Johnson Controls TEC22 2-3 LonWorks Series, TEC2202-3 LonWorks, TEC2262-3 LonWorks Installation Instructions Manual

TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat
Installation Instructions
Part No. 24-9890-471, Rev. —
Issued September 8, 2006

Applications

The TEC2202-3 non-programmable and TEC2262-3 programmable thermostats are L
ONWORKS® networked devices that provide control of
heat pump equipment. The technologically advanced TEC22x2-3 thermostats feature a Building Automation System (BAS) L
ONWORKS network communication
capability that enables remote monitoring and programmability for efficient space temperature control.
IMPORTANT: The TEC22x2-3 thermostat is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostat.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipm ent in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Location Considerations

Locate the TEC22x2-3 thermostat:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: Allow for vertical air circulation to the TEC22x2-3 thermostat.
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the security screw on the bottom of the thermostat cover.
2. Pull the bottom edge of the thermostat cover and open the thermostat as illustrated in Figure 1.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat Installation
l
v m
r
_
r v
c
: G
I F
Figure 1: Removing the Thermostat Cover
Instructions
1
3. Carefully pull the locking tabs on the right side of the thermostat mounting base and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 2.
PCB Locking Tabs
d
r b
_
t
c
r
c
_ d
t
n
r
p
: G
I F
Figure 2: Opening the Thermosta t PCB
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat mounting base.
5. Align the thermostat mounting base on the wall and use the base as a template to mark the two mounting hole locations.
Note: Be sure to position the thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat.
6. Drill a 3/16 in. (5 mm) hole at each of the two marked locations and tap nylon anchors (include d with the thermostat) flush to the wall surface.
7. Position the thermostat mounting base on the wall and use the two mounting screws (included with the thermostat) to secure the base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat mounting base.
9. Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4.
s k
c
l
b
_
l
n m
r
t
: G
I F
Figure 4: Removing the Screw Terminal Blocks

Wiring

When an existing thermostat is replaced, remove and label the wires to identify the terminal functions. When a TEC22x2-3 thermostat is replaced, sim ply re m ov e the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
! !
making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Figure 3: Securing the Thermostat
Mounting Base to the Wall
TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat Installation Instructions2
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC22x2-3 thermostat.
s
b
_ g
n
t
n m
: G
I F
To wire the thermostat:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Figure 5 and Figure 7.
Note: For more details on wiring the L
ONWORKS network, refer to the
L
ONWORKS Network Layout Technical Bulletin
(LIT-1162150).
2. Carefully push any excess wire back into the wall. Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the L
ONWORKS communication wires to
the LON terminal block. See Figure 5. Note: If inserting multiple wires into the terminals,
be sure to properly twist wires together prior to inserting them into the terminal connectors.
5. Reattach the thermostat cover to the mounting base (top side first).
6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat cover.
Three-Pole Right Top Connector
RH W1
C
56
Scom
OS
O/B
8
7
MS
LW
ON ORKS
Bus Te rminals
Five-Pole Left Top Connector
Y2
1
Y1 G
23
RC
4
Seven-Pole Bottom Connector
Aux
DI1 DI2 RS
Table 1: Terminal Identification (See Figure 5.)
Number Label Function
1Y2Energizes second-stage compressor
2Y1Energizes first-stage compressor on
3GEnergizes fan in accordance with
4RC24 VAC from equipment transformer 5C24 VAC (Common) from equipment
6RH24 VAC for heating stage 7W1Energizes on a call for auxiliary heat. 8 O/B Energizes reversing valve.
10 Aux Auxiliary output 11 DI1 Configurable Digital Input 1 12 DI2 Configurable Digital Input 2 13 RS Remote Room Air Temperature
14 Scom Sensor Common 15 OS Auxiliary/Outdoor Air Sensor
3
_
2 x
2
2 C E T
_ m
r
t
: G
I F
16 MS Remote Monitoring Supply
Blank Blank L
on a call for heating or cooling.
a call for heating or cooling.
selected fan mode.
transformer
Configurable to energize valve on a call for heating or a call for cooling.
Sensor
Temperature Sensor
ONWORKS Bus
10
11
12
13
14
15 16
Figure 5: TEC22x2-3 Thermostat Terminals
Y2 Y1
Comp 2
Thermostat Power
Comp 1
24 VAC
G
Fan
RC
RH W1
C
Aux
Heat
If using the same power source for the the r m ostat and heating loads, install a j um per across RC and RH .
Figure 6: TEC22x2-3 Thermostat General Application
O/B
Rev
Valve
Aux
Aux
DI1
Isolated Contact
• Lighting
• On/Off Ac t uation
• Exhaus t Fan RS
DI2
Remote
Room
Sensor
Scom
Air Sensor
OS
Auxiliary/
Outdoor
Bus Terminals
MS
Remote
Monitoring
Supply
Temperature
Sensor
LW
ON ORKS
Supervisory
Controller
g
n
r w
_
p m
p
t
h
: G
I F
TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat Installation Instructions 3
Y2 Y1
G
RC C RH W1 O/B
R3
R2
R1
Separate 24 VAC
Transformer
R3-1
Y2 Y1
R1-1R2-1
G
Heat Pump Terminal In t erface
Figure 7: VDC Switching Application for Heat Pumps

