Johnson Controls TEC2216H-4, TEC2226H-4, TEC2216H-4+PIR, TEC2226-4, TEC2226H-4+PIR Installation Instructions Manual

...
Page 1
TEC22x6(H)-4 and TEC22x6H-4+PIR Series
LONWORKS
® Network Thermostat Controllers with Dehumidification Cap ability , Fan Control, and Occupancy Sensing Capability
Installation Instructions
Part No. 24-9890-1249, Rev. —
Issued February 8, 2010
Applications
The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers are L devices that provide control of two- or four-pipe fan coils, cabinet unit heaters, or other equipment using on/off, floating, or proportional 0 to 10 VDC control input, dehumidification capability, and up to three speeds of fan control. The TEC22x6H-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These devices maximize up to 30% energy savings in high-energy usage light commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints. See the Occupancy Sensor Operation – TEC22x6H-4+PIR Series Thermostat Controllers section for more information.
The technologically advanced TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers feature a Building Automation System (BAS) L
ONWORKS network communication capability that
enables remote monitoring and programming for efficient space temperature control. Specific models are available to accommodate commercial and hospitality applications.
The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers feature an intuitive User Interface (UI) with backlit display that makes se tup and operation quick and easy . Th e thermostat s also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostats.
IMPORTANT: The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat.
ONWORKS® network
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
Location Considerations
Locate the TEC22x6(H)-4 or TEC22x6H-4+PIR Series Thermostat Controller:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated Passive Infrared (PIR) models, make sure the thermostat controller is located centrally, where occupant movement is frequent.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat
Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing
1
Capability Installation Instructions
Page 2
Note: Allow for vertical air circulation to the
Figure 1: Removing the Thermostat Controller
Cover (TEC22x6H-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the Thermostat PCB
Tabs
TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers.
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the security screw on the bottom of the thermostat cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
2. Pull the bottom edge of the thermostat cover and open the thermostat as illustrated in Figure 1.
Note: PIR models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor. Carefully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the
connector block by pulling on the wires
PCB Locking
FIG:prnctbd
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat mounting base.
5. Align the thermostat mounting base on the wall and use the base as a template to mark the two mounting hole locations.
6. Position the thermostat mounting base so that the arrow on the base points upward to in dicate the top of the thermostat.
3. Carefully pull the locking tabs on the right side of the thermostat mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) or 3 x 2 in. (76 x 51 mm) square boxes. This procedure ensures that you have enough space for cabling and end-of-line devices, if needed.
Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface.
7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
2
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 3
!
Figure 3: Securing the Thermostat
Mounting Base to the Wall
FI
Figure 4: Removing the Screw Terminal Blocks
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional
G:mtgbs
regulations. Do not exceed the electrical ratings of the TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers.
To wire the thermostat:
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
s k
c
l
b
_
l
n m
r
t
: G
I F
Wiring
When an existing thermostat is replaced, remove and label the wires to identify the terminal functions. When a TEC22x6(H)-4 or TEC22x6H-4+PIR Series Thermostat is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat.
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1, and Figure 6 through Figure 10.
Note: For more details on wiring the L network, refer to the L
ONWORKS Network Layout
ONWORKS
Technical Bulletin (LIT-1162150).
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the L
ONWORKS communication wires to
the LON terminal block. See Figure 5. Note: If inserting multiple wires into t he termin als,
be sure to properly twist wires together prior to inserting them in the terminal connectors.
5. Reattach the thermostat cover to the mounting base (top side first).
6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat cover.
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical connections to avoid electric shock.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
3
Page 4
Figure 5: Terminal Blocks
1
Fan-H
Hot
Com
BO5 Aux
BO5 Aux
BO3
BO2
BO1 AO1
BI1
Scom
BI2 UI3
LON
LON
F
I
G
:
t
r
m
_
b
l
k
s
_
2
2
x
6
RS
BO4 AO2
Five-Pole Top Left Connector
Eight-Pole Bottom Connector
Fan-M
Fan-L
24 V~
Three-Pole
T op Right Connector
24 V~
Table 1: Terminal Identification (See Figure 5.)
Terminal Number
TEC2216-4, TEC2216H-4, TEC2216H-4+PIR (On/Off Control)
Terminal Label Function
TEC2226-4, TEC2226H-4, TEC2226H-4+PIR, TEC2236-4, TEC2236H-4, TEC2236H-4+PIR (On/Off or Floating Control)
1 Fan-H Fan-H Fan-H Fan On – High 2 Fan-M Fan-M Fan-M Fan On – Medium 3 Fan-L Fan-L Fan-L Fan On – Low 4 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 VAC from Transformer 5 24 V~ Com 24 V~ Com 24 V~ Com 24 VAC (Common) from Transformer 6 BO5 Aux BO5 Aux BO5 Aux Aux BO (Auxiliary Output) 7 BO5 Aux BO5 Aux BO5 Aux Aux BO (Auxiliary Output) 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Closed Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Closed Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 RS RS RS Remote Sensor 14 Scom Scom Scom Sensor Common 15 BI2 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 UI3 Configurable Universal Input 3 Blank L
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
4
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
23
910
4
5678
12
11
13 14
15 16
TEC2246-4, TEC2246H-4, TEC2246H-4+PIR, TEC2256-4, TEC2256H-4, TEC2256H-4+PIR (Proportional Control)
ONWORKS Bus
Page 5
Figure 6: Wiring the TEC22x6(H)-4 or TEC22x6H-4+PIR Series Thermostat Controller (See Table 1.)
