Johnson Controls TEC20x6-2 Series, TEC20x6H-2 Series Installation Instructions Manual

Page 1
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
Installation Instructions
Part No. 24-9890-765, Rev. A
Issued August 31, 2009
Supersedes March 17, 2008
Applications
IMPORTANT: The TEC20x6(H)-2 Series Wireless
Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostat controller.
The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming. This TEC Series System integrates into a supervisory controller using BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.
TEC20 Coordinators allow the supervisory controlle r to communicate with multiple TEC Wireless Thermostat Controllers. TEC20x6(H)-2 Series Wireless Thermostat Controllers control two- or four-pipe fan coils, cabinet unit heaters, or other equipment using on/off, floating, or proportional 0 to 10 VDC control input, three speeds of fan control, and dehumidification capability.
The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC Wireless Thermostat Controllers, creating a resilient, self-healing mesh network.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs,
Dehumidification Capability, and Three Speeds of Fan Control
1
Page 2
Mounting
Figure 1: Removing the Cover
F
I
G
:
c
v
r
_
r
m
v
l
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Location Considerations
Locate a thermostat controller:
on a partitioning wall, approximately 1.5 m (5 ft) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Allow for vertical air circulation to the thermostat controller.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a TEC20 Coordinator and a TEC Wireless Thermostat Controller (or between TEC Wireless Thermostat Controllers) can be less than the recommended distances shown in Table 1. The effective transmission range for indoor applications varies because of Radio Frequency (RF) signal absorption and re flectio n due to metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
Type Distance
Through Walls 10 m (32.8 ft) Open Space 30 m (98.4 ft)
2. Pull the bottom edge of the cover and open the thermostat controller as illustrated in Figure 1.
3. Carefully pull the locking tabs on the right side of the mounting base and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 2.
PCB Locking
For detailed information on locating devices for optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294), which is available on the Johnson Controls® Portal intranet site.
Mounting the Thermostat Controller
Follow these steps to mount the thermostat controller:
1. Use a Phillips-head screwdriver to loosen the security screw (if installed) on the bottom of the cover.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
2
Three Speeds of Fan Control
d
r
b
4. Pull approximately 152 mm (6 in.) of wire from the wall and insert the wire through the hole in the mounting base.
5. Align the mounting base on the wall, and use the base as a template to mark the two mounting hole locations.
Note: Be sure to position the mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller.
6. Drill a 5 mm (3/16 in.) hole at each of the two marked locations, and tap nylon anchors (include d) flush to the wall surface.
Note: Other means of anchoring the device may be desired, depending on the wall medium.
Page 3
7. Position the mounting base on the wall, and use
Figure 3: Securing the
Mounting Base to the Wall
Figure 4: Removing the Screw Terminal Blocks
!
!
the two mounting screws (included) to secure the base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
s
b
_ g
n
t
n m
: G
I F
8. Swing the PCB back to the right, and carefully snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks as illustrated in Figure 4.
s k
c
l
b
_
l
n m
r
t
: G
I F
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the thermostat controller.
When replacing an existing thermostat controller, remove and label the wires to identify the terminal functions. When replacing a thermostat controller o f the same model, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and connect them to the appropriate screw terminals as indicated in Figure 5.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
4. Reattach the cover to the mounting base (top sid e first).
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the cover.
See Figure 5, Figure 6, Figu re 7, and Table 2 for information on wiring the thermostat controllers.
