TEC20x6(H)-2 Series Wireless Thermostat Controllers with
Two Outputs, Dehumidification Capability, and Three
Speeds of Fan Control
Installation Instructions
Part No. 24-9890-765, Rev. A
Issued August 31, 2009
Supersedes March 17, 2008
Applications
IMPORTANT: The TEC20x6(H)-2Series Wireless
Thermostat Controllers are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
thermostat controllercould lead to personal injury or
property damage to the controlled equipment or
other property, additional precautions must be
designed into the control system. Incorporate and
maintain other devices such as supervisory or alarm
systems or safety or limit controls intended to warn
of, or protect against, failure or malfunction of the
thermostat controller.
The TEC Series Wireless Thermostat Controller
System provides wireless networked control of
Heating, Ventilating, and Air Conditioning (HVAC)
equipment on a Building Automation System (BAS)
that enables remote monitoring and programming. This
TEC Series System integrates into a supervisory
controller using BACnet® Internet Protocol (IP) or
BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controlle r to
communicate with multiple TEC Wireless Thermostat
Controllers. TEC20x6(H)-2 Series Wireless Thermostat
Controllers control two- or four-pipe fan coils, cabinet
unit heaters, or other equipment using on/off, floating,
or proportional 0 to 10 VDC control input, three speeds
of fan control, and dehumidification capability.
The wireless mesh network uses ZigBee™ technology
to enable remote monitoring and programming and to
enhance reliability by providing redundant transmission
paths through other TEC Wireless Thermostat
Controllers, creating a resilient, self-healing mesh
network.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with
the limits for a Class A digital device pursuant to Part 15 of
the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when
this equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be
required to correct the interference at his/her own
expense.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1.This device may not cause harmful interference, and
2.This device must accept any interference received,
including interference that may cause undesired
operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user’s
authority to operate the equipment.
Canada
This Class (A) digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes
les exigences du Règlement sur le matériel brouilleur du
Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number
only signifies that the Industry Canada technical
specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est conforme
aux spécifications techniques d'Industry Canada.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs,
Dehumidification Capability, and Three Speeds of Fan Control
1
Page 2
Mounting
Figure 1: Removing the Cover
F
I
G
:
c
v
r
_
r
m
v
l
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Location Considerations
Locate a thermostat controller:
•on a partitioning wall, approximately 1.5 m (5 ft)
above the floor in a location of average
temperature
•away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
Allow for vertical air circulation to the thermostat
controller.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a
TEC20 Coordinator and a TEC Wireless Thermostat
Controller (or between TEC Wireless Thermostat
Controllers) can be less than the recommended
distances shown in Table 1. The effective transmission
range for indoor applications varies because of Radio
Frequency (RF) signal absorption and re flectio n due to
metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
TypeDistance
Through Walls 10 m (32.8 ft)
Open Space 30 m (98.4 ft)
2. Pull the bottom edge of the cover and open the
thermostat controller as illustrated in Figure 1.
3. Carefully pull the locking tabs on the right side of
the mounting base and unlock the Printed Circuit
Board (PCB). Open the PCB to the left as
illustrated in Figure 2.
PCB
Locking
For detailed information on locating devices for
optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294), which is
available on the Johnson Controls® Portal intranet site.
Mounting the Thermostat Controller
Follow these steps to mount the thermostat controller:
1. Use a Phillips-head screwdriver to loosen the
security screw (if installed) on the bottom of the
cover.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
2
Three Speeds of Fan Control
d
r
b
4. Pull approximately 152 mm (6 in.) of wire from the
wall and insert the wire through the hole in the
mounting base.
5. Align the mounting base on the wall, and use the
base as a template to mark the two mounting hole
locations.
Note: Be sure to position the mounting base so that
the arrow on the base points upward to indicate the top
of the thermostat controller.
6. Drill a 5 mm (3/16 in.) hole at each of the two
marked locations, and tap nylon anchors (include d)
flush to the wall surface.
Note: Other means of anchoring the device may be
desired, depending on the wall medium.
Page 3
7. Position the mounting base on the wall, and use
Figure 3: Securing the
Mounting Base to the Wall
Figure 4: Removing the Screw Terminal Blocks
!
!
the two mounting screws (included)to secure the
base to the surface as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting
screws.