BI2 UI3
BI1
Scom
Remote Inputs
Contact
• COC/NH Normally Heat
= Cold Water
• COC/NC Normally Cool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
Controller
the terminals.
FIG:22x6wir
LW
Network Wires
ON ORKS
LW
Network
Terminal Block
ON ORKS
Power and Fan
BO5
Aux
BO5
Aux
Aux
24 VAC
Thermostat
Power
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Same 24 VAC Power Source
for Auxiliary Output (24 VAC Maximum)
• Reheat
• Lighting
• Exhaus t Fan
Power
Com
Hot
• Reheat
• Lighting
• On/Of f Actua ti on
• Exhaus t Fan
Aux Contact (Isolate d C o m mon)
24 V~
Power and Fan
24 V~
Fan
-L
Fan
-M
Aux Contact (Isolate d C o m mon)
• On/Of f Actua ti on
Fan
-H
BO5
Aux
BO5
Aux
Aux
SS (Supply Sensor) COS (Ch ange Over Se nsor)
- OR -
Voltage-Free
Closed Contact
Closed Contact
24 VAC
Thermostat
Supervisory
Separate 24 VAC Power Source
for Auxiliary Output (24 VAC Maximum)
LON
LON
Twist wires together before i nserting them into
Thermostat-to-Network Connection
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
5
Page 6
Figure 7: Wiring TEC2216(H)-4 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Four-Pipe Applications
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 8: Wiring TEC2226(H)-4 and TEC2236(H)-4 Thermostat Controllers for On/Off Control
Two -Pip e Applicat ions
Four-Pipe Applications
FIG:TEC2226( H)-4onof f
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 9: Wiring TEC2226(H)-4 and TEC2236(H)-4 Thermostat Controllers for Floating Control
Four-Pipe Applications
FIG:TEC2226(H)-4floating
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 10: Wiring TEC2246(H)-4 and TEC2256(H)-4 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
FIG:TEC2 246(H)-4 prop
Heating/Cooling
Valve
Com
Hot
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
24 V~
24 V~
FIG:TEC2216 (H)-4ono ff
24 V~
Two -Pip e Applic ations
24 V~
AO2
BO4
24 V~
24 V~
24 V~
BO2 BO3
AO1
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
6
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 7
Connecting the LONWORKS Network
Figure 11: Fro nt Cover of Thermostat Controller (TEC22x6H-4+PIR Model Shown)
70.0ºF
FIG:TEC22x6(H)PIR_wrlss_
Status LED beneath cover
indicates network sta tu s.
Five keys on the thermostat controller make operation easy and intuitive.
Backl i t, plain text
Liquid Crystal Display (LCD)
is easy to rea d in any condition.
Light-Emitting Diodes (LEDs) indicate system activit y.
PIR mot io n detector
saves ener gy using
standby se tp oi nt s.
The wiring rules for the LONWORKS network differ from the wiring rules for the Metasys® N2 Bus and the BACnet® Master-Slave/Token-Passing (MS/TP) Bus. For more details on wiring the L refer to the L
ONWORKS Network Layout Technical
ONWORKS network,
Bulletin (LIT-1162150). To connect the thermostat to the L
1. Connect the L L
ONWORKS network terminal block on the
ONWORKS network wires to the
ONWORKS network:
thermostat (Figure 5 and Figure 6). Note: There is no polarity when connecting the
L
ONWORKS network wires to the thermostat;
however, we recommend keeping the polarity consistent throughout the network.
Setup and Adjustments
2. After the L
ONWORKS network wires are connected
to the first thermostat, continue in a daisy-chained fashion to the next device.
Note: The L
ONWORKS network wiring must be
twisted-pair lines.
Do not run the L
ONWORKS network wiring in the same
conduit as line voltage wiring (higher than 30 VAC) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
The L
ONWORKS network requires proper termination
and biasing at the end of a segment (a segment is a physically continuous length of wire). The thermostat is not equipped with the ability to provide this termination; therefore, it cannot be located at the physical end of a L
ONWORKS network segment unless a terminator is
attached. Refer to L
ONWORKS Network Layout
Technical Bulletin (LIT-1162150) for end-of-line
solutions.
Thermostat User Interface Keys
The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat UI consists of five keys on the front cover (Figure 11). The function of each key is as follows:
MODE key toggles among the system modes available, as defined by selecting the appr op ria te operation sequence in the Installer Configuration Menu (Off, Heat, Cool, Auto).