3
Page 4
Fan
-H
Three-Pole Right Top Connector
BO2
BO5
Aux
BO1/ AO1
UI3
BI1
BI2
Fan
-M
Fan
-L
24 V~
Hot
24 V~
Com
BO4/
AO2
Five-Pole
Left T o p Connector
1 2 3 4 5
F
I
G
:
T
E
C
2
0
x
6
H
2
_
T
R
M
N
L
S
Figure 5: TEC20x6(H)-2 Series
Thermostat Controller Terminals
BO5
BO3
Aux
6 7 8
Eight-Pole Bottom Connector
Scom
RS
9 10 11 12 13 14 15 16
Table 2: TEC20x6(H)-2 Series Thermostat Controller Terminals
Terminal Number
TEC2016(H)-2 (On/Off Control)
1 Fan-H Fan-H Fan-H Fan On – High 2 Fan-M Fan-M Fan-M Fan On – Medium 3 Fan-L Fan-L Fan-L Fan On – Low 4 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 VAC 5 24 V~ Com 24 V~ Com 24 V~ Com 24 VAC (Common) 6 BO5 Aux BO5 Aux BO5 Aux Auxiliary Binary Output 7 BO5 Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat
10 Blank BO1 AO1 Open Cool
11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 RS RS RS Remote Sensor 14 Scom Scom Scom Sensor Common 15 BI2 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 UI3 Configurable Universal Input 3
Terminal Label by Model Function
TEC2026(H)-2, TEC2036(H)-2 (On/Off or Floating Control)
TEC2046(H)-2, TEC2056(H)-2 (Proportional 0 to 10 VDC Control)
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
4
Three Speeds of Fan Control
Page 5
Figure 6: TEC20x6(H)-2 Series Thermostat Controller with Separate Power Source for Auxiliary
Contact
FIG:TEC20x6H2_SEP
Scom
Contact
• COC/NH
= Cold Water
• COC/NC Normally C ool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
Separate 24 VAC
(24 VA C Maximum)
BO5
Aux
BO5
Aux
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Power and Fan
Independent Contacts
• Reheat
• Lighting
• Exhaust Fan
Aux
Fan
-H
Fan
-M
Fan
-L
Scom
Contact
• COC/NH
= Cold Water
• COC/NC Normall y Cool
= Hot Wate r
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
C
(24 VAC Ma ximum )
Power and Fan
BO5
Aux
BO5
Aux
Contacts
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fa n
Aux
24 VAC
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Figure 7: TEC20x6(H)-2 Series Thermostat Controller with Same Power Source for Auxiliary Contact
Power Source for Auxiliary Output
• On/Off Actuation
Remote Inputs
Power Source for Auxiliary Output
Same 24 VA
BI1
Independent
BI1
BI2 UI3
- OR -
Supply S ensor Changeover Sensor
Remote Inputs
BI2
UI3
Voltage-Free
Normally Heat Closed Contact
Closed Contact
M A S _
2 H
6 x
0
2 C E T
: G
I F
- OR -
Supply Sensor
Thermostat Power
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
Changeover Sensor
Voltage-Free
Normally Heat Closed Contact
Closed Contact
5
Page 6
Sample Applications
Figure 8: Wiring TEC2016(H)-2 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 9: Wiring TEC2026(H)-2 and TEC2036(H)-2 Thermostat Controllers for On/Off Control
Two -Pip e Applicat ions
Four-Pipe Applications
F
I
G
:
T
E
C
2
0
2
6
H
2
_
T
E
C
2
0
3
6
H
2
_
o
n
o
f
f
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 10: Wiring TEC2026(H)-2 and TEC2036(H)-2 Thermostat Controllers for Floating Control
Two -Pip e Applic ations
F
I
G
:
T
E
C
2
0
2
6
H
2
_
T
E
C
2
0
3
6
H
2
_
f
l
t
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 8 through Figure 11 show sample applications for these thermostat controllers.
