Johnson Controls TEC2245-4 Catalog Page

TEC2245-4
TEC2245-4 LONWORKS Network
Thermostat Controller
Code No. LIT-1900634 Issued February 8, 2010
LONW
® Network Thermostat Controller with Single Proportional
Output and One-Speed Fan Control
Description
The TEC2245-4 Thermostat Controller is a L
ONWORKS® network device that provides
control of two-pipe fan coils, cabinet unit heaters, or other equipment using a proportional 0 to 10 VDC control input and one-speed fan control. The technologically advanced TEC2245-4 Thermostat Controller features a Building Automation System (BAS)
ONWORKS communication capability that
L enables remote monitoring and programming for efficient space temperature control.
The TEC2245-4 Thermostat Controller features an intuitive User Interface (UI) with backlit display that makes setup and operation quick and easy. The thermostat controller also employs a unique, Proportional-Integral (PI) control algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers.
Refer to the TEC2245-4 L
Thermostat with Single Proportional Output and One-Speed Fan Control Product Bulletin (LIT-12011609) for important product
application information.
ONWORKS® Network
Features
•LONWORKS network communication — provides compatibility with a proven communication network; L network is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers
ONWORKS
• password protection option — protects against unwanted thermostat controller tampering
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, plain text messages with constant backlight that brightens during user interaction
• proportional 0 to 10 VDC control — offers additional application flexibility by providing more advanced control signals
• single/dual setpoint adjustment — enables user setpoint options to accommodate application
• override interface key — allows easy access for temporarily overriding the unoccupied mode
• simplified setpoint adjustment — enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys
• two configurable binary inputs — provide additional inputs for advanced functions such as remote night setback, service or filter alarms, motion detector, and window status
• over 20 configurable parameters — enable the thermostat to adapt to any application, allowing installer parameter access without opening the thermostat cover
• optional discharge air sensor — monitors unit efficiency
Repair Information
If the TEC2245-4 Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls® representative.
Selection Chart
Thermostat Controller Models
Code Number Description Applications
TEC2245-4 LONWORKS network, Two-Pipe, Proportional 0 to 10 VDC Control
Accessories
Code Number Description
TEC-6-PIR TE-636M-1 SEN-600-4
TE-636S-1 Strap-Mount Temperature Sensor
1. The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2245-4 Thermostat Controller to provide occupancy sensing
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product
3. Only the occupancy override function can be accomplished using the SEN-600-4 with the TEC2245-4.
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
1
2
3
capability. Bulletin (LIT-216320) for more details.
Output, and One-Speed FanControl Thermostat Controller
Cover with Occupancy Sensor Duct Mount Air Temperature Sensor Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1 of 2
Control of Two-Pipe Fan Coils, Cabinet Unit Heater s, or Other Equipment Using a Proportional 0 to 10 VDC Control Input and One-Speed Fan Control
www.johnsoncontrols.com
TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional
Thermostat Dimensions, in. (mm)
70.0ºF
Room Temp
(125)
3-3/8
(86)
(29)
FIG:dmnsns_2245
Output and One-Speed Fan Control (Continued)
4-15/16
1-1/8
Technical Specifications
TEC2245-4 LONWORKS Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or SafetyExtra-Low Voltage (SELV) Analog Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum) Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Mini mum, 3.0 A In-Rush Auxiliary Output
Rating Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type I I Negat ive Temperature Coefficient (NTC)
Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended
ONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with a Repeater;
L
Thermostat Controller Measurement Range
Sensor Type Local 10k ohm NTC Thermistor Resolution ±0.2F°/±0.1C° Control Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Temperature Range Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Default Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Mini mum, 3.0 A In-Rush
Thermistor Sensors
6,250 ft (1,905 m) Maximum (Bus Topology)
-40.0°F/-40.0°C to 122.0°F/50.0°C
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C in 0.5° Increments Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C in 0.5° Increments
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 2004/108/EC Australia and New
Zealand
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
ONMARK® Certification 3.4
L
Under CAN/CSA C22.2 No. 24, TemperatureIndicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
2 of 2
www.johnsoncontrols.com
Loading...