FAN key toggles am on g th e fan mo de s available, as defined by selecting the appropriate fan menu options defined in the Installer Configuration Menu (Low, Med, High, Auto).
Room Temp
frntvw
OVERRIDE key (commercial models) overrides the unoccupied mode to occupied at the local user interface for the specified TOccT ime. (TOccTime is defined by selecting the appropriate time period in the Installation Configuration Menu.) If one of the binary inputs is configured to operate as a remote override contact, this OVERRIDE function is disabled. The OVERRIDE key also allows access to the Installer Configuration Menu. See the
Configuring the TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers
section.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
7
Page 8
°C/°F key (hospitality models) changes the temperature scale to either Celsius or Fahrenheit and allows access to the Installer Configuration Menu. See the Configuring the TEC22x6(H)-4 and
TEC22x6H-4+PIR Series Thermostat Controllers
section.
System Mode
Occupancy Status (Occupied/Unoccupied/Override)
Applicable Alarms (The backlight lights up as an alarm condition is displayed.)
Note: For hospitality models, binary inputs can override the unoccupied mode to occupied mode.
UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment.
Backlit Liquid Crystal Display (LCD)
The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostats include a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat is left unattended for 45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on.
Integrated PIR Sensor – TEC22x6H-4+PIR Series Thermostat Controllers
The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Stand-By temperature setpoints without user interaction. This feature generates inc rem en tal energ y savings during scheduled occupied period s while the space is unoccupied.
Status Display Menu
The Status Display Menu is displayed during normal thermostat operation. This menu continuously scrolls through the following parameters:
Room Temperature (All Models) and Humidity (TEC2236-4, TEC2236H-4, TEC2236H-4+PIR, TEC2256-4, TEC2256H-4, and TEC2256H-4+PIR Models)
Note: For models with dehumidification capability, the default setting is no humidity reading on the display (%RH disp parameter is set to off.) The %RH disp parameter must be set to on to display the current humidity reading.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.
Status LED
The status LED shows the operational status of the thermostat. The S tatus LED is a small green light un der the thermostat cover (under the L
ONWORKS daughter
board on the left edge when facing the thermostat).
Table 2: Status LED Explanation
Status LED
Explanation
Condition
Continuously OnThe thermostat does not have an
application loaded in its memory.
Flashing at a
0.5 Hz rate
Continuously Off
The thermostat has an application loaded in its memory but is not configured. Use a LONWORKS network management tool to bind the thermostat to a LONWORKS network.
The thermostat has an application loaded in its memory and is bound to a L
ONWORKS network.
Dehumidification Operation – TEC2236(H)-4 and TEC2256(H)-4 Models Only)
Upon detection of space humidity above the adjust able humidity setpoint as sensed by the internal humidity sensor, dehumidification activates.
Note: Dehumidi fication operates only in Cooling mode. Dehumidification does not operate in Off or Heating system mode.
Note: A central network command can globally lock out dehumidification to all thermostats.
If the room temperature resides in the deadband between the Cooling and Heating Setpoint:
the thermostat forces the fan to low speed
the chilled water valve opens to the specified maximum value set by CoolMax
the thermostat stages heating to maintain space temperature at the cooling setpoint as sensed by the thermostat
If the room temperature falls below the curr en t he at ing setpoint, the thermostat disables dehumidification.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
8
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 9
If the thermostat is in cooling demand:
Figure 12: Increasing Room Temperature Setpoints
St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
the chilled water valve opens to 100%
the thermostat stages heating to maintain space temperature at the cooling setpoint as sensed by the thermostat
If the thermostat is in cooling demand and the room temperature rises 2°F above the cooling setpoint, the thermostat automatically disables dehumidification. If the thermostat is in cooling demand and the room temperature falls below the current heating setpoint, the thermostat disables dehumidification.
Occupancy Sensor Operation – TEC22x6H-4+PIR Series Thermostat Controllers
A TEC22x6H-4+PIR Series Thermostat Controller (or a TEC22x6(H)-4 Series Thermostat Controller equipped with a PIR accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the thermostat controller is programmed to be Unoccupied, the PIR function does not have an effect on the occupancy strategy.
The thermostat controller automatically switches occupancy levels from Occupied to Stand-By and Unoccupied as required, when local movement is sensed.
Occupancy sensing is enabled only if a PIR cover is installed on the thermostat controller (PIR models) or if a remote input is configured as a remote PIR sensor (MotionNO or MotionNC).
PIR Warm-Up Period
When a PIR cover is used and a thermostat controller is powered up, there is a 1-minute warm-up period before any local movement can be detected and acknowledged by the PIR sensing device. The local status LEDs for the PIR function are not active, and the sensor is in Stand-By mode for the 1-minute period. The PIR functionality and local movement status LEDs are activated after the 1-minute warm-up period has elapsed after the initial powering of the thermostat controller. If movement is present, the mode changes to Occupied.
PIR Diagnostic LEDs
The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period.
Setpoints
The Stand-By setpoints are under the same limitations and restrictions as the Occupied and Unoccupied setpoints. Stand-By setpoints reside between the corresponding Occupied and Unoccupie d se tp oint values.