Four-Pipe Applications
24 V~
24 V~
24 V~
f
f o
n
o _
2 H 6
1
0 2 C E T
: G
I F
BO2 BO3
BO4
Four-Pipe Applications
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
6
Three Speeds of Fan Control
24 V~
24 V~
Page 7
Figure 11: Wiring TEC2046(H)-2 and TEC2056(H)-2 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
F
I
G
:
T
E
C
2
0
4
6
H
2
_
T
E
C
2
0
5
6
H
2
_
p
r
o
p
Heating/Cooling
Valve
Com
Hot
AO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
Figure 12: Front Cover (TEC20x6H-2 Models)
Backlit
LCD
System
Activity
LEDs
Intuitive
Operation
Keys
F
I
G
:
T
E
C
2
0
x
6
H
_
w
r
l
s
s
_
f
r
n
t
v
w
Status LED
(beneath cover)
AO2
24 V~
24 V~
Setup and Adjustments
Overview
Figure 12 shows the front cover of the thermostat controller, including features used for setting up and adjusting the thermostat controller.
Plain-Text
Room Temp
70.0ºF
MODE FAN
User Interface Keys
The user interface consists of keys on the front cover as illustrated in Figure 12. The function of each key is as follows:
OVERRIDE key (commercial models) overrides the unoccupied mode to occupied at the local user interface for the specified TOccT ime. (TOccTime is defined by selecting the appropriate time period in the Installer Configuration Menu.) The OVERRIDE key also allows access to the Installer Configuration Menu. (See Table 6.)
Note: If one of the binary inputs is configured to operate as a remote override contact, this OVERRIDE key is disabled.
°C/°F key (hospitality models) changes the temperature scale to either Celsius or Fahrenheit and allows access to the Installer Configuration Menu. (See Table 6.)
UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment.
Light-Emitting Diodes (LEDs)
System Activity LEDs indicate the status and actions of the thermostat controller.
•The FAN LED is on when the fan is on.
•The HEAT LED is on when heating or reheat is on.
•The COOL LED is on when cooling is on.
MODE key toggles among the system modes available, as defined by selecting the appr op ria te operation sequence in the Installer Configuration Menu (for example Off, Heat, Cool, Auto).
FAN key toggles am on g th e fa n mo de s av aila ble , as defined by selecting the appropriate fan menu options defined in the Installer Configuration Menu (for example Low, Med, High, Auto).
The Status LED, located beneath the cover, flashes at 5-second intervals to provide indication of the network
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
7
Page 8
status of the thermostat controller. See Table 3.
Table 3: Status LED
Flashes per
Condition Indicated 5-Second Interval
1 Power On 2 Power On, Communicating 3 Power On, Communicating, Found
Wireless Network
4 Power On, Communicating, Found
Wireless Network, Communicating with
TEC20 Coordinator
Configuring the Thermostat Controller
The thermostat controller comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 6. To reconfigure the parameters, follow the steps in this section.
To access the Installer Configuration Menu, press and hold the center key for approximately 8 seconds. Once the Installer Configuration Menu begins, release and press the center key to scroll through the parameters listed in Table 6. When the desired parameter displays, use the UP/DOWN arrow keys to choose the desired selection option. Then press and release the center key to continue scrolling through the parameters.
Backlit Liquid Crystal Display (LCD)
The thermostat controller includes a 2- line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unattended for 45 seconds.
Status Display Menu
The Status Display Menu displays during normal operation. This menu scrolls through several parameters:
Room Temperature
Room Temperature and Humidity (TEC2036-2, TEC2036H-2, TEC2056-2, and TEC2056H-2 models)
System Mode
Occupancy Status (Occupied/Unoccupied/ Override)
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.
Note: Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed in Table 6.
When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat controller reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm condition, an alarm condition displays locally when the input closes. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water switching or supply air temperature monitoring at the thermostat controller.
Each input can be configured to the Selection Options included in Table 6.