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
s
b
_
g
n
t
n
m
:
G
I
F
8. Swing the PCB back to the right, and carefully
snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks as illustrated in
Figure 4.
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the thermostat controller.
When replacing an existing thermostat controller,
remove and label the wires to identify the terminal
functions. When replacing a thermostat controller o f the
same model, simply remove the old screw terminal
blocks and reinsert them onto the PCB of the
replacement thermostat controller.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material
to prevent drafts from affecting the ambient
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the terminals,
be sure to properly twist the wires together prior to
inserting them into the terminal connectors.
4. Reattach the cover to the mounting base (top sid e
first).
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the cover.
See Figure 5, Figure 6, Figu re 7, and Table 2 for
information on wiring the thermostat controllers.
3
Page 4
Fan
-H
Three-Pole
Right Top
Connector
BO2
BO5
Aux
BO1/
AO1
UI3
BI1
BI2
Fan
-M
Fan
-L
24 V~
Hot
24 V~
Com
BO4/
AO2
Five-Pole
Left T o p Connector
1 2 3 4 5
F
I
G
:
T
E
C
2
0
x
6
H
2
_
T
R
M
N
L
S
Figure 5: TEC20x6(H)-2 Series
Thermostat Controller Terminals
BO5
BO3
Aux
6 7 8
Eight-Pole Bottom Connector
Scom
RS
9 10 11 12 13 14 15 16
Table 2: TEC20x6(H)-2 Series Thermostat Controller Terminals
Terminal
Number
TEC2016(H)-2
(On/Off Control)
1Fan-HFan-HFan-HFan On – High
2Fan-MFan-MFan-MFan On – Medium
3Fan-LFan-LFan-LFan On – Low
424 V~ Hot24 V~ Hot24 V~ Hot24 VAC
524 V~ Com24 V~ Com24 V~ Com24 VAC (Common)
6BO5 AuxBO5 AuxBO5 AuxAuxiliary Binary Output
7BO5 AuxBO5 AuxBO5 AuxAuxiliary Binary Output
8BO3BO3BlankOpen Heat
9BlankBO4AO2Close Heat
TEC2026(H)-2,
TEC2036(H)-2
(On/Off or Floating
Control)
TEC2046(H)-2,
TEC2056(H)-2
(Proportional
0 to 10 VDC Control)
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
4
Three Speeds of Fan Control
Page 5
Figure 6: TEC20x6(H)-2 Series Thermostat Controllerwith Separate Power Source for Auxiliary
Contact
FIG:TEC20x6H2_SEP
Scom
Contact
• COC/NH
= Cold Water
• COC/NC
Normally C ool
= Hot Water
Voltage-Free
Contact
• Door
• Remote
Override
• Filter Alarm
• Service Alarm
Voltage-Free
Contact
• Remote NSB
• Motion
• Window
Separate 24 VAC
(24 VA C Maximum)
BO5
Aux
BO5
Aux
24 VAC
Thermostat Power
24 V~
Com
24 V~
Hot
Power and Fan
Independent
Contacts
• Reheat
• Lighting
• Exhaust Fan
Aux
Fan
-H
Fan
-M
Fan
-L
Scom
Contact
• COC/NH
= Cold Water
• COC/NC
Normall y Cool
= Hot Wate r
Voltage-Free
Contact
• Door
• Remote
Override
• Filter Alarm
• Service Alarm
Voltage-Free
Contact
• Remote NSB
• Motion
• Window
C
(24 VAC Ma ximum )
Power and Fan
BO5
Aux
BO5
Aux
Contacts
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fa n
Aux
24 VAC
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Figure 7: TEC20x6(H)-2 Series Thermostat Controller with Same Power Source for Auxiliary Contact
Power Source for Auxiliary Output
• On/Off Actuation
Remote Inputs
Power Source for Auxiliary Output
Same 24 VA
BI1
Independent
BI1
BI2UI3
- OR -
Supply S ensor
Changeover Sensor
Remote Inputs
BI2
UI3
Voltage-Free
Normally Heat
Closed Contact
Closed Contact
M
A
S
_
2
H
6
x
0
2
C
E
T
:
G
I
F
- OR -
Supply Sensor
Thermostat Power
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
Changeover Sensor
Voltage-Free
Normally Heat
Closed Contact
Closed Contact
5
Page 6
Sample Applications
Figure 8: Wiring TEC2016(H)-2 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 9: Wiring TEC2026(H)-2 and TEC2036(H)-2 Thermostat Controllers for On/Off Control
Two -Pip e Applicat ions
Four-Pipe Applications
F
I
G
:
T
E
C
2
0
2
6
H
2
_
T
E
C
2
0
3
6
H
2
_
o
n
o
f
f
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 10: Wiring TEC2026(H)-2 and TEC2036(H)-2 Thermostat Controllers for Floating Control
Two -Pip e Applic ations
F
I
G
:
T
E
C
2
0
2
6
H
2
_
T
E
C
2
0
3
6
H
2
_
f
l
t
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 8 through Figure 11 show sample applications
for these thermostat controllers.
