Johnson Controls TEC2103-2 Installation Instructions Manual

24-9890-161, Rev. C
Installation Instructions Issue Date March 2016
TEC2103-2 Networked Multi-Stage Thermostat
Application
The TEC2103-2 thermostat is an N2 networked thermostat that provides control of multi-stage HVAC equipment. The TEC2103-2 thermostat provides exceptional accuracy through the use of a unique Proportional-Integral (PI) time proportioning algorithm. The algorithm virtually eliminates temperature offset associated with traditional, dif f er entia l-bas ed on/ of f thermostats. The TEC2103-2 thermostat also uses an adaptive control logic algorithm to control the space temperature during recovery to minimize overshoot while providing maximum comfort.
The TEC2103-2 thermostat has Metasys® N2 communication capability. This communication allows the user to view and adjust parameters from a remote workstation. Additionally, the menu driven backlit display, plain text menus, and five keys on the TEC2103-2 thermostat make operating the thermostat easy and intuitive.
Note: In this document, Building Automation System (BAS) is a generic term that refers to the Metasys Network (Network Control Module [NCM] or N30 Series), and Companion (CPN) supervisory systems. The specific system names are used when referring to system specific applications.
Installation
Location Considerations
Locate the TEC2103-2 thermostat:
on a partitioning interior wall, and approximately 5 ft. (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unheated/uncooled areas, or sources of electrical interference
To install the thermostat:
1. Remove the security screw on the bottom of the thermostat cover using a Phillips-head screwdriver. Open the thermostat by pulling on the bottom side of the thermostat cover (Figure 1).
2. Unlock the Printed Circuit Board (PCB) by carefully pressing the locking tabs to the right (Figure 2). Open the thermostat’s PCB to the left.
3. Pull out approximately 6 in. (152 mm) of wires from the wall and insert the cable through the hole in the base.
4. Align the base on the wall, and using the base as a template, mark the location of the two mounting holes on the wall. Confirm the thermostat base is installed with the proper side up.
5. Use the supplied anchors and screws for mounting on drywall or plaster. Drill two 3/16 in. (4.7 mm) holes at the marked locations and tap nylon anchors flush to wall surface (Figure 3).
6. Position base on the wall, insert screws through mounting base, and fasten into wall anchors. Do not overtighten screws.
7. Swing the thermostat PCB back to the right to close. Gently press on the PCB to secure each of the locking tabs.
8. Pull out the screw terminal blocks using the pull-tabs on each connector (Figure 4).
Note: The number of terminals on the terminal blocks varies depending on the TEC model.
© 2016 Johnson Controls, Inc.
Part No. 24-9890-161, Rev. C www.johnsoncontrols.com
IMPORTANT: Use this TEC2103-2 networked
T600_TEC_Remove_Cover
P
C
B
L
o
ck
in
g
Tab
s
T
6
0
0
_
T
E
C
_O
p
e
n
m
_
S
t
a
t
T600_TEC_Mounting_Base
T600_TEC_Terminal_Blocks
multi-stage thermostat only as an operating control. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat.
IMPORTANT : Utiliser ce TEC2103-2 networked multi-stage thermostat uniquement en tant que dispositif de contrôle de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du thermostat.
Figure 2: Opening the Thermostat PCB
Figure 1: Removing the Thermostat Cover
2 TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
Figure 3: Mounting the Thermostat Base
Figure 4: Removing the Terminal Blocks
Wiring
!
!
CAUTION: Risk of Electric Shock. Disconnect the power suppl y before m ak ing electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Note: When replacing an existing thermostat, remove and label wires to identify terminal designations. When replacing a TEC2103 thermostat, simply remove the terminal blocks and reinsert onto the new thermostat.
To wire the thermostat:
1. Strip each wire 1/4 in. (6.35 mm) and connect to the appropriate terminal according to the TEC2103-2 thermostat wiring diagram (Figure 5).
2. Gently push excess wire back into the wall, plug the wall hole with fireproof m aterial to prevent drafts from affecting ambient temperature readings, and install screw terminal blocks back onto the PCB.
