Johnson Controls TEC2101-3 N2 Installation Instructions Manual

Page 1
TEC2101-3 N2 Networked Single-Stage Thermostat
Installation Instructions
Part No. 24-9890-420, Rev. —
Issued September 14, 2006
Applications
The TEC2101-3 Thermostat is an N2 networked device that provides control of single-stage heating/cooling equipment. The technologically advanced TEC2101-3 Thermostat features a Building Automation System (BAS) N2 Bus communication capability that enables remote monitoring and programmability for efficient space temperature control.
IMPORTANT: The TEC2101-3 Thermostat is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostat.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipm ent in a residential area is likely to cause harmful interference, in which case the user is required to correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
Location Considerations
Locate the TEC2101-3 Thermostat:
on a partitioning wall, approximately 5 ft ( 1. 5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: Allow for vertical air circulation to the TEC2101-3 Thermostat.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructio ns 1
Page 2
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the security screw on the bottom of the thermostat cover.
2. Pull the bottom edge of the thermostat cover and open the thermostat as illustrated in Figure 1.
l
v m
r
_
r v
c
: G
I F
Figure 1: Removing the Thermostat Cover
3. Carefully pull the locking tabs on the right side of the thermostat mounting base and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 2.
PCB Locking Tabs
Note: Be sure to position the thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat.
6. Drill a 3/16 in. (5 mm) hole at each of the two marked locations and tap nylon anchors (included with the thermostat) flush to the wall surface.
7. Position the thermostat mounting base on the wall and use the two mounting screws (included with the thermostat) to secure the base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
s
b
_ g
n
t
n m
: G
I F
Figure 3: Securing the Thermostat
Mounting Base to the Wall
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat mounting base.
9. Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4.
Figure 2: Opening the Thermosta t PCB
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat mounting base.
5. Align the thermostat mounting base on the wall and use the base as a template to mark the two mounting hole locations.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions2
d
r b
_
t
c
r
c
_ d
t
n
r
p
: G
I F
s k
c
l
b
_
l
n m
r
t
: G
I F
Figure 4: Removing the Screw Terminal Blocks
Page 3
Wiring
When an existing thermostat is replaced, remove and label the wires to identify the terminal functions. When a TEC2101-3 Thermostat is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat.
CAUTION: Risk of Electric Shock.
Disconnect power supply before making
!
!
electric connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC2101-3 Thermostat.
To wire the thermostat:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Figure 5.
2. Carefully push any excess wire back into the wall. Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the thermostat cover to the mounting base (top side first).
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat cover.
Terminal
W1
Y1
G
RC
C
RH Aux DI1 DI2
RS
Scom
OS
+, -, REF
Y1 RC
Cool 1
Thermostat Power
G RS
Fan
24 VAC
Function
Energize s on Call for Heati ng Energize s on Call for Coolin g Energizes Fan in Accordance with the Selected Fa n M ode 24 VAC from Equipment Transform er 24 VAC (Comm on from Equipment T r ansformer 24 VAC for He at ing Stage Auxiliary Out put Configurable Digital Input 1 Configurable Digital Input 2 Remote Room Tem perature Sensor Sensor Co m m on Outdoo r Air Sensor N2 Bus
C
)
RH W1
Heat 1
If using the same power source for the the r m ostat and heating loa ds, install a j um per across RC and RH.
Aux
Aux
Independent Contact
• Lighting
• On/Off Actuation
• Exhaus t Fan DI1
+
-
REF
DI2
Four-Pole Left Top Connect or
Y1 G RC C
2
1
Seven-Pole Bottom Connector (MS Terminal Not Used)
910111213
Remote
Room
Sensor
Aux
Scom
Outdoor
Air Sensor
3
4
DI1 DI2 RS
OS
Two-Pole Right Top Connector
RH W1
5
Scom
14 15616
+
78
OS
-
Supervisory
Controller
REF
g n
r w
: G
I F
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 3
Figure 5: Wiring the TEC2101-3 Thermostat
Page 4
Connecting the N2 Bus
To connect the N2 Bus:
1. Set the N2 address of the TEC2101-3 Thermostat per the engineering drawings prior to wiring the thermostat. (See the Com addr parameter in Table 2 to set the N2 address for the thermostat.) Also test for N2 voltage, polarity, and isolation prior to wiring the thermostat.
2. Observe the polarity when connecting the N2 Bus wires to the thermostat.
3. After the N2 Bus wires are connected to the first thermostat, continue in a daisy-chained fashion to the next thermostat.
