control CPH (TEC2627-2 Model)
Direct/Reverse Acting (TEC2647-2 Model)
TEC26x7-aaa
8, 9
MSV 36 1 = 0.5 Minutes
3
MSV 37 1 = 3 CPH
3
BV 38 0 = Direct Acting
Device 72aaa N/A
Range
2=1.0Minute 3=1.5Minutes 4=2.0Minutes 5=2.5Minutes 6=3.0Minutes 7=3.5Minutes 8=4.0Minutes 9=4.5Minutes 10 = 5.0 Minutes 11= 5.5 Minutes 12 = 6.0 Minutes 13 = 6.5 Minutes 14 = 7.0 Minutes 15 = 7.5 Minutes 16 = 8.0 Minutes 17 = 8.5 Minutes 18 = 9.0 Minutes
2=4CPH 3=5CPH 4=6CPH 5=7CPH 6=8CPH
1 = Reverse Acting
1. This MS/TP Bus object is readable and only writable if the corresponding override object is set. (For example, Room Temp has a corresponding override object of Room Temp Override. This corresponding override object needs to be set to 1=Override to be able to write Room Temp to a diffe r e nt value.)
2. This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
3. This MS/TP Bus object is readable and writable.
4. This MS/TP Bus object is valid only if it is written via the network.
5. This MS/TP Bus object is readable only.
6. The BI object type status is available even if the configuration is set to None.
7. If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermostat to maintain the minimum deadband between the two setpoints.
8. The designation aaa is the address of the device (from 004 to 127) on the MS/TP network.
9. Max_Master is writable.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions12
Page 13

Connecting the MS/TP Bus

To connect the MS/TP Bus:
1. Set the MS/TP address of the TEC26x7-2 Series Thermostat per the engineering drawings and test for bus voltage, polarity, and isolation prio r to wiring the MS/TP Bus. (See the Com addr parameter in Table 5 to set the MS/TP address for the thermostat.)
Note: Pressing and holding the UP/DOWN arrow keys simultaneously displays the MS/TP address that is assigned.
Note: The wiring rules for the MS/TP Bus differ from the wiring rules for the N2 Bus. For more details on wiring the MS/TP Communications Bus, refer to the
MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Observe the polarity when connecting the bus wires to the thermostat.
3. After the bus wires are connected to the fir st thermostat, continue in a daisy-chained fashion to the next thermostat.
Note: The bus wiring must be twisted-pair lines. Do not run the bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
The MS/TP Bus requires proper termination and biasing at each end of a segment (a segment is a physically continuous length of wire). The thermostat is not equipped with the ability to provide this termination; therefore, it is not recommended that it be located at the physical ends of a bus segment.
Note: See Table 6 for end-of-line te rm in ato r ord eri ng information.
It is recommended that the thermostat be configured for automatic baud rate detection. Do not exceed the maximum number of devices allowed on a Field Bus. Be sure that the wiring terminations are set correctly, and that all communication wiring is daisy-chained with no taps.
A small green light under the thermostat cover (on the left edge when facing the thermostat) indicates the communications mode when the thermostat is operating. The following blink codes may be seen:
Off: indicates that there is no power to the thermostat or that the MS/TP wiring polarity is reversed.
Long: Indicates that the MS/TP communication daughter board is the wrong type for the main board.

