TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat
Controllers with Dehumidification Capability, Fan Control, and
Occupancy Sensing Capability
Installation Instructions
Part No. 24-9890-1095, Rev. B
Issued July 13, 2010
Supersedes May 17, 2010
Applications
The TEC Series Wireless Thermostat Controller
System provides wireless networked control of
Heating, Ventilating, and Air Conditioning (HVAC)
equipment on a Building Automation System (BAS)
that enables remote monitoring and programming. This
TEC Series System integrates into a supervisory
controller that uses BACnet® Internet Protocol (IP) or
BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controlle r to
communicate with multiple TEC Wireless Thermostat
Controllers. TEC20x6(H)-4 and TEC20x6H-4+PIR
Series Wireless Thermostat Controllers control two- or
four-pipe fan coils, cabinet unit heaters, or other
equipment using on/off, floating, or proportional
0 to 10 VDC control input, three speeds of fan control,
and dehumidification capability.
The TEC20x6H-4+PIR Series Thermostat Controllers
have occupancy sensing capability built into the device.
These devices maximize up to 30% energy savings in
high-energy usage light commercial buildings, such as
schools and hotels, during occupied times by using
additional standby setpoints. See the Occupancy
Sensor Operation – TEC20x6H-4+PIR Series
Thermostat Controllers section for more information.
The wireless mesh network uses ZigBee™ technology
to enable remote monitoring and programming and to
enhance reliability by providing redundant transmission
paths through other TEC Wireless Thermostat
Controllers, creating a resilient, self-healing mesh
network.
IMPORTANT: The TEC20x6(H)-4 and
TEC20x6H-4+PIRSeries WirelessThermostat
Controllers are intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controllercould lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the
thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with
1.This device may not cause harmful interference, and
2.This device must accept any interference received,
including interference that may cause undesired
operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by
the party responsible for compliance could void the
user’s authority to operate the equipment
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability
.
1
Page 2
Canada
Figure 1: Removing the Cover
FIG:cvr_ rmvl
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number
only signifies that the Industry Canada technical
specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est
conforme aux spécifications techniques d'Industrie
Canada.
Installation
Location Considerations
Locate a thermostat controller:
•on a partitioning wall, approximately 1.5 m (5 ft)
above the floor in a location of average
temperature
For detailed information on locating devices for
optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294).
Installing the Thermostat Controller
Follow these steps to install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the
security screw if it is installed on the bottom of the
thermostat controller cover.
Note: Normally, the security screw is packaged
separately in a plastic bag with the thermostat
controller. Skip this step if the screw is not installed
on the bottom of the cover.
2. Pull the bottom edge of the thermostat cover and
open the thermostat as illustrated in Figure 1.
Note: PIR Models have a wiring connection
between the cover and the Printed Circuit Board
(PCB). This connection allows for proper wiring of
the occupancy sensor . Car efully remove the wiring
connection from the PCB by pulling up on the
connector block. Do not attempt to remove the connector block by pulling on the wires.
•away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
Note: Allow for vertical air circulation to the
TEC20x6(H)-4 and TEC20x6H-4+PIR Series
Thermostat Controllers.
For integrated Passive Infrared (PIR) models, make
sure the thermostat controller is located centrally,
where occupant movement is frequent.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a
TEC20 Coordinator and a TEC Wireless Thermostat
Controller (or between TEC Wireless Thermostat
Controllers) can be less than the recommended
distances shown in Table 1. The effective transmission
range for indoor applications varies because of Radio
Frequency (RF) signal absorption and re flectio n due to
metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
TypeDistance
Through Walls 10 m (32.8 ft)
Open Space 30 m (98.4 ft)
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
2
Capability, Fan Control, and Occupancy Sensing Capability
Page 3
3. Carefully pull the locking tabs on the right side of
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Figure 3: Securing the
Mounting Base to the Wall
Figure 4: Removing the Screw Terminal Blocks
the mounting base and unlock the PCB. Open the
PCB to the left as illustrated in Figure 2.
PCB
Locking
d
r
b
4. Pull approximately 152 mm (6 in.) of wire from the
wall and insert the wire through the hole in the
mounting base.
5. Align the mounting base on the wall, and use the
base as a template to mark the two mounting hole
locations.
Note: If you need to install the thermostat on an
electrical junction box, use 2-1/2 x 4 in.
(63 x 101 mm) square boxes with mud ring covers,
and avoid smaller 1-1/2 x 4 in. (38 x 101 mm)
square or 3 x 2 in. (76 x 51 mm) boxes. This
procedure ensures you have enough space for
cabling and end-of-line devices, if needed.
s
b
_
g
n
t
n
m
:
G
I
F
8. Swing the PCB back to the right, and carefully
snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks that are
attached to a disposable adhesive. Figure 4
illustrates the locations of the screw terminal
blocks on the thermostat controller.
Note: For surface-mount applications, use
durable mounting hardware such as Molly bolt
anchors that cannot be easily pulled out of the
mounting surface.