Note: The thermostat N2 Bus is self-terminating. The N2 Bus wiring must be twisted-pair lines. Do not run the N2 Bus wiring in the same conduit as line voltage wiring (30 VAC or above) or other wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).
For more N2 Bus overview information, refer to the N2 Communications Bus Technical Bulletin (LIT-636018) and ASC and N2 Bus Networking and Troubleshooting Technical Bulletin (LIT-6363003).
N2 Device Mapping
Define the TEC2101-3 Thermostat as a Vendor Device (VND) when adding the thermostat to the supervisory controller.
The Thermostat Point (T ype/Address) is the fixed-point definition inside the thermostat. The most recent N2 command received by any of the Object T y pes listed in Table 1 controls the thermostat.
Only one of the setpoints (either Heating SP or Cooling SP) can be overridden at a time. Overrides t ake priority over any local adjustment or command in the thermostat.
If a setpoint is overridden, the thermostat adjusts the other setpoint, if necessary, to maintain the minimum deadband between the two setpoints. The setpoints can be spread farther apart but can never be adjusted closer than 2F°/1C° apart.
If a supervisory controller commands an override of an analog or binary object, all local changes attempted through the thermostat keypad for that object are ignored until the override is released. For example, if the supervisory controller sends an override message to turn System Mode Off, and then the user selects System Mode On at the thermostat keypad, the thermostat keeps the System Mode Off.
When an override is released, the object may once again be changed through the thermostat keypad, but the thermostat does not retain any data entered at the thermostat keypad during the override.
All overrides are released automatically after 10 minutes of no communications (for example, if the network cable is removed from the thermost at, causing a loss of network communications).
Metasys® System Person-Machine Interface (PMI)
Do not direct-map any points; instead, run control of these points through the Control System (CS) object. The supervisory controller Model Point Type is the definition inside the model file. Use a CS object to retrieve the data.
Metasys System Extended Archit ecture
There must not be a Relinquish Default for the setpoints if it is desired to change them from the thermostat display. If there is a Relinquish Default for the setpoints, the supervisory controller always has an Override for either an Adjusted value or the Relinquish Default value. Use the Operator Override and the Release Operator Override to command the setpoint and release it to local control. At that time, the user is able to change the setpoint from the local display.
Table 1: N2 Bus Objects (Part 1 of 2)
Point Name Thermostat Point
(Type/Address)
Room Temp Aux Temp/Outdoor Temp
Heating SP (Occupied Heating SP)
Cooling SP (Occupied Cooling SP)
Setback Heating SP (Unoccupied Heating SP)
1
1,2
1,2
1,2
ADI-1 N2 AI CSAD 32 to 122°F (0 to 50°C)
1
ADI-2 N2 AI CSAD -40 to 122°F
ADI-3 N2 AO CSAD 40 to 90°F (4.5 to 32°C)
ADI-4 N2 AO CSAD 54 to 100°F
ADI-5 N2 AO CSAD 40 to 90°F (4.5 to 32°C)
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions4
N2 Bus Object Type
Model Point Type Range
(-40 to 50°C)
(12 to 37.5°C)
Page 5
Table 1: N2 Bus Objects (Part 2 of 2)
Point Name Thermostat Point
(Type/Address)
Setback Cooling SP
1,2
(Unoccupied Cooling SP) Minimum Heat SP ADI-7 N2 AI CSAD 40°F (4.5°C)
Maximum Heat SP Minimum Cool SP
1
1
Maximum Cool SP ADI-10 N2 AI CSAD 100°F (37.5°C)
1
Fan
1
Mode
Occupancy
1
W1 State BD-4 N2 BI CSBD 0 = Off
Y1 State BD-6 N2 BI CSBD 0 = Off
G State - Fan BD-8 N2 BI CSBD 0 = Off
Temp Units
1,5
(Local Display Only) Occupancy Override BD-10 N2 BI CSBD 0 = No Override
6,7
DI1
Temp Alarm
6,7
DI2
6
ADI-6 N2 AO CSAD 54 to 100°F
ADI-8 N2 AO CSAD 40 to 90°F (4.5 to 32°C) ADI-9 N2 AO CSAD 54 to 100°F
BD-1 N2 BO CSBD 0 = Auto
BD-2
BD-3 N2 BO CSBD 0 = Unoccupied
BD-9 N2 BO See Footnote 5. 0 = °C
BI-1 N2 BI CSBI 0 = Off
BI-2 N2 BI CSBI 0 = Normal
BI-3 N2 BI CSBI 0 = Off
N2 Bus Object Type
N2 MSO
3,4
Model Point Type Range
(12 to 37.5°C)
(12 to 37.5°C)