MS/TP Device Mapping

Preparation

Before mapping a TEC26x7-2 Series Thermostat into a Network Automation Engine (NAE):
1. Decide which point objects within the thermostat need to be mapped. Only map the point objects that need to be viewed on a regular basis, since excessive mapping lowers system performance. Suggested point objects for mapping include: Room Temp, System Mode, Fan Status, Occupied Heat Setpoint, Occupied Cool Setpoint, Unoccupied Heat Setpoint, and Unoccupied Cool Setpoint. In addition, alarm points may be mapped if they are used, and other point objects may be mapped if required. Use the Engineering view to examine infrequently used point objects.
Note: It is recommended that all thermostat configuration parameters be set as desired, prior to mapping the objects into the controller. If any thermostat configuration parameters are altered after the objects are mapped into the controller, it is recommended that all objects be re-mapped.
2. Verify that a Field Bus is defined in the NAE. BACnet MS/TP devices attach to a Field Bus. Refer to the BACnet MS/TP Integration with the NAE Technical Bulletin (LIT-12011013) for instructions on how to define a Field Bus.
3. Verify that a BACnet Integration is defined for the Field Bus. The thermostat is mapped as a BACnet device under a Field Bus BACnet Integration. Refer to the BACnet System Integration with NAE Technical Bulletin (LIT-1201531) for instructions on how to define a BACnet Integration.
At this point, the thermostat and the required point objects inside the thermostat can be mapped.
Short-Short-Long: Indicates that the baud rate is known and that communication is active.
Short-Short: Indicates that the thermostat is scanning for the correct baud rate and that ther e is no communication.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 13
Page 14

Adding a Thermostat

The thermostat must be added before its point s can be mapped. To do this, select the BACnet Integration under the Field Bus (refresh the tree view if required to see a newly added BACnet Integration) and choose Field Device from the Insert menu. Assisted Definition using Auto Discovery is the easiest way to add a new thermostat online; however, this requires that the thermostat that is to be added is connected and ready to communicate.

Adding Point Objects

The required point objects must be mapped under the thermostat device. To accomplish this, select the thermostat device under the BACnet Integration (refresh the tree view if required to see a newly added thermostat device) and choose Field Point from the Insert menu. Assisted Definition using Auto Discovery is the easiest way to add new point objects online; however, this requires that the thermostat that is to be mapped is connected and ready to communicate.
Device object names used with BACnet Communication must be unique to fully satisfy the requirements of BACnet. The thermostat automatically selects a device object name for itself using the format TEC26x7-aaa, where aaa designates the address selected (from 004 to 127) on the MS/TP network. If this name needs to be changed by writing a new one into the thermostat device object, that should be done before any point objects are mapped. Be sure that the name of the new thermostat being added to the NAE matches that of the thermostat itself. This name goes into the Name field, Object section, Configuration tab of the Configure step in the Insert Field Device Wizard.
Device object IDs used with BACnet communications must be unique to fully satisfy the requirements of BACnet MS/TP network guidelines. The thermostat automatically selects a device object ID for itself using the format 72aaa, where aaa designates the address selected (from 004 to 127) on the MS/TP network (for example, 72004, 72005). If this ID needs to be changed by writing a new one into the thermostat device object, that should be done before any po int objects are mapped. Be sure that the ID of the new thermostat being added to the NAE matches that of the thermostat itself. This number goes into the Instance Number field, Network section, Hardware tab of the Configure step in the Insert Field Device Wizard.
When mapping point objects, the point type must match the BACnet object type (for example, AV, MV, BI), and the point instance number must match the point BACnet instance number.

Overriding via the NAE

The last override command to any point object is used or saved.
One override can be used at a time at each point object (for example, if an override from the network is active, the local adjustment and internal control are disabled).
If a setpoint is overridden, the thermostat adjusts the other setpoint, if necessary, to maintain the minimum deadband between the two setpoints. The setpoints can be spread farther apart but can never be adjusted closer than 2F°/1C° or the Deadband parameter selection.
All network overrides are released automatically after 10 minutes of no communication to any other device (for example, if the network cable is removed from the thermostat). Other devices can be the NAE, another thermostat, or a VAV Modular Assembly (VMA).
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions14
Page 15

Setup and Adjustments

Thermostat Operation Overview

Backlit, pl ain text
LCD is easy to read
in any condi t io n.
Three key s on the thermostat make operation easy and intuitive.
Figure 19: Front Cover of Thermostat