6. Position the thermostat mounting base on the wall
so that the arrow on the base points upward to
indicate the top of the thermostat.
7. Secure the mounting base to the wall surface using
two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting
screws.
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
3
Capability, Fan Control, and Occupancy Sensing Capability
Page 4
Wiring
!
!
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
Note: If multiple wires are inserted into the screw
terminals, be sure to properly twist the wires
together prior to inserting them into the screw
terminals.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the
ambient temperature readings.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the thermostat controller.
When replacing an existing thermostat controller,
remove and label the wires to identify the terminal
functions. When replacing a thermostat controller of the
same model, simply remove the old screw terminal
blocks and reinsert them onto the PCB of the
replacement thermostat controller.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the
terminals, be sure to properly twist the wires
together prior to inserting them into the terminal
connectors.
4. Reattach the cover to the mounting base (top side
first).
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the cover.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
4
Capability, Fan Control, and Occupancy Sensing Capability
Page 5
See Figure 5, Figure 6, Figure 7, and Table 2 for
Fan
-H
Three-Pole
Right Top
Connector
BO2
BO5
Aux
BO1/
AO1
UI3
BI1
BI2
Fan
-M
Fan
-L
24 V~
Hot
Com
BO4/
AO2
Left T o p Connector
1 2 3 4 5
F
I
G
:
T
E
C
2
0
x
6
H
2
_
T
R
M
N
L
S
Figure 5: TEC20x6(H)-4 and TEC20x6H-4+PIR
Series Thermostat Controller Terminals
Figure 6: TEC20x6(H)-4 and TEC20x6H-4+PIR Series Thermostat Controllerwith
Separate Power Source for Auxiliary Contact
Scom
Contact
• COC/NH
= Cold Water
• COC/NC
Normall y Cool
= Hot Water
Voltage-Free
Contact
• Door
• Remote
Override
• Filter Alarm
• Service Alarm
Voltage-Free
Contact
• Remote NSB
• Motion
• Window
(24 VA C Maximum )
BO5
Aux
BO5
Aux
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Power and Fan
Aux Contact
(Isolated Co m m on)
• Reheat
• Lighting
• Exhaust Fan
Aux
Fan
-H
Fan
-M
Fan
-L
information on wiring the thermostat controllers.
Five-Pole
24 V~
BO5
BO3
Aux
6 7 8
Eight-Pole Bottom Connector
Scom
RS
9 10 11 12 13 14 15 16
Separate 24 VAC
Power Source for Auxiliary Output
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
• On/Off Actuation
Remote Inputs
BI1
- OR -
Supply S ensor
Changeover Sensor
FIG:TEC20x6 H4_SEP
BI2UI3
Voltage-Free
Normally Heat
Closed Contact
Closed Contact
5
Page 6
Figure 7: TEC20x6(H)-4 and TEC20x6H-4+PIR Series Thermostat Controller with
Same Power Source for Auxiliary Contact
Scom
Contact
• COC/NH
= Cold Water
• COC/NC
Normally C ool
= Hot Water
Voltage-Free
Contact
• Door
• Remote
Override
• Filter Alarm
• Service Alarm
Voltage-Free
Contact
• Remote NSB
• Motion
• Window
C
Power Source for Auxiliary Output
(24 VA C Maximum)
Power and Fan
BO5
Aux
BO5
Aux
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fan
Aux
24 VAC
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Same 24 VA
Aux Contact
(Isolated Co m m on)
BI1
Remote Inputs
BI2
FIG:TEC20x6 H4_SAM
UI3
Voltage-Free
Thermostat Power
Table 2: TEC20x6(H)-4 and TEC20x6H-4+PIR Series Thermostat Controller Terminals
TEC2026-4,
TEC2026H-4,
TEC2026H-4+PIR
TEC2036-4,
TEC2036H-4,
TEC2036H-4+PIR
(On/Off or Floating
Control)
1Fan-HFan-HFan-HFan On – High
2Fan-MFan-MFan-MFan On – Medium
3Fan-LFan-LFan-LFan On – Low
424 V~ Hot24 V~ Hot24 V~ Hot24 VAC from Transformer
524 V~ Com24 V~ Com24 V~ Com24 VAC from Transformer
Figure 8: Wiring TEC2016(H)-4 and TEC2016H-4+PIR Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Four-Pipe Applications
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 9: Wiring TEC2026(H)-4, TEC2026H-4+PIR, TEC2036(H)-4, and TEC2036H-4+PIR
Thermostat Controllers for On/Off Control
Two -Pip e Applicat ions
FIG:TEC2026H4_TEC2036H4_onoff
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 10: Wiring TEC2026(H)-4, TEC2026H-4+PIR, TEC2036(H)-4, and TEC2036H-4+PIR
Thermostat Controllers for Floating Control
Four-Pipe Applications
FIG:TEC2026H4_TEC203 6H4_flt
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 8 through Figure 11 show sample applications
for these thermostat controllers.
