Johnson Controls TEC2045-4 Installation Instructions Manual

Page 1
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
Installation Instructions
TEC2045-4
Part No. 24-9890-1109, Rev. B
Issued July 13, 2010
Supersedes May 17, 2010
Application
IMPORTANT: The TEC2045-4 Wireless
Thermostat Controller is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller.
The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming. This TEC Series System integrates into a supervisory controller that uses BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.
TEC20 Coordinators allow the supervisory controlle r to communicate with multiple TEC Wireless Thermostat Controllers. TEC2045-4 Wireless Thermostat Controllers control two-pipe fan coils, cabinet unit heaters, or other equipment using a proportional 0 to 10 VDC control input and one-speed fan control.
The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC Wireless Thermostat Controllers, creating a resilient, self-healing mesh network.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
RF Transmitters: Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industrie Canada.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-
1
Speed Fan Control Installation Instructions
Page 2
Installation
Figure 1: Removing the Cover
F
I
G
:
c
v
r
_
r
m
v
l
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Location Considerations
Locate a thermostat controller:
on a partitioning wall, approximately 1.5 m (5 ft) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: Allow for vertical air circulation to the TEC2045-4 Thermostat Controllers.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a TEC20 Coordinator and a TEC Wireless Thermostat Controller (or between TEC Wireless Thermostat Controllers) can be less than the recommended distances shown in Table 1. The effective transmission range for indoor applications varies because of Radio Frequency (RF) signal absorption and re flectio n due to metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
Type Distance
Through Walls 10 m (32.8 ft) Open Space 30 m (98.4 ft)
2. Pull the bottom edge of the thermostat cover and open the thermostat illustrated in Figure 1.
3. Carefully pull the locking tabs on the right side of the mounting base and unlock the Printed Circuit Board (PCB). Open the PCB to the left as illustrated in Figure 2.
PCB Locking
For detailed information on locating devices for optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294), which is available on the Johnson Controls® Portal intranet site.
Installing the Thermostat Controller
Follow these steps to install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
2
Installation Instructions
d
r
b
4. Pull approximately 152 mm (6 in.) of wire from the wall, and insert the wire through the hole in the mounting base.
5. Align the mounting base on the wall, and use the base as a template to mark the two mounting hole locations.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed.
Page 3
Note: For surface-mount applications, use
Figure 3: Securing the
Mounting Base to the Wall
F
I
G
:
m
n
t
n
g
_
b
s
Figure 4: Removing the Screw Terminal Blocks
!
!
durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface.
6. Position the thermostat mounting base on the wall so that the arrow on the base points upward to indicate the top of the thermostat.
7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the thermostat controller.
When replacing an existing thermostat controller, remove and label the wires to identify the terminal functions. When replacing a thermostat controller o f the same model, simply remove the old screw terminal blocks, and reinsert them onto the PCB of the replacement thermostat controller.
8. Swing the PCB back to the right, and carefully snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
s k
c
l
b
_
l
n m
r
t
: G
I F
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.), and connect them to the appropriate screw terminals as indicated in Figure 5.
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB. Note: If multiple wires are inserted into the
terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
4. Reattach the cover to the mounting base (top sid e first).
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the cover.
See Figure 5, Figure 6, Figure 7, and Table 2 for information on wiring the thermostat controllers.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
3
Installation Instructions
Page 4
Figure 5: TEC2045-4 Thermostat Controller
Terminals
Fan
Two-Pole
Blank
24 V~
Hot
24 V~
Com
BO5
Aux
BO5
Aux
Scom
AO1
UI3
BI1
BI2
34
5
67
2
F
I
G
:
T
E
C
2
0
4
5
_
t
r
m
n
l
s
Figure 6: TEC2045-4 Thermostat Controller with Separate Power Source for Auxiliary Contact
Separate 24 VAC
Power Source for Auxiliary Output
(24 VA C Maximum )
BO5 Aux
BO5 Aux
24 VAC
Thermostat Power
Fan
24 V~
Com
0 to 10 VDC 24 VAC Com
Analog Output
and Valve
24 V~
Hot
AO1
Fan
Power and Fan
Aux Contact (Isolate d Common)
• Reheat
• Lighting
• On/Of f Actuation
• Exhaus t Fan
Aux Load
Scom
- OR -
SS (Supply Sensor) COS (Cha nge Over Sensor)