The installer must be certain that the difference between the Stand-By and Occupied values can be recovered within a timely fashion to ensure occupancy comfort. In addition, the difference between the two values must be large enough to warrant maximum energy savings.
Hotel and lodging applications can benefit from the addition of an entry door switch wired to one of the binary inputs of the thermostat controller. When a door contact is used and configured, the S ta nd-By timer and its configuration are no longer active or used. The occupancy toggle between Occupied and Stand-By is then dictated by both the door contact an d the PIR sensing device used. If movements are detected by the PIR sensor and the door is closed, the room is considered occupied. The thermostat controller switches back to St and-By mode only if the door switch toggles open/closed. Motion is ignored when the door switch indicates an open door.
PIR occupancy functionality is dictated by both the Stand-By timer and Unoccupied timer configuration value and movements present in the area.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
9
Page 10
Unoccupied Timer Disable
Stand-By
Unoccupied
Stand-By
= 2 Hours
= 6 Hours
Time
Last Mov ement Detec t ed
by PIR Devi ce
Stand-By Time Elapsed = Stand-By Mode
Stand-By
= 2 Hrs
Unoccu pied Time
= 6 Hour s
Last Mov ement Dete ct ed
by PIR Devi ce
Stand-By Time Elapsed = Stand-By Mode
= Unoccu pied Mode
FIG:unocc6sb2
First Movement
Detected
by PIR Device
First Movement
Detected by PIR Device
Figure 13: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
Stand-By
Unoccupied
Stand-By
= 2 Hrs
= 0 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed = Stand-By Mode
Unoccupied Time
= 0 Hours
Last Movement Det ected
by PIR Device
Stand-By Time Elapsed = Stand-By Mode
FIG:unocc0sb2
First Movement Detected
by PIR Device
Stand-By
= 2 Hrs
First Movement Detected
by PIR Device
Figure 14: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours
It might be preferable for the local area to stay out of Unoccupied mode and always stay at the Stand-By occupancy level when no activity is present. In instances when areas always need to be in Stand-By mode, ready to respond to demand at any given point in time, we recommend disabling the Unoccupied timer . When the local PIR occupancy routine is running at the thermostat controller, the zone drifts into Unoccupied mode when the Unoccupied timer is set above its factory default value of 0.0 hours.
For more information on occupancy sensor operation, refer to the TEC2x45-4, TEC2xx6(H)-4,
TEC2xx6H-4+PIR, and TEC2xx7-4 Series Thermostat Controllers Application Note (LIT-12011594).
Occupied
Unoccupied Time
Time
Occupied
Unoccupied Ti m e Elapsed
Unoccupied Time
Time
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
10
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 11
Configuring the TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers
The TEC22x6(H)-4 and TEC22x6H-4+PIR Series Thermostat Controllers are shipped with default settings for all configurable parameters. The default settings are shown in Table 5. To reconfigure the parameters via the thermostat, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the center key for approximately 8 seconds.
Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MODE key to proceed through the Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins, press and release the center key to scroll through the parameters listed in Table 5.
3. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option.
4. Press and release the center key to continue scrolling through the parameters.
Note: Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed in Table 5.
When the thermostat is in the Installer Configuration Menu and left unattended for approximate ly 8 seconds, the thermostat reverts to the Status Display Menu.
For additional information on commissioning and configuring thermostat controllers, adding the rm os tat controllers to a Network Automation Engine (NAE), thermostat controller mapping, and remote thermostat controller commanding, refer to TEC22x6(H)-4 and
TEC22x6H-4+PIR L Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Technical Bulletin (LIT-12011610).
ONWORKS® Network Thermostat
Configuring the Thermostat Controller’s Neuron® Identification
Press and hold the UP/DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat controller’s Neuron Identification on the L
ONWORKS network.
If the cover is removed, you can see a green LED under the LON board flash when the thermostat broadcasts the Neuron ID. The Neuron ID is on a label on the Echelon® chip.
You cannot send the Neuron ID while in the Installer Configuration menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water switching or supply air temperature monitoring at the thermostat.
Each input can be configured to the Selection Options included in Table 5.