1 = On
CSMS 0 = Off
1 = Cool 2 = Heat 3 = Auto
1 = Occupied
1 = On
1 = On
1 = On
1 = °F
1 = Override
1 = On
1 = Alarm
1 = On
1. Commandable.
2. The Heating and Cooling Setpoint (SP) cannot be overridden simultaneously (this also applies to the Setback Heating SP and Setback Cooling SP). The overridden setpoint must be released prior to overriding the other setpoint. Additionally, if one setpoint is overridden, the other setpoint may be automatically adjusted by the TEC2101-3 thermostat to maintain the minimum deadband between the two setpoints.
3. The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs).
4. When defining the N2 MSO, select TEC Mode from the States Text Menu. Type 4 for the TEC2101-3 thermostat.
5. On the Metasys Network Control Module (NCM) system, map BD-9 Temp Units Mode as a Binary Output (BO) object with Auto Restore and Local Control set.
6. Can be a Change-of-State (COS) alarm to the BAS or N2 Dialer Module (NDM) to initiate a dial-out.
7. The state of DI1 and DI2 is communicated over the N2 network even if the digital inputs are configured as None through the local interface at the thermostat.
The Controller Point Type is the fixed-point definition inside the controller. The BAS Model Point type is the definition inside the model file. Use an NCM CS object to retrieve the data.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 5
The most recent N2 command received by any of the N2 Bus Objects listed in Table 1 controls the thermostat.
Page 6
If an Analog Data (AD) object is overridden by the Metasys system, all local changes attempted through the thermostat keypad for that AD object are ignored until the override is released. For example, if the Metasys system sends a write command to turn System Mode Off, and then the occupant selects System Mode On at the TEC keypad, the TEC ends up with the System Mode On; however, if the Metasys system sends an override command to turn System Mode Off, and then the occup ant selects System Mode On at the TEC keypad, the TEC keeps the System Mode Off.
Once an override is released, the AD object may once again be changed through the thermostat keypad, but the thermostat does not retain any data entered at the TEC keypad during the override.
Only one of the setpoints (Heating SP or Cooling SP) can be overridden at a time.
The value for Heating SP (ADI-3) and Setback Heating SP (ADI-5) must stay within the limits established in the controller by Minimum Heat SP (ADI-7 read-only) and Maximum Heat SP (ADI-8).
The value for Cooling SP (ADI-4) and Setback Cooling SP (ADI-6) must stay within the limits established in the controller by Minimum Cool SP (ADI-9) and Maximum Cool SP (ADI-10 read-only).
If a setpoint is overridden, the TEC, if necessary, adjusts the other setpoint to maint ain the minimum 2 F° deadband between the setpoints. The setpoint s can be spread farther apart but can never be adjusted closer than 2 F° apart.
Failure to stay within the limits for a command results in an N2 Negative Acknowledge (NAK) error from the TEC2101-3 thermostat.
Overrides take precedence over any local adjustment or command in the TEC2101-3 thermostat.
You must not have a Relinquish Default for the setpoints if you want to change them from the thermostat display.
If there is a Relinquish Default for the setpoints, the Network Automation Engine (NAE) always has an Override for either an adjusted value or the Relinquish Default Value. You should use Operator Override and Release Operator Override if you want to command the setpoint and release it to local control.
Once all the NAE commands are released, the Override Status in the Hardware tab should be False. At that time, the user should be able to change the setpoint from the local display.
All overrides are released automatically after 10 minutes of no communications (for example, network cable is removed from the TEC, causing loss of network communications).
Setup and Adjustments
Thermostat Operation Overview
Backlit, pl ain text
LCD is easy to read
in any condi t io n.
Five keys on the therm ostat make operation easy and intuitive.
Room Temp
70.0ºF
YES NO
Figure 6: Front Cover of Thermostat
LEDs indicate system activity.
w
v
_
t
n
r
f
: G
I F
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions6
Page 7
Thermostat User Interface Keys
The TEC2101-3 Thermostat user interface consists of five keys on the front cover (as illustrated in Figure 6). The function of each key is as follows:
•Use the YES/SCROLL key to:
- confirm menu selections and to advance to the next menu item
- stop the Status Display Menu fr om scrolling and to manually scroll to the next parameter on the menu
Note: When the thermostat is left unattended for 45 seconds, the thermostat display resumes scrolling.