3. Reattach the thermostat cover to the installed base (top side first) and install the security screw on the bottom.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
MISE EN GARDE : Risque de dégâts matériels. Ne pas mettre le système sous tension av ant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions 3
T
EC
21
0
3-
2
_W
ir
i
ng
Y2
Y1
G
RC
C
RH W1 W2
D1
D2 RS
Scom
5-pole left top connector
3-pole right top connector
5-pole bottom connector
24 VAC
Thermos tat Power
Y2
Y1
G
RC C
If usi ng the sam e power source for the thermostat an d heating loads, install a jumper across RC and RH.
Heat 1
Heat 2
RH W1
W2
Fan
Cool 1
Energizes on a c all for first stage coo ling Energizes on a c all for second stage cooling Energizes fan in accordance with the selected f an mode 24 VAC from equipment tra ns former 24 VAC (common) from equipment transformer 24 VAC for heating stages Energizes on a c all for first stage heating Energizes on a c all for second stage heating Configurable digit al input Configurable digit al input Remote room sensor Sensor common Auxil iary/Outdoor air sensor N2 Bus
Function
Y1 Y2
G
RC
C RH W1 W2
D1 D2
RS
Scom
OS
N2+, N2-, REF
Terminal
OS
D2
Scom
RS
D1
Remote
Room
Sensor
OS
REF
N2-
N2+
Auxiliary/Outdoor
Sensor
N2-
N2+
REF
Metasys, CPN,
NCM
Cool 2
Figure 5: TEC2103-2 Thermostat Wiring Schematic
Connecting the N2 Bus
To connect the N2 Bus:
1. Observe the polarity when connecting the N2 Bus wires to the TEC2103-2 thermostat.
Note: An End-of-Line (EOL) is not needed on the
2. Continue this process for each TEC2103-2
N2 Bus at the TEC2103-2 thermostat. However, one EOL is needed at the BAS (N30, Companion, Network Control Module).
thermostat using the daisy chain wiring method.
N2 Device Mapping
When adding the TEC2103-2 thermostat to the Metasys system (Person-Machine Interface [PMI] and Companion system), you must define the TEC2103-2 thermostat as a Vendor Device (VND). For the NCM, except as noted in Table 1, Footnote c, do not direct map any points. Run control of these points through the Control System (CS) object. See the Setting the N2 Address (N2 addr) section to set the address for the thermostat.
4 TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
Table 1: N2 Bus Objects
32 to 122°F (0 to 50°C)
-40 to 122°F (-40 to 50°C)
Heating SP
a, g
(Occupied Heating SP)
(Occupied Cooling SP)
Setback Heating SP
a, g
(Unoccupied Heating SP)
ADI-5
N2 AO
CSAD
Setback Cooling SP
a, g
(Unoccupied Cooling SP)
ADI-6
N2 AO
CSAD
Minimum Heat SP
ADI-7
N2 AI
CSAD
40°F (4.5°C)
Maximum Heat SPa
ADI-8
N2 AO
CSAD
40 to 90°F (4.5 to 32°C)
Minimum Cool SPa
ADI-9
N2 AO
CSAD
54 to 100°F (12 to 37.5°C)
Maximum Cool SP
ADI-10
N2 AI
CSAD
100°F (37.5°C)
Fana
BD-1
N2 BO
CSBD
0 = Auto, 1 = On
Modea
BD-2
N2 MS O
d, e
CSMS
0 = Off, 1 = Cool, 2 = Heat, 3 = Auto
Occupancya
BD-3
N2 BO
CSBD
0 = Unoccupied, 1 = Occupied
W1 State
BD-4
N2 BI
CSBD
0 = Off, 1 = On
W2 State
BD-5
N2 BI
CSBD
0 = Off, 1 = On
Y1 State
BD-6
N2 BI
CSBD
0 = Off, 1 = On
Y2 State
BD-7
N2 BI
CSBD
0 = Off, 1 = On
G State – Fan
BD-8
N2 BI
CSBD
0 = Off, 1 = On
Temp Units
a, c
(Local Display Only)
BD-9
N2 BO
See Footnote c.
