Johnson Controls TEC2604-4, TEC2604-4+PIR Installation Instructions Manual

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat Controllers
Installation Instructions
TEC2604-4 and TEC2604-4+PIR
Part No. 24-9890-1079, Rev. B
Issued June 22, 2010
Supersedes January 27, 20
10
Applications
The TEC2604-4 and TEC2604-4+PIR Thermostat Controllers are BACnet® Master-Slave/ Token-Passing (MS/TP) networked devices that provide control of single- or multi-stage unitary rooftop units with economizers. The TEC2604-4+PIR Thermostat Controller provides advanced active occupancy logic that automatically switches occupancy from Occupied to Unoccupied as required by the presence of local activity. See the Occupancy Sensor Operation – TEC2604-4+PIR Thermostat Controller section for more information.
The technologically advanced TEC2604-4 and TEC2604-4+PIR Thermostat Controllers feature a Building Automation System (BAS) BACnet MS/TP communication capability that enables remote monitoring and programming for efficient space temperature control.
The TEC2604-4 and TEC2604-4+PIR Thermostat Controllers feature an intuitive user interface with backlit display that makes setup and operation quick and easy. The thermostat controllers also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers. Economizer functions include a 0 to 10 VDC control signal, dry bulb changeover strategy, adjustable minimum position, and mixed air setpoint control.
IMPORTANT: The TEC2604-4 and TEC2604-4+PIR Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat could lead to persona l injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
Location Considerations
Locate the TEC2604-4 or TEC2604-4+PIR Thermost at Controller:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells, and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure that the thermostat controller is located centrally , where occupant movement is frequent.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked
Multi-Stage Economizer Thermostat Controllers Installation Instructions
1
Note: Allow for vertical air circulation to the
Figure 1: Removing the Thermostat Controller
Cover (TEC2604-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the Thermost a t Contro ller PCB
Tabs
F
I
G
TEC2604-4 or TEC2604-4+PIR Thermostat Controller. To install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
3. Carefully pull the locking tabs on the right side of the thermostat controller mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
PCB Locking
2. Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1.
Note: PIR Models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor. Carefully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires.
d
r b
_
t
c
r
c
_ d
t
n
r
p
:
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat controller mounting base.
5. Align the thermostat controller mounting base on the wall and use the base as a template to mark the two mounting hole locations.
6. Position the thermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
2
Controllers Installation Instructions
Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface.
7. Secure the base to the wall surface using two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
8. Swing the PCB back to the right and carefully snap
Figure 3: Securing the Thermostat Controller
Mounting Base to the Wall
F
I
G
:m
n
t
n
g
_
b
s
Figure 4: Removing the Screw Terminal Blocks
!
!
it into the locking tabs on the thermostat controller mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
Wiring
When an existing thermostat controller is replaced, remove and label the wires to identify the terminal functions. When a TEC2604-4 or TEC2604-4+PIR Thermostat Controller is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller.
IMPORTANT: Because some of the objects may not directly correlate to a previous version (TEC26xx-2), you must rediscover all point objects for the TEC2604-4 or TEC2604-4+PIR version. For detailed information on this mapping, refer to the
TEC BACnet® MS/TP Network Series Thermostat Controllers Technical Bulletin (LIT-12011592).
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC2604-4 or TEC2604-4+PIR Thermostat Controller.
s k
c
l
b
_
l
n m
r
t
: G
I F
To wire the thermostat controller:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Figure 5.
Note: If multiple wires are inserted into the screw terminals, make sure to properly twist the wires together prior to inserting them into the screw terminals.
Note: For more details on wiring the MS/TP Communications Bus, refer to the
MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
3. Reinsert the screw terminal blocks onto the PCB.
3
Controllers Installation Instructions
4. Reattach the thermostat contro ller cover to the
Figure 5: Wiring the TEC2604-4 or TEC2604-4+PIR Thermostat Controller
24 VAC
Thermostat Power
Y2 Y1
RC C
If using the same power source install a jumper across RC and RH.
Heat 1
Heat 2
RH W1 W2
Cool 1
Energi zes on a Cal l for Fi r s t -Sta ge Cooling
24 VAC from Equipment Transformer 24 VAC (Co m m on) from Eq uipment Transformer 24 VAC for Heating Stages Energi zes on a Cal l for Fi r s t -Sta ge Heating Energ izes on a Call for Sec o nd-Sta ge Heati ng Auxiliary Output Configur able Digital Input 1 Configur able Digital Input 2 Remote R oom Sens or Sensor C ommon Auxiliary/Outdoor Air Sensor Remote Monitoring Supply Temperature Sensor 0 to 10 VDC Economizer Actuator Output MS/TP Bus
Function
Y1 Y2
G
RC
C RH W1 W2
Aux
DI1 DI2 RS
Scom
OS MS EC
+, -, REF
Terminal
RS
• Lighting
• On/Of f Actuation
• Exhaust Fan
Outdoor
Controller
EC
0 to 10
VDC
24 VAC
Common
Supply Sensor
Cool 2
FIG:wrng
Y2
G
C
RS
Three-Pole Right Top Connector
Eight-Pole Bottom Connector
OS
-
+
EC
G
Fan
Room
mounting base (top side first).
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat controller cover.
Energ izes on a Call for Sec o nd-Sta ge Cooli n g Energizes Fan in Accordance wi th th e Selected Fan Mode
Aux
Aux
DI1
Five-Pole Left Top Con nec tor
Y1
REF
Aux
Aux Cont act (High Side Common)
DI2
Scom
Remote
RC
DI1 DI2
OS
Auxiliary/
RH W1 W2
Scom
+
Supervisory
Remote
Monitoring
MS
REF
-
for the thermostat and heating loads,
Connecting the MS/TP Bus
To connect the MS/TP Bus:
1. Set the MS/TP address of the TEC BACnet MS/TP Network Series Thermostat Controller per the engineering drawings and test for bus voltage, polarity, and isolation prior to wiring the MS/TP Bus. Use the Com addr parameter to set the MS/ TP address for the thermostat controller.
