TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked
Multi-Stage Economizer Thermostat Controllers
Installation Instructions
TEC2604-4 and TEC2604-4+PIR
Part No. 24-9890-1079, Rev. B
Issued June 22, 2010
Supersedes January 27, 20
10
Applications
The TEC2604-4 and TEC2604-4+PIR Thermostat
Controllers are BACnet® Master-Slave/
Token-Passing (MS/TP) networked devices that
provide control of single- or multi-stage unitary rooftop
units with economizers. The TEC2604-4+PIR
Thermostat Controller provides advanced active
occupancy logic that automatically switches occupancy
from Occupied to Unoccupied as required by the
presence of local activity. See the Occupancy Sensor Operation – TEC2604-4+PIR Thermostat Controller
section for more information.
The technologically advanced TEC2604-4 and
TEC2604-4+PIR Thermostat Controllers feature a
Building Automation System (BAS) BACnet MS/TP
communication capability that enables remote
monitoring and programming for efficient space
temperature control.
The TEC2604-4 and TEC2604-4+PIR Thermostat
Controllers feature an intuitive user interface with
backlit display that makes setup and operation quick
and easy. The thermostat controllers also employ a
unique, Proportional-Integral (PI) time-proportioning
algorithm that virtually eliminates temperature offset
associated with traditional, differential-based
thermostat controllers. Economizer functions include a
0 to 10 VDC control signal, dry bulb changeover
strategy, adjustable minimum position, and mixed air
setpoint control.
IMPORTANT: The TEC2604-4 and
TEC2604-4+PIR Thermostat Controllers are
intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat could lead to persona l
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the thermostat.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the TEC2604-4 or TEC2604-4+PIR Thermost at
Controller:
•on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
•away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills, or
stairwells, and from behind doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure
that the thermostat controller is located centrally , where
occupant movement is frequent.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked
Figure 2: Opening the Thermost a t Contro ller PCB
Tabs
F
I
G
TEC2604-4 or TEC2604-4+PIR Thermostat Controller.
To install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the
security screw if it is installed on the bottom of the
thermostat controller cover.
Note: Normally, the security screw is packaged
separately in a plastic bag with the thermostat
controller. Skip this step if the screw is not installed
on the bottom of the cover.
3. Carefully pull the locking tabs on the right side of
the thermostat controller mounting base and
unlock the PCB. Open the PCB to the left as
illustrated in Figure 2.
PCB
Locking
2. Pull the bottom edge of the thermostat controller
cover and open the thermostat controller as
illustrated in Figure 1.
Note: PIR Models have a wiring connection
between the cover and the Printed Circuit Board
(PCB). This connection allows for proper wiring of
the occupancy sensor. Carefully remove the wiring
connection from the PCB by pulling up on the
connector block. Do not attempt to remove the connector block by pulling on the wires.
d
r
b
_
t
c
r
c
_
d
t
n
r
p
:
4. Pull approximately 6 in. (152 mm) of wire from the
wall and insert the wire through the hole in the
thermostat controller mounting base.
5. Align the thermostat controller mounting base on
the wall and use the base as a template to mark
the two mounting hole locations.
6. Position the thermostat controller mounting base
so that the arrow on the base points upward to
indicate the top of the thermostat controller.
Note: If you need to install the thermostat on an
electrical junction box, use 2-1/2 x 4 in.
(63 x 101 mm) square boxes with mud ring covers,
and avoid smaller 1-1/2 x 4 in. (38 x 101 mm)
square or 3 x 2 in. (76 x 51 mm) boxes. This
procedure ensures you have enough space for
cabling and end-of-line devices, if needed.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
2
Controllers Installation Instructions
Note: For surface-mount applications, use
durable mounting hardware such as Molly bolt
anchors that cannot be easily pulled out of the
mounting surface.
7. Secure the base to the wall surface using two
mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting
screws.
Page 3
8. Swing the PCB back to the right and carefully snap
Figure 3: Securing the Thermostat Controller
Mounting Base to the Wall
F
I
G
:m
n
t
n
g
_
b
s
Figure 4: Removing the Screw Terminal Blocks
!
!
it into the locking tabs on the thermostat controller
mounting base.
9. Remove the screw terminal blocks that are
attached to a disposable adhesive. Figure 4
illustrates the locations of the screw terminal
blocks on the thermostat controller.