Thermostat User Interface Keys

The TEC26x7-2 Series Thermostat user interface consists of three keys on the front cover (as illustrated in Figure 19). The function of each key is as follows:
OVERRIDE key overrides the unoccupied mode to occupied at the local user interface for the specified TOccTime. (TOccTime is defined by selecting the appropriate time period in the Inst aller Configuration Menu.) The OVERRIDE key also allows access to the Installer Configuration Menu. See the Configuring the TEC26x7-2 Series Thermostat section.
Note: If one of the binary inputs is configured to operate as a remote override contact, this OVERRIDE key is disabled.
Room Temp
70.0ºF
LEDs indicate system activity.
w
v
_
t
n
r
f
: G
I F

Light-Emitting Diodes (LEDs)

Two LEDs are included to call for heat or call for cooling:
•The HEAT LED is on when heating or reheat is on.
•The COOL LED is on when cooling is on.

Status Display Menu

The Status Display Menu is displayed during normal thermostat operation. This menu continuously scrolls through the following parameters:
Room Temperature
System Mode
Occupancy Status (Occupied/Unoccupied/Override)
UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment.

Backlit Liquid Crystal Display (LCD)

The TEC26x7-2 Series Thermostats include a 2-line, 8-character backlit display. Low-level backlighting is
Applicable Alarms (The backlight lights up as an alarm condition is displayed.)
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter. present during normal operation, and it brighten s when any user interface key is pressed. The backlight returns to low level when the thermostat is left unattended for 45 seconds.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 15
Page 16

Configuring the TEC26x7-2 Series Thermostat

The TEC26x7-2 Series Thermostat comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 5. To reconfigure the parameters via the thermostat, follow the steps in this section.
To access the Installer Configuration Menu, press and hold the OVERRIDE key for approximately 8 seconds. Once the Installer Configuration Menu begins, release and press the OVERRIDE key to scroll through the parameters listed in Table 5. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option. Then press and release the OVERRIDE key to continue scrolling through the parameters.
When the thermostat is in the Installer Configuration Menu and left unattended for approximate ly 8 seconds, the thermostat reverts to the Status Display Menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water switching or supply air temperature monitoring at the thermostat.
Each input can be configured to the Selection Options included in Table 5.

Configuring the Output Options (Out1Conf)

For applications that enable heating/cooling operation from the same output, choose the selection option (2.0) in the Out1Conf parameter. For applications that enable heating/cooling operation from differ ent outputs, choose the selection option (4.0).

Configuring the Sequence of Operation (SeqOpera)