Four-Pipe Applications
24 V~
24 V~
24 V~
f
f
o
n
o
_
2
H
6
1
0
2
C
E
T
:
G
I
F
BO2 BO3
BO4
Four-Pipe Applications
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
6
Three Speeds of Fan Control
24 V~
24 V~
Page 7
Figure 11: Wiring TEC2046(H)-2 and TEC2056(H)-2 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
F
I
G
:
T
E
C
2
0
4
6
H
2
_
T
E
C
2
0
5
6
H
2
_
p
r
o
p
Heating/Cooling
Valve
Com
Hot
AO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
Figure 12: Front Cover (TEC20x6H-2 Models)
Backlit
LCD
System
Activity
LEDs
Intuitive
Operation
Keys
F
I
G
:
T
E
C
2
0
x
6
H
_
w
r
l
s
s
_
f
r
n
t
v
w
Status LED
(beneath cover)
AO2
24 V~
24 V~
Setup and Adjustments
Overview
Figure 12 shows the front cover of the thermostat
controller, including features used for setting up and
adjusting the thermostat controller.
Plain-Text
Room Temp
70.0ºF
MODE FAN
User Interface Keys
The user interface consists of keys on the front cover
as illustrated in Figure 12. The function of each key is
as follows:
•OVERRIDE key (commercial models) overrides
the unoccupied mode to occupied at the local user
interface for the specified TOccT ime. (TOccTime is
defined by selecting the appropriate time period in
the Installer Configuration Menu.) The OVERRIDE
key also allows access to the Installer
Configuration Menu. (See Table 6.)
Note: If one of the binary inputs is configured to
operate as a remote override contact, this OVERRIDE
key is disabled.
•°C/°F key (hospitality models) changes the
temperature scale to either Celsius or Fahrenheit
and allows access to the Installer Configuration
Menu. (See Table 6.)
•UP/DOWN arrow keys change the configuration
parameters and activate a setpoint adjustment.
Light-Emitting Diodes (LEDs)
System Activity LEDs indicate the status and actions of
the thermostat controller.
•The FAN LED is on when the fan is on.
•The HEAT LED is on when heating or reheat is on.
•The COOL LED is on when cooling is on.
•MODE key toggles among the system modes
available, as defined by selecting the appr op ria te
operation sequence in the Installer Configuration
Menu (for example Off, Heat, Cool, Auto).
•FAN key toggles am on g th e fa n mo de s av aila ble ,
as defined by selecting the appropriate fan menu
options defined in the Installer Configuration Menu
(for example Low, Med, High, Auto).
The Status LED, located beneath the cover, flashes at
5-second intervals to provide indication of the network
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
7
Page 8
status of the thermostat controller. See Table 3.
Table 3: Status LED
Flashes per
Condition Indicated
5-Second
Interval
1Power On
2Power On, Communicating
3Power On, Communicating, Found
Wireless Network
4Power On, Communicating, Found
Wireless Network, Communicating with
TEC20 Coordinator
Configuring the Thermostat Controller
The thermostat controller comes from the factory with
default settings for all configurable parameters. The
default settings are shown in Table 6. To reconfigure
the parameters, follow the steps in this section.
To access the Installer Configuration Menu, press and
hold the center key for approximately 8 seconds. Once
the Installer Configuration Menu begins, release and
press the center key to scroll through the parameters
listed in Table 6. When the desired parameter displays,
use the UP/DOWN arrow keys to choose the desired
selection option. Then press and release the center
key to continue scrolling through the parameters.