Wiring
When an existing thermostat controller is replaced,
remove and label the wires to identify the terminal
functions. When a TEC2604-4 or TEC2604-4+PIR
Thermostat Controller is replaced, simply remove the
old screw terminal blocks and reinsert them onto the
PCB of the replacement thermostat controller.
IMPORTANT: Because some of the objects may
not directly correlate to a previous version
(TEC26xx-2), you must rediscover all point objects
for the TEC2604-4 or TEC2604-4+PIR version. For
detailed information on this mapping, refer to the
TEC BACnet® MS/TP Network Series Thermostat
Controllers Technical Bulletin (LIT-12011592).
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the TEC2604-4 or TEC2604-4+PIR Thermostat
Controller.
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
To wire the thermostat controller:
1. Strip the ends of each wire 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
Note: If multiple wires are inserted into the screw
terminals, make sure to properly twist the wires
together prior to inserting them into the screw
terminals.
Note: For more details on wiring the
MS/TP Communications Bus, refer to the
MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the
ambient temperature readings.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
3. Reinsert the screw terminal blocks onto the PCB.
3
Controllers Installation Instructions
Page 4
4. Reattach the thermostat contro ller cover to the
Figure 5: Wiring the TEC2604-4 or TEC2604-4+PIR Thermostat Controller
24 VAC
Thermostat Power
Y2Y1
RCC
If using the same power source
install a jumper across RC and RH.
Heat 1
Heat 2
RHW1W2
Cool 1
Energi zes on a Cal l for Fi r s t -Sta ge Cooling
24 VAC from Equipment Transformer
24 VAC (Co m m on) from Eq uipment Transformer
24 VAC for Heating Stages
Energi zes on a Cal l for Fi r s t -Sta ge Heating
Energ izes on a Call for Sec o nd-Sta ge Heati ng
Auxiliary Output
Configur able Digital Input 1
Configur able Digital Input 2
Remote R oom Sens or
Sensor C ommon
Auxiliary/Outdoor Air Sensor
Remote Monitoring Supply Temperature Sensor
0 to 10 VDC Economizer Actuator Output
MS/TP Bus
Function
Y1
Y2
G
RC
C
RH
W1
W2
Aux
DI1
DI2
RS
Scom
OS
MS
EC
+, -, REF
Terminal
RS
• Lighting
• On/Of f Actuation
• Exhaust Fan
Outdoor
Controller
EC
0 to 10
VDC
24 VAC
Common
Supply
Sensor
Cool 2
FIG:wrng
Y2
G
C
RS
Three-Pole
Right Top
Connector
Eight-Pole Bottom Connector
OS
-
+
EC
G
Fan
Room
mounting base (top side first).
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
controller cover.
Energ izes on a Call for Sec o nd-Sta ge Cooli n g
Energizes Fan in Accordance wi th th e Selected Fan Mode
Aux
Aux
DI1
Five-Pole
Left Top Con nec tor
Y1
REF
Aux
Aux Cont act (High Side Common)
DI2
Scom
Remote
RC
DI1 DI2
OS
Auxiliary/
RH W1 W2
Scom
+
Supervisory
Remote
Monitoring
MS
REF
-
for the thermostat and heating loads,
Connecting the MS/TP Bus
To connect the MS/TP Bus:
1. Set the MS/TP address of the TEC BACnet MS/TP
Network Series Thermostat Controller per the
engineering drawings and test for bus voltage,
polarity, and isolation prior to wiring the MS/TP
Bus. Use the Com addr parameter to set the MS/
TP address for the thermostat controller.
Note: The wiring rules for the MS/TP Bus differ
from the wiring rules for the N2 Bus. For more
details on wiring the MS/TP Communications Bus,
refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
2. Observe the polarity when connecting the bus
wires to the thermostat controller.
3. After the bus wires are connected to the first
thermostat controller, continue in a daisy-chained
fashion to the next thermostat controller.
Note: The bus wiring must be twisted-pair lines.
Do not run the bus wiring in the same conduit as
line voltage wiring (30 VAC or above) or other
wiring that switches power to highly inductive loads
(such as contactors, coils, motors, or generators).
Page 5
The MS/TP Bus requires proper termination and
Figure 6: Front Cover of Thermostat Controller (TEC2604-4+PIR Model Shown)
70.0ºF
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any condition.
