Johnson Controls TEC2201-2, TEC2204-2, TEC2203-2, TEC2202-2 Installation Instructions Manual

Page 1
Installation Instructions Issue Date November 23, 2005
TEC220x-2 Series Non-Programmable LONWORKS®
Application Requirements
The TEC220x-2 Series Non-Programmable
ONWORKS® Network Configurable Staged
L Thermostats are specifically designed for single-stage and multi-stage control of heating/cooling equipment, such as rooftop and heat pump units.
Accurate temperature control is achieved with a time proportional control algorithm, which virtually eliminates the temperature offset associated with traditional, differential-based thermostats. For more advanced applications, an economizer control logic has been integrated onto the thermostat for use with proportional damper economizer actuators.
All programmable models contain a Single-Pole Single-Throw (SPST) auxiliary switch, which can be used to control lighting or disable the economizer function.
Mechanical Installation
Location
Install away from any heat source. Do not install the thermostat:
Installation
To install the thermostat: Note: Wall surface must be flat and clean.
1. Remove security screw on the bottom of thermostat cover.
2. Open up by pulling on the bottom side of thermostat (
Figure 1).
3. Swing the thermostat circuit board to the left by pressing the pull tabs (
Figure 2).
4. Pull cables 6” out of the wall.
5. Insert cable in the central hole of the base.
6. Align the base and mark the location of the two mounting holes on the wall. Install proper side of base up.
on an outside wall
near an air discharge grill
in a location affected by direct sun radiation
in an area that restrains vertical air circulation to
the thermostat
Figure 2: Pull Tabs
e
s a
b g
in
t n u
o m
7. Install anchors in the wall.
8. Insert screws in mounting holes on each side of
the base (
Figure 2).
9. Gently swing the circuit board back on the base
and push until the tabs lock.
10. Pull out the screw terminal blocks using the pull
l a
v o
m e
r
r e
v o
c
tabs on each connector (Figure 3).
Figure 1: Bottom of Thermostat
© 2005 Johnson Controls, Inc.
Code No. LIT-1201911 www.johnsoncontrols.com
Software Release 1.0
1
Page 2
11. Strip each wire 1/4 inch.
12. Insert each wire according to wiring diagram.
13. Gently push excess wirin g back into the hole.
14. Install wiring terminals.
15. Reinstall the cover (top side first) and gently push extra wire length back in the hole in the wall.
16. Install se curity screw.
s
k
c o
l
b
l a
n
i m
r e
t
Figure 3: Security Screw
Caution
If replacing an old thermostat, label the wires before removal of the old thermostat.
Electronic controls are static sensitive devices. Discharge yourself properly before installing the thermostat.
Wiring
If the same power source is used for the heating stages, install jumper across RC and RH. Maximum current is 2.0 amperes.
If auxiliary output is used to toggle occupancy of the electronic control card inside the equipment, configure the relay parameter (Aux cont ) to the Normally Open (N.O.) setting. A second relay can be added for additional functionality of the occupancy output.
Economizer output uses a half bridge rectifier. Reference of the control signal is the common of the power supply of the thermostat, terminal C.
Electromechanical contacts are to be used with the digital inputs. Electronic triacs cannot be used as mean of switching for the input. The switched leg to the input is terminal C (common)
The transformer of the unit provides power to the thermostat and the additional loads that are wired to the thermostat.
Electrical Installation
Planning and Selecting Cables
Plan the placement of cables for inputs, outputs, communication, and power.
Place input, output, power, and network cables to avoid the effects of ambient noise.
Separate analog type cables for power, communication, inputs, and outputs from other types of cables.
Short circuits or incorrect wiring may permanently damage the thermostat or the equipment.
Anti-short cycling can be set to 0 minutes for equipment that possesses its own anti-cycling timer. Do not use that value unless the equipment is equipped with such internal timer. Failure to do so can damage the equipment.