•Use the NO key to decline a parameter change and to advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or to exit the menu
(See the Programming Overview section.)
- access the Installer Configuration Menu or to
exit the menu (See the Configuring the TEC2101-3 Thermostat section.)
•Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment.
Backlit Liquid Crystal Display (LCD)
The TEC2101-3 Thermostat includes a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brighten s when any user interface key is pressed. The backlight returns to low level when the thermostat is left unattended for 45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
•The FAN LED is on when the fan is on.
•The HEAT LED is on when heating is on.
•The COOL LED is on when cooling is on.
Programming Overview
There are three menus used to view, program, and configure the TEC2101-3 thermostat.
The Status Display Menu is displayed during normal thermostat operation. This menu continuously scrolls through the following parameters:
Room Temperature
System Mode
Occupancy Status – Occupied/Unoccupied/ Override
Outdoor Temperature – An outdoor air temperature sensor must be connected.
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: Press the YES/SCROLL key to temporarily stop this menu from scrolling.
The Main User Menu is used to access and change the basic operating parameters of the thermostat. Access this menu by pressing the MENU key during normal thermostat operation.
The Installer Configuration Menu is used to set up the thermostat for application-specific operation. To access this menu, press and hold the MENU key for approximately 8 seconds.
Configuring the TEC2101-3 Thermostat
The TEC2101-3 Thermostat comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 2. To reconfigure the parameters via the thermostat, follow these steps:
1. To access the Installer Configuration Menu, press and hold the MENU key for approximately 8 seconds.
2. Once the Installer Configuration Menu begins, press the NO key to scroll through the parameters listed in Table 2.
3. When the desired parameter is displayed, use the YES key to choose the desired selection option.
4. Press the YES key and then the NO key to continue scrolling through the parameters.
To exit the Installer Configuration Menu at any time, press the MENU key and press the YES key at the exit prompt. To pass over a parameter without changing it, press the NO key.
When the thermostat is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat reverts to the Status Display Menu.
Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
Both inputs can be configured to the Selection Options included in Table 2.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 7
Page 8
Table 2: Installer Configuration Menu (Part 1 of 3)
Parameter
Description and Default Selection Options Appearing on Display
DI1 Configuration of Digital Input 1.
Default: None
DI2 Configuration of Digital Input 2.
Default: None
Lockout Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
Pwr del
1
Sets the delay time period at
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
(None): No function is associated with an input. (Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(None): No function is associated with an input. (Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
Function Level
Resume/Occupancy Override Scheduling
Permanent T emperature Setpoints
T emporary T emperature Setpoints
System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Range: 10.0 to 120.0 sec
(0) (1) (2)
Access Access No Access
Access No Access No Access
Access Access No Access
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions8
Page 9
Table 2: Installer Configuration Menu (Part 2 of 3)
Parameter
Description and Default Selection Options Appearing on Display
Frost pr Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default: off
Heat max
Cool min
Anticycl Anti-Short Cycle timer sets the
Heat cph Sets the maximum number of
Cool cph Sets the maximum number of
Deadband Sets the minimum deadband
Fan cont Determines how the fan is activated
Fan del Fan delay extends fan operation
Com addr N2 network address at the
2
2
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°/12.0°C
minimum on/off times for heating
and cooling.
Default: 2.0 min
Heating cycles per hour.
Default: 4.0
Cooling cycles per hour.
Default: 4.0
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
in response to a call for heating.
Fan cont applies to W1 and Fan
Mode auto only. Fan cont does not
affect fan operation on a call for
cooling (Y1).
Default: on
after a heating or cooling cycle has
ended.
Default: off
thermostat; coincides with the
address assigned at the supervisory
controller.
Default: 4
(on): Enabled (off): Disabled
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
Range: 0.0 to 5.0 min adjustable in 1-minute increments Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C° increments
(off): The thermostat does not activate the fan in response to a call for heating. The fan is activated by the equipment fan and limit control.
(on): Enables the thermostat to control the fan.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended. (off): No extension of fan operation after a heating or cooling cycle
has ended. The fan delay is only active when the fan is in the Auto mode.
Range: 1 to
255
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 9
Page 10
Table 2: Installer Configuration Menu (Part 3 of 3)
Parameter
Description and Default Selection Options Appearing on Display
TOccTime Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary hea ting or cooling
setpoints set using the up/down
arrow keys.