Configuring the Sequence of Operation (SeqOpera)
Choose the appropriate sequence of operation. The modes presented are user-dependent on the sequen ce of operation selected. For 2-pipe applications using a COS, choose 0 = Cooling only. Changeover occurs between Cooling on ly and Heat ing only. For example sequences of operation, see Figure 15 through Figure 20.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
11
Page 12
Table 3: Control Sequences for 2-Pipe Applications
Sequence Control
Curves
On/Off Control
0 = Cooling Only See Figure 15. #10 NO Cool
1 = Heating Only See Figure 16. #10 NO Heat
2 = Cooling with Reheat See Figure 17. #6 and #7 Reheat
3 = Heating with Reheat See Figure 18. #6 and #7 Reheat
#11 NC Cool
#11 NC Heat
#10 NO Cool #11 NC Cool
#10 NO Heat #11 NC Heat
Table 4: Control Sequences for 4-Pipe Applications
Sequence Control
Curves
On/Off Control
0 = Cooling Only See Figure 15. #10 NO Cool
#11 NC Cool
1 = Heating Only See Figure 16. #10 NO Heat
2 = Cooling with Reheat
3 = Heating with Reheat
4 = Cooling/Heating Four Pipes
5 = Cooling/Heating with Reheat, Four Pipes
See Figure 17. #6 and #7 Reheat
See Figure 18. #6 and #7 Reheat
See Figure 19. #8 NO Cool
See Figure 20. #6 and #7 Reheat
#11 NC Heat
#10 NO Cool #11 NC Cool
#10 NO Heat #11 NC Heat
#9 NC Cool #10 NO Heat #11 NC Heat
#8 NO Cool #9 NC Cool #10 NO Heat #11 NC Heat
Terminals Used (See Table 1.)
Floating Control
#10 Open Cool #11 Close Cool
#10 Open Heat #11 Close Heat
#6 and #7 Reheat #10 Open Cool #11 Close Cool
#6 and #7 Reheat #10 Open Heat #11 Close Heat
Proportional Control
#10 Proportional Cool
#10 Proportional Heat
#6 and #7 Reheat #10 Proportional Cool
#6 and #7 Reheat #10 Proportional Heat
Terminals Used (See Figure 6.)
Floating Control
#10 Open Cool #11 Close Cool
#10 Open Heat #11 Close Heat
#6 and #7 Reheat #10 Open Cool #11 Close Cool
#6 and #7 Reheat #10 Open Heat #11 Close Heat
#8 Open Cool #9 Close Cool #10 Open Heat #11 Close Heat
#6 and #7 Reheat #8 Open Cool #9 Close Cool #10 Open Heat #11 Close Heat
Proportional Control
#10 Proportional Cool
#9 Proportional Heat
#6 and #7 Reheat #10 Proportional Cool
#6 and #7 Reheat #9 Proportional Heat
#9 Proportional Heat #10 Proportional Cool
#6 and #7 Reheat #9 Proportional Heat #10 Proportional Cool
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
12
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 13
Figure 15: Cooling Only,
Two- or Four-Pipe Applications
oo
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
c
l
_
Figure 16: Heating Only,
Two- or Four-Pipe Applications
oo
Device Closed
Heating Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
_
Figure 17: Cooling with Reheat,
Two- or Four-Pipe Applications
Temper at ur e Increase
(Increments of 1 F/0.5 C)
oo
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
_
r
h
t
Deadband
Reheat
or Propor t ional
Outputs
Heating Output
Cooling output
Off
Off
On
On
Figure 18: Heating with Reheat, Two- or Four-Pipe Applications
oo
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 19: Heating/Cooling,
Four-Pipe Applications
Heating Setpoint
Closed
Device
Opened
FIG:htng_clng
Deadband
or Propor t ional
Outputs
Heating Output Cooling Output
Device Closed
Device
Opened
Temperature Increa se
(Increments of 1 F/0.5 C)
n
o
On
t
h
r _
t h
: G
I F
100%
0%
Temperature Increase
(Increments of 1 F/0.5 C)
n
o
On/Off, Floating,
Temperature Increase
(Increments of 1 F/0.5 C)
On/Off, Floating,
Device
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Cooling Setpoint
Device
Temperature Increase
(Increm ents of 1F°/0.5C°)
13
Page 14
Figure 20: Heating/Cooling with Reheat, Four-Pipe Applications
Temperature Increase
(Increments of 1 F/0.5 C)
oo
Heating Setpoint
Device
Closed
Device Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
h
t
_
r
h
t
_
4
p
p
Deadband
Reheat Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put
Cooling output
Off
Off
On
On
Figure 21: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature Deviation from Setpoint, F°
2.0F°/1. 0C° to
5.0F°/2.5C° Deadband
100%
0%
2.5
2.5
2.0 2.0
1.5
1.50.5 0.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Setpoint
High
FIG:fn_oprtn
Fan
Speed
The fan is of f between the
heating and
if the
parameter is
set to .
Auto Fan
AS AD
s
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer Configuration menu to set the available Fan Mode options. Use the FAN key to select the desired Fan Mode option.
Heating
cooling se t points
When selection option (2): Low-Med-High-Auto is chosen in the Fan Menu parameter, the fan operates as shown in Figure 21. When selection option (3): Low-High-Auto is chosen in the Fan Menu parameter, the fan operates at only the low and high settings, ignoring the medium setting (Figure 21). This operation applies to the occupied mode when the fan is set to Auto.
Cooling Setpoint
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
14
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 15
Installer Configuration Menu
Table 5: Installer Configuration Menu (Part 1 of 8)
Parameter Appearing on Display
Pswrd Sets the protective access
BI1 Configuration of Binary Input 1.
BI2 Configuration of Binary Input 2.
Description and Default Selection Options
Range: 0 to 1,000 password to prevent unauthorized access to the Installer Configuration Menu.