24 V~
24 V~
FIG:TEC2016 H4_onoff
24 V~
Two -Pip e Applic ations
Four-Pipe Applications
24 V~
BO2 BO3
BO4
24 V~
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
7
Page 8
Setup and Adjustments
Figure 11: Wiring TEC2046(H)-4, TEC2046H-4+PIR, TEC2056(H)-4, and TEC2056H-4+PIR
Thermostat Controllers fo r Pr oportional Control
Two -Pip e Applic ations
Four-Pipe Applications
FIG:TEC2046H4_TEC2056H4_prop
Heating/Cooling
Valve
Com
Hot
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
Figure 12: Front Cover (TEC20x6H-4+PIR Model Shown)
70.0ºF
FIG:TEC20x6(H)PIR_wrlss_
Status LED beneath cover
indicates network status.
Five keys on the therm ost at controll er
make operation easy and intuitive.
Backl i t, plain t ex t
Liquid Crystal Display (LCD)
is easy to rea d in any conditio n.
Light-Emitting Diodes (LEDs)
indicate system acti vi t y.
PIR mot io n detector
saves ener gy using
standby se tp oi nt s.
AO1
AO2
24 V~
24 V~
Thermostat Controller User Interface Keys
The user interface consists of keys on the front cover
(Figure 12). The function of each key is as follows:
•MODE key toggles among the system modes
available, as defined by selecting the appropriate
operation sequence in the Installer Configuration
Menu (Off, Heat, Cool, Auto).
•FAN key toggle s am on g th e fan mode s available,
as defined by selecting the appropriate fan menu
options defined in the Installer Configuration Menu
(Low, Med, High, Auto).
•OVERRIDE key (commercial models) overrides
the unoccupied mode to occupied at the local user
interface for the specified TOccT ime. (T OccTime is
defined by selecting the appropriate time period in
the Installer Configuration Menu.)
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
8
Capability, Fan Control, and Occupancy Sensing Capability
Room Temp
•°C/°F key (hospitality models) changes the
•UP/DOWN arrow keys change the configuration
frntvw
If one of the binary inputs is configured to operate
as a remote override contact, this OVERRIDE
function is disabled. The OVERRIDE key also
allows access to the Installer Configuration Menu.
(See the Configuring the Thermostat Controller
section.)
temperature scale to either Celsius or Fahrenheit
and allows access to the Installer Configuration
Menu. (See the Configuring the Thermostat Controller section.)
Note: For hospitality models, binary inputs can
override from the unoccupied mode to occupied
mode.
parameters and activate a setpoint adjustment.
Page 9
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•The fan LED is on when the fan is on.
Status Display Menu
The Status Display Menu displays during normal
operation. This menu scrolls through several
parameters:
•Room Temperature
•The heat LED is on when heating is on.
•The cool LED is on when cooling is on.
The Status LED, located beneath the cover, flashes at
5-second intervals to provide indication of the network
status of the thermostat controller. See Table 3.
Table 3: Status LED
Flashes per
5-Second
Interval
1Power On
2Power On, Communicating
3Power On, Communicating, Found
4Power On, Communicating, Found
Condition Indicated
Wireless Network
Wireless Network, Communicating with
TEC20 Coordinator
Integrated PIR Sensor –
TEC20x6H-4+PIR Series Thermostat
Controllers
The integrated PIR sensor allows for automatic
switching between fully adjustable Occupied and
Stand-By temperature setpoints without user
interaction. This feature generates incremental energy
savings during scheduled occupied periods while the
space is unoccupied.
Backlit Liquid Crystal Display (LCD)
The thermostat controller includes a 2-line, 8-ch aracter
backlit display. Low-level backlighting is present during
normal operation, and it brightens when any user
interface key is pressed. The backlight returns to low
level when the thermostat controller is left unattended
for 45 seconds.
•Room Temperature and Humidity (TEC2036-4,
TEC2036H-4, TEC2036H-4+PIR, TEC2056-4,
TEC2056H-4, and TEC2056H-4+PIR mod e ls)
Note: For models with dehumidification capability ,
the default setting is no humidity reading on the
display (%RH disp parameter is set to off.) The
%RH disp parameter must be set to on to display
the current humidity reading.
•System Mode
•Occupancy Status (Occupied/Unoccupied/
Override)
•Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Dehumidification Operation –
TEC2036(H)-4 and TEC2056(H)-4 Thermostat
Models
Upon detection of room humidity above the adjustable
humidity setpoint as sensed by the integral humidity
sensor, dehumidification activates.
Note: Dehumidification operation functions only in the
Cooling mode; dehumidification operation does not
function in either the Off or the Heating mode.
Note: A central network command can globally
lock out dehumidification operation to all thermostats.
If the room temperature resides in the deadband
between the Heating and Cooling setpoint:
•the thermostat forces the fan to low speed
•the chilled water valve opens to the specified
maximum value set by CoolMax
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
•the thermostat stages Heating to maint ain the room
temperature at the Cooling setpoint, as sensed by
the thermostat
If the room temperature falls below the current Heating
setpoint, the thermostat disables dehum idification
operation.