Backlit Liquid Crystal Display (LCD)
The thermostat controller includes a 2- line, 8-character
backlit display. Low-level backlighting is present during
normal operation, and it brightens when any user
interface key is pressed. The backlight returns to low
level when the thermostat controller is left unattended
for 45 seconds.
Status Display Menu
The Status Display Menu displays during normal
operation. This menu scrolls through several
parameters:
•Room Temperature
•Room Temperature and Humidity (TEC2036-2,
TEC2036H-2, TEC2056-2, and TEC2056H-2
models)
•System Mode
•Occupancy Status (Occupied/Unoccupied/
Override)
•Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature parameter.
Note: Pressing the FAN key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 6.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition displays locally when the
input closes. An alarm message is included on the
scrolling Status Display Menu and when the message
is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water
switching or supply air temperature monitoring at the
thermostat controller.
Each input can be configured to the Selection Options
included in Table 6.
Configuring the Sequence of Operation (S eqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequen ce
of operation selected. For two-pipe applications using a
changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between
Cooling Only and Heating Only. See Figure 13
through Figure 18 for sequence of operation
examples.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
8
Three Speeds of Fan Control
Page 9
Table 4: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 13.10: Normally Open
(1): Heating OnlySee Figure 14.10: N.O. Heating
(2): Cooling and ReheatSee Figure 15.6 and 7: Reheat
(3): Heating and ReheatSee Figure 16.6 and 7: Reheat
Control
Curve
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off ControlFloating ControlProportional
(N.O.) Cooling
11: Normally Closed
(N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling
11: N.C. Cooling
10: N.O. Heating
11: N.C. Heating
10: Open Cooling
11: Closed Cooling
10: Open Heating
11: Closed Heating
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
10: Open Heating
11: Closed Heating
Table 5: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 13.10: N.O. Cooling
(1): Heating OnlySee Figure 14.8: N.O. Heating
(2): Cooling and ReheatSee Figure 15.6 and 7: Reheat
(3): Heating and ReheatSee Figure 16.6 and 7: Reheat
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
10: Proportional Heating
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
9: Proportional Heating
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
10: Proportional Cooling
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
9
Page 10
Temperatur e Increase
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 13: Cooling Only
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 14: Heating Only
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
or Propor t ional
Outputs
Heating Output
Cooling Output
Off
Off
On
On
Figure 15: Cooling with Reheat
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 16: Heating with Reheat
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
Deadband
or Propor t ional
Outputs
Heating Output
Cooling Output
Off
Off
On
On
Figure 17: Heating/Cooling When Out1Conf = 4.0
(Increments of 1F°/0.5C°)
On
100%
0%
On/Off, Floating,
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
Device
(Increments of 1F°/0.5C°)
On/Off, Floating,
(Increments of 1F°/0.5C°)
Temperature Increase
Device
Temperat ure Increase
t
h
r
Temperat ure Increase
(Increments of 1F°/0.5C°)
10
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
Page 11
Temperatur e Increase
Heating Setpoint
Device
Closed
Device
Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat
Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put
Cooling Output
Off
Off
On
On
Figure 18: Heating/Cooling When Out1Conf = 4.0
Figure 19: Two-Speed and Three-Speed Fan Operation
Temperat ur e Deviation fro m Setpoint, F°
2.0F°/1. 0C° to
5.0F°/2.5C°
Deadband
100%
0%
2.5
2.5
2.02.0
1.5
1.50.50.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Heating
Setpoint
Cooling
High
FIG:fn_oprtn
Fan
Speed
(Increments of 1F°/0.5C°)
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer
Configuration menu to set the available Fan Mode
options. Use the FAN key to select the desired Fan
Mode option.
When selection option (2): Low-Med-High-Auto is
chosen in the Fan Menu parameter, the fan operates
as shown in Figure 19. When selection option
(3): Low-High-Auto is chosen in the Fan Menu
parameter, the fan operates at only the low and high
settings, ignoring the medium setting (Figure 19). This
operation applies to the occupied mode when the fan is
set to Auto.
Setpoint
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
11
Page 12
Configuring the Wireless Mesh Network Settings
Use the following process to configure the wireless
mesh network.