Contact
• COC/NH
= Cold Water
• COC/NC Normall y Cool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Windo w
Three-Pole Left Top Connect or
Right Top Connector
Six-Pole Bottom Connector
11 1
10
14 1516
Table 2: TEC2045-4 Thermostat Controller
Terminals
Terminal Number
3 Fan Fan On 4 24 V~ Hot 24 VAC from Transformer 5 24 V~ Com 24 VAC from Transformer
6 BO5 Aux Auxiliary Binary Output 7 BO5 Aux Auxiliary Binary Output 10 AO1 Open Cool 11 Blank Close Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3
Terminal Label
Remote Inputs
Function
(Common)
BI1
BI2 UI3
Voltage-Free
Normall y Heat Closed Co ntact
Closed Co ntact
FIG:TEC2045_diff
4
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions
Page 5
Figure 7: TEC2045-4 Thermostat Controller with Same Power Source for Auxiliary Contact
Same 24 VAC
Power Source for Auxiliary Output
(24 VA C Maximum )
24 VAC
Thermostat Power
Fan
24 V~
Com
0 to 10 VDC 24 VAC Com
Analog Output
and Valve
24 V~
Hot
AO1
Fan
Power and Fan
BO5 Aux
BO5 Aux
Aux Contact (Isolate d Common )
• Reheat
• Lighting
• On/Of f Actuation
• Exhaus t Fan
Aux Load
Scom
Contact
• COC/NH
= Cold Water
• COC/NC Normall y Cool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
Figure 8: Front Cover of TEC2045-4 Thermostat Controller
70.0ºF
Room Temp
FIG:TEC2045_wrlss_frntvw
Status L ED beneath c over
indicat es network sta tu s.
Five keys on the therm ost at controll er make operation easy and intuitive.
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any con di tion.
Light-Emitting Diodes (LEDs) indicate system activity .
FIG:TEC2045_sme
Remote Inputs
Setup and Adjustments
BI1
SS (Supply Sensor) COS (Cha nge Over Sensor)
BI2 UI3
- OR -
Voltage-Free
Normally Heat Closed Contact
Closed Contact
Thermostat Controller User Interface Keys
The user interface consists of keys on the front cover
(Figure 8). The function of each key is as follows:
MODE key toggles among the system modes available, as defined by selecting the appr op ria te operation sequence in the Installer Configuration Menu (Off, Heat, Cool, Auto).
FAN key toggles between ON and AUTO for fan control. ON energizes the fan all the time and AUTO operates the fan only on a call for heating or cooling, for both occupied and unoccupied periods.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
OVERRIDE key overrides the unoccupied mode to
UP/DOWN arrow keys change the configuration
occupied at the local user interface for the specified TOccTime. (TOccTime is defined by selecting the appropriate time period in the Insta ller Configuration Menu.) If one of the binary inputs is configured to operate as a remote override co ntact, this OVERRIDE function is disabled. The OVERRIDE key also allows access to the Installer Configuration Menu. See the Configuring the Thermostat Controller section.
parameters and activate a setpoint adjustment.
Installation Instructions
5
Page 6
Light-Emitting Diodes (LEDs)
Three System Activity LEDs are included to indicate the status and actions of the thermostat controller:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on.
Configuring the Thermostat Controller
The thermostat controller ships from the factory with default settings for all configurable parameters. The default settings are shown in Table 5. To reconfigure the parameters using the user interface keys, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the OVERRIDE key for approximately 8 seconds.
The Status LED, located beneath the cover, flashes at 5-second intervals to provide indication of the network status of the thermostat controller. See Table 3.
Table 3: Status LED
Flashes per
Condition Indicated 5-Second Interval
1 Power On 2 Power On, Communicating 3 Power On, Communicating, Found
Wireless Network 4 Power On, Communicating, Found
Wireless Network, Communicating with
TEC20 Coordinator
Backlit Liquid Crystal Display (LCD)
The thermostat controller includes a 2- line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unattended for 45 seconds.
Status Display Menu
The Status Display Menu is displayed during normal operation. This menu continuously scrolls through the following parameters:
Room Temperature
System Mode
Occupancy Status (Occupied/Unoccupied/ Override)
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.
Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MODE key to proceed through the Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins, press and release the OVERRIDE key to scroll through the parameters listed in Table 5.
3. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option.
4. Press and release the OVERRIDE key to continue scrolling through the parameters.
Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed in Table 5.
When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat contr oller reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm condition, an alarm condition displays locally when the input closes. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water switching, or supply air temperature monitoring at the thermostat controller.