Default: 0 Note: The default setting does not
lock out access to the Installer Configuration Menu.
(None): No function is associated with an input. Default: None
Default: None
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When th e contact closes, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat goes into the occupied mode for a specified TOccTime.
Once the TOccTime begins, the thermostat remains in the occupied
mode if the contact is closed, until the TOccTime expires.
(Window): Cancels the thermostat heating or cooling action when a
window is open. The fan operation is only affected if the Fan Menu
parameter is set to (4): On-Auto and Auto is the selected fan mode.
A Window alarm appears, indicating that the window needs to be
closed to resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to MotionNO
or MotionNC. (See the BI1 parameter in this table.) The occupancy
is now dictated via BI1 and BI2. Any motion detected sets the zone
to Occupied status. The zone remains permanently in occupied
mode until the door contact switch opens momentarily. The
thermostat then enters stand-by mode. If more movements are
detected, the occupied mode resumes. While the door is opened,
any movements detected by the remote PIR sensor or the PIR
accessory cover are ignored. Use a Normally Closed contact
switching device. Contact opened = Door opened,
Contact closed = Door closed.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
15
Page 16
Table 5: Installer Configuration Menu (Part 2 of 8)
Parameter
Description and Default Selection Options Appearing on Display
UI3 Configuration of Universal Input 3.
Default: None
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on AutoMode Enables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat cover.)
Default: on C or F Provides temperature scale options
for display.
Default: °F %RH dis Displays the current humidity
reading (TEC2236-4, TEC2236H-4,
TEC2236H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models).
Default: off Lockout Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
(None): No function is associated with an input. (COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems.
• A water temperature greater than 78.0°F (25.6°C) indicates hot
• A water temperature less than 75.0°F (23. 9°C) indicates cold Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/
Heat Four-Pipe and Reheat applications. (SS): Supply Air Sensor Monitoring
(on): The scroll is active. (off): The scroll is inactive.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°F): Fahrenheit scale (°C): Celsius scale
(on): Display%RH (off): No display of%RH
Lock out Level
water is present. water is present.
Function
System Mode Setting
(0) Access Access Access Access (1) Access Access No Access Access (2) No Access No Access Access Access (3) No Access No Access No Access Access (4) No Access No Access Access No Access (5) No Access No Access No Access No Access
Fan Mode Setting
Unoccupied Override
Occupied Temperature Setpoints
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
16
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 17
Table 5: Installer Configuration Menu (Part 3 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Pipe No Selectable number of pipes in the
system.
Default: 4.0
CntrlTyp Defines the control output for the
type of valves used in the
installation (TEC2226-4,
TEC2226H-4, TEC2226H-4+PIR,
TEC2236-4, TEC2236H-4, and
TEC2236H-4+PIR models only).
Default: Floating SeqOpera Determines the sequence of
operation.
Default: 1
Fan Menu Sets the Fan Mode options.
Default: 4
DHumidLCK Locks out dehumidification
capability (TEC2236-4,
TEC2236H-4, TEC2236H-4+PIR,
TEC2256-4, TEC2256H-4, and
TEC2256H-4+PIR models).
Default: on %RH set Sets dehumidification setpoints
(TEC2236-4, TEC2236H-4,
TEC2236H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models). This
parameter can be used only if
dehumidification sequence is
enabled.
Default: 50.0% RH
(2.0): Limits the number of sequences of operation available from 0 to 3, and enables heat/cool operation from the same output.
(4.0): Allows access to all sequences of operation from 0 to 5, and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.) 24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating valves.
(0): Cooling Only (Off-Cool). The default is Cool. (1): Heating Only (Off-Heat). The default is Heat. (2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto. (3): Heating and Reheat (Off-Heat). The default is Heat. (4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Auto. (5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Auto. * Auto can be disabled with the AutoMode parameter. Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan relays (L-M-H). Default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H). Default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan speed mode using three fan relays (L-M-H). Default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed mode using two fan relays (L-H). Default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. Default is Auto.
Note: (2) and (3) automatically cycle the fan through speeds,
based on the room temperature.
(on): Dehumidification Allowed (off): Dehumidification Locked Out
Range: 30.0 to 95.0%.RH
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
17
Page 18
Table 5: Installer Configuration Menu (Part 4 of 8)
Parameter
Description and Default Selection Options Appearing on Display
DehuHyst Sets the dehumidification hysteresis
(TEC2236-4, TEC2236H-4,
TEC2236H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models). This
parameter can only be used if
dehumidification sequence is
enabled.
Default: 5.0% RH DehuCool Sets the maximum dehumidification
cooling output (TEC2236-4,
TEC2236H-4, TEC2236H-4+PIR,
TEC2256-4, TEC2256H-4, and
TEC2256H-4+PIR models). This
parameter can only be used if
dehumidification sequence is
enabled.
Default: 100.0% St-By TM Sets stand-by timer value when
used with occupancy sensor; time
delay between moment where
occupancy sensor detected the last
movement in the area and the time
which the thermostat stand-by mode
and setpoints become active.