1. Select a PAN ID and Channel. Use these same
values for every TEC Wireless Thermostat
Controller (and the associated TEC20 Coordinator)
on the same wireless mesh network. See Table 6.
2. Select a Com Address for each TEC Wireless
Thermostat Controller (1 to 254). This address
must be unique to each TEC Wireless Thermostat
Controller on the same wireless network (that is,
unique to the PAN ID/Channel combination). See
Table 6.
After configuring the wireless mesh network settings,
refer to the TEC Series Wireless Thermostat Controller System T echnical Bulletin (LIT-12011414) for directions
on integrating the TEC Wireless Thermostat
Controllers and TEC20 Coordinator with a supervisory
controller.
Dehumidification (TEC2036[H]-2 and TEC2056[H]-2
Models Only)
Upon detection of room humidity above the adjustable
humidity setpoint as sensed by the integral humidity
sensor, dehumidifica tion activates.
Note: Dehumidification operation functions only in the
Cooling mode; dehumidification operation does not
function in either the Off or the Heating mode.
Note: A central network command can globally
lock out dehumidification operation to all thermostat
controllers.
If the room temperature resides in the deadband
between the Heating and Cooling setpoint:
•the thermostat controller forces the fan to low
speed
•the chilled water valve opens to the specified
maximum value set by CoolMax
•the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
If the thermostat controller is in Cooling demand:
•the chilled water valve opens to 100%
•the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the thermostat controller is in Cooling demand and
the room temperature rises 2F°/1C° above the Cooling
setpoint, the thermostat controller automatically
disables dehumidification operation. Likewise, if the
thermostat controller is in Cooling demand and the
room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
Table 6: Installer Configuration Menu (Part 1 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Com addrWireless address at the thermostat
controller; Default: 4
PAN IDSets the Personal Area Network
Identification (PAN ID) of the
wireless network. All devices on a
network must have the same
PA N ID setting to communicate with
each other. Default: 0ChannelSets the mesh network channel the
device uses for communication.
Only devices using the same mesh
network channel can communicate
with each other. Default: 10GET FROMParameter not available at this time.N/A
Range: 000 to 254
Addresses of each item on the wireless bus must be uniquely
numbered, increasing from 1.
Note: Setting this parameter to 0 disables the function.
Range: 0 to 500Note: Setting this parameter to 0 disables the function.
Range: 11 to 26Note: Setting this parameter to 10 disables the function.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
12
Three Speeds of Fan Control
Page 13
Table 6: Installer Configuration Menu (Part 2 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
BI1Configuration of Binary Input 1.
Default: None
BI2Configuration of Binary Input 2.
Default: None
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is open, until the
TOccTime expires.
(MotionNC*): Temp orary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat controller goes into the occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the occupied mode if the contact is closed, until the
TOccTime expires.
(Window): Cancels the heating or cooling action when a window is
open. The fan operation is only affected if the Fan Menu parameter
is set to (4): On-Auto and Auto is the selected fan mode. A window
alarm appears, indicating that the window needs to be closed to
resume heating or cooling.
*These settings disable any local override function.
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC. (See the BI1 parameter earlier in this
table.) The occupancy is now dictated via BI1 and BI2. Any motion
detected sets the zone to Occupied status. The thermostat controller
remains in the occupied mode until a DoorOpen is detected, at
which point the thermostat controller goes to the unoccupied mode.
If the door stays open more than the specified door time, the
thermostat controller remains unoccupied. (See the Door Time
parameter later in this table.)
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. This input can be tied into the air
conditioning unit control card, which provides an alarm should there
be a malfunction.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
13
Page 14
Table 6: Installer Configuration Menu (Part 3 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
UI3Configuration of Universal Input 3.
Default: None
MenuScroGives the option of having the
display continuously scroll the
parameters.
Default: onAutoModeEnables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the
thermostat controller cover.)
Default: off
C or FProvides temperature scale options
%RH disp
LockoutSelectable Lockout Levels for
for display.
Default: °F
Displays the current humidity
reading (TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models).
Default: off
limiting end user keypad interaction.
Default: 0
(None): No function is associated with an input.
(COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water
changeover switching. Valid only for two-pipe systems.
Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between
Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/
Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring
Note: If UI3 is set to None, COC/NH, or COC/NC, then UI3 S tatus
is available as a point for integration and Supply Temperature is
not available as a point for integration. If UI3 is set to COS or SS,
then Supply Temperature is available as a point for integration and
UI3 Status is not available as a point for integration.