9
Capability, Fan Control, and Occupancy Sensing Capability
Page 10
If the thermostat is in Cooling demand:
•the chilled water valve opens to 100%
•the thermostat stages Heating to maint ain the room
temperature at the Cooling setpoint, as sensed by
the thermostat
If the thermostat is in Cooling demand and the room
temperature rises 2F°/1C° above the Cooling setpoint,
the thermostat automatically disables dehumidification
operation. Likewise, if the thermostat is in Cooling
demand and the room temperature falls below the
current Heating setpoint, the thermostat disables
dehumidification operation.
Occupancy Sensor Operation –
TEC20x6H-4+PIR Series Thermostat
Controllers
A TEC20x6H-4+PIR Series Thermostat Controller–or a
TEC20x6(H)-4 Series Thermostat Controller equipped
with a PIR accessory cover–provides advanced
occupancy logic.
Note: The PIR strategy is an occupied strategy. If the
thermostat controller is programmed to be Unoccupied,
the PIR function does not have an effect on the
occupancy strategy.
The thermostat controller automatically switches
occupancy levels from Occupied to Stand-By and
Unoccupied as required, when local movement is
sensed.
Occupancy sensing is enabled only if a PIR cover is
installed on the thermostat controller (PIR models) or if
a remote input is configured as a remote PIR sensor
(MotionNO or MotionNC).
PIR Warm-Up Period
When a PIR cover is used and a thermostat controller
is powered up, there is a 1-minute warm-up period
before any local movement can be detected and
acknowledged by the PIR sensing device. The local
status LEDs for the PIR function are not active, and the
sensor is in Stand-By mode for the 1-minute period.
The PIR functionality and local movement status LEDs
are activated after the 1-minute warm-up period has
elapsed after the initial powering of the thermostat
controller. If movement is present, the mode changes
to Occupied.
PIR Diagnostic LEDs
The diagnostic LEDs inside the PIR lens brighten when
movement is detected within the first 30 minutes after
powerup. The LEDs do not light up or brighten after the
initial 30-minute period.
Setpoints
The Stand-By setpoints are under the same limitations
and restrictions as the Occupied and Unoccupied
setpoints. Stand-By setpoints reside between the
corresponding Occupied and Unoccupie d se tp oint
values.
The installer must be certain that the difference
between the Stand-By and Occupied values can be
recovered within a timely fashion to ensure occupancy
comfort. In addition, the difference between the two
values must be large enough to warrant maximum
energy savings.
Hotel and lodging applications can benefit from the
addition of an entry door switch wired to one of the
binary inputs of the thermostat controller. When a door
contact is used and configured, the S t and-By timer and
its configuration are no longer active or used. The
occupancy toggle between Occupied and Stand-By is
then dictated by both the door contact and the
PIR sensing device used. If movements are detected
by the PIR sensor and the door is closed, the room is
considered occupied. The thermostat controller
switches back to S tand-By m ode only if the door switch
toggles open/closed. Motion is ignored when the door
switch indicates an open door.
PIR occupancy functionality is dictated by both the
Stand-By timer and Unoccupied timer configuration
value and movements present in the area.
Unoccupied Timer Disable
It might be preferable for the local area to stay out of
Unoccupied mode and always stay at the Stand-By
occupancy level when no activity is present. In
instances when areas always need to be on Stand-By
status, ready to respond to demand at any given point
in time, we recommend disabling the Unoccupied timer .
When the local PIR occupancy routine is running at the
thermostat controller, the zone drifts into Unoccupied
mode when the Unoccupied timer is set above its
factory default value of 0.0 hours.
For more information on occupancy sensor operation,
refer to the TEC2x45-4, TEC2xx6(H)-4,
TEC2xx6H-4+PIR, and TEC2xx7-4 Series Thermostat
Controllers Application Note (LIT-12011594).
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
10
Capability, Fan Control, and Occupancy Sensing Capability
Page 11
St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Figure 13: Increasing Room Temperature Setpoints
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hours
= 6 Hours
Time
Last Mov ement Detected
by PIR Devi ce
Stand-By Time Elapsed
= Stand-By Mode
Stand-By
= 2 Hrs
Unoccu pied T ime
= 6 Hour s
Last Mov ement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
= Unoccu pied Mode
FIG:unocc6sb2
First Movement
Detected
by PIR Device
First Movement
Detected by PIR Device
Figure 14: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
Stand-By
Unoccupied
Stand-By
= 2 Hrs
= 0 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time
= 0 Hours
Last Movement D et ected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
FIG:unocc0sb2
First Movement Detected
by PIR Device
Stand-By
= 2 Hrs
First Movement Detected
by PIR Device
Figure 15: Unoccupied Timer Set to 0 Hours and Stand-by Timer Set to 2 Hours
Occupied
Unoccupied T ime
Time
Unoccupied Time Elapsed
Unoccupied T ime
Time
Configuring the Thermostat Controller
The thermostat controller ships from the factory with
default settings for all configurable parameters. The
default settings are shown in Table 6. To reconfigure
the parameters, follow the steps in this section.