Connecting the LONWORKS Network

The wiring rules for the LONWORKS network differ from the wiring rules for the Metasys® N2 Bus and the BACnet® MS/TP Bus. For more details on wiring the LONWORKS network, refer to the LONWORKS Network Layout Technical Bulletin (LIT-1162150).
To connect the thermostat to the LONWORKS network:
1. Connect the L
ONWORKS network terminal block on the
L thermostat (Figure 5, Figure 6, Figure 7, and Figure 8).
ONWORKS network wires to the
LW
ON ORKS
Bus Te rminals
R4
T o Auxiliary
Heat Circuit
Note:
Use 24 VAC
interface relays R1-1,
R4-1
RC
R2-1, R3-1, and R4-1 (provided by the user).
O/B
p m
p
_
t
h
: G
I F
Note: There is no polarity when connecting the
ONWORKS network wires to the thermostat; however,
L we recommend keeping the polarity consistent throughout the network.
2. After the L
ONWORKS network wires are connected
to the first thermostat, continue in a daisy-chained fashion to the next device.
Note: The L
ONWORKS network wiring must be twisted-
pair lines. Do not run the L
ONWORKS network wiring in the same
conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
Supervisory
Controller
LW
ON ORKS
Network Wires
ON ORKS
LW
Network
Terminal Block
Twist wires together before inserting them into the terminals.
Figure 8: Thermostat to Network Connection
TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat Installation Instructions4
ONWORKS network requires proper termination
The L and biasing at the end of a segment (a segment is a physically continuous length of wire). The thermostat is not equipped with the ability to provide this termination; therefore, it cannot be located at the physical end of a
ONWORKS network segment unless a terminator is
L attached. Refer to L
ONWORKS Network Layout
Technical Bulletin (LIT-1162150) for end-of-line
solutions.
r
i w
_ N O L
: G
I F

Setup and Adjustments

Y

Thermostat Operation Overview

Backlit, pl ain text
LCD is easy to read
in any condi t io n.
LEDs indicate system activity.
Five keys on the therm ostat make operation easy and intuitive.
Figure 9: Front Cover of Thermostat

Thermostat User Interface Keys

The TEC22x2-3 thermostat user interface consists of five keys on the front cover (as illustrated in Figure 9). The function of each key is as follows:
•Use the YES/SCROLL key to:
- confirm menu selections and to advance to the next menu item
- stop the Status Display Menu fr om scrolling and to manually scroll to the next parameter on the menu
Note: When the thermostat is left unattended for 45 seconds, the thermostat display resumes scrolling.
•Use the NO key to decline a parameter change and to advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or to exit the menu
(See the Main User Menu section.)
Room Temp
70.0ºF
ES NO
w
v _
t n
r
f
: G
I F

Backlit Liquid Crystal Display (LCD)

The TEC22x2-3 thermostat includes a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens wh en any user interface key is pressed. The backlight returns to low level when the thermostat is left unattended for 45 seconds.

Light-Emitting Diodes (LEDs)

Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
•The FAN LED is on when the fan is on.
•The AUX HEAT LED is on when auxiliary heat is on.
•The HEAT PUMP LED is on when the heat pump compressor is on.

Programming Overview

There are three menus used to view, program, and configure the TEC22x2-3 thermostat.
The Status Display Menu is displayed during normal thermostat operation. This menu continuously scrolls through the following parameters:
Room Temperature
Clock (TEC2262-3 only)
System Mode
Occupancy Status – Occupied/Unoccupied/ Override
Outdoor Temperature – An outdoor air temperature sensor must be connected.
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: Press the YES/SCROLL key to temporarily stop this menu from scrolling.
The Main User Menu is used to access and change the basic operating parameters of the thermostat. Access this menu by pressing the MENU key during normal thermostat operation.
- access the Installer Configuration Menu or to exit the menu (See the Configuring the TEC22x2-3 Thermostat section.)
•Use the UP/DOWN arrow keys to change the
The Installer Configuration Menu is used to set up the thermostat for application-specific operation. To access this menu, press and hold the MENU key for approximately 8 seconds.
configuration parameters and to activate a setpoint adjustment.
TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat Installation Instructions 5

Configuring the TEC22x2-3 Thermostat

The TEC22x2-3 thermostat comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 2. To reconfigure the parameters via the thermostat, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the MENU key for approximately 8 seconds.
2. Once the Installer Configuration Menu begins, press the NO key to scroll through the parameters listed in Table 2.
3. When the desired parameter is displayed, use the YES key to choose the desired selection option.
4. Press the YES key and then the NO key to continue scrolling through the parameters.
To exit the Installer Configuration Menu any time, press the MENU key, and at the exit prompt, press the YES key. To pass over a parameter without changing it, press the NO key.
When the thermostat is in the Installer Configuration Menu and left unattended for approximate ly 8 seconds, the thermostat reverts to the Status Display Menu.
For additional information on commissioning and configuring thermostats, adding thermostats to a Network Automation Engine (NAE), thermostat mapping, and remote thermostat commanding, refer to
TEC226x-3 and TEC220x-3 Series L
ONWORKS®
Network Configurable Staged Thermostats Technical Bulletin (LIT-12011196).

Configuring the Thermostat’s Neuron® Identification

Press and hold the UP/DOWN arrow keys simultaneously for 5 seconds to broadcast the thermostat’s Neuron Identification on the L
ONWORKS
network. If the cover is removed, you can see a green LED
under the LON board flash when the thermostat broadcasts the Neuron ID. The Neuron ID is on a label on the Echelon® chip.
You cannot send the Neuron ID while in the Installer Configuration menu.

Configuring Inputs DI1 and DI2

When DI1 and DI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu, and when the message is displayed, the backlight momentarily lights up.
Table 2: Installer Configuration Menu (Part 1 of 5)
Parameter
Description and Default Selection Options Appearing on Display
DI1
1
Configuration of Digital Input 1.
Default: None
(None): No function is associated with an input. (Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
Each input can be configured to the Selection Options included in Table 2.
TEC22x2-3 LONWORKS® Networked Heat Pump Thermostat Installation Instructions6
Loading...
+ 13 hidden pages