(off): The scroll is inactive.
(on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale
(°F): Fahrenheit scale
(on): Displays the current humidity reading in% RH.
(off): Does not display the current humidity reading.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
14
Three Speeds of Fan Control
Page 15
Table 6: Installer Configuration Menu (Part 4 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Pipe NoSelectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTypDefines the control output for the
SeqOperaDetermines the sequence of
Fan MenuSets the Fan Mode options.
DHumiLCK Locks out the dehumidification
%RH set
DehuHyst
1
type of valves used in the
installation (TEC2026-2,
TEC2026H-2, TEC2036-2, and
TEC2036H-2 models).
Default: Floating
operation.
Default: 1
Default: 4
capability (TEC2036[H]-2, and
TEC2056[H]-2 models).
Default: on
Sets the dehumidification setpoints
(TEC2036[H]-2, and TEC2056[H]-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 50.0% RH
1
Sets the dehumidification hysteresis
(deadband) (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For proportional three-wire control of 24 VAC floating
valves.
(0): Cooling Only (Off-Cool). The default is Cool.
(1): Heating Only (Off-Heat). The default is Heat.
(2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Heat.
(3): Heating and Reheat (Off-Heat). The default is Heat.
(4): Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is Heat.
(5): Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is Heat.
* Auto can be disabled with the AutoMode parameter.
Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Choose the selection option (2): Cooling
and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(0): Low-Med-High: Three-speed configuration using three fan relays (L-M-H). The default is High.
(1): Low-High: Two-speed configuration using two fan relays (L-H). The default is High.
(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan speed mode using three fan relays (L-M-H). The default is High.
(3): Low-High-Auto: Two-speed configuration with Auto Fan speed mode using two fan relays (L-H). The default is High.
(4): On-Auto: One-speed configuration, (H) Auto is for Fan on demand and On is for Fan on all the time. The default is Auto.
(off): Dehumidification is locked out.
(on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
Range: 2.0 to 20.0% RH
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
15
Page 16
Table 6: Installer Configuration Menu (Part 5 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
1
DehuCool
Unocc HTSets the Unoccupied Heating
Unocc CLSets the Unoccupied Cooling
Heat maxSets the Occupied and Unoccupied
Cool minSets the Occupied and Unoccupied
Set typeProvides the option of temporarily
TOccTimeSets the duration of the Temporary
DoorTimeEngages the Unoccupied mode if
DeadbandSets the minimum deadband
Cal RSSets the desired room air sensor
Sets the maximum dehumidification
cooling output (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 100%
setpoint value.
Default: 62.0°F/16.5°C
setpoint value.
Default: 80.0°F/26.5°C
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an Override Function enabled in
the Main User Menu (when the
thermostat controller is in the
Unoccupied mode)
• a temporary heating or cooling
setpoint
Default: 2.0 hrs
the door stays open minimally for
the time specified.
Default: 2.0 min
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C°
Range: 20.0 to 100.0%Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat controller memory.
Range: 0.0 to 24.0 hrs in 1-hour increments
Range: 1.0 to
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C°
increments)
Note: When adjusting the
temperature, press the UP/DOWN arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN arrow keys
to change the temperature
in 5.0F°/5.0C° increments.
10.0 min
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
16
Three Speeds of Fan Control
Page 17
Table 6: Installer Configuration Menu (Part 6 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Cal RHSets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2036-2, TEC2036H-2,
TEC2056-2, and TEC2056H-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 0.0% RHAux contDetermines the auxiliary contact
function and configuration.
Default: 0
FL timeSets the maximum actuator stroke
timing (floating CntrlTyp
TEC2026-2, TEC2026H-2,
TEC2036-2, and TEC2036H-2
models).
Default: 1.5 minCphSets the maximum number of cycles
per hour (TEC2016-2,
TEC2016H-2, and on/off CntrlTyp
TEC2026-2, TEC2026H-2,
TEC2036-2, and TEC2036H-2
models).
Default: 4RA/DAChoice of reverse or direct acting
analog output signal (TEC2046-2,
TEC2046H-2, TEC2056-2, and
TEC2056H-2 models).
