Johnson Controls TEC20x6-2 Series, TEC20x6H-2 Series Installation Instructions Manual

TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
Installation Instructions
Part No. 24-9890-765, Rev. A
Issued August 31, 2009
Supersedes March 17, 2008
Applications
IMPORTANT: The TEC20x6(H)-2 Series Wireless
Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostat controller.
The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming. This TEC Series System integrates into a supervisory controller using BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.
TEC20 Coordinators allow the supervisory controlle r to communicate with multiple TEC Wireless Thermostat Controllers. TEC20x6(H)-2 Series Wireless Thermostat Controllers control two- or four-pipe fan coils, cabinet unit heaters, or other equipment using on/off, floating, or proportional 0 to 10 VDC control input, three speeds of fan control, and dehumidification capability.
The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC Wireless Thermostat Controllers, creating a resilient, self-healing mesh network.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs,
Dehumidification Capability, and Three Speeds of Fan Control
1
Mounting
Figure 1: Removing the Cover
F
I
G
:
c
v
r
_
r
m
v
l
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Location Considerations
Locate a thermostat controller:
on a partitioning wall, approximately 1.5 m (5 ft) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Allow for vertical air circulation to the thermostat controller.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a TEC20 Coordinator and a TEC Wireless Thermostat Controller (or between TEC Wireless Thermostat Controllers) can be less than the recommended distances shown in Table 1. The effective transmission range for indoor applications varies because of Radio Frequency (RF) signal absorption and re flectio n due to metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
Type Distance
Through Walls 10 m (32.8 ft) Open Space 30 m (98.4 ft)
2. Pull the bottom edge of the cover and open the thermostat controller as illustrated in Figure 1.
3. Carefully pull the locking tabs on the right side of the mounting base and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 2.
PCB Locking
For detailed information on locating devices for optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294), which is available on the Johnson Controls® Portal intranet site.
Mounting the Thermostat Controller
Follow these steps to mount the thermostat controller:
1. Use a Phillips-head screwdriver to loosen the security screw (if installed) on the bottom of the cover.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
2
Three Speeds of Fan Control
d
r
b
4. Pull approximately 152 mm (6 in.) of wire from the wall and insert the wire through the hole in the mounting base.
5. Align the mounting base on the wall, and use the base as a template to mark the two mounting hole locations.
Note: Be sure to position the mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller.
6. Drill a 5 mm (3/16 in.) hole at each of the two marked locations, and tap nylon anchors (include d) flush to the wall surface.
Note: Other means of anchoring the device may be desired, depending on the wall medium.
7. Position the mounting base on the wall, and use
Figure 3: Securing the
Mounting Base to the Wall
Figure 4: Removing the Screw Terminal Blocks
!
!
the two mounting screws (included) to secure the base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
s
b
_ g
n
t
n m
: G
I F
8. Swing the PCB back to the right, and carefully snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks as illustrated in Figure 4.
s k
c
l
b
_
l
n m
r
t
: G
I F
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the thermostat controller.
When replacing an existing thermostat controller, remove and label the wires to identify the terminal functions. When replacing a thermostat controller o f the same model, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and connect them to the appropriate screw terminals as indicated in Figure 5.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
4. Reattach the cover to the mounting base (top sid e first).
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the cover.
See Figure 5, Figure 6, Figu re 7, and Table 2 for information on wiring the thermostat controllers.
3
Fan
-H
Three-Pole Right Top Connector
BO2
BO5
Aux
BO1/ AO1
UI3
BI1
BI2
Fan
-M
Fan
-L
24 V~
Hot
24 V~
Com
BO4/
AO2
Five-Pole
Left T o p Connector
1 2 3 4 5
F
I
G
:
T
E
C
2
0
x
6
H
2
_
T
R
M
N
L
S
Figure 5: TEC20x6(H)-2 Series
Thermostat Controller Terminals
BO5
BO3
Aux
6 7 8
Eight-Pole Bottom Connector
Scom
RS
9 10 11 12 13 14 15 16
Table 2: TEC20x6(H)-2 Series Thermostat Controller Terminals
Terminal Number
TEC2016(H)-2 (On/Off Control)
1 Fan-H Fan-H Fan-H Fan On – High 2 Fan-M Fan-M Fan-M Fan On – Medium 3 Fan-L Fan-L Fan-L Fan On – Low 4 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 VAC 5 24 V~ Com 24 V~ Com 24 V~ Com 24 VAC (Common) 6 BO5 Aux BO5 Aux BO5 Aux Auxiliary Binary Output 7 BO5 Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat
10 Blank BO1 AO1 Open Cool
11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 RS RS RS Remote Sensor 14 Scom Scom Scom Sensor Common 15 BI2 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 UI3 Configurable Universal Input 3
Terminal Label by Model Function
TEC2026(H)-2, TEC2036(H)-2 (On/Off or Floating Control)
TEC2046(H)-2, TEC2056(H)-2 (Proportional 0 to 10 VDC Control)
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
4
Three Speeds of Fan Control
Figure 6: TEC20x6(H)-2 Series Thermostat Controller with Separate Power Source for Auxiliary
Contact
FIG:TEC20x6H2_SEP
Scom
Contact
• COC/NH
= Cold Water
• COC/NC Normally C ool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
Separate 24 VAC
(24 VA C Maximum)
BO5
Aux
BO5
Aux
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Power and Fan
Independent Contacts
• Reheat
• Lighting
• Exhaust Fan
Aux
Fan
-H
Fan
-M
Fan
-L
Scom
Contact
• COC/NH
= Cold Water
• COC/NC Normall y Cool
= Hot Wate r
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
C
(24 VAC Ma ximum )
Power and Fan
BO5
Aux
BO5
Aux
Contacts
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fa n
Aux
24 VAC
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Figure 7: TEC20x6(H)-2 Series Thermostat Controller with Same Power Source for Auxiliary Contact
Power Source for Auxiliary Output
• On/Off Actuation
Remote Inputs
Power Source for Auxiliary Output
Same 24 VA
BI1
Independent
BI1
BI2 UI3
- OR -
Supply S ensor Changeover Sensor
Remote Inputs
BI2
UI3
Voltage-Free
Normally Heat Closed Contact
Closed Contact
M A S _
2 H
6 x
0
2 C E T
: G
I F
- OR -
Supply Sensor
Thermostat Power
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
Changeover Sensor
Voltage-Free
Normally Heat Closed Contact
Closed Contact
5
Sample Applications
Figure 8: Wiring TEC2016(H)-2 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 9: Wiring TEC2026(H)-2 and TEC2036(H)-2 Thermostat Controllers for On/Off Control
Two -Pip e Applicat ions
Four-Pipe Applications
F
I
G
:
T
E
C
2
0
2
6
H
2
_
T
E
C
2
0
3
6
H
2
_
o
n
o
f
f
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 10: Wiring TEC2026(H)-2 and TEC2036(H)-2 Thermostat Controllers for Floating Control
Two -Pip e Applic ations
F
I
G
:
T
E
C
2
0
2
6
H
2
_
T
E
C
2
0
3
6
H
2
_
f
l
t
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 8 through Figure 11 show sample applications for these thermostat controllers.
Four-Pipe Applications
24 V~
24 V~
24 V~
f
f o
n
o _
2 H 6
1
0 2 C E T
: G
I F
BO2 BO3
BO4
Four-Pipe Applications
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
6
Three Speeds of Fan Control
24 V~
24 V~
Loading...
+ 13 hidden pages