Default: 0.5 hours Unocc TM Sets Unoccupied Timer Value when
used with occupancy sensor; time
delay between the moment where
the thermostat toggles to stand-by
mode and the time which the
thermostat unoccupied mode and
setpoints become active.
Default: 0.0 hours
Range: 2.0 to 20.0% RH
Range: 20.0 to 100.0%. Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Range: 0.5 to 24.0 hours, in 0.5 hour increments
0.0 hours or Factory Value: Setting this parameter to its default 0 value disables the occupied timer and prevents the thermostat from drifting from stand-by mode to unoccupied mode when occupancy sensor functions are used.
Range: 0.0 to 24.0 hours in 0.5 hour increments
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
18
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 19
Table 5: Installer Configuration Menu (Part 5 of 8)
Parameter
Description and Default Selection Options Appearing on Display
St-By HT Sets Stand-by heating setpoint
when used with occupancy sensor;
value is between occupied and
unoccupied heating setp oi n ts.
Default: 69.0°F/20.6°C St-By CL Sets Stand-by cooling setpoint limit
when used with occupancy sensor;
value is between occupied and
unoccupied cooling setpoints.
Default: 78.0°F/25.6°C Unocc HT Sets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C Pband Proportional Band used by the PI
temperature control loop of the
thermostat.
Pband is not converted with C or F
scale and is always shown with a
range of 3 to 10.
Default: 3 (3F°/1.7C°)
Set type Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to 100°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to 100°F/37.5°C
Value F Scale Pband/C Scale Pband 3 3.0F°/1.7C° 4 4.0F°/2.2C° 5 5.0F°/2.8C° 6 6.0F°/3.3C° 7 7.0F°/3.9C° 8 8.0F°/4.4C° 9 9.0F°/5.0C° 10 10.0F°/5.6C° Note: The use of a larger proportional band is not to use the
thermostat as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat location errors that cannot be worked around.
(temporar): Local changes to the heating or coolin g setpoints are temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are permanently stored in the thermostat memory.
Note: When adjusting the temperature, press the UP/DOWN arrow keys to change the temperature in
0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
19
Page 20
Table 5: Installer Configuration Menu (Part 6 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Spt Func Determines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
TOccTime Sets the duration of the Temporary
Occupancy Time when the
thermostat controller is in the
Unoccupied mode and a Schedule
Override Function is enabled using
either the Main User Menu or BI1, or
BI2 is configured as a temporary
override remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints using the UP/DOWN
arrow keys.
Default: 2.0 hrs Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C° Cal RS Sets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C° Cal RH Sets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2236-4, TEC2236H-4,
TEC2236H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 0% RH
(Attch Stp): Single Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. Both the heating and cooling setpoints are changed simultaneously, while respecting the minimum configured deadband. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. The heating and cooling setpoints can be separated individually, allowing the minimum configured deadband to expand. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Range: -15.0% RH to 15.0% RH (adjustable in 1% RH increments)
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
20
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 21
Table 5: Installer Configuration Menu (Part 7 of 8)
Parameter
Description and Default Selection Options Appearing on Display
Aux cont Determines the auxiliary contact
function and configuration.
Default: 0
Auto Fan Affects the auto mode of operation
for the following Fan Menu
parameter selection options only:
(2): Low-Med-High-Auto
(3): Low-High-Auto
Default: AS
FL time Sets the maximum actuator stroke
timing.
Note: Floating CntrlTyp
TEC2226-4, TEC2226H-4,
TEC2226H-4+PIR, TEC2236-4,
TEC2236H-4, and
TEC2236H-4+PIR models only.
Default: 1.5 min Cph Sets the maximum number of cycles
per hour.
Note: TEC2216-4, TEC2216H-4,
TEC2216H-4+PIR, and on/off
CntrlTyp TEC2226-4,
TEC2226H-4, TEC2226H-4+PIR,
TEC2236-4, TEC2236H-4, and
TEC2236H-4+PIR models only.
Default: 4
(AS AD): The fan is on Auto during occupied periods. The Med and High speeds operate automatically on a temperature error from the setpoint. The Low speed operates Auto on demand. When there is no demand, the Low speed shuts down. The Low speed is only re-activated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on Auto during unoccupied periods. The Low, Med, and High speeds operate automatically on a temperat ure error from the setpoint.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
Range: 3 to 8 cycles per hour
(0) Not used,
or used for reheat
(1) Auxiliary
N.O.
(2) Auxiliary
N.C.
(3) Auxiliary
N.O.
(4) Auxiliary
N.C.
(5) Auxiliary On/Off control through the
auxiliary network command. The output can be commanded through the network for any required auxiliary functions via a separate and dedicated network variable.
If the Sequence of Operation is set to reheat (2, 3, or 5), ignore this parameter.
Occupied = contact closed Unoccupied = contact open
Occupied = contact open Unoccupied = contact
closed Occupied and fan On =
contact closed Unoccupied and fan On or
Off = contact open Occupied and fan On =
contact open Unoccupied and fan On or
Off = contact closed
The output aligns with occupancy.