Default: DA
Range: -15.0% RH to 15.0% RH (adjustable in 1% RH increments)
* If option (3) or (4) is used, it functions like option (1) or (2),
respectively.
Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments)
Range: 3 to 8 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC
(DA): Direct acting, 0 to 100% = 0 to 10 VDC
(0)Not used,
or used for
reheat
(1)Auxiliary
N.O.
(2)Auxiliary
N.C.
(3*)Do not use this selection option.
(4*)Do not use this selection option.
(5)Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network
variable.
If the sequence of operation is set to
reheat (2, 3, or 5), ignore this parameter.
Occupied = contact
closed
Unoccupied = contact
open
Occupied = contact open
Unoccupied = contact
closed
The output
aligns with
occupancy.
The output
aligns with
the
secondary
network
occupancy
command.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
17
Page 18
Table 6: Installer Configuration Menu (Part 7 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
ReheatSets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 disDisplays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
1.When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0): 15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
Used as a diagnostic/service help to troubleshoot and diagnose
sensor operation.
Troubleshooting
See Table 7 for display messaging. Refer to the
TEC Series Wireless Thermostat Controller System
Technical Bulletin (LIT-12011414) for troubleshooting
details.
Repair Information
Accessories
All the accessories in Table 8include mounting
hardware; contact the nearest Johnson Controls
representative to order any of these parts.
Note: Review the technical specifications of the
accessories prior to their use in an application.
If aTEC20x6(H)-2 Wireless Thermostat Controller fails
to operate within its specifications, replace the unit. For
a replacement thermostat controller, contact the
nearest Johnson Controls® representative.
Table 7: Display Messages
DisplayFunction
ServiceIndicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
FilterIndicates that the filte r(s) is dirty in accordance with the programmable Binary Input (BI2).
WindowIndicates that an outside window or door is open and has cancelled the thermostat controller heating or
cooling action in accordance with the programmable Binary Input (BI1).
Table 8: Accessories (Order Separately)
Code NumberDescription
ACC-INSL-0Foam Insulation Pad Kit (10 adhesive-backed foam pads)
SEN-600-1Remote Indoor Air Temperature Sensor
SEN-600-4Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
TE-6361M-1
TE-636S-1Strap-Mount Temperature Sensor
Duct Mount Air Temperature Sensor
1.Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
18
Three Speeds of Fan Control
Page 19
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification
Capability, and Three Speeds of Fan Control
Power Requirements19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Relay/Tr iac Contact RatingOn/Off and Floating Co ntrol: 30 VAC, 1.0 A Maximum, 3.0 A In-Rush, Class 2 or SELV
Analog Output Rating Proportional Control: 0 to 10 VDC into 2k ohm Resistance (Minimum)
Fan Relay Output Rating30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Auxiliary Output RatingTriac Output: 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush
Digital InputsVoltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Wire Size18 AWG Maximum, 22 AWG Recommended
Recommended Transmission
Range
RF BandDirect-Sequence Spread-Spectrum Transmission; 2.4 Ghz unlicensed band
Transmission Power10 mW Maximum
Temperature RangeBacklit Display: -40.0°C/-40.0°F to 50.0°C/122.0°F in 0.5° increments
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Resolution ±0.1C°/±0.2F°
Control AccuracyTemperature: ±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated
Minimum Deadband1C° /2F° between Heating and Cooling
Ambient ConditionsOperating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Compliance (Pending)United States:
Dimensions (H x W x D)125 x 86 x 29 mm (4-15/16 x 3-3/8 x 1-1/8 in.)
Shipping Weight0.75 lb (0.34 kg)
Safety Extra-Low Voltage (SELV)
Through Walls: 10 m (30 ft)
Line-of-Sight (Open Space): 30 m (100 ft)
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments
Cooling Control: 12.0°C/54.0°F to 38.0°C/100.0°F in 0.5° Increments
Humidity: ±5% RH from 20 to 80% RH at 10 to 32°C (50 to 90°F)
Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters
Transmitter FCC Identification: (pending)
Canada:
UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Industry Canada (IC) Identification: (pending)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
TEC20x6(H)-2 Series Wireless Thermostat Controllers with Two Outputs, Dehumidification Capability, and
Three Speeds of Fan Control
Published in U.S.A.www.johnsoncontrols.com
19
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.