Occupancy Override
BD-10
N2 BI
CSBD
0 = No Override, 1 = Override
DI1
b, f
BI-1
N2 BI
CSBI
0 = Off, 1 = On
Temp Alarmb
BI-2
N2 BI
CSBI
0 = Normal, 1 = Alarm
DI2
b, f
BI-3
N2 BI
CSBI
0 = Off, 1 = On
Unocc Cooling SP). The overridden setpoint must be released prior to overriding the other setpoint. Additionally, if one
Point Name TEC Point
Type/ Address
Room Tempa Aux Temp / Outdoor Tempa
Cooling SP
a, g
ADI-1 N2 AI CSAD ADI-2 N2 AI CSAD ADI-3 N2 AO CSAD
ADI-4 N2 AO CSAD
N30/NAE Object Type
BAS Model Point Type
Override Range
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
0 = °C, 1 = °F
Notes: a. Commandable. b. Can be a Change-of-State (COS) alarm to the BAS or N2 Dialer Module (NDM) to initiate a dial-out. c. On the Metasys NCM system, map BD9 Temp Units Mode as a Binary Output (BO) object with Auto Restore and
Local Control set. d. The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs). e. When defining the N2 MSO object, select TEC Mode from the States Text Menu. Type 4 for the TEC2103-2
thermostat.
f. The state of DI1 and DI2 is communicated over the N2 network even if the digital inputs are configured as None
through the local interface at the thermostat. g. The Heating and Cooling SP cannot be overridden simultaneously (this also applies to the Unocc Heating SP and
setpoint is overridden, the other setpoint may be automatically adjusted by the TEC2103-2 thermostat to maintain the
minimum deadband between the two setpoints.
TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions 5
The Controller Point Type is the fixed-point definition inside the controller. The BAS Model Point type is the definition inside
If an AD object is overridden by the Metasys system, all local changes attempted through the thermostat keypad for that AD
red until the override is released. For example, if the Metasys system sends a write command to turn System
If there is a Relinquish Default for the setpoints, the Network Automation Engine (NAE) always has an Override for either an
from the TEC causing loss of network communications).
the model file. Use an NCM CS object to retrieve the data. The most recent N2 command received by any of the N2 Bus Objects listed in Table 1 controls the thermostat.
object are igno Mode Off, then the occupant selects System Mode On at the TEC keypad, the TEC ends up with the System Mode On; however, if the Metasys system sends an override command to turn System Mode Off, then the occupant selects System Mode On at the TEC keypad, the TEC keeps the System Mode Off.
Once an override is released, the AD object may once again be changed through the thermostat keypad, but the thermostat does not retain any data entered at the TEC keypad during the override.
Only one of the setpoints (Heating Setpoint or Cooling Setpoint) can be overridden at a time.
The value for Heating SP (ADI-3) and Setback Heating SP (ADI-5) must stay within the limits established in the controller by Minimum Heat SP (ADI-7 read-only) and Maximum Heat SP (ADI-8).
The value for Cooling SP (ADI-4) and Setback Cooling SP (ADI-6) must stay within the limits established in the controller by Minimum Cool SP (ADI-9) and Maximum Cool SP (ADI-10 read-only).
If a setpoint is overridden, the TEC, if necessary, adjusts the other setpoint to maintain the minimum 2 F° deadband between the setpoints. The setpoints can be spread further apart but can never be adjusted closer than 2 F° apart.
Failure to stay within the limits for a command results in an N2 Negative Acknowledge (NAK) error from the TEC2103-2 thermostat.
Overrides take precedence over any local adjustment or command in the TEC2103-2. You must not have a Relinquish Default for the setpoints if you want to change them from the thermostat display.
Adjusted value or the Relinquish Default value. You should use Operator Override and Release Operator Override if you want to command the setpoint and release it to local contr ol.
Once all the NAE commands are released, the Override Status in the Hardware tab should be False. At that time, the user should be able to change the setpoint from the local display.
All overrides are released automatically after 10 minutes of no communications (for example, network cable is removed
6 TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
Loading...
+ 13 hidden pages