Five keys on the thermostat contr oller
make ope ra t ion easy and i nt uitive.
indicate system activi ty.
FIG:frnt_v w
PIR motio n de te ct or
saves ene r gy using
standby setpoints.
biasing at each end of a segment (a segment is a
physically continuous length of wire). Because the
rooftop controller is not equipped with end-of-line
termination, a Johnson Controls MS-BACEOL-0 Endof-Line Terminator (see Table 3; ordered separately) or
similar device is recommended to provide this end-ofline termination. An end-of-line terminator is required if
a supervisory controller is not at the end of the
segment. If a supervisory controller is at the end of the
segment, then the end-of-line terminator switch on the
supervisory controller must be set in the ON position.
The thermostat controller has automatic baud rate
detection. Do not exceed the maximum number of
devices allowed on a field bus. Be sure that the wiring
terminations are set correctly and that all
communication wiring is daisy-chained with no taps.
A small green light under the thermostat controller
cover (on the left edge when facing the thermostat
controller) indicates the communications mode when
the thermostat controller is operating.
Setup and Adjustments
The following blink codes may be seen:
•Short-Short-Long: Indicates that the baud rate is
known and that communication is active.
•Short-Short: Indicates that the thermostat
controller is scanning for the correct baud rate and
that there is no communication.
•Off: Indicates that there is no power to the
thermostat controller or that the MS/TP wiring
polarity is reversed.
•Long: Indicates that the MS/TP communication
daughter board is the wrong type for the main
board.
MS/TP Thermostat Controller Mapping
For detailed information on MS/TP Bus objects and
thermostat controller mapping, refer to the TEC
BACnet MS/TP Network Series Thermostat Controllers
Technical Bulletin (LIT-12011592).
Thermostat Controller User Interface Keys
The TEC2604-4 and TEC2604-4+PIR Thermost at
Controller user interface consists of five keys on the
front cover (Figure 6). The function of each key is as
follows:
•Use the YES key to:
-confirm menu selections and to advance to the
next menu item
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
Room Temp
Light-Emitting Diodes (LEDs)
-stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu
Note: When the thermostat controller is left
unattended for 45 seconds, the thermostat
controller display resumes scrolling.
•Use the NO key to decline a parameter change and
to advance to the next menu item.
5
Controllers Installation Instructions
Page 6
•Use the MENU key to:
-access the Main User Menu or to exit the menu
(See the Main User Menu
-access the Installer Configuration Menu or to
exit the menu (See the Configuring the
TEC2604-4 or TEC2604-4+PIR Thermostat
Controller section.)
•Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
section.)
Backlit Liquid Crystal Display (LCD)
The TEC2604-4 and TEC2604-4+PIR Thermostat
Controllers include a 2-line, 8-character backlit display.
Low-level backlighting is present during normal
operation, and it brightens when any user interface key
is pressed. The backlight returns to low level when the
thermostat controller is left unattended for 45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•The fan LED is on when the fan is on.
•The heat LED is on when heating is on.
•The cool LED is on when cooling is on.
Integrated PIR Sensor –
TEC2604-4+PIR Thermostat Controller
The integrated PIR sensor allows for automatic
switching between fully adjustable Occupied and
Unoccupied temperature setpoints without user
interaction. This feature generates inc rem en tal energ y
savings during scheduled occupied period s while the
space is unoccupied.
Programming Overview
Three menus are used to view, program, and configure
the TEC2604-4 and TEC2604-4+PIR Thermostat
Controllers: the Status Display Menu, the Main User
Menu, and the Installer Configuration Menu.
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation, and continuously
scrolls through the following parameters:
•Room Temperature
•System Mode
•Schedule Status
(Occupied/Unoccupied/Override [PIR Models])
•Outside Temperature – An outside air temperature
sensor must be installed and connected.
•Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: Press the YES key to temporarily stop this
menu from scrolling.
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Main User Menu
The Main User Menu is used to access and change the
basic operating parameters of the thermost at controller .
During normal thermostat controller operation, press
the MENU key once to access the Main User Menu.
This menu is most commonly used by the zone
occupant, and includes the following parameters:
•Temperature Setpoints
•System Mode
•Fan Mode
The Main User Menu uses Auto Help. Auto Help is
displayed automatically in the main User Menu when
there is a pause in programming activity.