Default: 3.0 hrs Cal RS Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C Cal OS Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C° H lock Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C C lock Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C Aux cont Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
(n.c.): Contact open = Occupied; contact closed = Unoccupied. (n.o.): Contact closed = Occupied; contact open = Unoccupied.
The contact toggles with the internal Occupied/Unoccupied schedule (or the NSB contact on one of the digital inputs, if used).
1. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and hold the UP or DOWN arrow key to change the numeric value in increments of ten.
2. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions10
Page 11
Operation
Programming/Operating the TEC2101-3 Thermostat
Once the thermostat is configured via the Installer Configuration Menu, its operating parameters can be programmed via the Main User Menu. Access this menu by pressing the MENU key during normal thermostat operation. The Main User Menu contains the basic operating features of the thermostat.
The Main User Menu also uses Auto Help, which is displayed automatically in the menu when there is a pause in programming activity. To exit Auto Help, continue with the programming selection. When the thermostat is in the Main User Menu and is left unattended for 45 seconds, the menu reverts to the Status Display Menu.
Enabling Override Schedule
Note: Enabling Override Schedule only appears when in the Unoccupied Mode.
The override schedule prompt only appears when the thermostat is in the unoccupied state. This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the amount of time specified under the TOccTime parameter . See the Configuring the TEC2101-3 Thermostat section.
Note: If one of the digital inputs is configured to operate as a remote override contact, this menu is disabled.
T o o verride the unoccupied state while in the Main User Menu:
1. Press the NO key to all prompts until the Override Schedule prompt appears. If the thermostat is in the unoccupied state, this is the first prompt.
2. Press the YES key to resume the programmed schedule.
The thermostat returns to the Status Display Menu.
Entering Permanent Temperature Setpoints
The first prompt appearing in the Main User Menu of the thermostat when in the occupied state is to set the permanent temperature setpoint.
To enter the permanent heating and cooling setpoints for the Occupied and Unoccupied Modes, follow the steps in Table 3. When changing the temperatures, press the keys once to change the temperature in
0.5F°/0.5C° increments; press and hold down the keys
to change the temperature in 5.0F°/5.0C° increments.
Table 3: Entering Permanent Temperature
Setpoints (Part 1 of 2)
Thermostat Display
RoomTemp
75.0°F
Temperat set? Y/N
Cooling set? Y/N
Cooling
75.0°F
Description
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
Press the NO key to all prompts until the temperature setpoint prompt appears on the display (it may be the first prompt). Press the YES key to enter the temperature setting menu.
Press the YES key to change the occupied cooling setpoint. Press the NO key to advance to the occupied heating setpoint menu.
Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu.
2. Press the YES key to enable the temporary override. The thermostat returns to the Status Display Menu.
When scrolling through the Status Display Menu, Override now appears for the occupancy status parameter.
Resuming the Programmed Schedule
This menu only appears when the thermostat is in the unoccupied override mode.
To resume the schedule while in the Main User Menu:
1. Press the NO key to all prompts until the Cancel ovrd Y/N prompt appears. If the thermostat is in the unoccupied override state, this is the first prompt.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 1 1
Heating set? Y/N
Heating
68.0°F
Unocc CL set? Y/N
Press the YES key to change the occupied heating setpoint. Press the NO key to advance to the unoccupied cooling setpoint menu.
Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu.
Press the YES key to change the unoccupied cooling setpoint. Press the NO key to advance to the unoccupied heating setpoint.
Page 12
Table 3: Entering Permanent Temperature
Setpoints (Part 2 of 2)
Thermostat
Description
Display
Press the UP/DOWN arrow keys to
Unocc CL
80.0°F
Unocc HT set? Y/N
Unocc HT
62.0°F
C
°F/°
set? Y/N
Exit? Y/N
set the temperature. Press the key to store the value and advance to the next menu.
Press the unoccupied heating setpoint. Press the temperature display units.
Press the set the temperature. Press the key to store the value and advance to the next menu.
Press the units to °F or °C. Press the advance to the temperature setpoint type menu.
Press the Status Display Menu or press the key to reenter the temperature setting menu.
YES key to change the
NO key to advance to the
UP/DOWN arrow keys to
YES key to set the display
YES key to return to the
YES
YES
NO key to
NO
Entering Temporary Temperature Setpoints
To temporarily change the setpoint, press the UP/DOWN arrow keys to change the temporary setpoint for the current mode of operation.
Note: Whether the thermostat is heating or cooling, the respective setpoint is temporarily adjusted. To toggle between the temporary heating and cooling setpoints, press the NO key while changing the temporary setpoints.