1. To access the Installer Configuration Menu, press
and hold the center key for approximately
8 seconds.
Note: If the Password parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
Use the UP/DOWN arrow keys to indicate the
configured password, then press the MODE key to
proceed through the Installer Configuration Menu
parameters.
2. Once the Installer Configuration Menu begins,
press and release the center key to scroll through
the parameters listed in Table 6.
3. When the desired parameter is displayed, use the
UP/DOWN arrow keys to choose the desired
selection option.
4. Press and release the center key to continue
scrolling through the parameters.
11
Page 12
Note: Pressing the FAN key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 6.
The UI3 input provides changeover of hot/cold water
switching or supply air temperature monitoring at the
thermostat controller.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition displays locally when the
input closes. An alarm message is included on the
scrolling Status Display Menu and when the message
is displayed, the backlight momentarily lights up.
Each input can be configured to the Selection Options
included in Table 6.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequen ce
of operation selected. For two-pipe applications using a
changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between
Cooling Only and Heating Only. See Figure 16
through Figure 21 for sequence of operation examples.
Table 4: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 16.10: Normally Open
(1): Heating OnlySee Figure 17.10: N.O. Heating
(2): Cooling with ReheatSee Figure 18.6 and 7: Reheat
(3): Heating with ReheatSee Figure 19.6 and 7: Reheat
Control
Curve
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off ControlFloating ControlProportional
(N.O.) Cooling
11: Normally Closed
(N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling
11: N.C. Cooling
10: N.O. Heating
11: N.C. Heating
10: Open Cooling
11: Closed Cooling
10: Open Heating
11: Closed Heating
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
10: Open Heating
11: Closed Heating
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
10: Proportional Heating
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
12
Capability, Fan Control, and Occupancy Sensing Capability
Page 13
Table 5: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 16.10: N.O. Cooling
(1): Heating OnlySee Figure 17.8: N.O. Heating
(2): Cooling with ReheatSee Figure 18.6 and 7: Reheat
(3): Heating with ReheatSee Figure 19.6 and 7: Reheat
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
9: Proportional Heating
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
10: Proportional Cooling
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
13
Capability, Fan Control, and Occupancy Sensing Capability
Page 14
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 16: Cooling Only
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 17: Heating Only
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
or Propor t ional
Outputs
Heating Output
Cooling Output
Off
Off
On
On
Figure 18: Cooling with Reheat
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 19: Heating with Reheat
Figure 20: Heating/Cooling When Out1Conf = 4.0
Heating Setpoint
Closed
Device
Opened
FIG:htng_clng
Deadband
or Propor t ional
Outputs
Heating Output
Cooling Output
Device
Closed
Device
Opened
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
(Increments of 1F°/0.5C°)
On/Off, Floating,
On
Temperature Increase
Cooling Setpoint
100%
0%
t
h
r
On/Off, Floating,
Device
Temperature In cr ease
(Increments of 1F°/0.5C°)
14
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
Device
Temperature Increase
(Increm ents of 1F°/0. 5C°)
Page 15
Heating Setpoint
Device
Closed
Device
Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat
Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put
Cooling Output
Off
Off
On
On
Figure 21: Heating/Cooling with Reheat, Four-Pipe Applications
Figure 22: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature Deviation fr om Setpoint, F°
2.0F°/1. 0C° to
5.0F°/2.5C°
Deadband
100%
0%
2.5
2.5
2.02.0
1.5
1.50.50.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Setpoint
High
FIG:fn_oprtn
Fan
Speed
The fan is of f
between the
heating and
if the
parameter is
set to .
Auto Fan
AS AD
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer
Configuration menu to set the available Fan Mode
options. Use the FAN key to select the desired Fan
Mode option.
When selection option (2): Low-Med-High-Auto is
chosen in the Fan Menu parameter, the fan operates
as shown in Figure 22. When selection option
(3): Low-High-Auto is chosen in the Fan Menu
parameter, the fan operates at only the low and high
settings, ignoring the medium setting (Figure 22). This
operation applies to the occupied mode when the fan is
set to Auto.
Heating
cooling se t points
Cooling
Setpoint
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
15
Page 16
Configuring the Wireless Mesh Network
Settings
Use the following process to configure the wireless
mesh network.
1. Select a PAN ID and Channel. Use these same
values for every TEC Wireless Thermostat
Controller (and the associated TEC20 Coordinator)
on the same wireless mesh network. See Table 6.
2. Select a Com Address for each TEC Wireless
Thermostat Controller (1 to 254). This address
must be unique to each TEC Wireless Thermostat
Controller on the same wireless network (that is,
unique to the PAN ID/Channel combination). See
Table 6.
After configuring the wireless mesh network settings,
refer to the TEC20xx-4 and TEC20xx-4+PIR Series
Wireless Thermostat Controller System Technical
Bulletin (LIT-12011596) for directions on integrating the
TEC Wireless Thermostat Controllers and TEC20
Coordinator with a supervisory controlle r.