Installer Configuration Menu
Use the Installer Configuration Menu to set up the
thermostat controller for application-specific operation.
To access the menu, press and hold the MENU key for
approximately 8 seconds.
A TEC2604-4+PIR Thermostat Controller (or a
TEC2604-4 Thermostat Controller equipped with a PIR
accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the
thermostat controller is programmed to be Unoccupied ,
the PIR function does not have an effect on the
occupancy strategy.
The thermostat controller automatically switches the
occupancy level between Occupied and Unoccupied as
required, when local movement is sensed. In the
Occupied mode, if no movement is detected beyond
the Unocc TM parameter setting, the mode changes to
Unoccupied. Once movement is detected, the mode
changes back to Occupied.
Occupancy sensing is enabled only if a PIR cover is
installed. The PIR cover, when installed, is auto
detected.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
6
Controllers Installation Instructions
Page 7
PIR Diagnostic LEDs
Figure 7: Increasing Room Temperature Setpoints
Occ Heat
= 72°F
Occ Cool
= 75°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
The diagnostic LEDs inside the PIR lens brighten when
movement is detected within the first 30 minutes after
powerup. The LEDs do not light up or brighten after the
initial 30-minute period.
Setpoints
The installer must be certain that the difference
between the Occupied and Unoccupied setpoints can
be recovered within a timely fashion to ensure
occupancy comfort. In addition, the difference between
the two setpoints must be large enough to warrant
maximum energy savings.
These setpoints and Unoccupied time are adjust able to
allow for customization, as dictated by the individual
space requirements. See Figure 7 for an example of
increasing room temperature setpoints.
Configuring the TEC2604-4 or TEC2604-4+PIR
Thermostat Controller
The TEC2604-4 and TEC2604-4+PIR Thermost at
Controllers ship from the factory with default settings
for all configurable parameters. The default settings are
shown in T able 1. To reconfigure the parameters via the
thermostat controller, follow the steps in this section.
1. To access the Installer Configuration Menu, press
and hold the MENU key for approximately
8 seconds.
Note: If the Password parameter is configur ed,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the UP/DOWN arrow
keys to indicate the configured password, then
press the MENU key to proceed through the
Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins,
release and press the NO key to scroll through the
parameters listed in Table 1.
3. When the desired parameter is displayed, use the
YES key to choose the desired selection option.
4. Press the YES key and then the NO key to
continue scrolling through the parameters.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
7
Controllers Installation Instructions
Page 8
Both inputs can be configured to the Selection Options
included in Table 1.
Table 1: Installer Configuration Menu (Part 1 of 5)
Parameter
Description and DefaultSelection Options
Appearing
on Display
PswrdSets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
Com addrMS/TP address at the thermostat
controller; coincides with the
address assigned at the supervisory
controller.
Default: 254DI1Configuration of Digital Input 1.
Default: None
DI2Configuration of Digital Input 2.
Default: None
Range: 0 to 1,000
Range: 004 to 127
(None): No function is associated with an input.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. Tie this input into the air conditioning
unit control card, which provides an alarm if a malfunction occurs.
(Fan lock): A backlit flashing Fan lock alarm is displayed on the
thermostat controller when the input is not energized. This alarm is
used in conjunction with a local airflow sensor connected to the
input. The thermostat controller heating or cooling action is locked
out if no airflow is detected 10 seconds after the fan (Te rminal G) is
energized. Contact open = no airflow; contact closed = airflow
present.
(None): No function is associated with an input.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. Tie this input into the air conditioning
unit control card, which provides an alarm if a malfunction occurs.
(Fan lock): A backlit flashing Fan lock alarm is displayed on the
thermostat controller when the input is not energized. This alarm is
used in conjunction with a local airflow sensor connected to the
input. The thermostat controller heating or cooling action is locked
out if no airflow is detected 10 seconds after the fan (Te rminal G) is
energized. Contact open = no airflow; contact closed = airflow
present.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
8
Controllers Installation Instructions
Page 9
Table 1: Installe r Configuration Menu (Part 2 of 5)
Parameter
Description and DefaultSelection Options
Appearing
on Display
MenuScroGives the option of having the
display continuously scroll the
parameters.