All Thermostat devices are to be used only as operating controls. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system to protect against such catastrophic failures.
2 TEC220x-2 Series Non-Programmable L
ONWORKS Network Configurable Staged Thermostats Installation
Instructions
Connectors
The board connectors accept wires or flat cables: 22-12 AWG (0.14-2.5 mm²) per pole.
Table 1: Cable Specifications
Cable Specification
Power Inputs Digital
Outputs Analog
Outputs
Minimum cable section 18 AWG Minimum cable section 20 AWG – twisted pair Minimum cable section 18 AWG
Minimum cable section 20 AWG – twisted pair
Page 3
Wiring Analog Outputs
When configured as a digital type, the analog outputs can provide 60 mA of current for relay, or solid-state relay, operation.
Table 2: Analog Output Characteristics
Analog Output Characteristic
Voltage
Max Current
Protection
Table 3: Thermostat Models
0 to 10 VDC when configured as an analog output
0 to 12 VDC when configured as a digital output
60 mA @ 12 VDC when configured as digital (200 ohm load)
50 mA @ 10 VDC when configured as analog
Auto-reset fuse: 100 mA @ 68°F (20°C) 0 mA @ 140°F (60°C)
Application 1 Heat/1 Cool 2 Heat/2 Cool 2 Heat/2 Cool
and Economizer
Model (Non-Programming without Scheduling)
TEC2201-2 TEC2203-2 TEC2204-2 TEC2202-2
Heat Pump
TEC220x-2 Series Non-Programmable L
ONWORKS Network Configurable Staged Thermostats Installation
Instructions 3
Page 4
Non-Programmable Thermostat Wiring
TEC2201-2 Single-Stage Thermostat
The TEC2201-2 features one fan, one heating stage, and one cooling stage.
Thermostat Terminals – TEC 22 01 -2
Y1
Figure 4 shows a wiring example.
RC C
G
DI1
W1
RH
Scom
OS
RSDI2
Thermostat in ternal wiring System wiring Jumper J1
Cool
Stage 1
GY1 RC C
Fan
24 Vac
T1
Jumper J1
RH W1 DI2DI1 OSScom
Heat
Stage 1
24 Vac
Optional
T2
If T2 is not used install jumper J1 across RC and RH.
Digital Input # 1 Digital Input # 2
RS
Remote
Room
Sensor
Figure 4: TEC2201-2 Single-Stage Thermostat
TEC2203-2 Multi-Stage Thermostat
The TEC2203-2 features one fan, two heating stages, and two cooling stages.
Thermostat Terminals – TEC2203-2
Y1Y2 G
Remote Outdoor
Sensor
Field contact s
Figure 5 shows a wiring example.
C
RC
RH
W1
W2
Jumper J1
Y2
Y1 G CRH
Cool
Stage 2
Cool
Stage 1
Thermostat internal wiring System wiring Jumper J1
RC
Fan
24 Vac
T1
Figure 5: TEC2203-2 Multi-Stage Thermostat
4 TEC220x-2 Series Non-Programmable L
Instructions
Scom
RS
DI2
Digital Input #1 Digital Input #2
W1 W2 DI2DI1 OSScom
24 Vac
T2
Heat
Stage 1
Heat
Stage 2
Optional If T2 is not used install jumper J1 across RC and RH.
Remote
Room
Sensor
RS
OSDI1
Field con tacts
Remote Outdoor
Sensor
ONWORKS Network Configurable Staged Thermostats Installation
Page 5
TEC2204-2 Economizer Thermostat
The TEC2204-2 features one fan, two heating stages, two cooling stages, and an economizer. wiring example.
Thermostat Terminals – TEC2204-2
Y2 Y1
RCG
C
RH
W1
Figure 6 shows a
W2
EC
DI1 DI2
Y1
Y2
Cool
Stage 2
Cool
Stage 1
Thermostat internal wiring System wiring Jumper J1
G RC
Fan
24 Vac
T1
Jumper J1
C
RH W1
Heat
Stage 1
24 Vac
T2
W2
Heat
Stage 2
Optional If T2 is not used install jumper J1 across RC and RH.