Configuring the Sequence of Operation (S eqOpera)
Choose the appropriate sequence of operation. The modes presented are user-dependent on the sequen ce of operation selected. For two-pipe applications using a changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between Cooling Only and Heating Only. See Figure 13
through Figure 18 for sequence of operation examples.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
8
Three Speeds of Fan Control
Page 9
Table 4: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection Option
(0): Cooling Only See Figure 13. 10: Normally Open
(1): Heating Only See Figure 14. 10: N.O. Heating
(2): Cooling and Reheat See Figure 15. 6 and 7: Reheat
(3): Heating and Reheat See Figure 16. 6 and 7: Reheat
Control Curve
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off Control Floating Control Proportional
(N.O.) Cooling 11: Normally Closed (N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
10: N.O. Heating 11: N.C. Heating
10: Open Cooling 11: Closed Cooling
10: Open Heating 11: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 10: Open Heating 11: Closed Heating
Table 5: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection Option
(0): Cooling Only See Figure 13. 10: N.O. Cooling
(1): Heating Only See Figure 14. 8: N.O. Heating
(2): Cooling and Reheat See Figure 15. 6 and 7: Reheat
(3): Heating and Reheat See Figure 16. 6 and 7: Reheat
(4): Cool/Heat Four-Pipe See Figure 17. 8: N.O. Heating
(5): Cool/Heat Four-Pipe and Reheat
Control Curve
See Figure 18. 6 and 7: Reheat
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off Control Floating Control Proportional
11: N.C. Cooling
9: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating
9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
10: Open Cooling 11: Closed Cooling
8: Open Heating 9: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating
8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 10: Proportional Heating
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating
9: Proportional Heating 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating 10: Proportional Cooling
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
9
Page 10
Temperatur e Increase
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 13: Cooling Only
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 14: Heating Only
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
or Propor t ional
Outputs
Heating Output Cooling Output
Off
Off
On
On
Figure 15: Cooling with Reheat
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 16: Heating with Reheat
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
Deadband
or Propor t ional
Outputs
Heating Output Cooling Output
Off
Off
On
On
Figure 17: Heating/Cooling When Out1Conf = 4.0
(Increments of 1F°/0.5C°)
On
100%
0%
On/Off, Floating,
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
Device
(Increments of 1F°/0.5C°)
On/Off, Floating,
(Increments of 1F°/0.5C°)
Temperature Increase
Device
Temperat ure Increase
t
h
r
Temperat ure Increase
(Increments of 1F°/0.5C°)
10
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
Page 11
Temperatur e Increase
Heating Setpoint
Device Closed
Device Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put Cooling Output
Off
Off
On
On
Figure 18: Heating/Cooling When Out1Conf = 4.0
Figure 19: Two-Speed and Three-Speed Fan Operation
Temperat ur e Deviation fro m Setpoint, F°
2.0F°/1. 0C° to
5.0F°/2.5C° Deadband
100%
0%
2.5
2.5
2.0 2.0
1.5
1.50.5 0.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Heating Setpoint
Cooling
High
FIG:fn_oprtn
Fan
Speed
(Increments of 1F°/0.5C°)
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer Configuration menu to set the available Fan Mode options. Use the FAN key to select the desired Fan Mode option.
When selection option (2): Low-Med-High-Auto is chosen in the Fan Menu parameter, the fan operates as shown in Figure 19. When selection option (3): Low-High-Auto is chosen in the Fan Menu parameter, the fan operates at only the low and high settings, ignoring the medium setting (Figure 19). This operation applies to the occupied mode when the fan is set to Auto.
Setpoint
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
11
Page 12
Configuring the Wireless Mesh Network Settings
Use the following process to configure the wireless mesh network.
1. Select a PAN ID and Channel. Use these same values for every TEC Wireless Thermostat Controller (and the associated TEC20 Coordinator) on the same wireless mesh network. See Table 6.
2. Select a Com Address for each TEC Wireless Thermostat Controller (1 to 254). This address must be unique to each TEC Wireless Thermostat Controller on the same wireless network (that is, unique to the PAN ID/Channel combination). See Table 6.
After configuring the wireless mesh network settings, refer to the TEC Series Wireless Thermostat Controller System T echnical Bulletin (LIT-12011414) for directions on integrating the TEC Wireless Thermostat Controllers and TEC20 Coordinator with a supervisory controller.