Dehumidification (TEC2036[H]-4, TEC2036H-4+PIR,
TEC2056[H]-4, and TEC2056H-4+PIR Models Only)
Upon detection of room humidity above the adjustable
humidity setpoint as sensed by the integral humidity
sensor, dehumidifica tion activates.
Note: Dehumidification operation functions only in the
Cooling mode; dehumidification operation does not
function in either the Off or the Heating mode.
Note: A central network command can globally
lock out dehumidification operation to all thermostat
controllers.
If the room temperature resides in the deadband
between the Heating and Cooling setpoint:
•the thermostat controller forces the fan to low
speed
•the chilled water valve opens to the specified
maximum value set by CoolMax
•the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
If the thermostat controller is in Cooling demand:
•the chilled water valve opens to 100%
•the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the thermostat controller is in Cooling demand and
the room temperature rises 2F°/1C° above the Cooling
setpoint, the thermostat controller automatically
disables dehumidification operation. Likewise, if the
thermostat controller is in Cooling demand and the
room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
Table 6: Installer Configuration Menu (Part 1 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
PswrdSets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
Com addrWireless address at the thermostat
controller; Default: 254
PAN IDSets the Personal Area Network
Identification (PAN ID) of the
wireless network. All devices on a
network must have the same
PA N ID setting to communicate with
each other. Default: 0
Range: 0 to 1,000
Range: 000 to 254
Addresses of each item on the wireless bus must be uniquely
numbered, increasing from 1.
Note: Setting this parameter to 0 disables the function.
Range: 0 to 500Note: Setting this parameter to 0 disables the function.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
16
Capability, Fan Control, and Occupancy Sensing Capability
Page 17
Table 6: Installer Configuration Menu (Part 2 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
ChannelSets the mesh network channel the
device uses for communication.
Only devices using the same mesh
network channel can communicate
with each other. Default: 10
GET FROMParameter not available at this time.N/A
BI1Configuration of Binary Input 1.
Default: None
BI2Configuration of Binary Input 2.
Default: None
Range: 11 to 26
Note: Setting this parameter to 10 disables the function.
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is open, until the
TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is closed, until the
TOccTime expires.
(Window): Cancels the heating or cooling action when a window is
open. The fan operation is only affected if the Fan Menu parameter
is set to (4): On-Auto and Auto is the selected fan mode. A window
alarm appears, indicating that the window needs to be closed to
resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC. (See the BI1 parameter earlier in this
table.) The occupancy is now dictated via BI1 and BI2. Any motion
detected sets the zone to Occupied status. The zone remains
permanently in occupied mode until the door contact switch opens
momentarily. The thermostat then enters stand-by mode. If more
movements are detected, the occupied mode resumes. While the
door is opened, any movements detected by the remote PIR sensor
or the PIR accessory cover are ignored. Use a Normally Closed
contact switching device. Contact opened = Door opened,
Contact closed = Door closed.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. This input can be tied into the air
conditioning unit control card, which provides an alarm should there
be a malfunction.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
17
Capability, Fan Control, and Occupancy Sensing Capability
Page 18
Table 6: Installer Configuration Menu (Part 3 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
UI3Configuration of Universal Input 3.
Default: None
MenuScroGives the option of having the
display continuously scroll the
parameters.
Default: onAutoModeEnables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat controller cover.)
Default: on
C or FProvides temperature scale options
%RH disp
LockoutSelectable Lockout Levels for
for display.
Default: °F
Displays the current humidity
reading (TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models).
Default: off
limiting end user keypad interaction.
Default: 0
(None): No function is associated with an input.
(COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water
changeover switching. Valid only for two-pipe systems.
Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between
Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/
Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring
Note: If UI3 is set to None, COC/NH, or COC/NC, then UI3 Status
is available as a point for integration and Supply Temperature is
not available as a point for integration. If UI3 is set to COS or SS,
then Supply Temperature is available as a point for integration and
UI3 Status is not available as a point for integration.
(off): The scroll is inactive.
(on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale
(°F): Fahrenheit scale
(on): Displays the current humidity reading in% RH.
(off): Does not display the current humidity reading.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
18
Capability, Fan Control, and Occupancy Sensing Capability
Page 19
Table 6: Installer Configuration Menu (Part 4 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Pipe NoSelectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTypDefines the control output for the
SeqOperaDetermines the sequence of
Fan MenuSets the Fan Mode options.
DHumiLCK Locks out the dehumidification
%RH set
DehuHyst
1
type of valves used in the
installation (TEC2026-2,
TEC2026H-2, TEC2036-2, and
TEC2036H-2 models).
Default: Floating
operation.
Default: 1
Default: 4
capability (TEC2036[H]-2, and
TEC2056[H]-2 models).
Default: on
Sets the dehumidification setpoints
(TEC2036[H]-2, and TEC2056[H]-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 50.0% RH
1
Sets the dehumidification hysteresis
(deadband) (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating
valves.
(0): Cooling Only (Off-Cool). The default is Cool.
(1): Heating Only (Off-Heat). The default is Heat.
(2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto.
(3): Heating and Reheat (Off-Heat). The default is Heat.