EC
0-10 Vdc
24V Com
Digital Input #1 Digital Input #2
DI2DI1 RS
Remote
Room
Sensor
Figure 6: TEC2204-2 Economizer Thermostat
TEC2202-2 Heat Pump Thermostat
The TEC2202-2 features one fan, three heating stages, and two cooling stages.
Thermostat Terminals – TEC2202-2
Y2
Y1 RCG
DI1 DI2
Scom
OS
Remote Outdoor Sensor
MS
MSScom OS
Remote
Mixed Air
Sensor
RS
Field contacts
Figure 7 shows a wiring example.
C
RH
Scom
RS OS
W1
O/B
Y2
Y1
Compressor
Stage 2
Compressor
Stage 1
Thermost at int er na l wiring System wiring Jumper J1
TEC220x-2 Series Non-Programmable L
Jumper J1
RC
G CRH
Fan
24 Vac
T1
24 Vac
T2
Auxiliary
O/B
W1
Heat
Reversing
Valve
Optional If T2 is not used in stall jumper J1 acr os s R C and RH .
DI2DI1
Figure 7: TEC2202-2 Heat Pump Thermostat
ONWORKS Network Configurable Staged Thermostats Installation
Digital Input #1 Digital Input #2
RS
Remote
Room
Sensor
Field contacts
OSScom
Remote
Outdoor
Sensor
Instructions 5
Page 6
Technical Specifications
Product
TEC220x-2 Series Non-Programmable L Thermostats
Agency Approvals
FCC Class A - Class A computing device, Subpart J of Part 15 CULus UL873 File E234137 with CCN’s XAPX (US) and XAPX7 (Canada)
Power Requirements Ambient Operating
19-30 VAC 50 or 60 HZ; 2 VA (RC and C) Class 2 0 to 50ºC; (32 to 122ºF) 0 to 95% RH
Conditions Ambient Storage
-30 to 50ºC; (-22 to 122ºF) 0 to 95% RH
Conditions Processor Communication Transceiver Memory Sensor Resolution Control Accuracy Occupied and Unoccupied
Neuron® 3120 LonTalk® Protocol TP/FT-10; 78 Kbps EEPROM Local 10 K NTC thermistor
± 0.1ºC (±0.2ºF) ±0.5ºC (±0.9ºF) @21ºC (70ºF) typical calibrated
12 to 37.5ºC; (54 to 100ºF)
Setpoint Range Cooling Occupied and Unoccupied
4.5 to 32ºC; (40 to 90ºF)
Setpoint Range Heating Room and Outdoor Air
-40 to 50ºC; (-40 to 122ºF)
Temperature Range Proportional Band for
Both outputs: 1.1ºC (2.0ºF)
Room temperature Control Digital Inputs Contact Output Rating
Relay dry contact only across C terminal to DI1 or DI2 Each relay output: (Y1, Y2, G, W1, W2 and AU) 30 VAC, 1 A maximum/30 VAC, 3 A in-rush
Economizer Analog
0 to 10 VDC into 2 K ohm resistance minimum
Output Rating Economizer Analog
±3% typical
Output Accuracy Wire Gauge Dimensions Shipping Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
18 gauge maximum, 22 gauge recommended 125 mm x 86 mm x 29 mm (4.94” x 3/38” x 1.13”)
0.34 kg (0.75 lb)
ONWORKS Network Configurable Staged
Controls Group
507 E. Michigan Street P.O. Box 423 Published in U.S.A. Milwaukee, WI 53201
6 TEC220x-2 Series Non-Programmable L Instructions
www.johnsoncontrols.com
ONWORKS Network Configurable Staged Thermostats Installation
Loading...