Ending Temporary Temperature Setpoints
The temporary setpoints remain in effect for the duration set in the TOccTime parameter or until manually released.
To release the temporary setpoint sooner, while in the Main User Menu:
1. Press the YES key to the first prompt that appears.
2. If the thermostat does not immediately return to the Status Display Menu, press the MENU key again and press the YES key to exit the Main User Menu.
The setpoint reverts to the Permanent Temperature Setpoint.
Selecting the System Mode
The thermostat has four system modes:
Automatic Mode (auto): Automatic changeover between heating and cooling. This is the default setting.
Cooling Mode (cool): Cooling operation only
Heating Mode (heat): Heating operation only
Off Mode (off): The thermostat is off; however, when frost protection (Frost pr parameter) is enabled, the thermostat still calls for heat (if required).
To set the system mode while in the Main User Menu:
1. Press the NO key to all prompts until the system mode prompt appears on the display. Press the YES key to select the desired system mode.
2. Press the UP/DOWN arrow keys to locate the desired system mode. Press the YES key to select the desired system mode.
3. Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu.
Selecting the Fan Mode
The thermostat has three fan mode settings:
On Fan Mode (on): Energizes the fan all the time for both occupied and unoccupied states, even if the system mode is set to off.
Automatic Fan Mode (auto): Energizes the fan only on a call for heating or cooling, for both occupied and unoccupied states.
Smart Fan Mode (smart): Energizes the fan all the time for occupied states, and only on a call for heating or cooling in unoccupied states. This is the default setting.
To select the fan mode while in the Main User Menu:
1. Press the NO key to all prompts until the fan mode prompt appears on the display. Press the YES key to set the fan mode.
2. Press the UP/DOWN arrow keys to locate the desired fan mode. Press the YES key to select the desired fan mode.
3. Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions12
Page 13
Accessories
All the accessories in Table 4 include mounting
Note: Review the technical specifications of the optional accessories prior to their use in an application .
hardware; contact the nearest Johnson Controls® representative to order any of these parts.
Table 4: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-6361M-1 TE-6363P-1
1
1
Duct Mount Air Temperature Sensor Outdoor Air Temperature Sensor
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
Series Temperature Sensors Product Bulletin (LIT-216320)
for more details.
Repair Information
If the TEC2101-3 Thermostat fails to operate within its specifications, see Table 5 for troubleshooting details and Table 6 for alarm messaging. For a replacement thermostat, contact the nearest Johnson Controls representative.
Table 5: Troubleshooting Details
Error/Trouble Condition
Thermostat Cycles Online and Offline
Thermostat Does Not Come Online
N2 Bus is Offline The wiring on the N2 Bus is broken. Repair the wiring.
Possible Cause Solution
Two or more controllers have the same address. Change each duplicate address to a unique
number.
There are Y or T taps on the N2 Bus, or the repeater has lost power or is wired incorrectly.
Two or more controllers have the same address. Change each duplicate address to a unique
The N2 Bus contains too many devices. Do not exceed the maximum number of devices
The thermostat does not have power. Apply power to the thermostat. The N2 cable runs are broken. Locate the break and correct the wiring. The thermostat device type is incorrect. Change the thermostat device type to VND.
No point mapping has been entered. Define the BAS dataset.
Refer to the
Bulletin (LIT-636018)
number.
allowed on the N2 Bus per supervisory controller limitations.
N2 Communications Bus Technical
.
TE-6300
Table 6: Display Messages
Display Function
Frost ON Indicates that heating is energized by the low limit frost protection room temperature setpoint. Service Indicates that there is a service alarm in accordance with the programmable Digital Inputs (DI1 or DI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Digial Inputs (DI1 or DI2).
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 13
Page 14
Technical Specifications
TEC2101-3 N2 Networked Single-Stage Thermostat
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating 30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV Digital Inputs Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2 Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended Temperature Sensor Type Local 10k ohm Type II Negative Temperature Coefficient (NTC) Thermistor Temperature
Range
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Minimum Deadband 2F°/1C° between Heating and Cooling Ambient
Conditions Compliance United States UL Listed, File E27734, CCN XAPX,
Shipping Weight 0.75 lb (0.34 kg)
Backlit Display
Heating Control
Cooling Control
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 89/336/EEC Australia and
New Zealand
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street Milwaukee, WI 53202
© 2006 Johnson Controls, Inc.
TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions14
Published in U.S.A. www.johnsoncontrols.com
Loading...