Johnson Controls TEC22x7-4 Series Catalog Page

TEC22x7-4 Series
TEC22x7-4 Series Thermostat Controller
Code No. LIT-1900633 Issued February 8, 2010
LONW
® Network Thermostat Controllers with Two Outputs
Description
The TEC22x7-4 Series Thermostat Controllers are L that provide control of local hydronic reheat valves, pressure dependent Variable Air Volume (VAV) equipment with or without local reheat, or other zoning equipment using an on/ off, floating, or proportional 0 to 10 VDC control input. The technologically advanced TEC22x7-4 Series Thermostat Controllers feature a Building Automation System (BAS)
ONWORKS network communication capability
L that enables remote monitoring and programming for efficient space temperature control.
The TEC22x7-4 Series Thermostat Controllers feature an intuitive User Interface (UI) with backlit display that makes setup and operation quick and easy. The thermostat controllers also employ a unique, Proportional­Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers.
Refer to the TEC22x7-4 Series L
Network Thermostat Controllers with Two Outputs Product Bulletin (LIT-12011608) for
important product application information.
ONWORKS® network devices
ONWORKS
Features
•LONWORKS network communication — provides compatibility with a proven communication network; L network is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers
• password protection option — protects against unwanted thermostat controller tampering
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English plain text messages with constant backlight that brightens during user interaction
• on/off, floating, or proportional 0 to 10 VDC control — offers additional application flexibility by providing more advanced control signals
• override interface key — allows easy access for temporarily overriding the unoccupied mode
• simplified setpoint adjustment — enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys
• two configurable binary inputs — provide additional inputs for advanced functions such as remote night setback, service or filter alarms, motion detector, and window status
• over 20 configurable parameters — enable the thermostat to adapt to any application, allowing installer parameter access without opening the thermostat cover
• optional discharge air sensor — monitors unit efficiency
ONWORKS
Repair Information
If a TEC22x7-4 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.
Selection Chart
Code Number Control Outputs
TEC2227-4 Two On/Off or Floating TEC2247-4 Two Proportional 0 to 10 VDC
Accessories
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupa ncy Override and LED
TEC-7-PIR TE-6361M-1
TE-636S-1 Strap-Mount Temperature Sensor
1. The TEC-7-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC22x7-4 Thermostat Controller to provide occupancy sensing
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
1
capability. Product Bulletin (LIT-216320) for more details.
Zone Controller Cover with Occupancy Sensor
2
Duct Mount Air Temperature Sensor
www.johnsoncontrols.com
1 of 2
TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs
Thermostat Dimensions, in. (mm)
70.0ºF
Room Temp
(125)
3-3/8
(86)
(29)
FIG:dmnsns_22x7
(Continued)
4-15/16
1-1/8
Technical Specifications
TEC22x7-4 Series LONWORKS Network Thermostat Controllers with Two Outputs
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or Safet yExtra-Low Voltage (SELV) Relay/Triac Contact
Rating Analog Output
Rating Auxiliary Output
Rating Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm JohnsonControls Type II Negative Temperature Coefficient (NTC)
Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Wire Size Unshielded twisted pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended
ONWORKS Network Standard 64 Devices Maximum without a Repeater , 127 Devices Maximum with a Repeat er; 6,250ft (1,905m) Maximum (Bus
L
Thermostat Controller Measurement Range
Temperature Sensor Type Local 10k ohm NTC Thermistor Resolution ±0.2F°/±0.1C° Control Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Control Range Heating 40.0°F/4.5°C to 90.0°F/32.0°C in 0.5° Increments
Default Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
On/Off and Floating Control
Proportional Control
Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Cooling 54.0°F/12.0°C to 100.0°F/38.0°C in 0.5° Increments
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 2004/108/EC Australia and New
Zealand
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
0 to 10 VDC into 2k ohm Resistance (Minimum)
Thermistor Sensors
Topology)
-40.0°F/-40.0°C to 122.0°F/50.0°C
ONMARK® Certification 3.4 (Pending)
L FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, TemperatureIndicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
2 of 2
www.johnsoncontrols.com