Each input can be configured to the Selection Options included in Table 4.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
6
Installation Instructions
Page 7
Configuring the Sequence of Operation
Figure 9: Cooling Only
Device Closed
Device Opened
Proportional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 10: Heating Only
Device Closed
Device Opened
Proportional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 11: Cooling with Reheat
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
Proportional
Output
Cooling Output
Off
Off
On
On
Figure 12: Heating with Reheat
FIG:htg_wt
Reheat
Output
Off
Off
On
(SeqOpera)
Choose the appropriate sequence of operation. The modes presented are user-dependent on the seque nce of operation selected. For applications using a changeover sensor, choose the selection option
(0): Cooling Only. Changeover occurs between Cooling Only and Heating Only . See Figure 9 through
Figure 12 for sequence of operation example.
Table 4: Selection Options for Sequence of Operation
Selection Option Control Curve Terminal Numbers Used
(See Figure 5.)
0: Cooling Only See Figure 9. 10: Proportional Cooling 1: Heating Only See Figure 10. 10: Proportional Heating 2: Cooling and Reheat See Figure 11. 6 and 7: Reheat
10: Proportional Cooling
3: Heating and Reheat See Figure 12. 6 and 7: Reheat
10: Proportional Heating
Cooling Setpoint
Heating Output
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Heating Setpoint
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Device
On
Temperature Increase
100%
(Increments of 1F°/0.5C°)
Proportional
0%
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
h_rht
Temp er at ure Increase
(Increments of 1F° /0 . 5C °)
7
Installation Instructions
Page 8
Configuring the Wireless Mesh Network Settings
Use the following process to configure the wireless mesh network.
1. Select a PAN ID and Channel. Use these same values for every TEC Wireless Thermostat Controller (and the associated TEC20 Coordinator) on the same wireless mesh network. See Table 5.
Table 5: Installer Configuration Menu (Part 1 of 6)
Parameter Appearing on Display
Pswrd Sets the protective access
Com addr Wireless address at the thermostat
PAN ID Sets the Personal Area Network
Channel Sets the mesh network channel the
GET FROM Parameter not available at this time. N/A
Description and Default Selection Options
password to prevent unauthorized access to the Installer Configuration Menu.
Default: 0 Note: The default setting does not
lock out access to the Installer Configuration Menu.
controller; Default: 254
Identification (PAN ID) of the wireless network. All devices on a network must have the same PA N ID setting to communicate with each other. Default: 0
device uses for communication. Only devices using the same mesh network channel can communicate with each other. Default: 10
Range: 0 to 1,000
Range: 000 to 254 Addresses of each item on the wireless bus must be uniquely
numbered, increasing from 1. Note: Setting this parameter to 0 disables the function.
Range: 0 to 500 Note: Setting this parameter to 0 disables the function.
Range: 11 to 26 Note: Setting this parameter to 10 disables the function.
2. Select a Com Address for each TEC Wireless Thermostat Controller (1 to 254). This address must be unique to each TEC Wireless Thermostat Controller on the same wireless network (that is, unique to the PAN ID/Channel combination). See Table 5.
After configuring the wireless mesh network settings, refer to the TEC20xx-4 and TEC20xx-4+PIR Series
Wireless Thermostat Controller System Technical Bulletin (LIT-12011596) for directions on integrating the
TEC Wireless Thermostat Controllers and TEC20 Coordinator with a supervisory controller.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
8
Installation Instructions
Page 9
Table 5: Installer Configuration Menu (Part 2 of 6)
Parameter
Description and Default Selection Options Appearing on Display
BI1 Configuration of Binary Input 1.
Default: None
BI2 Configuration of Binary Input 2.
Default: None
(None): No function is associated with an input. (Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat controller TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is open, until the TOccTime expires.
(MotionNC*): Temporary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat controller goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is closed, until the TOccTime expires.
(Window**): Cancels the heating or cooling action when a window is open. A Window alarm is displayed indicating that the window needs to be closed to resume heating or cooling.
* These settings disable any local override function. **When this setting is selected, the heating and/or cooling outputs
are enabled only when the contact is closed. If the fan is set to Auto, it is enabled only when the contact is closed. If the fan is set to On, it is not affected by this setting.
(None): No function is associated with an input. (Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC. (See the BI1 parameter earlier in this
table.) The occupancy is now dictated via BI1 and BI2. Any motion detected sets the zone to Occupied status. The zone remains permanently in occupied mode until the door contact switch opens momentarily. The thermostat then enters stand-by mode. If more movements are detected, the occupied mode resumes. Use a Normally Closed contact switching device. Contact opened = Door opened, Contact closed = Door closed.
(RemOVR): Temporary occupancy request by means of a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller when the input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
enters the occupied mode for a specified
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
9
Installation Instructions
Page 10
Table 5: Installer Configuration Menu (Part 3 of 6)
Parameter
Description and Default Selection Options Appearing on Display
UI3 Configuration of Universal Input 3.