The output aligns with occupancy and the fan on command.
The output aligns with the secondary network occupancy command.
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
21
Page 22
Table 5: Installer Configuration Menu (Part 8 of 8)
Parameter
Description and Default Selection Options Appearing on Display
RA/DA Choice of direct or reverse acting
analog output signal.
Note: TEC2246-4, TEC2246H-4,
TEC2246H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models only.
Default: DA Reheat Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis Displays the supply or changeover
temperature when UI3 is configured
as an analog input (SS or COS).
Used as a diagnostic/service help,
to troubleshoot and diagnose
sensor operation.
Default: -40°F/-40°C
(DA): Direct Acting, 0 to 100% = 0 to 10 VDC (RA): Reverse Acting, 0 to 100% = 10 to 0 VDC
(0): 15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat systems.
(1): 10 seconds (six cycles per minute), for various equipment with solid-state relays that withstand short duty cycles such as electric heat.
Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation.
Troubleshooting
See Table 8 for display messages. See Table 7 for further troubleshooting details.
Accessories
All the accessories in Table 6 include mounting
Repair Information
If a TEC22x6(H)-4 or TEC22x6H-4+PIR Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest
Johnson Controls representative.
hardware; contact the nearest Johnson Controls® representative to order any of these parts.
Note: Review the technical specifications of the optional accessories prior to their use in an application.
Table 6: Accessories (Order Separately)
Code
Description
Number
SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
TE-6361M-1 TE-636S-1 Strap-Mount Temperature Sensor
TEC-6-PIR TEC-6H-PIR
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2. The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC22x6-4 Series Thermostat Controller to provide occupancy sensing capability.
3. The TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC22x6H-4 Series Thermostat Controller to provide occupancy sensing capability.
Duct Mount Air Temperature Sensor
2
Cover with Occupancy Sensor
3
Cover with Occupancy Sensor for Hospitality Models
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
22
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Page 23
Table 7: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat heating or
cooling action in accordance with the programmable Binary Input (BI1).
Table 8: Troubleshooting Details
Symptom Cause Solution(s)
No display on the thermostat
Keyboard menu does not access all functions
Temperature setpoints revert to original value after a certain time
Thermostat does not call for heating
Thermostat does not call for cooling
Digital display shows missing digits or erratic segments
Reheat does not operate
Heating or cooling does not function properly
Absent or incorrect supply voltage
Overloaded power transformer
Keyboard locked Change configuration parameter nviRemLockout to value 0 to access all
Temporary setpoint active for a period of time set by parameter TOccTime
Wrong mode selected
Thermostat in Unoccupied mode
Heating setpoint is satisfied
Wrong mode selected
Thermostat in Unoccupied mode
Cooling setpoint is satisfied
Defective display Replace thermostat
Wrong mode selected
Wrong reversing valve configuration Note: TEC2246-4, TEC2246H-4, TEC2246H-4+PIR, TEC2256-4, TEC2256H-4, and TEC2256H-4+PIR only
1. Check power supply voltage between RC and C to be from 19 to 30 VAC
2. Check for tripped fuse or circuit breaker Verify that the transformer used is powerful enough (enough VAs) to supply all
controlled devices including the thermostat
levels of the menu.
T o do a permanent change to the setpoints you must enter the Set type menu and change it from Temporar to Permnent, then modify the setpoints to the desired temperature.
Select heating mode
Select Override to force the thermostat Occupied heating setpoint
Raise the Heating setpoint
Select cooling mode
Select Override to force the thermostat Occupied cooling setpoint
Lower the cooling setpoint
From the SeqOpera menu, set the value to 2, 3 or 5.
From the Rev Valve setting select either:
1. DA (Direct Acting) 0 to 100% = 0 to 10 VDC or
2. RA (Reverse Acting) 0 to 100% = 10 to 0 VDC
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
23
Page 24
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Technical Specifications
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Triac Output Rating (BO1, BO2, BO3, BO4)
Analog Output Rating
Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Auxiliary
Output Rating Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Temperature Sensor Type Local 10k ohm NTC Thermistor Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm
L
ONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with a Repeater;
Temperature Range
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling Ambient
Conditions Compliance United States UL Listed, File E27734, CCN XAPX,
Shipping Weight TEC22x6(H)-4 Models: 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
On/Off and Floating Control
Proportional Control
Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments Heating
Control Cooling
Control
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncond ensing
Canada UL Listed, File E27734, CCN XAPX7, Under
Europe CE Mark, EMC Directive 2004/108/EC, standards EN 61000-6-3 and EN 61000-6-1 Australia and
New Zealand
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
0 to 10 VDC into 2k ohm Resistance (Minimum)
Temperature Coefficient (NTC) Thermistor Sensors
Diameter) Recommended
6,250 ft (1,905 m) Maximum (Bus Topology)
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
L
ONMARK® Certification 3.4
CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
TEC22x6H-4+PIR Models: 0.77 lb (0.35 kg)
TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
24
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
Loading...