(4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Auto.
(5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Heat.
* Auto can be disabled with the AutoMode parameter. When Auto
is disabled, the default for (2) and (4) is Heat.Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling
and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H). The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. The default is Auto.
(off): Dehumidification is locked out.
(on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
Range: 2.0 to 20.0% RH
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
19
Capability, Fan Control, and Occupancy Sensing Capability
Page 20
Table 6: Installer Configuration Menu (Part 5 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
1
DehuCool
St-By TMSets stand-by timer value when
Unocc TMSets Unoccupied Timer Value when
St-By HTSets Stand-by heating setpoint
St-By CLSets Stand-by cooling setpoint limit
Unocc HTSets the Unoccupied Heating
Unocc CLSets the Unoccupied Cooling
Heat maxSets the Occupied and Unoccupied
Cool minSets the Occupied and Unoccupied
Sets the maximum dehumidification
cooling output (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 100%
used with occupancy sensor; time
delay between moment where
occupancy sensor detected the last
movement in the area and the time
which the thermostat stand-by mode
and setpoints become active.
Default: 0.5 hours
used with occupancy sensor; time
delay between the moment where
the thermostat toggles to stand-by
mode and the time which the
thermostat unoccupied mode and
setpoints become active.
Default: 0.0 hours
when used with occupancy sensor;
value is between occupied and
unoccupied heating setp oi n ts.
Default: 69.0°F/20.6°C
when used with occupancy sensor;
value is between occupied and
unoccupied cooling setpoints.
Default: 78.0°F/25.6°C
setpoint value.
Default: 62.0°F/16.5°C
setpoint value.
Default: 80.0°F/26.5°C
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Range: 20.0 to 100.0%Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Range: 0.5 to 24.0hours, in 0.5 hour increments
0.0 hours or Factory Value: Setting this parameter to its default 0
value disables the occupied timer and prevents the thermostat from
drifting from stand-by mode to unoccupied mode when occupancy
sensor functions are used.
Range: 0.0 to 24.0hours in 0.5 hour increments.
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Note: When adjusting the temperature, press the UP/
DOWN arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN arrow keys
to change the temperature
in 5.0F°/5.0C° increments.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
20
Capability, Fan Control, and Occupancy Sensing Capability
Page 21
Table 6: Installer Configuration Menu (Part 6 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
PbandProportional Band used by the PI
temperature control loop of the
thermostat.
Pband is not converted with C or F
scale and is always shown with a
range of 3 to 10.
Default: 3 (3F°/1.7C°)
Set typeProvides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnentSpt FuncDetermines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
TOccTimeSets the duration of the Tempo r ary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or BI1 or BI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 2.0 hrsDeadbandSets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
ValueF Scale Pband/C Scale Pband
33.0F°/1.7C°
44.0F°/2.2C°
55.0F°/2.8C°
66.0F°/3.3C°
77.0F°/3.9C°
88.0F°/4.4C°
99.0F°/5.0C°
1010.0F°/5.6C°
Note: The use of a larger proportional band is not to use the
thermostat as a discharge air controller device. The use of a larger
proportional band can be used to solve issues for flawed HVAC
design with basic sizing and thermostat location errors that cannot
be worked around.
(temporar): Local changes to the heating or coolin g setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat controller memory.
(Attch Stp): Single Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. Both the heating and
cooling setpoints are changed simultaneously, while respecting the
minimum configured deadband. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. The heating and cooling
setpoints can be separated individually, allowing the minimum
configured deadband to expand. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
Range: 0.0 to 24.0 hrs adjustable in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
21
Capability, Fan Control, and Occupancy Sensing Capability
Page 22
Table 6: Installer Configuration Menu (Part 7 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Cal RSSets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C°Cal RHSets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2036-4, TEC2036H-4,
TEC2036H-4+PIR, TEC2056-4,
TEC2056H-4, and
TEC2056H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 0.0% RHAux contDetermines the auxiliary contact
function and configuration.
Default: 0
Auto FanAffects the auto mode of operation
for the following Fan Menu
parameter selection options only:
• (2): Low-Med-High-Auto
• (3): Low-High-Auto
Default: AS
FL timeSets the maximum actuator stroke
timing (floating CntrlTyp
TEC2026-4, TEC2026H-4,
TEC2026H-4+PIR, TEC2036-4,
TEC2036H-4, and
TEC2036H-4+PIR models).
Default: 1.5 min
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Range: -15.0% RH to 15.0% RH (adjustable in 1% RH increments)
* If option (3) or (4) is used, it functions like option (1) or (2),
respectively.
(AS AD): The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only
re-activated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperature error from the setpoint.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
(0)Not used,
or used for
reheat
(1)Auxiliary
N.O.
(2)Auxiliary
N.C.
(3*)Do not use this selection option.
(4*)Do not use this selection option.
(5)Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network
variable.
If the sequence of operation is set to
reheat (2, 3, or 5), ignore this parameter.
Occupied = contact
closed
Unoccupied = contact
open
Occupied = contact open
Unoccupied = contact
closed
The output
aligns with
occupancy.