Dehumidification (TEC2036[H]-2 and TEC2056[H]-2 Models Only)
Upon detection of room humidity above the adjustable humidity setpoint as sensed by the integral humidity sensor, dehumidifica tion activates.
Note: Dehumidification operation functions only in the Cooling mode; dehumidification operation does not function in either the Off or the Heating mode.
Note: A central network command can globally lock out dehumidification operation to all thermostat controllers.
If the room temperature resides in the deadband between the Heating and Cooling setpoint:
the thermostat controller forces the fan to low speed
the chilled water valve opens to the specified maximum value set by CoolMax
the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint, as sensed by the thermostat controller
If the room temperature falls below the current Heating setpoint, the thermostat controller disables dehumidification operation.
If the thermostat controller is in Cooling demand:
the chilled water valve opens to 100%
the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint, as sensed by the thermostat controller
If the thermostat controller is in Cooling demand and the room temperature rises 2F°/1C° above the Cooling setpoint, the thermostat controller automatically disables dehumidification operation. Likewise, if the thermostat controller is in Cooling demand and the room temperature falls below the current Heating setpoint, the thermostat controller disables dehumidification operation.
Table 6: Installer Configuration Menu (Part 1 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Com addr Wireless address at the thermostat
controller; Default: 4
PAN ID Sets the Personal Area Network
Identification (PAN ID) of the
wireless network. All devices on a
network must have the same
PA N ID setting to communicate with
each other. Default: 0 Channel Sets the mesh network channel the
device uses for communication.
Only devices using the same mesh
network channel can communicate
with each other. Default: 10 GET FROM Parameter not available at this time. N/A
Range: 000 to 254 Addresses of each item on the wireless bus must be uniquely
numbered, increasing from 1. Note: Setting this parameter to 0 disables the function.
Range: 0 to 500 Note: Setting this parameter to 0 disables the function.
Range: 11 to 26 Note: Setting this parameter to 10 disables the function.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
12
Three Speeds of Fan Control
Page 13
Table 6: Installer Configuration Menu (Part 2 of 7)
Parameter
Description and Default Selection Options Appearing on Display
BI1 Configuration of Binary Input 1.
Default: None
BI2 Configuration of Binary Input 2.
Default: None
(None): No function is associated with an input. (Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat controller goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temp orary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat controller goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is closed, until the TOccTime expires.
(Window): Cancels the heating or cooling action when a window is open. The fan operation is only affected if the Fan Menu parameter is set to (4): On-Auto and Auto is the selected fan mode. A window alarm appears, indicating that the window needs to be closed to resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input. (Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC. (See the BI1 parameter earlier in this
table.) The occupancy is now dictated via BI1 and BI2. Any motion detected sets the zone to Occupied status. The thermostat controller remains in the occupied mode until a DoorOpen is detected, at which point the thermostat controller goes to the unoccupied mode. If the door stays open more than the specified door time, the thermostat controller remains unoccupied. (See the Door Time parameter later in this table.)
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller when the input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
13
Page 14
Table 6: Installer Configuration Menu (Part 3 of 7)
Parameter
Description and Default Selection Options Appearing on Display
UI3 Configuration of Universal Input 3.
Default: None
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on AutoMode Enables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat controller cover.)
Default: off
C or F Provides temperature scale options
%RH disp
Lockout Selectable Lockout Levels for
for display.
Default: °F
Displays the current humidity
reading (TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models).
Default: off
limiting end user keypad interaction.
Default: 0
(None): No function is associated with an input. (COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems.
Note: Choose the selection option (0): Cooling Only for the SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/ Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring Note: If UI3 is set to None, COC/NH, or COC/NC, then UI3 S tatus
is available as a point for integration and Supply Temperature is not available as a point for integration. If UI3 is set to COS or SS, then Supply Temperature is available as a point for integration and
UI3 Status is not available as a point for integration. (off): The scroll is inactive.