Default: None
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on AutoMode Enables the Auto function (if
Option 2 is chosen in the SeqOpera
parameter) to be visible within the
MODE key menu. (The MODE key
is the key at the far left of the cover.)
Default: on C or F Provides temperature scale options
for display.
Default: °F Lockout Selectable Lockout Levels for
limiting end user keypad interaction.
Default: 0
SeqOpera Determines the sequence of
operation.
Default: 1
(None): No function is associated with an input. (COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems.
Note: Choose the selection option (0): Cooling Only for the SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. Choose the selection option (2): Cooling and Reheat to allow changeover to occur between Cooling and Reheat and Heating and Reheat.
(SS): Supply Air Sensor Monitoring Note: If UI3 is set to None, COC/NH, or COC/NC, then UI3 Status
is available as a point for integration and Supply Temperature is not available as a point for integration. If UI3 is set to COS or SS, then Supply Temperature is available as a point for integration and
UI3 Status is not available as a point for integration. (off): The scroll is inactive.
(on): The scroll is active.
(on): The Auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(°C): Celsius scale (°F): Fahrenheit scale
Lockout Level
(0): Cooling Only (Off-Cool). The default is Cool. (1): Heating Only (Off-Heat). The default is Heat. (2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto. (3): Heating and Reheat (Off-Heat). The default is Heat.
* Auto can be disabled with the AutoMode parameter . When Auto is disabled, the default for (2) is Heat.
Note: Choose the selection option (0): Cooling Only when using a changeover sensor to allow changeover to occur between Cooling
Only and Heating Only.
Function
Mode Setting
(0) Access Access Access Access (1) Access Access No Access Access (2) No Access No Access Access Access (3) No Access No Access No Access Access (4) No Access No Access Access No Access (5) No Access No Access No Access No Access
Fan Setting
Local Override
Occupied Temperature Setpoints
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
10
Installation Instructions
Page 11
Table 5: Installer Configuration Menu (Part 4 of 6)
Parameter
Description and Default Selection Options Appearing on Display
St-By TM Sets stand-by timer value; time
delay between moment where
occupancy sensor detected the last
movement in the area and the time
which the thermostat stand-by mode
and setpoints become active.
Default: 0.5 hours Unocc TM Sets Unoccupied Timer Value; time
delay between the moment where
the thermostat controller toggles to
stand-by mode and the time which
the thermostat controller
unoccupied mode and setpoint s
become active.
Default: 0.0 hours St-By HT Sets Stand-by heating setpoint;
value is between occupied and
unoccupied heating setp oi n ts.
Default: 69.0°F/20.6°C St-By CL Sets Stand-by cooling setpoint limit;
value is between occupied and
unoccupied cooling setpoints.
Default: 78.0°F/25.6°C Unocc HT Sets the Unoccupied Heating
setpoint value.
Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied Cooling
setpoint value.
Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C Pband Proportional Band used by the PI
temperature control loop of the
thermostat controller.
Pband is not converted with C or F
scale and is always shown with a
range of 3 to 10.
Default: 3 (3F°/1.7C°)
Range: 0.5 to 24.0 hours, in 0.5 hour increments
0.0 hours or Factory Value: Setting this parameter to its default 0 value disables the occupied timer and prevents the thermostat controller from drifting from stand-by mode to unoccupied mode when occupancy sensor functions are used.
Range: 0.0 to 24.0 hours in 0.5 hour increments
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range:
100.0°F/37.5°C
Value F Scale Pband/C Scale Pband 3 3.0F°/1.7C° 4 4.0F°/2.2C° 5 5.0F°/2.8C° 6 6.0F°/3.3C° 7 7.0F°/3.9C° 8 8.0F°/4.4C° 9 9.0F°/5.0C° 10 10.0F°/5.6C° Note: The use of a larger proportional band is not to use the
thermostat controller as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat controller location errors that cannot be worked around.
Note: When adjusting the temperature, press the UP/ DOWN arrow keys to change the temperature in
0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.
54.0°F/12.0°C to
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
11
Installation Instructions
Page 12
Table 5: Installer Configuration Menu (Part 5 of 6)
Parameter
Description and Default Selection Options Appearing on Display
Set type Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent Spt Func Determines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
TOccTime Sets the duration of the Temporary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or BI1 or BI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary hea ting or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 2.0 hrs Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C° Cal RS Sets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default: 0.0F°/0.0C°
(temporar): Local changes to the heating or cooling setpoints are temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are permanently stored in the thermostat controller memory.