Default: on
LockoutSelectable Lockout Levels for
Pwr del
Frost prProvides a minimum heating
Heat max
Cool min
PbandProportional Band used by the PI
1
2
2
limiting end user keypad interaction.
Default: 0
Sets the delay time period at
thermostat controller powerup, or at
each time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat controller.
Default: off
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
temperature control loop of the
thermostat controller.
Pband is not converted with C or F
scale and is always shown with a
range of 2 to 8.
Default: 2 (2.0F°/1.1C°)
(off): The scroll is inactive.
(on): The scroll is active.
FunctionLevel
Resume/Override
Scheduling
Permanent
T emperature
Setpoints
T emporary
T emperature
Setpoints
System Mode SettingAccessNo AccessNo Access
Fan Mode SettingAccessNo AccessNo AccessRange: 10.0 to 120.0 sec
(on): Enabled
(off): Disabled
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
ValueF Scale Pband/C Scale Pband
22.0F°/1.1C°
33.0F°/1.7C°
44.0F°/2.2C°
55.0F°/2.8C°
66.0F°/3.3C°
77.0F°/3.9C°
88.0F°/4.4C°
Note: The use of a larger proportional band is not to use the
thermostat controller as a discharge air controller device. The use of
a larger proportional band can be used to solve issues for flawed
HVAC design with basic sizing and thermostat controller location
errors that cannot be worked around.
(0)(1)(2)
AccessAccessNo Access
AccessNo AccessNo Access
AccessAccessNo Access
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
9
Controllers Installation Instructions
Page 10
Table 1: Installer Configuration Menu (Part 3 of 5)
Parameter
Description and DefaultSelection Options
Appearing
on Display
AnticyclAnti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Note: Set the anti-short cycle timer
to 0.0 min for equipment that
already has its own anti-short cycle
timer.
Default: 2.0 minHeat cphSets the maximum number of
Heating cycles per hour.
Default: 4.0Cool cphSets the maximum number of
Cooling cycles per hour.
Default: 4.0DeadbandSets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°Fan contDetermines how the fan is activated
in response to a call for heating or
cooling.
Default: on
Fan delFan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
TOccTimeSets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in
the Main User Menu (when the
thermostat controller is in the
Unoccupied mode)
• a temporary heating or cooling
setpoint
default: 3.0 hrs
Cal RSSets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Cal OSSets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
(off): Enables the thermostat controller to activate the fan in
response to a call for cooling only.
(on): Enables the thermostat controller to activate the fan in
response to a call for heating or cooling.
When there is a call for auxiliary heating, the fan is activated by the
equipment fan and limit control.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
10
Controllers Installation Instructions
Page 11
Table 1: Installe r Configuration Menu (Part 4 of 5)
Parameter
Description and DefaultSelection Options
Appearing
on Display
H stageReverts the operation of a two-stage
thermostat controller to a single-
stage thermostat controller when
the second heating stage is not
needed.
Default: 2.0C stageReverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second cooling stage is
not needed.
Default: 2.0
H lockDiscontinues heating operation in
C lockDiscontinues cooling operation in
Unocc TMSets the time delay between the
Aux contEnergizes peripheral devices
Chngstpt
2
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C
moment when the thermostat
controller toggles from the Occupied
mode to the Unoccupied mode after
the last motion is detected by the
occupancy sensor.
Default: 0.5 hours
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
Sets the economizer changeover
strategy, based on the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
When the OA temperature is below
the changeover setpoint, free
cooling is used (economizer
operation). When the OA
temperature is above the setpoint,
mechanical cooling is used
(compressor operation).
Default: 55.0°F/13.0°C
(1.0): One Stage
(2.0): Two Stages
(1.0): One Stage
(2.0): Two Stages
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C°
increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
Range: 0.5 hours to 24.0 hours adjustable in 0.5 hour increments
(n.c.): Contact open = Occupied; contact closed = Unoccupied.
(n.o.): Contact closed = Occupied; contact open = Unoccupied.
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
Range: 14.0°F/-10.0°C to 70.0°F/21.0°C
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
11
Controllers Installation Instructions
Page 12
Table 1: Installer Configuration Menu (Part 5 of 5)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Min posSets the minimum position for the
OA dampers on the economizer.
These dampers are energized to
minimum position when the fan
(Terminal G) is energized and the
thermostat controller is in the
Occupied mode. When the
schedule is in the Unoccupied
mode, the minimum position is 0%.