Choose the appropriate sequence of operation. The modes presented are user-dependent on the sequen ce of operation selected. For two-pipe applications using a changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between Cooling Only and Heating Only. See Figure 20
through Figure 25 for sequence of operation examples.
Table 3: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection Option
(0): Cooling Only See Figure 20. 10: N.O. Cooling
(1): Heating Only See Figure 21. 10: N.O. Heating
(2): Cooling and Reheat See Figure 22. 6 and 7: Reheat
(3): Heating and Reheat See Figure 23. 6 and 7: Reheat
Control Curve
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off Control Floating Control Proportional
10: Open Cooling
11: N.C. Cooling
11: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
10: N.O. Heating 11: N.C. Heating
11: Closed Cooling 10: Open Heating
11: Closed Heating 6 and 7: Reheat
10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 10: Open Heating 11: Closed Heating
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 10: Proportional Heating
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions16
Page 17
Table 4: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection Option
(0): Cooling Only See Figure 20. 10: Normally Open
(1): Heating Only See Figure 21. 8: N.O. Heating
(2): Cooling and Reheat See Figure 22. 6 and 7: Reheat
(3): Heating and Reheat See Figure 23. 6 and 7: Reheat
(4): Cool/Heat Four-Pipe See Figure 24. 8: N.O. Heating
(5): Cool/Heat Four-Pipe and Reheat
Control Curve
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off Control Floating Control Proportional
(N.O.) Cooling 11: Normally Closed (N.C.) Cooling
9: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating
9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
See Figure 25. 6 and 7: Reheat
8: N.O. Heating 9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
10: Open Cooling 11: Closed Cooling
8: Open Heating 9: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating
8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating
9: Proportional Heating 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating 10: Proportional Cooling
Device Opened
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor tional
Device Closed
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Figure 20: Cooling Only,
Two- or Four-Pipe Applications
Heating Setpoint
On/Off, Floating,
or Propor t ional
Output
Temperature Increase
(Increments of 1F°/0.5C°)
Device Closed
Output
On/Off, Floating,
Heating Output
or Propor t ional
Outputs
Heating Setpoint
Cooling Output
Cooling Setpoint
Deadband
Device
Opened
t
h
r
_
h
t w
_ g
n
l
c
: G
I F
On
On
Reheat
Off
Off
Device Closed
y
l
n _
g
n
l
c
: G
I F
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Figure 22: Cooling with Reheat,
Two- or Four-Pipe Applications
y
l n
_
g n
t h
: G
I F
Figure 21: Heating Only,
Two- or Four-Pipe Applications
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 17
Page 18
On
On
Reheat
Off
On/Off, Floating,
or Propor t ional
Outputs
Heating Output Cooling Output
Off
On/Off, Floating,
or Propor t ional
Output
Temperature Increase
(Increments of 1F°/0.5C°)
Figure 23: Heating with Reheat,
Two- or Four-Pipe Applications
Heating Setpoint
Device
Opened
On
On
Reheat Output
Off
Off
100%
0%
Heating Setpoint
Cooling Setpoint
Deadband
Device
Opened
On
On
Off
Device
Off
t
h
r _
h
t w
_
g
t
h
: G
I F
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Figure 24: Heating/Cooling,
Closed
g n
l
c
_
g n
t h
: G
I F
Four-Pipe Applications
On/Off, Floating,
or Propor t ional
Outputs
Cooling Setpoint
Deadband
Heatin g O ut put Cooling Output
Device
Opened
Device Closed
Tempe rature Increase
(Increments of 1F°/0.5C°)
Device Closed
t h
r _
g
n
l
c _
g
n
t
h
: G
I F
Figure 25: Heating/Cooling with Reheat,
Four-Pipe Applications
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions18
Page 19
Table 5: Installer Configuration Menu (Part 1 of 4)
Parameter
Description and Default Selection Options Appearing on Display
Com addr MS/TP address at the thermostat;
coincides with the address assigned
at the supervisory controller.
Default: 4 BI1 Configuration of Binary Input 1.
Default: None
BI2 Configuration of Binary Input 2.
Default: None
Range: 004 to 127
(None): No function is associated with an input. (Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat remains in the occupied mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat remains in the occupied mode if the contact is closed, until the TOccTime expires.
(Window**): Cancels the thermostat heating or cooling action when a window is open. A Window alarm is displayed indicating that the window needs to be closed to resume heating or cooling.
* These settings disable any local override function. ** When this setting is selected, the heating and or cooling outputs
are enabled only when the contact is closed.
(None): No function is associated with an input. (Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC. (See the BI1 parameter earlier in this table.) The occupancy is now dictated via BI1 and BI2. Any motion detected sets the zone to Occupied status. The thermostat remains in the occupied mode until a DoorOpen is detected, at which point the thermostat goes to the unoccupied mode. If the door stays open more than the specified door time, the thermostat will remain unoccupied. (See the Door Time parameter later in this table.)
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat when the input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 19
Page 20
Table 5: Installer Configuration Menu (Part 2 of 4)
