TEC20x6(H)-2 Series Wireless Thermostat Controllers with
Two Outputs, Dehumidification Capability, and Three
Speeds of Fan Control
Installation Instructions
Part No. 24-9890-765, Rev. A
Issued August 31, 2009
Supersedes March 17, 2008
Applications
IMPORTANT: The TEC20x6(H)-2Series Wireless
Thermostat Controllers are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
thermostat controllercould lead to personal injury or
property damage to the controlled equipment or
other property, additional precautions must be
designed into the control system. Incorporate and
maintain other devices such as supervisory or alarm
systems or safety or limit controls intended to warn
of, or protect against, failure or malfunction of the
thermostat controller.
The TEC Series Wireless Thermostat Controller
System provides wireless networked control of
Heating, Ventilating, and Air Conditioning (HVAC)
equipment on a Building Automation System (BAS)
that enables remote monitoring and programming. This
TEC Series System integrates into a supervisory
controller using BACnet® Internet Protocol (IP) or
BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controlle r to
communicate with multiple TEC Wireless Thermostat
Controllers. TEC20x6(H)-2 Series Wireless Thermostat
Controllers control two- or four-pipe fan coils, cabinet
unit heaters, or other equipment using on/off, floating,
or proportional 0 to 10 VDC control input, three speeds
of fan control, and dehumidification capability.
The wireless mesh network uses ZigBee™ technology
to enable remote monitoring and programming and to
enhance reliability by providing redundant transmission
paths through other TEC Wireless Thermostat
Controllers, creating a resilient, self-healing mesh
network.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with
the limits for a Class A digital device pursuant to Part 15 of
the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when
this equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be
required to correct the interference at his/her own
expense.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1.This device may not cause harmful interference, and
2.This device must accept any interference received,
including interference that may cause undesired
operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user’s
authority to operate the equipment.
Canada
This Class (A) digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur du
Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number
only signifies that the Industry Canada technical
specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est conforme
aux spécifications techniques d'Industry Canada.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs,
Dehumidification Capability, and Three Speeds of Fan Control
1
Mounting
Figure 1: Removing the Cover
F
I
G
:
c
v
r
_
r
m
v
l
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Location Considerations
Locate a thermostat controller:
•on a partitioning wall, approximately 1.5 m (5 ft)
above the floor in a location of average
temperature
•away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
Allow for vertical air circulation to the thermostat
controller.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a
TEC20 Coordinator and a TEC Wireless Thermostat
Controller (or between TEC Wireless Thermostat
Controllers) can be less than the recommended
distances shown in Table 1. The effective transmission
range for indoor applications varies because of Radio
Frequency (RF) signal absorption and re flectio n due to
metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
TypeDistance
Through Walls 10 m (32.8 ft)
Open Space 30 m (98.4 ft)
2. Pull the bottom edge of the cover and open the
thermostat controller as illustrated in Figure 1.
3. Carefully pull the locking tabs on the right side of
the mounting base and unlock the Printed Circuit
Board (PCB). Open the PCB to the left as
illustrated in Figure 2.
PCB
Locking
For detailed information on locating devices for
optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294), which is
available on the Johnson Controls® Portal intranet site.
Mounting the Thermostat Controller
Follow these steps to mount the thermostat controller:
1. Use a Phillips-head screwdriver to loosen the
security screw (if installed) on the bottom of the
cover.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
2
Three Speeds of Fan Control
d
r
b
4. Pull approximately 152 mm (6 in.) of wire from the
wall and insert the wire through the hole in the
mounting base.
5. Align the mounting base on the wall, and use the
base as a template to mark the two mounting hole
locations.
Note: Be sure to position the mounting base so that
the arrow on the base points upward to indicate the top
of the thermostat controller.
6. Drill a 5 mm (3/16 in.) hole at each of the two
marked locations, and tap nylon anchors (include d)
flush to the wall surface.
Note: Other means of anchoring the device may be
desired, depending on the wall medium.
7. Position the mounting base on the wall, and use
Figure 3: Securing the
Mounting Base to the Wall
Figure 4: Removing the Screw Terminal Blocks
!
!
the two mounting screws (included)to secure the
base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting
screws.
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
s
b
_
g
n
t
n
m
:
G
I
F
8. Swing the PCB back to the right, and carefully
snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks as illustrated in
Figure 4.
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the thermostat controller.
When replacing an existing thermostat controller,
remove and label the wires to identify the terminal
functions. When replacing a thermostat controller o f the
same model, simply remove the old screw terminal
blocks and reinsert them onto the PCB of the
replacement thermostat controller.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material
to prevent drafts from affecting the ambient
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the terminals,
be sure to properly twist the wires together prior to
inserting them into the terminal connectors.
4. Reattach the cover to the mounting base (top sid e
first).
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the cover.
See Figure 5, Figure 6, Figu re 7, and Table 2 for
information on wiring the thermostat controllers.
3
Fan
-H
Three-Pole
Right Top
Connector
BO2
BO5
Aux
BO1/
AO1
UI3
BI1
BI2
Fan
-M
Fan
-L
24 V~
Hot
24 V~
Com
BO4/
AO2
Five-Pole
Left T o p Connector
1 2 3 4 5
F
I
G
:
T
E
C
2
0
x
6
H
2
_
T
R
M
N
L
S
Figure 5: TEC20x6(H)-2 Series
Thermostat Controller Terminals
BO5
BO3
Aux
6 7 8
Eight-Pole Bottom Connector
Scom
RS
9 10 11 12 13 14 15 16
Table 2: TEC20x6(H)-2 Series Thermostat Controller Terminals
Terminal
Number
TEC2016(H)-2
(On/Off Control)
1Fan-HFan-HFan-HFan On – High
2Fan-MFan-MFan-MFan On – Medium
3Fan-LFan-LFan-LFan On – Low
424 V~ Hot24 V~ Hot24 V~ Hot24 VAC
524 V~ Com24 V~ Com24 V~ Com24 VAC (Common)
6BO5 AuxBO5 AuxBO5 AuxAuxiliary Binary Output
7BO5 AuxBO5 AuxBO5 AuxAuxiliary Binary Output
8BO3BO3BlankOpen Heat
9BlankBO4AO2Close Heat