Default: 0.0%
C mechDetermines whether to allow
mechanical cooling (compressor
operation) if free cooling
(economizer operation) cannot
maintain the cooling setpoint.
Default: off
Mix stpt
MS tempDisplays the mixed air temperature.
2
Establishes the mixed air
temperature when operating in the
economizer mode.
Default: 55.0°F/13.0°C
Requires that an MS be installed
and connected.
Default: N/A
Range: 0.0 to 100.0% equals 0 to 10 VDC output range
(on): Typically applies when the MS is installed before the
mechanical cooling refrigeration coils in the mixing plenum. In this
scenario, mechanical cooling is allowed when free cooling cannot
maintain the cooling setpoint.
(off): Typically applies when the remote Mixed air Sensor (MS) is
installed after the mechanical cooling refrigeration coils. In this
scenario, mechanical cooling will never operate at the same time as
free cooling.
Range: 50.0°F/10.0°C to 90.0°/32.0°C
The mixed air temperature can be used to help service and
troubleshoot the equipment and the economizer operation. The
mixed air temperature is only accessible via the Installer
Configuration Menu.
% OASetting for 0 to 10 VDC
Actuator
Setting for 2 to 10 VDC
Actuator
1.When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
2.When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
Operation
Programming/Operating the TEC2604-4 or
TEC2604-4+PIR Thermostat Controller
Once the thermostat controller is configured via the
Installer Configuration Menu, its operating parameters
can be programmed via the Main User Menu. Access
this menu by pressing the MENU key during normal
thermostat controller operation. The Main User Menu
contains the basic operating features of the thermostat
controller.
The Main User Menu also uses Auto Help, which is
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help,
Enabling Override Schedule
Note: Enabling Override Schedule only appear s when
in the Unoccupied Mode.
The override schedule prompt only appears when the
thermostat controller is in the unoccupied state. This
menu selection gives the user the option of overriding
the unoccupied setpoints with the occupied setpoints
for the amount of time specified under the TOccTime
parameter. See the Configuring the TEC2604-4 or TEC2604-4+PIR Thermostat Controller section.
Note: If one of the digital inp uts is configured to
operate as a remote override contact, this menu is
disabled.
continue with the programming selection. When the
thermostat controller is in the Main User Menu and is
left unattended for 45 seconds, the menu revert s to the
Status Display Menu.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
12
Controllers Installation Instructions
Page 13
T o o verride the unoccupied state while in the Main User
75.0°F
set? Y/N
set? Y/N
75.0°F
set? Y/N
68.0°F
set? Y/N
80.0°F
set? Y/N
62.0°F
C
set? Y/N
Y/N
Menu:
1. Press the NO key to all prompts until the Cancel
ovrd prompt appears. If the thermostat controll er is
in the unoccupied state, this is the first prompt.
2. Press the YES key to enable the temporary
override. The thermostat controller returns to the
Status Display Menu.
When scrolling through the Status Display Menu,
Override now appears for the schedule status
parameter.
Resuming the Programmed Schedule
This menu only appears when the thermost at controller
is in the override mode.
To resume the schedule while in the Main User Menu:
1. Press the NO key to all prompts until the Resume
Schedule prompt appears. If the thermostat
controller is in the override state, this is the first
prompt.
2. Press the YES key to resume the programmed
schedule.
The thermostat controller returns to the Status Display
Menu.
Entering Permanent Temperature Setpoints
The first prompt appearing in the Main User Menu of
the thermostat controller when in the occupied state is
to set the permanent temperature setpoint. Permanent
setpoints are stored in the programmed schedule.
To enter the permanent heating and cooling setpoints
for the Occupied and Unoccupied Modes, follow the
steps in Table 2. When changing the temperatures,
press the keys once to change the temperature in
0.5F°/0.5C° increments; press and hold down the keys
to change the temperature in 5.0F°/5.0C° increments.
Table 2: Entering Permanent Temperature
Setpoints (Part 1 of 2)
Thermostat
Display
RoomTemp
Description
Press the MENU key while in the
Status Display Menu to enter the
Main User Menu.