(on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale (°F): Fahrenheit scale
(on): Displays the current humidity reading in% RH. (off): Does not display the current humidity reading.
Lockout Level
Function
Mode Setting
(0) Access Access Access Access (1) Access Access No Access Access (2) No Access No Access Access Access (3) No Access No Access No Access Access (4) No Access No Access Access No Access (5) No Access No Access No Access No Access
Fan Setting
Local Override
Occupied T emperature Setpoints
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
14
Three Speeds of Fan Control
Page 15
Table 6: Installer Configuration Menu (Part 4 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Pipe No Selectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTyp Defines the control output for the
SeqOpera Determines the sequence of
Fan Menu Sets the Fan Mode options.
DHumiLCK Locks out the dehumidification
%RH set
DehuHyst
1
type of valves used in the
installation (TEC2026-2,
TEC2026H-2, TEC2036-2, and
TEC2036H-2 models).
Default: Floating
operation.
Default: 1
Default: 4
capability (TEC2036[H]-2, and
TEC2056[H]-2 models).
Default: on
Sets the dehumidification setpoints
(TEC2036[H]-2, and TEC2056[H]-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 50.0% RH
1
Sets the dehumidification hysteresis
(deadband) (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
(2.0 Pipes): Limits the number of sequences of operation available from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5, and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.) 24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating valves.
(0): Cooling Only (Off-Cool). The default is Cool. (1): Heating Only (Off-Heat). The default is Heat. (2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Heat. (3): Heating and Reheat (Off-Heat). The default is Heat. (4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Heat. (5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Heat. * Auto can be disabled with the AutoMode parameter. Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H). The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. The default is Auto.
(off): Dehumidification is locked out. (on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
Range: 2.0 to 20.0% RH
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
15
Page 16
Table 6: Installer Configuration Menu (Part 5 of 7)
Parameter
Description and Default Selection Options Appearing on Display
1
DehuCool
Unocc HT Sets the Unoccupied Heating
Unocc CL Sets the Unoccupied Cooling
Heat max Sets the Occupied and Unoccupied
Cool min Sets the Occupied and Unoccupied
Set type Provides the option of temporarily
TOccTime Sets the duration of the Temporary
DoorTime Engages the Unoccupied mode if
Deadband Sets the minimum deadband
Cal RS Sets the desired room air sensor
Sets the maximum dehumidification
cooling output (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 100%
setpoint value.
Default: 62.0°F/16.5°C
setpoint value.
Default: 80.0°F/26.5°C
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in the Main User Menu (when the thermostat controller is in the Unoccupied mode)
• a temporary heating or cooling setpoint
Default: 2.0 hrs
the door stays open minimally for the time specified.
Default: 2.0 min
between the heating and cooling setpoints.
Default: 2.0F°/1.0C°
calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.
Default: 0.0F°/0.0C°
Range: 20.0 to 100.0% Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime. (permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat controller memory.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 1.0 to
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Note: When adjusting the temperature, press the UP/ DOWN arrow keys to change the temperature in
0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.
10.0 min
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
16
Three Speeds of Fan Control
Page 17
Table 6: Installer Configuration Menu (Part 6 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Cal RH Sets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 0.0% RH Aux cont Determines the auxiliary contact
function and configuration.
Default: 0
FL time Sets the maximum actuator stroke
timing (floating CntrlTyp
TEC2026-2, TEC2026H-2,
TEC2036-2, and TEC2036H-2
models).
Default: 1.5 min Cph Sets the maximum number of cycles
per hour (TEC2016-2,
TEC2016H-2, and on/off CntrlTyp
TEC2026-2, TEC2026H-2,
TEC2036-2, and TEC2036H-2
models).
Default: 4 RA/DA Choice of reverse or direct acting
analog output signal (TEC2046-2,
TEC2046H-2, TEC2056-2, and
TEC2056H-2 models).