The output
aligns with
the
secondary
network
occupancy
command.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
22
Capability, Fan Control, and Occupancy Sensing Capability
Page 23
Table 6: Installer Configuration Menu (Part 8 of 8)
Parameter
Description and DefaultSelection Options
Appearing
on Display
CphSets the maximum number of cycles
per hour (TEC2016-4,
TEC2016H-4, TEC2016H-4+PIR,
and on/off CntrlTyp TEC2026-4,
TEC2026H-4, TEC2026H-4+PIR,
TEC2036-4, TEC2036H-4, and
TEC2036H-4+PIR models).
Default: 4RA/DAChoice of reverse or direct acting
analog output signal (TEC2046-4,
TEC2046H-4, TEC2046H-4+PIR,
TEC2056-4, TEC2056H-4, and
TEC2056H-4+PIR models).
Default: DAReheatSets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 disDisplays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
Range: 3 to 8 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC
(DA): Direct acting, 0 to 100% = 0 to 10 VDC
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0): 15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
Used as a diagnostic/service help to troubleshoot and diagnose
sensor operation.
1.When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
Troubleshooting
See Table 7 for display messaging. Refer to the
TEC20xx-4 and TEC20xx-4+PIR Series Wireless
Thermostat Controller System Technical Bulletin
(LIT-12011596) for troubleshooting details.
Repair Information
Accessories
All the accessories in Table 8include mounting
hardware; contact the nearest Johnson Controls
representative to order any of these parts.
Review the technical specifications of the accessories
prior to their use in an application.
If aTEC20x6(H)-4 or TEC20x6H-4+PIR Wireless
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls® representative.
Table 7: Display Messages
DisplayFunction
ServiceIndicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
FilterIndicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).
WindowIndicates that an outside window or door is open and has cancelled the thermostat controller heating or
cooling action in accordance with the programmable Binary Input (BI1).
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
23
Capability, Fan Control, and Occupancy Sensing Capability
Page 24
Table 8: Accessories (Order Sepa rately)
Code NumberDescription
SEN-600-1Remote Indoor Air Temperature Sensor
SEN-600-4Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
TE-6361M-1
TE-636S-1Strap-Mount Temperature Sensor
TEC20-A-1Replacement Antenna for TEC20 Coordinator
TEC20-RA-1
NPB-PWR
TEC20-8X-1120 VAC to 15 VDC Power Supply for TEC20 Coordinator
TEC20-9B-1Replacement Battery Pack for TEC20 Coordinator
TEC-6-PIR
TEC-6H-PIR
1.Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
2.This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by
3.DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail
4.The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC20x6-4 Series Thermostat
5.TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC20x6H-4 Series Thermostat
3
4
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
physical installation.
mounted options.
Controller to provide occupancy sensing capability.
Controller to provide occupancy sensing capability.
Duct Mount Air Temperat ure Sensor
2
Remote Antenna for TEC20 Coordinator
DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
Cover with Occupancy Sensor
5
Cover with Occupancy Sensor for Hospitality Models
Technical Specifications
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability (Part 1 of 2)
Power Requirements19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay/Triac Contact RatingOn/Off and Floating Control: 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum,
3.0 A In-Rush, Class 2 or SELV
Analog Output Rating Proportional Control: 0 to 10 VDC into 2k ohm Resistance (Minimum)
Fan Relay Output Rating19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Auxiliary Output RatingTriac Outpu t: 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Binary InputsVoltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Analog InputsResistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Range
RF BandDirect-Sequence Spread-Spectrum Transmission; 2.4 Ghz unlicensed band
Transmission Power10 mW Maximum
Temperature RangeBacklit Display: -40.0°C/-40.0°F to 50.0°C/122.0°F in 0.5° increments
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Resolution ±0.1C°/±0.2F°
Temperature Coefficient (NTC) Thermistor Sensors
Through Walls: 10 m (30 ft)
Line-of-Sight (Open Space): 30 m (100 ft)
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments
Cooling Control: 12.0°C/54.0°F to 38.0°C/100.0°F in 0.5° Increments
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
24
Capability, Fan Control, and Occupancy Sensing Capability
Page 25
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability (Part 2 of 2)
Control AccuracyTemperature: ±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated
Humidity: ±5% RH from 20 to 80% RH at 10 to 32°C (50 to 90°F)
Minimum Deadband1C° /2F° between Heating and Cooling
Ambient ConditionsOperating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
Compliance (Pending)United States:
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters
Transmitter FCC Identification: (pending)
Canada:
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Industry Canada (IC) Identification: (pending)
Dimensions (H x W x D)125 x 86 x 29 mm (4-15/16 x 3-3/8 x 1-1/8 in.)
Shipping WeightTEC20x6(H)-4 Models: 0.75 lb (0.34 kg)
TEC20x6H-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc., shall not be liable for damages resulting from misapplication
or misuse of its products.
TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Published in U.S.A.www.johnsoncontrols.com
Capability, Fan Control, and Occupancy Sensing Capability
25
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.