Note: The wiring rules for the MS/TP Bus differ from the wiring rules for the N2 Bus. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Observe the polarity when connecting the bus wires to the thermostat controller.
4
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat Controllers Installation Instructions
Air Sensor
Temperature
Sensor
3. After the bus wires are connected to the first thermostat controller, continue in a daisy-chained fashion to the next thermostat controller.
Note: The bus wiring must be twisted-pair lines. Do not run the bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
The MS/TP Bus requires proper termination and
Figure 6: Front Cover of Thermostat Controller (TEC2604-4+PIR Model Shown)
70.0ºF
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any condition.
Five keys on the thermostat contr oller make ope ra t ion easy and i nt uitive.
indicate system activi ty.
FIG:frnt_v w
PIR motio n de te ct or
saves ene r gy using
standby setpoints.
biasing at each end of a segment (a segment is a physically continuous length of wire). Because the rooftop controller is not equipped with end-of-line termination, a Johnson Controls MS-BACEOL-0 End­of-Line Terminator (see Table 3; ordered separately) or similar device is recommended to provide this end-of­line termination. An end-of-line terminator is required if a supervisory controller is not at the end of the segment. If a supervisory controller is at the end of the segment, then the end-of-line terminator switch on the supervisory controller must be set in the ON position.
The thermostat controller has automatic baud rate detection. Do not exceed the maximum number of devices allowed on a field bus. Be sure that the wiring terminations are set correctly and that all communication wiring is daisy-chained with no taps.
A small green light under the thermostat controller cover (on the left edge when facing the thermostat controller) indicates the communications mode when the thermostat controller is operating.
Setup and Adjustments
The following blink codes may be seen:
Short-Short-Long: Indicates that the baud rate is known and that communication is active.
Short-Short: Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication.
Off: Indicates that there is no power to the thermostat controller or that the MS/TP wiring polarity is reversed.
Long: Indicates that the MS/TP communication daughter board is the wrong type for the main board.
MS/TP Thermostat Controller Mapping
For detailed information on MS/TP Bus objects and thermostat controller mapping, refer to the TEC
BACnet MS/TP Network Series Thermostat Controllers Technical Bulletin (LIT-12011592).
Thermostat Controller User Interface Keys
The TEC2604-4 and TEC2604-4+PIR Thermost at Controller user interface consists of five keys on the front cover (Figure 6). The function of each key is as follows:
•Use the YES key to:
- confirm menu selections and to advance to the next menu item
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
Room Temp
Light-Emitting Diodes (LEDs)
- stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu
Note: When the thermostat controller is left unattended for 45 seconds, the thermostat controller display resumes scrolling.
•Use the NO key to decline a parameter change and to advance to the next menu item.
5
Controllers Installation Instructions
•Use the MENU key to:
- access the Main User Menu or to exit the menu (See the Main User Menu
- access the Installer Configuration Menu or to exit the menu (See the Configuring the
TEC2604-4 or TEC2604-4+PIR Thermostat Controller section.)
•Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment.
section.)
Backlit Liquid Crystal Display (LCD)
The TEC2604-4 and TEC2604-4+PIR Thermostat Controllers include a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unattended for 45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on.
Integrated PIR Sensor – TEC2604-4+PIR Thermostat Controller
The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Unoccupied temperature setpoints without user interaction. This feature generates inc rem en tal energ y savings during scheduled occupied period s while the space is unoccupied.
Programming Overview
Three menus are used to view, program, and configure the TEC2604-4 and TEC2604-4+PIR Thermostat Controllers: the Status Display Menu, the Main User Menu, and the Installer Configuration Menu.
Status Display Menu
The Status Display Menu is displayed during normal thermostat controller operation, and continuously scrolls through the following parameters:
Room Temperature
System Mode
Schedule Status (Occupied/Unoccupied/Override [PIR Models])
Outside Temperature – An outside air temperature sensor must be installed and connected.
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: Press the YES key to temporarily stop this menu from scrolling.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.
Main User Menu
The Main User Menu is used to access and change the basic operating parameters of the thermost at controller . During normal thermostat controller operation, press the MENU key once to access the Main User Menu. This menu is most commonly used by the zone occupant, and includes the following parameters:
Temperature Setpoints
System Mode
Fan Mode
The Main User Menu uses Auto Help. Auto Help is displayed automatically in the main User Menu when there is a pause in programming activity.
Installer Configuration Menu
Use the Installer Configuration Menu to set up the thermostat controller for application-specific operation. To access the menu, press and hold the MENU key for approximately 8 seconds.
Occupancy Sensor Operation – TEC2604-4+PIR Thermostat Controller
A TEC2604-4+PIR Thermostat Controller (or a TEC2604-4 Thermostat Controller equipped with a PIR accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the thermostat controller is programmed to be Unoccupied , the PIR function does not have an effect on the occupancy strategy.
The thermostat controller automatically switches the occupancy level between Occupied and Unoccupied as required, when local movement is sensed. In the Occupied mode, if no movement is detected beyond the Unocc TM parameter setting, the mode changes to Unoccupied. Once movement is detected, the mode changes back to Occupied.
Occupancy sensing is enabled only if a PIR cover is installed. The PIR cover, when installed, is auto detected.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
6
Controllers Installation Instructions
Loading...
+ 11 hidden pages