(Attch Stp): Single Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. Both the heating and cooling setpoints are changed simultaneously, while respecting the minimum configured deadband. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. The heating and cooling setpoints can be separated individually, allowing the minimum configured deadband to expand. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
Range: 0.0 to 24.0 hrs adjustable in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° increments)
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
12
Installation Instructions
Page 13
Table 5: Installer Configuration Menu (Part 6 of 6)
Parameter
Description and Default Selection Options Appearing on Display
Aux cont Determines the auxiliary contact
function and configuration.
Default: 0
DA/RA Choice of direct or reverse acting
analog output signal.
Default: DA Reheat Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor). Used as a
diagnostic/service help, to
troubleshoot and diagnose sensor
operation.
Default:
-40°F/-40°C
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC (DA): Direct acting, 0 to 100% = 0 to 10 VDC
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric heat.
(0): 15 minutes (four cycles per hour), for various equipment with mechanical relays or contactors controlling mechanical reheat systems.
Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation.
(0) Not used,
or used for reheat
(1) Auxiliary
N.O.
(2) Auxiliary
N.C.
(3) Auxiliary
N.O.
(4) Auxiliary
N.C.
(5) Auxiliary On/Off control through the
auxiliary network command. The output can be commanded through the network for any required auxiliary functions via a separate and dedicated network variable.
If the SeqOpera is set to reheat (Option 2 or 3), ignore this parameter.
Occupied = contact closed
Unoccupied = contact open
Occupied = contact open Unoccupied = contact
closed Occupied and fan On =
contact closed
Unoccupied and fan On or Off = contact open
Occupied and fan On =
contact open
Unoccupied and fan On or Off = contact closed
The output aligns with occupancy.
The output aligns with occupancy and the fan on command.
The output aligns with the secondary network occupancy command.
Troubleshooting
See Table 6 for display messaging. Refer to the
TEC20xx-4 and TEC20xx-4+PIR Series Wireless Thermostat Controller System Technical Bulletin (LIT-12011596) for troubleshooting details.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
Accessories
All the accessories in Table 7 include mounting hardware; contact the nearest Johnson Controls representative to order any of these parts.
Note: Review the technical specifications of the accessories prior to their use in an application.
13
Installation Instructions
Page 14
Repair Information
If the TEC2045-4 Wireless Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative.
Table 6: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or
Table 7: Accessories (Order Separately)
Code Number Description
SEN-600-4 TE-6361M-1
TE-636S-1 Strap-Mount Temperature Sensor TEC-6-PIR
TEC20-A-1 Replacement Antenna for TEC20 Coordinator TEC20-RA-1 NPB-PWR
TEC20-8X-1 120 VAC to 15 VDC Power Supply for TEC20 Coordinator TEC20-9B-1 Replacement Battery Pack for TEC20 Coordinator
1
3
5
cooling action in accordance with the programmable Binary Input (BI1).
Remote Indoor Air T e mperature Sensor with Occupancy Override and LED
2
Duct Mount Air Temperature Sensor
Commercial Fan Coil Controller Cover for Occupancy Sensor
4
Remote Antenna for TEC20 Coordinator DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
1. Only the occupancy override function can be accomplished using the SEN-600-4 with the TEC2045-4.
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
3. The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2045-4 Thermostat Controller to provide occupancy sensing capability.
4. This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by physical installation.
5. DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail mounted options.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
14
Installation Instructions
Page 15
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Technical Specifications
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Analog Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum) Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV Auxiliary Output Rating Triac Output: 19 to 30 VAC , 1. 0 A Maximu m, 15 mA Minimum, 3.0 A In-Rush Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Sensor Type Local 10k ohm Negative T emperature Coef ficient (NTC) Thermistor Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended Recommended Transmission
Range RF Band Direct-Sequence Spread-Spectrum Transmission; 2.4 GHz unlicensed band Transmission Power 10 mW Maximum Resolution ±0.1C°/±0.2F° Temperature Range Backlit Display: -40.0°C/-40.0°F to 50.0°C/122.0°F in 0.5° increments
Accuracy ±0.5C°/±0.9F°/ at 21.0°C/70.0°F Typical Calibrated Minimum Deadband 1C°/2F° between Heating and Cooling Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Compliance (Pending) United States:
Shipping Weight 0.34 kg (0.75 lb)
Safety Extra-Low Voltage (SELV)
Te mperature Coefficient (NTC) Thermistor Sensors
Through Walls: 10 m (30 ft) Line-of-Sight (Open Space): 30 m (100 ft)
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F Cooling Control: 12.0°C/54.0°F to 38.0°C/100.0°F
Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification: (pending)
Canada:
UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003 Industry Canada (IC) Identification: (pending)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
Published in U.S.A. www.johnsoncontrols.com
Installation Instructions
15
Loading...