Parameter
Description and Default Selection Options Appearing on Display
UI3 Configuration of Universal Input 3.
Default: None
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on C or F Provides temperature scale options
for display.
Default: °F Lockout Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
Out1Conf Defines the type of operation
needed for Output 1.
Default: 4.0
CntrlTyp Defines the control output for the
type of valves used in the
installation (TEC2627-2 model).
Default:
Floating
(None): No function is associated with an input. (COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems.
Note: Choose the selection option (0): Cooling Only for the
(SS): Supply Air Sensor Monitoring (off): The scroll is inactive.
(on): The scroll is active.
(°C): Celsius scale (°F): Fahrenheit scale
Lockout Level
* If lockout level (2) or (3) is selected, the lockout functions like lockout level (0) or (1) respectively.
(2.0): Limits the number of sequences of operation available from 0 to 3, and enables heat/cool operation from the same output.
(4.0): Allows access to all sequences of operation from 0 to 5, and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.) 24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating valves.
SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. Choose the selection option (2): Cooling and Reheat to allow changeover to occur between Cooling and Reheat and Heating and
Reheat.
Function
Unoccupied Override Occupied Temperature
Setpoints
(0) Access Access
(1) No Access Access (2*) This lockout level is not used. (3*) This lockout level is not used.
(4) Access No Access
(5) No Access No Access
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions20
Page 21
Table 5: Installer Configuration Menu (Part 3 of 4)
Parameter
Description and Default Selection Options Appearing on Display
SeqOpera Determines the sequence of
operation.
Default: 1
Unocc HT Sets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C Set type Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent TOccTime Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in the Main User Menu (when the thermostat is in the Unoccupied mode)
• a temporary heating or cooling setpoint
Default: 2.0 hrs
DoorTime Engages the Unoccupied mode if
the door stays open minimally for the time specified.
Default: 2.0 min
Deadband Sets the minimum deadband
between the heating and cooling setpoints.
Default: 2.0F°/1.0C°
(0): Cooling Only (Off-Cool). The default is Cool. (1): Heating Only (Off-Heat). The default is Heat. (2): Cooling and Reheat (Off-Auto-Heat-Cool). The default is Heat. (3): Heating and Reheat (Off-Heat). The default is Heat. (4*): Cool/Heat Four-Pipe (Off-Auto-Heat-Cool). The default is Heat. (5*): Cool/Heat Four-Pipe and Reheat (Off-Auto-Heat-Cool). The
default is Heat. * Selection option (4.0) for Out1Conf only. (See Out1Conf parameter
earlier in this table.) Note: Choose the selection option (0): Cooling Only when using a
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
(temporar): Local changes to the heating or coolin g setpoints are
temporary, and remain effective for the specified TOccTime. (permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 1.0 to 10.0 min
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
changeover sensor to allow changeover to occur between Cooling Only and Heating Only. Choose the selection option (2): Cooling and Reheat when using a changeover sensor to allow changeover to occur between Cooling and
Reheat and Heating and Reheat.
Note: When adjusting the
temperature, press the UP/DOWN arrow keys to change the temperature in
0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in
5.0F°/5.0C° increments.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 21
Page 22
Table 5: Installer Configuration Menu (Part 4 of 4)
Parameter
Description and Default Selection Options Appearing on Display
Cal RS Sets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C° Aux cont Determines the auxiliary contact
function and configuration.
Default: 0
FL time Sets the maximum actuator stroke
timing (floating ContrlTyp
TEC2627-2 model).
Default: 1.5 min Cph Sets the maximum number of cycles
per hour (on/off CntrlTyp
TEC2627-2 model).
Default: 4 RA/DA Choice of reverse or direct acting
analog output signal (TEC2647-2
model).
Default: DA Reheat Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
* If option (3) or (4) is selected, the option functions like option (1) or (2) respectively.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
Range: 3 to 8 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC (DA): Direct acting, 0 to 100% = 0 to 10 VDC
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric heat.
(0): 15 minutes (four cycles per hour), for various equipment with mechanical relays or contactors controlling mechanical reheat systems.
Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation.
(0) Not used,
or used for reheat
(1) Auxiliary
N.O.
(2) Auxiliary
N.C.
(3*) This selection option is not used. (4*) This selection option is not used.
(5) Auxiliary On/Off control through the
auxiliary network command. The output can be commanded through the network for any required auxiliary functions via a separate and dedicated network variable.
If the Sequence of Operation is set to reheat (2, 3, or 5), ignore this parameter.
Occupied = contact closed
Unoccupied = contact open
Occupied = contact open Unoccupied = contact
closed
The output aligns with occupancy.
The output aligns with the secondary network occupancy command.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions22
Page 23