Default: DA
Range: -15.0% RH to 15.0% RH (adjustable in 1% RH increments)
* If option (3) or (4) is used, it functions like option (1) or (2), respectively.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
Range: 3 to 8 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC (DA): Direct acting, 0 to 100% = 0 to 10 VDC
(0) Not used,
or used for reheat
(1) Auxiliary
N.O.
(2) Auxiliary
N.C.
(3*) Do not use this selection option. (4*) Do not use this selection option.
(5) Auxiliary On/Off control through the
auxiliary network command. The output can be commanded through the network for any required auxiliary functions via a separate and dedicated network variable.
If the sequence of operation is set to reheat (2, 3, or 5), ignore this parameter.
Occupied = contact closed
Unoccupied = contact open
Occupied = contact open Unoccupied = contact
closed
The output aligns with occupancy.
The output aligns with the secondary network occupancy command.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
17
Page 18
Table 6: Installer Configuration Menu (Part 7 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Reheat Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
1. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and hold the UP or DOWN arrow key to change the numeric value in increments of ten.
(1): 10 seconds (six cycles per minute), for various equipment with solid-state relays that withstand short duty cycles such as electric heat.
(0): 15 minutes (four cycles per hour), for various equipment with mechanical relays or contactors controlling mechanical reheat systems.
Used as a diagnostic/service help to troubleshoot and diagnose sensor operation.
Troubleshooting
See Table 7 for display messaging. Refer to the
TEC Series Wireless Thermostat Controller System Technical Bulletin (LIT-12011414) for troubleshooting
details.
Repair Information
Accessories
All the accessories in Table 8 include mounting hardware; contact the nearest Johnson Controls representative to order any of these parts.
Note: Review the technical specifications of the accessories prior to their use in an application.
If a TEC20x6(H)-2 Wireless Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls® representative.
Table 7: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filte r(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or
cooling action in accordance with the programmable Binary Input (BI1).
Table 8: Accessories (Order Separately)
Code Number Description
ACC-INSL-0 Foam Insulation Pad Kit (10 adhesive-backed foam pads) SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
TE-6361M-1 TE-636S-1 Strap-Mount Temperature Sensor
Duct Mount Air Temperature Sensor
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
18
Three Speeds of Fan Control
Page 19
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2009 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Technical Specifications
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Relay/Tr iac Contact Rating On/Off and Floating Co ntrol: 30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV Analog Output Rating Proportional Control: 0 to 10 VDC into 2k ohm Resistance (Minimum) Fan Relay Output Rating 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV Auxiliary Output Rating Triac Output: 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Digital Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Wire Size 18 AWG Maximum, 22 AWG Recommended Recommended Transmission
Range RF Band Direct-Sequence Spread-Spectrum Transmission; 2.4 Ghz unlicensed band Transmission Power 10 mW Maximum Temperature Range Backlit Display: -40.0°C/-40.0°F to 50.0°C/122.0°F in 0.5° increments
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor Resolution ±0.1C°/±0.2F° Control Accuracy Temperature: ±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated
Minimum Deadband 1C° /2F° between Heating and Cooling Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Compliance (Pending) United States:
Dimensions (H x W x D) 125 x 86 x 29 mm (4-15/16 x 3-3/8 x 1-1/8 in.) Shipping Weight 0.75 lb (0.34 kg)
Safety Extra-Low Voltage (SELV)
Through Walls: 10 m (30 ft) Line-of-Sight (Open Space): 30 m (100 ft)
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments Cooling Control: 12.0°C/54.0°F to 38.0°C/100.0°F in 0.5° Increments
Humidity: ±5% RH from 20 to 80% RH at 10 to 32°C (50 to 90°F)
Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification: (pending)
Canada:
UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003 Industry Canada (IC) Identification: (pending)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and Three Speeds of Fan Control
Published in U.S.A. www.johnsoncontrols.com
19
Loading...