Johnson Controls TEC2201-2, TEC2204-2, TEC2203-2, TEC2202-2 Installation Instructions Manual

Installation Instructions Issue Date November 23, 2005
TEC220x-2 Series Non-Programmable LONWORKS®
Application Requirements
The TEC220x-2 Series Non-Programmable
ONWORKS® Network Configurable Staged
L Thermostats are specifically designed for single-stage and multi-stage control of heating/cooling equipment, such as rooftop and heat pump units.
Accurate temperature control is achieved with a time proportional control algorithm, which virtually eliminates the temperature offset associated with traditional, differential-based thermostats. For more advanced applications, an economizer control logic has been integrated onto the thermostat for use with proportional damper economizer actuators.
All programmable models contain a Single-Pole Single-Throw (SPST) auxiliary switch, which can be used to control lighting or disable the economizer function.
Mechanical Installation
Location
Install away from any heat source. Do not install the thermostat:
Installation
To install the thermostat: Note: Wall surface must be flat and clean.
1. Remove security screw on the bottom of thermostat cover.
2. Open up by pulling on the bottom side of thermostat (
Figure 1).
3. Swing the thermostat circuit board to the left by pressing the pull tabs (
Figure 2).
4. Pull cables 6” out of the wall.
5. Insert cable in the central hole of the base.
6. Align the base and mark the location of the two mounting holes on the wall. Install proper side of base up.
on an outside wall
near an air discharge grill
in a location affected by direct sun radiation
in an area that restrains vertical air circulation to
the thermostat
Figure 2: Pull Tabs
e
s a
b g
in
t n u
o m
7. Install anchors in the wall.
8. Insert screws in mounting holes on each side of
the base (
Figure 2).
9. Gently swing the circuit board back on the base
and push until the tabs lock.
10. Pull out the screw terminal blocks using the pull
l a
v o
m e
r
r e
v o
c
tabs on each connector (Figure 3).
Figure 1: Bottom of Thermostat
© 2005 Johnson Controls, Inc.
Code No. LIT-1201911 www.johnsoncontrols.com
Software Release 1.0
1
11. Strip each wire 1/4 inch.
12. Insert each wire according to wiring diagram.
13. Gently push excess wirin g back into the hole.
14. Install wiring terminals.
15. Reinstall the cover (top side first) and gently push extra wire length back in the hole in the wall.
16. Install se curity screw.
s
k
c o
l
b
l a
n
i m
r e
t
Figure 3: Security Screw
Caution
If replacing an old thermostat, label the wires before removal of the old thermostat.
Electronic controls are static sensitive devices. Discharge yourself properly before installing the thermostat.
Wiring
If the same power source is used for the heating stages, install jumper across RC and RH. Maximum current is 2.0 amperes.
If auxiliary output is used to toggle occupancy of the electronic control card inside the equipment, configure the relay parameter (Aux cont ) to the Normally Open (N.O.) setting. A second relay can be added for additional functionality of the occupancy output.
Economizer output uses a half bridge rectifier. Reference of the control signal is the common of the power supply of the thermostat, terminal C.
Electromechanical contacts are to be used with the digital inputs. Electronic triacs cannot be used as mean of switching for the input. The switched leg to the input is terminal C (common)
The transformer of the unit provides power to the thermostat and the additional loads that are wired to the thermostat.
Electrical Installation
Planning and Selecting Cables
Plan the placement of cables for inputs, outputs, communication, and power.
Place input, output, power, and network cables to avoid the effects of ambient noise.
Separate analog type cables for power, communication, inputs, and outputs from other types of cables.
Short circuits or incorrect wiring may permanently damage the thermostat or the equipment.
Anti-short cycling can be set to 0 minutes for equipment that possesses its own anti-cycling timer. Do not use that value unless the equipment is equipped with such internal timer. Failure to do so can damage the equipment.
All Thermostat devices are to be used only as operating controls. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system to protect against such catastrophic failures.
2 TEC220x-2 Series Non-Programmable L
ONWORKS Network Configurable Staged Thermostats Installation
Instructions
Connectors
The board connectors accept wires or flat cables: 22-12 AWG (0.14-2.5 mm²) per pole.
Table 1: Cable Specifications
Cable Specification
Power Inputs Digital
Outputs Analog
Outputs
Minimum cable section 18 AWG Minimum cable section 20 AWG – twisted pair Minimum cable section 18 AWG
Minimum cable section 20 AWG – twisted pair
Loading...
+ 4 hidden pages