Table 2: Entering Permanent Temperature
Setpoints (Part 2 of 2)
Thermostat
Description
Display
Press the YES key to change the
Cooling
Cooling
Heating
Heating
Unocc CL
Unocc CL
Unocc HT
Unocc HT
°F/°
occupied cooling setpoint. Press the
NO key to advance to the occupied
heating setpoint menu.
Press the
set the temperature. Press the
key to store the value and advance to
the next menu.
Press the
occupied heating setpoint. Press the
NO key to advance to the unoccupied
cooling setpoint menu.
Press the UP/DOWN arrow keys to
set the temperature. Press the
key to store the value and advance to
the next menu.
Press the
unoccupied cooling setpoint. Press
the NO key to advance to the
unoccupied heating setpoint.
Press the UP/DOWN arrow keys to
set the temperature. Press the
key to store the value and advance to
the next menu.
Press the
unoccupied heating setpoint. Press
the
temperature display units.
Press the
set the temperature. Press the
key to store the value and advance to
the next menu.
Press the
units to °F or °C. Press the
advance to the temperature setpoint
type menu.
UP/DOWN arrow keys to
YES key to change the
YES key to change the
YES key to change the
NO key to advance to the
UP/DOWN arrow keys to
YES key to set the display
NO key to
YES
YES
YES
YES
Press the NO key to all prompts until
Temperat
the temperature setpoint prompt
appears on the display (it may be the
first prompt). Press the YES key to
enter the temperature setting menu.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
Exit?
Press the
Status Display Menu or press the
key to reenter the temperature
setting menu.
YES key to return to the
Controllers Installation Instructions
NO
13
Page 14
Entering Temporary Temperature Setpoints
To temporarily change the setpoint, press the
UP/DOWN arrow keys to change the temporary
setpoint for the current mode of operation.
Note: Whether the thermostat controller is heating or
cooling, the respective setpoint is temporarily adjusted.
To toggle between the temporary heating and cooling
setpoints, press the NO key while changing the
temporary setpoints.
Ending Temporary Temperature Setpoints
The temporary setpoints remain in effect for the
duration set in the TOccTime parameter or until
manually released.
To release the temporary setpoint sooner, while in the
Main User Menu:
1. Press the YES key to the first prompt that appears.
2. If the thermostat controller does not immediately
return to the S tatus Display Menu, press the MENU
key again and press the YES key to exit the Main
User Menu.
The setpoint reverts to the Permanent Temperature
Setpoint.
Selecting the System Mode
The thermostat controller has four system modes:
•Automatic Mode (auto): Automatic changeover
between heating and cooling. This is the default
setting.
•Cooling Mode (cool): Cooling operation only
•Heating Mode (heat): Heating operation only
•Off Mode (off): The thermostat controller is off;
however, when frost protection (Frost pr
parameter) is enabled, the thermostat controller
still calls for heat (if required).
To set the system mode while in the Main User Menu:
1. Press the NO key to all prompts until the system
mode prompt appears on the display. Press the
YES key to select the desired system mode.
Selecting the Fan Mode
The thermostat controller has three fan mode settings:
•On Fan Mode (on): Energizes the fan all the time
for both occupied and unoccupied states, even if
the system mode is set to off.
•Automatic Fan Mode (auto): Energizes the fan
only on a call for heating or cooling, for both
occupied and unoccupied states.
•Smart Fan Mode (smart): Energizes the fan all
the time for occupied states, and only on a call for
heating or cooling in unoccupied states. This is the
default setting.
To select the fan mode while in the Main User Menu:
1. Press the NO key to all prompts until the fan mode
prompt appears on the display. Press the YES key
to set the fan mode.
2. Press the UP/DOWN arrow keys to locate the
desired fan mode. Press the YES key to select the
desired fan mode.
3. Press the YES key to return to the Status Display
Menu or press the NO key to return to the fan
mode selection menu.
T roubleshooting
See Table 4 for display messaging. See Table 5 for
troubleshooting details.
Accessories
All the accessories in Table 3 include mounting
hardware; contact the nearest Johnson Controls®
representative to order any of these parts.
Note: Review the technical specifications of the
optional accessories prior to their use in an application.
Repair Information
If a TEC2604-4 or TEC2604-4+PIR Thermostat
Controller fails to operate within its specifications,
replace the unit. For a replacement thermostat
controller, contact the nearest Johnson Controls
representative.