Accessories

All the accessories in Table 6 include mounting hardware; contact the nearest Johnson Controls® representative to order any of these parts.
Note: Review the technical specifications of the accessories prior to their use in an application.

Repair Information

If the TEC26x7-2 Series Thermostat fails to operate within its specifications, see Table 7 for troubleshooting details and Table 8 for display messaging. For a replacement thermostat, contact the nearest Johnson Controls representative.
Table 6: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor TE-6361M-1
SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TE-636S-1 Strap-Mount Temperature Sensor MS-BACEOL-0 RS485 End-of-Line Terminator
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
1
Duct Mount Air Temperature Sensor
Table 7: Troubleshooting Details1 (Part 1 of 2)
Symptom Probable Causes
Multiple Symptoms
Poor Performance See the probable causes listed in the Multiple Symptoms section earlier in this table.
Thermostat Goes Offline
Excessive bus errors may be occurring. A device may have been added or changed with a duplicate address (may not be the same address as
some devices having problems, and may have happened sometime before the problem was noticed). Wiring errors or wire problems may exist. The baud rate may have been changed on some devices on the network, but not all devices. Max_Master may have been changed incorrectly (may have happened sometime before the problem
was noticed). A download may be in progress. There may be a fault at a device. A repeater may be needed or may be configured incorrectly. There may be a duplicate device object name or instance.
Excessive bus traffic may exist (bus overload). The baud rate may be set too low. There may be too many devices on the network. There may be unaccounted devices on the network (not mapped to the NAE). There may be unusually slow devices on the network or devices that are slow to respond. See the probable causes listed in the Multiple Symptoms section earlier in this table. A power failure or other failure may have occurred at the thermostat. Communication may have been disabled at the thermostat.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 23
Page 24
Table 7: Troubleshooting Details1 (Part 2 of 2)
Symptom Probable Causes
Thermostat Will Not Come Online
1. For common MS/TP troubleshooting information, refer to the MS/TP Commun ications Bus Technical Bulletin (LIT-12011034).
See the probable causes listed in the Multiple Symp toms section earlier in this table. A thermostat may be connected to the wrong bus. A baud rate may be specified in the new thermostat that is incompatible with the running network. No device on the network is configured to us e a specific baud rate (normally the NAE), but all devices
are set to use auto baud. At least one device, typicall y the bus supervisor (NAE), must have an assigned baud rate. Set the baud rate in the bus supervisor and set all other devices to auto baud.
Table 8: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat heating or cooling
action in accordance with the programmable Binary Input (BI1).

Technical Specifications

TEC26x7-2 Series BACnet MS/TP Networked Thermostats with Two Outputs (Part 1 of 2)

Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Relay/Triac Contact Rating
Analog Output Rating
Auxiliary Output Rating
Digital Input s Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended MS/TP Network Guidelines 32 Devices Maximum; 4,000 ft (1,219 m) Maximum Cable Length Temperature
Range
Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Minimum Deadband 2F°/1C° between Heating and Cooling Ambient
Conditions
On/Off and Floating Control
Proportional Control
Triac Output 30 VAC, 1.0 A Maximum, 3.0 A In-Rush
Backlit Display
Heating Control
Cooling Control
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Safety Extra-Low Voltage (SEL V) 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance (Minimum)
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions24
Page 25
TEC26x7-2 Series BACnet MS/TP Networked Thermostats with Two Outputs (Part 2 of 2)
Compliance United States UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 89/336/EEC Australia and
New Zealand
Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
Controls Group
507 E. Michigan Street Milwaukee, WI 53202 © 2006 Johnson Controls, Inc.
TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 25
Published in U.S.A. www.johnsoncontrols.com
Loading...