2. Press the UP/DOWN arrow keys to locate the
desired system mode. Press the YES key to select
the desired system mode.
3. Press the YES key to return to the Status Display
Menu or press the NO key to return to the system
mode selection menu.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
14
Controllers Installation Instructions
Page 15
Table 3: Accessories (Order Separately)
Code NumberDescription
SEN-600-1Remote Indoor Air Temperature Sensor
SEN-600-4Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-6361M-1
TE-6363P-1
TEC-3-PIR
1.Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2.The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2604-4 Thermostat
Controller to provide occupancy sensing capability.
1
1
2
Duct Mount Air Te mperature Sensor
Outside Air Temperature Sensor
Cover with Occupancy Sensor
Table 4: Alarm Messages
DisplayFunction
FrostIndicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6°C (42°F).
Fan LockIndicates that the heating and cooling action are locked out due to a defective fan operation.
ServiceIndicates that there is a service alarm in accordance with a programmable Digital Input.
FilterIndicates that the filter(s) is dirty in accordance with a programmable Digital Input.
Table 5: Troubleshooting Details1 (Part 1 of 2)
SymptomProbable Causes
Multiple
Symptoms
Poor PerformanceSee the probable causes listed previously in the Multiple Symptoms section of this table.
Thermostat Goes
Offline
Excessive bus errors may be occurring.
A device may have been added or changed with a duplicate address (may not be the same address as
some devices having problems, and may have happened sometime before the problem was noticed).
Wiring errors or wire problems may exist.
The baud rate may have been changed on some devices on the network but not all devices.
Max_Master may have been changed incorrectly (may have happened sometime before the problem
was noticed).
A download may be in progress.
There may be a fault at a device.
A repeater may be needed or may be configured incorrectly.
There may be a duplicate device object name or instance.
Excessive bus traffic may exist (bus overload).
The baud rate may be set too low.
There may be too many devices on the network.
There may be unaccounted devices on the network (not mapped to the NAE).
There may be unusually slow devices on the network or devices that are slow to respond.
See the probable causes listed previously in the Multiple Symptoms section of this table.
A power failure or other failure may have occurred at the thermostat controller.
Communication may have been disabled at the thermostat controller.
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
15
Controllers Installation Instructions
Page 16
Table 5: Troubleshooting Details1 (Part 2 of 2)
SymptomProbable Causes
Thermostat Does
Not Come Online
See the probable causes listed previously in the Multiple Symptoms section of this table.
A thermostat controller may be connected to the wrong bus.
A baud rate may be specified in the new thermostat controller that is incompatible wit h the running
network.
No device on the network is configured to use a specific baud rate (normally the NAE), but all devices
are set to use auto baud. At least one device, typically the bus supervisor (NAE), must have an
assigned baud rate. Set the baud rate in the bus supervisor and set all other devices to auto baud.
1.For common MS/TP troubleshooting information, refer to the
(LIT-12011034).
MS/TP Communications Bus Technical Bulletin
Technical Specifications
TEC2604-4 and TEC2604-4+PIR BACnet MS/TP Networked Multi-Stage Economizer Thermostat
Controllers (Part 1 of 2)
Power Requirements19 to 30 VAC, 50/60 Hz, 2 V A (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating (Y1, Y2, G , W1,
W2, and AUX)
Digital InputsVoltage-Free Contacts across Terminal C to Termi nals DI1 and DI2
Analog InputsResistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Wire Size18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Temperature Sensor TypeLocal 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC)
Temperature RangeBacklit
Display
Heating
Control
Cooling
Control
AccuracyT emperature±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband2F°/1C° between Heating and Cooling
Ambient ConditionsOperating32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SEL V
Temperature Coefficient (NTC) Thermistor Sensors
Thermistor Sensor
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat
16
Controllers Installation Instructions
Page 17
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
TEC2604-4 and TEC2604-4+PIR BACnet MS/TP Networked Multi-Stage Economizer Thermostat
Controllers (Part 2 of 2)
ComplianceUnited States UL Listed, File E27734, CCN XAPX,
CanadaUL Listed, File E27734, CCN XAPX7,
EuropeCE Mark – Johnson Controls, Inc., declares that the BACnet Thermostats are
Australia and
New Zealand
BACnet
International
Shipping WeightTEC2604-4 Models: 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpa rt B, Cla ss A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
in compliance with the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC.